Академический Документы
Профессиональный Документы
Культура Документы
Technologies
Mu Wei, Zhe Chen
Department of Energy Technology, Aalborg University, Denmark
mwe@iet.aau.dk, zch@iet.aau.dk
3329
In this paper the second layer (Data Link Layer) is focused EMTDC/PSCAD is a fast, accurate, and easy-to-use power
to investigate the effects of LANs protocols on the power system simulation software for the design and verification of
system protection. Therefore the following Data Link Layer- all types of power systems. It is the visual design tool of
based LAN access techniques: Ethernet is elaborated. choice at commercial, industrial, and research organizations
B. LANs access technologies: Ethernet worldwide.
Ethernet defines a number of wiring and signaling The studied scenario is selected as bellow.
standards for the Physical Layer of the ISO reference A. Distribution power system scenario
networking model, through the means of network access at The single line of the distribution power system scenario is
the Media Access Control (MAC) /Data Link Layer, and a displayed in Fig. 4. It contains a 9 MW CHP and 3 wind
common addressing format. Ethernet is standardized as IEEE turbines of 600 kW. After the circuit breaker disconnecting
802.3. The combination of the twisted pair versions of the grid at 6 second, the CHP works standalone. Subsequently
Ethernet for connecting end systems to the network, along a three-phase-ground fault occurs at 15 second as shown in
with the fiber optic versions for site backbones, is the most Fig. 4. Once the fault happens, the closest (instantaneous)
widespread wired LAN technology. It supports all popular relay is supposed to send trip signal to the circuit breaker and
network and higher-level protocols. Traditional Ethernet the remote relays also pick up. However in case the
supports data transfers at the rate of 10 Megabits per second instantaneous relay does not work, then the trip signal will be
(Mbps). As the performance needs of LANs have increased, sent by the remote backup relays to clear the fault with some
the industry created additional Ethernet specifications for Fast delay. It happens sometimes, but it is critical, especially when
Ethernet and Gigabit Ethernet. the active distribution system is disconnected with the grid,
In this paper the switched Ethernet is selected due to the like in this scenario, the active distribution power system may
higher data transmission speed compared with the shared lose the stability, the collapse therewith happens.
Ethernet. Accordingly the communication nodes are all
connected to a switch. [9]
C. Structure of the communication network for the power
transmission system protection
A way of a communication network combined with a
power system is displayed in Fig. 3.The IED represents
Intelligent Electronics Device, who are the main components
collect data from the power system, and also deliver Fig. 4. Active distribution power system scenario.
commands to the power system.
In this case, the fault lasts for 150 ms, if the instantaneous
protection fails to operate, then the remote circuit breaks
should pick up and disconnect the fault line within a preset
time limit. The specific time arrangement for the operation of
the circuit breakers and the fault are as presented in Fig. 5.
Consequently, if the disconnection of the faulted line is
delayed according to the remote protection presetting, the
stability of the islanded distribution power system maybe in
risk. In order to avoid the instability, some protection
Fig. 3. A structure of combining a communication network and a power algorithms are developed to manage this fault protection.
system.
3330
B. Power system simulation results with conventional protection such as load shading, it may loss load and even cause system
scheme collapse.
The distribution power system in the given scenario is
simulated by the EMTDC/PSCAD. 2
Mechanical Speed
At 6 second, the switch disconnects the grid; thereby the Electrical Torque
islanded distribution power system experiences a transition of 1.5 Mechanical Torque
seven seconds, at nearly 13 second the distribution system is
recovered and returns stable again, which is as displayed in
Fig. 6. The CHP keeps stable operation during the 1
[pu]
second, reclosed successfully at 15.4 second), as illustrated in 0.5
Fig. 7.
55 0
-0.5
50 14 15 16 17 18 19 20 21 22 23 24
Time (s)
Fig. 8. WTs lose stability after fault.
Ws (Hz)
46
15 16 17 18 19 20 21
Time (s)
Fig. 7. Rotor speed of CHP after fault.
3331
Fig. 9. Hierarchical topology IED Ethernet LAN for distribution power Fig. 12. IED Ethernet LAN ETE delay for distribution power system.
system.
Some of the extracted simulation data are listed in Table II.
