COOLING AND HEATING LOADS FOR LOBBY

LOAD COMPONENT EQUATIONS DATA INPUT SENSIBLE LATENT HEATING

LOAD (QS) LOAD (QL) LOAD (QH)


QS=U (WALL) X A X CLTD ORIENTAION U(WALL) CLTD TD(W) A
QH=U (WALL) X A X TD(W) NORTH 2 7.5 24 0 0 0
EAST 2 9.5 24 0 0 0
SOUTH 2 8.5 24 0 0 0
WEST 2 16.5 24 0 0 0
GLASS ORIENTAION U(GLASS) CLTD TD(W) A
(CONDUCTION) QS=U (GLASS) X A X CLTD
QH=U (GLASS) X A X TD(W) NORTH 4 8.5 24 0 0
EAST 4 2.5 24 0 0 0
SOUTH 4 8.5 24 0 0
WEST 4 8.5 24 0 0 0
GLASS ORIENTAION SC SCL A
(RADIATION) QS= A X SC X SCL
NORTH 0.8 120 0
EAST 0.8 510 0
SOUTH 0.8 274 0
WEST 0.8 463 0 0
ROOF QS=U (ROOF) X A X CLTD U(ROOF) CLTD TD(W) A
QH=U (ROOF) X A X TD(W) 1.17 27 24 0 0
CEILING QS=U (CEILING) X A X TD(S) U(ROOF) TD(S) TD(W) A
QH=U (CEILING) X A X TD(W) 2.2 6 12 0 0 0
FLOOR QS=U (FLOOR) X A X TD(S) U(FLOOR) TD(S) TD(W) A
QH=U (FLOOR) X A X TD(W) 2.2 6 12 0 0 0
PARTITION QS=U (PARTITION) X A X TD(S) U(PARTITION) TD(S) TD(W) A
QH=U (PARTION) X A X TD(W) 2.16 6 12 0 0 0
LIGHTING QS=W X CLF CLF W
0.9 0 0
PEOPLE QS= NO X SHGXCLF SHG LHG CLF NO
QL= NO X LHG 70 45 0.9 0 0 0
APPLIANCES QS= PRXCLF CLF PR
0.9 0 0
INFILTRATION QS=1.23 X ACH X VOL X TD(S)/3.6 TD(S) HRD(S) TD(W) ACH VOL
QL=3010 X ACH X VOL X HRD(S)/3.6
QH=1.23 X ACH X VOL X TD(W)/3.6 12 0.00125 24 0 0 0 0 0
VENTILATION QS=1.23 X AFR X TD(S) TD(S) HRD(S) TD(W) AFR
QL=3010 X AFR X HRD(S)
QH=1.23 X AFR X TD(W) 12 0.00125 24 0 0 0 0
TOTAL (WATT) 0 0 0
ROOM LOAD (WATT) 0 0 0
CFM 0

DEFINITIONS:
QS SENSIBLE LOAD COMPONENT (W)
QL LATENT LOAD COMPONANT (W)
QH HEATING LOAD (W)
U(WALL) OVERALL HEAT TRANSFER COEFFICIENT FOR EXTERNAL WALL (W/M2.C)
U(ROOF) OVERALL HEAT TRANSFER COEFFICIENT FOR ROOF (W/M2.C)
U(CEILING) OVERALL HEAT TRANSFER COEFFICIENT FOR CEILING (W/M2.C)
U(FLOOR) OVERALL HEAT TRANSFER COEFFICIENT FOR FLOOR (W/M2.C)
U(PARTITION) OVERALL HEAT TRANSFER COEFFICIENT FOR INTERNAL PARTION (W/M2.C)
A AREA (M2)
CLTD COOLING LOAD TEMPERATURE DIFFERENCE (C)
TD TEMPERATURE DIFFERENCE (C)
HRD HUMIDITY RATIO DIFFERENCE (KG/KG)
CLF COOLING LOAD FACTOR
NO. NUMBER OF PEOPLE
SHG PERSON SENSIBLE HEAT GAIN
LHG PERSON LATENT HEAT GAIN
AFR AIR FLOW RATE (L/SEC)
W LIGHT (W) RATE
PR EQUIPMENT INPUT ELEC. POWER
ACH AIR CHANGES PER HOURS
VOL ZONE VOLUME (M3)

