CSEZenT: Advance Transformer Protection & Monitoring Solution

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
INTRODUCTION

CSEZen series offers a Multifunctional


comprehensive smart protection solution for CSEZenT/G Model
Feeder, Generator, Motor & Transformer
segment. CSEZenT is available in below models

CSEZen Family of protective relays are advance CSEZenT260: For 2-winding transformer
numeric relays that provides multi protection protection
and monitoring with reliable and fast protection
solution in a single unit.

In the same family of CSEZen series, the


CSEZenTxx is an advance transformer
protection solution which provides fast, sensitive
and secure protection on transformer internal &
external faults.

CSEZenTxx also provides a automation solution


of power control. It compliance with IEC60870-
5-103, IEC61850, Modbus protocol for high
integration of protection & control.

CSEZenTxx offers following model based


features to cover the wide range of user.

 Measurement, Protection & Metering


 Communication
 Disturbance Record
 Event Record
 Fault Record
 DI/DO/LED Matrix Programmability

APPLICATION
CSEZenT differential protections are used as
the main protection and control units for two
winding power transformers, for both internal CSEZenG380: For Generator Differential
faults and faults in the influence area of current Protection
transformers.

CSEZenT units require no intermediate


transformers to adjust CT Ratio and vector
group correction, as these adjustments are
made by the relay itself in software.

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Hardware Protection functions
 Three-phase differential protection
 7 Current and one voltage analogue inputs (87) with harmonic restrain
 Max 16 Digital inputs  Instantaneous differential (87)
 Max 16 Digital outputs  Restricted earth protection (87G)
 10 programmable led  Three phase time overcurrent
 LAN-RJ45 /RS485 /USB/IRIG-B ports for Communication protection in each winding (51)
 Three phase instantaneous
Functions protection in each winding (50)
 Ground time overcurrent (51G)
 Lockout Relay  Ground instantaneous overcurrent
 Open-Close Breaker Command (50G)
 Trip circuit supervision (74TC)  Over-under frequency(81 U/O)
 Over-under voltage (59/27)
 Over-excitation (24 V/Hz)
 Current unbalance (46)
 Thermal image (49)
 Breaker failure (50BF) in each
winding
 Neutral overcurrent (50N/51N) in
each winding

FUNCTIONAL DIAGRAM

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
PROTECTION FUNCTIONS
Instantaneous differential protection
The CSEZenT is a numerical multifunctional relay ideally
The trip operation takes place once the programmed
suited for the protection of any two winding transformer
time since the differential current exceeds the
against two phase internal faults, inter-turn faults and programmed setting has passed.
ground faults as well as overcurrent protection for both It does not have harmonic restraint.
phase faults and earth faults separately for each
transformer winding.
Restricted earth protection (87G)
Percent differential protection (87) Earth protection (50G, 51G) will be available either to
winding 1 or winding 2 which is selectable.
CSEZenT unit has dual slope characteristic for
differential protection with programmable percentage This function is applicable when a winding is an earthed
slope settings, adjustable slope breakpoints, and star and has a measurement CT in the earth wired.If the
adjustable additional time delay. This unit provides difference between the residual and neutral current
programmable CT ratio correction factor for primary and (algebraic sum of phase current) equals Iref exceeds the
secondary side of transformer and CT connection calculated value according to the tripping characteristic
configurations through programmable vector groups. then a trip signal is given.

The differential unit operation characteristic is the The restricted earth unit operation characteristic is the
following one: following one:

Phase Overcurrent (3x50/51)

Harmonic restraint This unit gives backup protection for transformer


external faults. If these external faults are not cleared by
A second and fifth harmonic restraint current is the primary protections, this overcurrent unit will actuate,
calculated for each phase and extracted using DFTs. otherwise the transformer will be seriously damaged due
The magnitude of this current is used to discriminate to overloads. Each winding features two levels.
between faults and inrush conditions, restraining
differential function during inrush caused by energization Ground Overcurrent (50G/51G)
and overexcitation.
This is an overcurrent function used on the current
If blocking on harmonic setting is enable then relay measured at the grounding of a power transformer,
nd th
should block all the tripping operation if 2 /5 harmonic being its function to detect faults to earth. Each winding
are higher than the set values. features two levels.

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Neutral Overcurrent (50N/51N)
AUTOMATION
This is an overcurrent function applied to the vectorial
sum of phase currents, being its function to detect faults
to earth. Each winding features two levels. Lockout relay (86)

Relays programme with this function will act when the


differential unit acts (instantaneous or percentage type)
Current unbalance (46) so that they can be used as a locking device for breaker
close circuits.
This function protects the installation against current
unbalances resulting from anomalies in the power Protection function locking
system or unbalanced loads.
Each protection function may be locked via a digital
Thermal Image (49) input.