TABLE II
IED ETHERNET LAN ETE DELAY FOR DISTRIBUTION POWER SYSTEM
Simulation Simulation
Delay (ms) Delay (ms)
Time (hour) Time (hour)
0.24 3.691696 2.40 3.701328
0.48 3.696932 2.64 3.701676
0.72 3.693941 2.88 3.701624
0.96 3.698742 3.12 3.702851
1.2 3.697538 3.36 3.701824
Fig. 10. Application deployment of the IED LAN. 1.44 3.699555 3.60 3.702334
1.68 3.70057 3.84 3.702197
The transferred file size is determined by the IED 1.92 3.700553 4.08 3.702722
2.16 3.700554 4.32 3.703426
categories. Suppose a monitoring instrument samples three-
phase voltages and three-phase currents, and it samples 128
data points per period for each analogue input channel, and E. Power system simulation results with communication
each sampling data is represented by 2 bytes. Then there are technology based protection scheme
6*128*2=1536 bytes transmitted every 20ms, and the data By introducing the IED Ethernet LAN ETE delay attribute
transmission speed is 1536*50=76800 bytes per second [11]. to the distribution power system [12], the distribution power
In this case, the size is thereby determined as 76800 bytes as system in the given scenario is simulated by the
shown in Fig. 11. EMTDC/PSCAD. In this condition, the remote circuit
breakers operation delay, according to the ETE delay of the
IED Ethernet LAN, which has been demonstrated in Part D as
-3
about 3.707×10 s. The corresponding specific time
arrangement of the fault and CBs are presented in Fig. 13.
The islanded distribution power system simulation results
show that not only the islanded distribution power system,
but also the WTs indeed keep stable under the control of the
IED Ethernet LAN, as illustrated in Fig. 14 and Fig. 15.
5
7
.4
.1
70
70
15
1
15
03
03
3.715
.2
15
15
3.71
Fig. 13. Fault and CBs time arrangements with Ethernet LAN.
3.705
3.7
ETE delay (ms)
3.695
3.69
3.685
3.68
3.675
3.67
0 5 10 15 20 25
Simulation Time (hour)
3332
52 with IEDs’ communication and without IEDs’
communication. Finally it is illustrated that with
51 communication technologies the amount of calculation
burden of the power system is dramatically reduced, thereby
the system responses accelerated rapidly, which can better
50
meet the power system stability and reliability requirements,
though the cost of such communication system would be
Ws (Hz)
0.5
in a Deregulated Environment,” Proceedings of the Hawaii‘s
International Conference on System Sciences, Maui, Hawaii, January
1999, pp. 1–8.
0
[6] P. M. Anderson, “Power System Protection”, McGraw-Hill, pp. 218,
1999
-0.5
[7] J. Duncan Glover and Mulukutla S. Sarma, “Power System Analysis
and Design,” Thomson Learning, pp. 438-491, 2002.
[8] IEC 61850, IEC, Geneva, Switzerland.
-1 [9] J. D. Gibson, The Communications Handbook, CRC Press, 2002.
15 16 17 18 19 20 21 22 23 24
[10] Access date 11th, March, 2010, http://en.wikipedia.org/wiki/OSI_model.
Time (s)
[11] Yanqiu Bi, Jianguo Zhao, and Dahai Zhang, “Research on Power
Fig. 15. WTs are stable after fault with Ethernet LAN. Communication Network and Power quality Monitoring Using
OPNET,” Second IEEE Conference on Industrial Electronics and
Applications, pp. 507-511, 2007.
By comparing Fig. 8 (WTs under the condition without [12] Mu Wei, and Zhe Chen, “Communication Systems and Study Method
communication IEDs) and Fig. 15 (WTs under the condition for Active Distribution Power System”, NORDAC 2010 Conference,
with communication IEDs), the conclusion can be drawn out accepted, September, 2010.
that the WTs in the distribution power system with
communication technologies under some scenarios, can easily
keep stable operation, which outstands the impact of
communications in power system.
V. CONCLUSION AND FUTURE WORK
The significance of the communication technologies is
demonstrated in the islanded distribution power system
protection by a practical case in this paper. Firstly the
Ethernet LAN based communication network is configured,
and the LAN’s ETE delay attribute is obtained by the OPNET
simulation. Secondly by deploying this attribute to the power
system, the islanded distribution power system with WTs is
simulated in the fault scenario with the instantaneous circuit
breaker fails to operate. The islanded distribution power
system’s performance is investigated and compared between
3333