DESIGN CONDITIONS
SUMMER WINTER
Tout DB 35 0
Tin DB 23 24
T WB 21
HUMIDITY RATIO 50%
DAILY OUTDOOR
TEMPERATURE
RANGE 13
CALCULATION SHEET NO. (1)
COOLING AND HEATING LOADS FOR DINING HALL

LOAD COMPONENT EQUATIONS DATA INPUT SENSIBLE LATENT HEATING

LOAD (QS) LOAD (QL) LOAD (QH)


QS=U (WALL) X A X CLTD ORIENTAION U(WALL) CLTD TD(W) A
QH=U (WALL) X A X TD(W) NORTH 2.5 7.5 24 52.4 983 3144
EAST 2.5 9.5 24 71.2 1691 4272
SOUTH 2.5 8.5 24 4.2 89 252
WEST 2.5 16.5 24 31.8 1312 1908
GLASS ORIENTAION U(GLASS) CLTD TD(W) A
(CONDUCTION) QS=U (GLASS) X A X CLTD
QH=U (GLASS) X A X TD(W) NORTH 6 8.5 24 8.8 449 1267
EAST 6 2.5 24 22 330 3168
SOUTH 6 8.5 24 0 0
WEST 6 8.5 24 13.2 673 1901
GLASS ORIENTAION SC SCL A
(RADIATION) QS= A X SC X SCL
NORTH 0.8 120 8.8 845
EAST 0.8 510 22 8976
SOUTH 0.8 274 0
WEST 0.8 463 13.2 4889
ROOF QS=U (ROOF) X A X CLTD U(ROOF) CLTD TD(W) A
QH=U (ROOF) X A X TD(W) 1.17 27 24 0 0
CEILING QS=U (CEILING) X A X TD(S) U(ROOF) TD(S) TD(W) A
QH=U (CEILING) X A X TD(W) 2.2 6 12 260 3432 6864
FLOOR QS=U (FLOOR) X A X TD(S) U(FLOOR) TD(S) TD(W) A
QH=U (FLOOR) X A X TD(W) 2.2 6 12 260 3432 6864
PARTITION QS=U (PARTITION) X A X TD(S) U(PARTITION) TD(S) TD(W) A
QH=U (PARTION) X A X TD(W) 2.16 6 12 48.6 630 1260
LIGHTING QS=W X CLF CLF W
0.9 3900 3510
PEOPLE QS= NO X SHGXCLF SHG LHG CLF NO
QL= NO X LHG 70 45 0.9 100 6300 4500
APPLIANCES QS= PRXCLF CLF PR
0.9 2000 1800
INFILTRATION & TD(S) HRD(S) TD(W) AFR
VENTILATION QS=1.23 X AFR X TD(S)
QL=3010 X AFR X HRD(S)
QH=1.23 X AFR X TD(W) 12 0.00125 24 1000 14760 3763 29520
TOTAL (WATT) 54100 8263 60420
ROOM LOAD (WATT) 39340 4500 30900
CFM 6098

DEFINITIONS:
QS SENSIBLE LOAD COMPONENT (W)
QL LATENT LOAD COMPONANT (W)
QH HEATING LOAD (W)
U(WALL) OVERALL HEAT TRANSFER COEFFICIENT FOR EXTERNAL WALL (W/M2.C)
U(ROOF) OVERALL HEAT TRANSFER COEFFICIENT FOR ROOF (W/M2.C)
U(CEILING) OVERALL HEAT TRANSFER COEFFICIENT FOR CEILING (W/M2.C)
U(FLOOR) OVERALL HEAT TRANSFER COEFFICIENT FOR FLOOR (W/M2.C)
U(PARTITION) OVERALL HEAT TRANSFER COEFFICIENT FOR INTERNAL PARTION (W/M2.C)
A AREA (M2)
CLTD COOLING LOAD TEMPERATURE DIFFERENCE (C)
TD TEMPERATURE DIFFERENCE (C)
HRD HUMIDITY RATIO DIFFERENCE (KG/KG)
CLF COOLING LOAD FACTOR
NO. NUMBER OF PEOPLE
SHG PERSON SENSIBLE HEAT GAIN
LHG PERSON LATENT HEAT GAIN
AFR AIR FLOW RATE (L/SEC)
W LIGHT (W) RATE
PR EQUIPMENT INPUT ELEC. POWER