The thermal image unit protects the transformer against


damage resulting from heating up during overloads. This
unit is based on the calculation of winding temperature MONITORING FUNCTION
via thermal image.

Breaker failure protection (50BF) Trip circuit supervision (74TC)

It verifies the breaker correct actuation clearing a fault, This feature detects any anomalies in the circuit with the
causing, otherwise, the trip of the necessary breakers to switch open or close. It detects trip circuit supply failure
clear that fault. of circuit breaker, tripping mechanism failure like circuit
breakage contact degeneration in wires, contacts and
coils.
Frequency protection (81O/U)

This unit features 2 frequency steps that may be


independently set as maximum frequency or minimum
frequency units, allowing load shedding.

Over-under voltage protection (59/27)

This unit protects transformers against overvoltages and


undervoltages, giving a trip command when the voltage
exceeds or drops below a set level for a set time.

Overexcitation protection (24)

The overexcitation unit prevents transformers from


working at a greater flow density than that for which they
were designed. Avoiding heatings and consequent
damage in the transformer due to overexcitation.
This unit is based on V/Hz overexcitation detection
method with two independent levels.

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
DATA ACQUISITION FUNCTION Disturbance Record

Measurements The CSEZenT/G relay has an oscillograph data recorder


with the following characteristics:
 Oscilloscopic recording can trigger on Pickup or
 L1,L2,L3 phase current measurements in
on trip or by DI. It is programmable.
primary winding
 Each record comprises the samples from 8
 L1,L2,L3 phase current measurements in
analog signals and the status of 16 digital inputs
secondary winding
and 16 digital outputs.
 L1,L2,L3 differential current measurements
 30 samples per cycle
 Earth current measurement
 It is saved a maximum of 1500 cycles, and the
 Restricted earth current measurement
number of cycles per record is programmable
 Current Maxi-meter
(for example: if 50 cycles are selected, there will
 Voltage
be there will be 30 records of 50 cycles).
 Frequency
 The prefault and postfault cycles are
programmable
 Records in non volatile memory
 The disturbances are collected and exported to
PC using USB interface. The data is graphically
displayed and can be taken on printer.

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Fault Record Event Record

CSEZenT/G records last 50 faults in its non volatile The unit stores in non volatile memory the last 200
memory with it’s time stamp. Each record has the events. When the available memory space is
following information: exhausted, the new fault automatically overwrites the
oldest Fault. Which can be retrieved from a PC, with the
 Magnitude of primary phase current’s, following data:
secondary phase current’s  Date and time of the event
 Magnitude of Restricted earth Fault current’s &  Descriptive text of the event
earth current
 Magnitude of differential phase current’s, The user can view event records via the front USB
second & fifth harmonic of differential phase interface software
current’s
 Date and time of fault
 Origin of fault (over current, differential, etc.)

The user can view fault records either via the front USB
interface software or remotely via the RS 485
communication.

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
MAN-MACHINE INTERFACES
CSEZenT460 offers a variety of front user interfaces, including:

Human-Machine Interface (HMI)

It comprises of Alphanumeric display and 9 push buttons for setting and other operations for local access:

 Five push switches for set values of normal tripping characteristics including a RESET push switch.
 2 push switches for the tripping of relay assigned to F1Key &F2Key
 2 push switches for the tripping of relay assigned to Circuit breaker open & Circuit breaker close.
 10 Programmable LEDs for pickup or tripping on fault’s & events.

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Communication: Local and remote USB Pen-Drive interface for data storage
device
The unit has:
 1 front USB port for direct connection to a PC
The CSEZenT has front USB port for transferring all the
 1 rear RS485 communication port
data like fault history, event history, editable parameter’s
setting of both group’s (group1,group2) from
Rear port’s programmable communication CSEZenT460 relay to data storage device & also to
protocols transfer editable parameter’s setting of both group’s
from storage device to CSEZenT460 relay.
The protocol for the rear port is programmable. The user
can choose either MODBUS or IEC 870-5-103
The CSEZenT460 includes an RS485 communication
PC interface on terminal A33 and A34 .This communication is
available for “MODBUS™” protocols. CSEZenT460
All the group’s setting, Fault, Event & Disturbance relay can transmit to the monitoring or SCADA system,
record is available on USB interface with CSE LIVELINK settings, measurements and last fault. A communication
with saving & printing option. This unit also has Front- failure dose not affects the protection functions of
end Live Link simulation support for testing of relay even CSEZenT460 relay.
without any three phase injection source.

