Вы находитесь на странице: 1из 2

AMS 1900 Product Line

Rectifier SMPS 48 V – 1900 W

Features
• analog system bus
• compact (195 W / l) and light (8 kg)
• efficiency ≥ 91 %
• power factor ~ 1.0 (sinusoidal input current)
• wide input voltage range: 185 – 275 Vrms
• display of output current
• constant output power characteristic
• convection cooling with full performance up to
50 °C ambient temperature
• overtemperature protection with derating
• democratic load sharing in parallel operation
• all connectors and test jacks on front panel
• full mechanical and electrical compatibility with
its predecessor SMPS 48 V – 1700 W

Applications
The SMPS 48 V - 1900 W is a single-phase rectifier based on switch mode technology
which is supplied by AC-network within the voltage range of 185 Vrms to 275 Vrms (nominal
voltage 230 Vrms) and the frequency range of 45 Hz to 65 Hz. The power factor is
approximately 1.
The SMPS 48 V – 1900 W rectifier has a single-phase mains input with a sinusoidal
current shaper. It feeds the load with effectively filtered DC-voltage. It is designed to work
in parallel with other rectifiers and it has an active load sharing function.
The rectifier can be used without external controller. It will then control the output voltage
to a single level. An overvoltage protection circuit is included in the unit.
The SMPS 48 V – 1900 W is designed to match constant-power characteristics of modern
telecom loads and thus reduces the required number of rectifiers in power supply systems
with battery backup.
The primary application of the rectifier SMPS 48 V - 1900 W are modular power systems for
the mobile telecommunication base stations.

Other versions
SMPS 48 V – 1500 W, SMPS 60 V – 1900 W

1900W.doc/1999-06-23/MiK
Rectifier SMPS 48 V - 1900 W – Technical specifications
general output characteristic
efficiency ≥ 91 %
60.0 V ~ 1900 W
power loss, max. 200 W
cooling natural convection 53.5 V
43.5 V
input
voltage range 185 ... 275 Vrms
frequency range 45 Hz … 66 Hz
31.7A 36.0A 44.0A
inrush current < 20 Apeak
nominal current 9.1 Arms control and monitoring
current harmonics EN 61 000-3-2 signalisation LED ‘OK’
total harmonic distortion <5% adjustments
power factor ~ 1.0 - output voltage potentiometer
EMI, conducted EN 55 022, class B - current limit potentiometer
mains connector IEC 320 - overvolt. protection potentiometer
input fuse ext. circuit breaker monitoring
- output voltage test jack
output - output current test jack
nominal voltage 53.5 Vdc PSC 200, PSC 500, analog system bus,
PSC 1000 refer to respective
voltage adj. range 40 ... 60 Vdc leaflets
voltage deviation, static ± 250 mVdc
selective OVP, adj. range 43 … 63 V mechanics
ripple + spikes < 200 mVp-p width, with front plate 140 mm (19” / 3)
psophometric noise < 1.5 mVrms (weighted) depth, without handle 350 mm
EMI, conducted EN 55 022, class B depth, with handle 400 mm
current limit, max. 44 Adc height, body 208 mm
current limit adj. range 9 … 44 Adc height, front panel 266 mm (6U)
load sharing < ± 2 Adc weight 8 kg
colour of front panel RAL 7021
power limit ~ 1900 W, fixed
output connector D SUB
safety
output protection ext. circuit breaker
safety standard EN 60 950, class I
EMI, radiated EN 55 022, class B

environment
immunity ETS 300 386-2-3
amb. temperature 0 °C … + 50 °C (full
performance)
relative humidity 10… 85 %, (non cond.)
altitude above sea < 2000 m

Ascom Energy Systems Oy


Juvan teollisuuskatu 15, P.O.Box 63
Fin-02921 Espoo
Tel. +358 9 8545 200
Fax. +358 9 8545 2010
http://www.ascom.fi Subject to change due to technical progress