DESIGN CONDITIONS
SUMMER WINTER
Tout DB 35 0
Tin DB 23 24
T WB 21
HUMIDITY RATIO 50%
DAILY OUTDOOR
TEMPERATURE
RANGE 13
CALCULATION SHEET NO. (1)
COOLING AND HEATING LOADS FOR CORODOR

LOAD COMPONENT EQUATIONS DATA INPUT SENSIBLE LATENT HEATING

LOAD (QS) LOAD (QL) LOAD (QH)


QS=U (WALL) X A X CLTD ORIENTAION U(WALL) CLTD TD(W) A
QH=U (WALL) X A X TD(W) NORTH 0.86 7.5 24 0 0
EAST 0.86 9.5 24 0 0
SOUTH 0.86 8.5 24 0 0
WEST 0.86 16.5 24 0 0
GLASS ORIENTAION U(GLASS) CLTD TD(W) A
(CONDUCTION) QS=U (GLASS) X A X CLTD
QH=U (GLASS) X A X TD(W) NORTH 3.41 8.5 24 0 0
EAST 3.41 2.5 24 0 0
SOUTH 3.41 8.5 24 0 0
WEST 3.41 8.5 24 0 0
GLASS ORIENTAION SC SCL A
(RADIATION) QS= A X SC X SCL
NORTH 0.55 120 0
EAST 0.55 510 0
SOUTH 0.55 274 0
WEST 0.55 463 0
ROOF QS=U (ROOF) X A X CLTD U(ROOF) CLTD TD(W) A
QH=U (ROOF) X A X TD(W) 1.17 27 24 0 0
CEILING QS=U (CEILING) X A X TD(S) U(ROOF) TD(S) TD(W) A
QH=U (CEILING) X A X TD(W) 2.2 6 12 45 594 1188
FLOOR QS=U (FLOOR) X A X TD(S) U(FLOOR) TD(S) TD(W) A
QH=U (FLOOR) X A X TD(W) 2.2 6 12 45 594 1188
PARTITION QS=U (PARTITION) X A X TD(S) U(PARTITION) TD(S) TD(W) A
QH=U (PARTION) X A X TD(W) 2.16 6 12 30.6 397 793
LIGHTING QS=W X CLF CLF W
0.9 675 608
PEOPLE QS= NO X SHGXCLF SHG LHG CLF NO
QL= NO X LHG 70 45 0.9 3 189 135
APPLIANCES QS= PRXCLF CLF PR
0.9 250 225
INFILTRATION & TD(S) HRD(S) TD(W) AFR
VENTILATION QS=1.23 X AFR X TD(S)
QL=3010 X AFR X HRD(S)
QH=1.23 X AFR X TD(W) 12 0.00125 24 30 443 113 886
TOTAL (WATT) 3049 248 4055
ROOM LOAD (WATT) 2606 135 3169
CFM 404
DEFINITIONS:
QS SENSIBLE LOAD COMPONENT (W)
QL LATENT LOAD COMPONANT (W)
QH HEATING LOAD (W)
U(WALL) OVERALL HEAT TRANSFER COEFFICIENT FOR EXTERNAL WALL (W/M2.C)
U(ROOF) OVERALL HEAT TRANSFER COEFFICIENT FOR ROOF (W/M2.C)
U(CEILING) OVERALL HEAT TRANSFER COEFFICIENT FOR CEILING (W/M2.C)
U(FLOOR) OVERALL HEAT TRANSFER COEFFICIENT FOR FLOOR (W/M2.C)
U(PARTITION) OVERALL HEAT TRANSFER COEFFICIENT FOR INTERNAL PARTION (W/M2.C)
A AREA (M2)
CLTD COOLING LOAD TEMPERATURE DIFFERENCE (C)
TD TEMPERATURE DIFFERENCE (C)
HRD HUMIDITY RATIO DIFFERENCE (KG/KG)
CLF COOLING LOAD FACTOR
NO. NUMBER OF PEOPLE
SHG PERSON SENSIBLE HEAT GAIN
LHG PERSON LATENT HEAT GAIN
AFR AIR FLOW RATE (L/SEC)
W LIGHT (W) RATE
PR EQUIPMENT INPUT ELEC. POWER