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
SETTING RANGES
Over Current Protection:

Setting Parameter Minimum Value Maximum Value Unit Step Tolerances


Blocking of Current
Protection NO YES
(BLOCK)
Phase Charactristics EINV,VINV, LINV,
DEFT
(CHAR) NINV1.3, NINV3.0

OverLoad Current ± 5 % from set value


0.2 4 xIn 0.05
Setting(Ipkup)
Overload inverse ± 3 % ± 20 ms
0.01 1.5 - 0.005
timing(ti)
+ 5% +20msec for VINV ,
NINV3.0/1.3
+ 7.5% + 20msec for
OverLoad Definite
0.1 150 Second 0.01 EINV , NINV0.6
timing(t)
Accuracy as per IEC-255-
3 within
I> (2 x IN to 40 x IN)

Short circuit Protection:

Minimum Maximum
Setting Parameter Unit Step Tolerances
Value Value
Blocking of Short Circuit
Current Protection NO YES
(BLOCK)
Short Circuit Current ± 5 % from set value
0.5 40 xIn 0.5
Setting(Ipkup)
Short Circuit defininte
0.02 20 Second 0.01 ± 5 % ± 20 ms
timing(t)

Restricted earth protection:

Setting Parameter Minimun Value Maximun Value Unit Step


Restricted Earth Fault Protection(Only star side will be protected)
Blocking of REF Protection(BLOCK) NO YES
Earth CT correction factor(ECTcorr) 0.1 4 0.01
Min. REF Pickup (m0_REF) 0.04 1 - 0.02
REF First Slope (m1REF) 10 100 % 1
Start point of slope (k1_REF) 0.04 3 - 0.02
Added Delay 0 60 sec 0.01

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Earth OverCurrent Protection:

Setting Parameter Minimun Value Maximun Value Unit Step Tolerances


Earth CT ratio 1 999 1
Blocking of Earth Low
Set Current Protection NO YES
(BLOCK)
Phase Characteristics EINV,VINV,LINV,
DEFT
(CHAR) ,NINV
Earth Low Set Current ± 5 % from set value
0.05 2.5 xIn 0.05
Setting (Ie_pkup)
Earth Low Set inverse ± 3 % ± 20 ms
0.01 1.5 Second 0.005
timing(ti)
+ 5% +20msec for
VINV,NINV3.0/1.3
+ 7.5% +20msec for
Earth Low Set Definite
0.03 150 Second 0.01 EINV , NINV0.6
timing(t)
Accuracy as per IEC-
255-3 within
I> (2 x IE to 40 x IE)
Blocking of Earth
HiSet Current NO YES
Protection(BLOCK)
Earth HiSet Current ± 5 % from set value
0.5 8 xIn 0.05
Setting(Ie_pkup)
Earth HiSet definite
0.02 20 Second 0.01 ± 5 % ± 20 ms
timing(t)

Differential Protection:
Percentage Differential Protection
Blocking of Differential
Protection(BLOCK) NO YES
Yd3/Yd5/Yd7/Yd9/Yd11/Dy1/Dy3/Dy5/
Dy7/Dy9/Dy11/YY0/DD0/YY2/DD2/YY
Vector Group Yd1 4/DD4/YY6/DD6/YY8/DD8/YY10/DD10
Primary CT correction factor(PriCTcorr) 0.3 1.5 0.01
Secondary CT correction
factor(SecCTcorr) 0.3 1.5 0.01
Added Delay 0 60 sec 0.01
Min. Pickup Current (m0) 0.04 1 amp 0.02
1st Slope (m1) 10 100 % 1
2nd Slope (m2) 10 100 % 1
Start point of 1st slope (k1) 0.04 2 amp 0.02
Start point of 2nd slope (k2) 1 10 amp 0.1
Instantaneous Transformer Differential Protection
Blocking of Differential
Protection(BLOCK) NO YES
Added Delay 0 60 sec 0.01
Hiset setting(HiSet) 5 15 amp 1
Differential Protection blocking on Harmonic
Protection Blocking on
harmonic(PDIFF BLOCK on H) NO YES
Second harmonic blocking limit(2ndH) 20 50 % 5
Fifth harmonic blocking limit(5thH) 20 50 % 5
Issue Date: 25:11:09
Revision No :1 Date: 02:03:10
Trip circuit supervision (74TC):

Setting Parameter Minimum Value Maximum Value Unit Step


Trip Circuit SuperVision
Blocking(BLOCK) NO YES
TCS Timing(td) 0.03 2 Second 0.01