DESIGN CONDITIONS
SUMMER WINTER
Tout DB 35 0
Tin DB 23 24
T WB 21
HUMIDITY RATIO 50%
DAILY OUTDOOR
TEMPERATURE
RANGE 13
CALCULATION SHEET NO. (1)
COOLING AND HEATING LOADS FOR BATHROOM

LOAD COMPONENT EQUATIONS DATA INPUT SENSIBLE LATENT HEATING

LOAD (QS) LOAD (QL) LOAD (QH)


QS=U (WALL) X A X CLTD ORIENTAION U(WALL) CLTD TD(W) A
QH=U (WALL) X A X TD(W) NORTH 2 7.5 24 0 0
EAST 2 9.5 24 8.25 157 396
SOUTH 2 8.5 24 23 391 1104
WEST 2 16.5 24 0 0
GLASS ORIENTAION U(GLASS) CLTD TD(W) A
(CONDUCTION) QS=U (GLASS) X A X CLTD
QH=U (GLASS) X A X TD(W) NORTH 6 8.5 24 0 0
EAST 6 2.5 24 0 0
SOUTH 6 8.5 24 0 0
WEST 6 8.5 24 0 0
GLASS ORIENTAION SC SCL A
(RADIATION) QS= A X SC X SCL
NORTH 0.8 120 0
EAST 0.8 510 0
SOUTH 0.8 274 0
WEST 0.8 463 0
ROOF QS=U (ROOF) X A X CLTD U(ROOF) CLTD TD(W) A
QH=U (ROOF) X A X TD(W) 1.17 27 24 0 0
CEILING QS=U (CEILING) X A X TD(S) U(ROOF) TD(S) TD(W) A
QH=U (CEILING) X A X TD(W) 2.2 6 12 23.7 313 626
FLOOR QS=U (FLOOR) X A X TD(S) U(FLOOR) TD(S) TD(W) A
QH=U (FLOOR) X A X TD(W) 2.2 6 12 23.7 313 626
PARTITION QS=U (PARTITION) X A X TD(S) U(PARTITION) TD(S) TD(W) A
QH=U (PARTION) X A X TD(W) 2.16 6 12 0 0
LIGHTING QS=W X CLF CLF W
0.9 355.5 320
PEOPLE QS= NO X SHGXCLF SHG LHG CLF NO
QL= NO X LHG 70 45 0.9 3 189 135
APPLIANCES QS= PRXCLF CLF PR
0.9 200 180
INFILTRATION & TD(S) HRD(S) TD(W) AFR
VENTILATION QS=1.23 X AFR X TD(S)
QL=3010 X AFR X HRD(S)
QH=1.23 X AFR X TD(W) 12 0.00125 24 30 443 113 886
TOTAL (WATT) 2305 248 3637
ROOM LOAD (WATT) 1862 135 2751
CFM 289
DEFINITIONS:
QS SENSIBLE LOAD COMPONENT (W)
QL LATENT LOAD COMPONANT (W)
QH HEATING LOAD (W)
U(WALL) OVERALL HEAT TRANSFER COEFFICIENT FOR EXTERNAL WALL (W/M2.C)
U(ROOF) OVERALL HEAT TRANSFER COEFFICIENT FOR ROOF (W/M2.C)
U(CEILING) OVERALL HEAT TRANSFER COEFFICIENT FOR CEILING (W/M2.C)
U(FLOOR) OVERALL HEAT TRANSFER COEFFICIENT FOR FLOOR (W/M2.C)
U(PARTITION) OVERALL HEAT TRANSFER COEFFICIENT FOR INTERNAL PARTION (W/M2.C)
A AREA (M2)
CLTD COOLING LOAD TEMPERATURE DIFFERENCE (C)
TD TEMPERATURE DIFFERENCE (C)
HRD HUMIDITY RATIO DIFFERENCE (KG/KG)
CLF COOLING LOAD FACTOR
NO. NUMBER OF PEOPLE
SHG PERSON SENSIBLE HEAT GAIN
LHG PERSON LATENT HEAT GAIN
AFR AIR FLOW RATE (L/SEC)
W LIGHT (W) RATE
PR EQUIPMENT INPUT ELEC. POWER

DESIGN CONDITIONS
SUMMER WINTER
Tout DB 35 0
Tin DB 23 24
T WB 21
HUMIDITY RATIO 50%
DAILY OUTDOOR
TEMPERATURE
RANGE 13