Rear port communication setting:

RS485 Communication
Protocol : MODBUS RTU
Baud rate selection : 2400/4800/9600/19200 baud
Parity selection : Even/Odd/None
Stop Bit : 1 bit
Data Bit : 8 bit data
Remote Address : To be specified in the “Edit” menu of the relay(1 to 32)

Relay setting:

These are the setting’s common for all the protections –

Setting Parameter Minimum Value Maximum Value Unit Step


Common Setting
Phase CT Ratio 1 999 1
Earth CT Ratio 1 999 1
Voltage PT Ratio 1 999 1
Nominal frequency 50 60 Hz

TECHNICAL DATA

Measuring Input

Rated data : Rated current IN 1A or 5A


Rated frequency FN 50Hz/60Hz
Power consumption in current circuit : At IN = 1A 0.2 VA
At IN = 5A 0.1 VA
Thermal withstand capability in : dynamic current withstand (half- 250 x IN
current circuit wave)
for 1 s 100 x IN
for 10 s 30 x IN
continuously 4 x IN
Rated data : Normal Voltage UN 100V,230 V,400V
Thermal withstand in voltage circuit : continuously 1.5XUN

Measurement accuracy

Quantity Range Frequency Accuracy


Range
Current 1.0-20xIn 50-60Hz Less then ± 2 %
20-40xIn 50-60Hz Less then ± 2 %

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Auxiliary Supply

Rated auxiliary voltage UH : Universal 80 VAC to 300 VAC


100 VDC to 270 VDC
Rated supply for digital input : Normal Voltage UN 100VDC/AC
Power consumption : Quiescent approx. 3W Operating appx 6W

Common Data

Dropout ratio : > 97 %


Returning time : 30 ms
Time lag error class index E : ± 10 ms
Minimum operating time : 30 ms
Transient overreach at instantaneous :
≤5 %
operation

Type Test

Design standard : VDE 04335, part 303, IEC 255-4, BS 142


Specified ambient service Temp. range : - 40 ºC to + 85 º C
For storage - 20 ºC to + 70 ºC
For operation
Environmental protection class F as per DIN : Relative humidity 95 % at 40 ºC for 56 days
40040 and per DIN IEC 68, part 2.3
Isolation test voltage, inputs and outputs : 2.5 kV (eff.) / 50 Hz, I min.
between themselves and to the relay frame as
per VDE 0435, part 303
Impulse test voltage, inputs and outputs : 5 kV; 1.2 / 50µs; 0.5.
between themselves and to the relay frame as
per VDE IEC 0435, part 303
High frequency interference test voltage, : 2.5 kV / 1 MHz
inputs and outputs between themselves and to
the relay frame as per DIN IEC 255, part 22-1
Electrical fast transient (Burst) test as per DIN : 4 kV / 2.5 kHz, 15 ms
VDE 0843, part 4
Radio interference suppression test as per DIN : Limit value class B
VDE 57 871
Electrostatic discharge (ESD) test as per DIN : 8 kV
VDE 0843 part 2
Radiated electromagnetic field test as per VDE : 10 V / m
0843 part 2

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Mechanical Tests

Shock : As per DIN IEC 41 B (CO) 38 : class 1


Vibration : As per DIN IEC 41 B (CO) 35 : class 1
Protection-front panel : IP 54
Protection-rear panel : IP 00
Weight : Approx. 1.5 kg

CONNECTION DIAGRAM

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
DIMENSIONAL DETAILS

Front View

Side View

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
Top View

Back View

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10
SELECTION TABLE

CSEZen - - - - - - - -

Transformer T
Generator G

MODEL-No
260
380

Auxiliary Supply
18-60 VDC/VAC AX1
86-280 VDC/VAC AX2

DIGITAL INPUTS Voltage Range


Range:18-60 VDC (48V) DV1
Range:86-280 VDC ( 110V) DV2

DIGITAL INPUT
8 -DI D1
16 -DI D2

DIGITAL OUTPUT
8-DO DO1
16-DO DO2

COMMUNICATION PROTOCOL
RS 485 with MODBUS A
RJ 45 with MODBUS B
RS 485 with IEC60870-5-103 C
RJ 45 with IEC 61850 D

TIME SYNCH
IRIG-B I

Continuous improvement of
its products is CS Electric
ltd one of the main
objectives, consequently this
catalogue’s information, can
be modified. To get
completer information,
consult the manual or
contact our sales department

Issue Date: 25:11:09


Revision No :1 Date: 02:03:10