DIVISION 31

EARTHWORK
Geofoam Applications
PART 1 − GENERAL
1.01 Scope
Pavement System
A. Material, accessories and quality
assurance practices for block molded
expanded polystyrene (EPS) rigid cellular Fill Mass (EPS blocks
Elevation™ geofoam in road applications, & soil cover, if any)
embankments and bridge approaches on
soft ground.
B. Typical installation techniques are
illustrated in this document, but the scope
of this document does not include design
nor qualification of installation contractors.
1.02 References
A. American Society for Testing and
Materials (ASTM):
1. ASTM D6817 Standard Specification for
Rigid Cellular Polystyrene Geofoam.
2. ASTM D7180 Standard Guide for Use
of Expanded Polystyrene (EPS) in
Geotechnical Projects.
3. ASTM D7557 Standard Practice for Foundation Soil
Sampling of Expanded Polystyrene
Geofoam Specimens.
4. ASTM C578 Standard Specification
for Rigid Cellular Polystyrene Thermal Construction of Highway Embankments. minimum values provided in Section
Insulation. 2. N CHRP Report 529 Guideline and 2.02 and 2.03 of this specification.
5. ASTM C203 Breaking Load and Flexural Recommended Standard for Geofoam 4. Elevation™ geofoam shall be cured
Properties of Block-Type Thermal Applications in Highway Embankments. a minimum of 72 hours at ambient
Insulation. temperature prior to use to allow
C. National Standards of Canada:
6. ASTM C303 Test Method for blowing agent and condensate
1. CAN/ULC S701 Standard for Thermal
Dimensions and Density of Preformed dissipation. Alternately, accelerated
Insulation, Polystyrene, Boards and
Block and Board-Type Thermal curing under heated area conditions
Pipe Coverings.
Insulation. shall be approved.
7. ASTM C2863 Test Method for 1.03 Design Requirements
5. All Elevation™ geofoam blocks shall be
Measuring the Minimum Oxygen A. Performance Requirements:
shop-trimmed (molded edges removed)
Concentration to Support Candle-Like 1. Unless specifically approved,
to assure face trueness and tight
Combustion of Plastics (Oxygen Index). the Elevation™ geofoam shall be
dimensional fit with adjacent blocks.
8. ASTM D1621 Test Method for manufactured using 100% virgin
6. Elevation™ geofoam shall be specified
Compressive Properties of Rigid Cellular feedstock for blocks having no
using the material type designations
Plastics. recycle content.
listed in ASTM D6817 “Standard
9. ASTM D1622 Apparent Density of Rigid 2. Atlas EPS standard size blocks shall
Specification for Rigid Cellular
Cellular Plastics. be used, generally 16 inches to 40
Polystyrene Geofoam”.
10. ASTM E84 Standard Test Method for inches in height, 48 inches width, and
7. In areas where termite damage is
Surface Burning Characteristics of 96 inches length. The use of ½ blocks,
of high concern over long periods,
Building Materials. smaller end pieces and thinner sheets
at the discretion of the engineer
B. National Cooperative Highway may be used as needed to offset joints
per project, the Elevation™ geofoam
Research Program: and complete project geometry.
shall be enhanced TalonGUARD
1. NCHRP Document 65 Geofoam 3. Regardless of dimensions or recycle
EPS approved and field-tested
Applications in the Design and content, product and accessories will
for construction applications.
be required to meet or exceed the
EPS block (typical) EPS block (typical)

Sloped-side fill Sloped-side fill

B. Design Considerations: c) T est reports from UL verifying D6817 requirements.


1. Elevation™ geofoam shall be selected compliance of project types c) Initial type testing in (b) above shall
for elastic compressive performance to ASTM D6817 compressive be repeated for every 650 cubic
as required to resist live and dead load resistance requirements. yards of each ASTM D6817 type
forces anticipated during in situ use d) Signed certification statement delivered to the project.
throughout the life of the structure. submitted from Atlas EPS d) All test results will be kept on
Refer to ASTM D6817 1% Deformation acknowledging the specifications file at Atlas EPS for review by
Compressive Strength minimum values for the project have been read and Underwriters Laboratories.
for elastic limit stress of each type. understood, and that all Elevation™ C. Additional Requirements–applicable
2. Elevation™ geofoam is a thermal geofoam blocks supplied to the only when termiticide-treated Elevation™
insulation which will isolate the project will meet the requirements geofoam is specified by the engineer:
adjoining material from normal in the specification. 1. Atlas EPS shall provide proof of
ground temperatures. As such, freeze B. Elevation™ geofoam block certification– EPA-registered, termiticide-treated
conditions and sufficient earth mass each delivery of Elevation™ geofoam blocks TalonGUARD EPS approved with building
over Elevation™ geofoam must be shall be traceable to compliance testing code regulations.
considered to avoid black ice conditions as follows: 2. The Elevation™ geofoam blocks shall
or other undesirable surface freeze 1. A collective “lot” of Elevation™ geofoam additionally be marked as required per
events of the supported structures. blocks shall be defined as those of the the building code authority.
3. Because the density of Elevation™ same ASTM D6817 type manufactured D. Elevation™ geofoam test blocks:
geofoam is roughly 1% of that of the (molded)consecutively on the same 1. Portions of sampled blocks that are
surrounding dirt, hydrostatic forces must calendar day. used for testing are not acceptable for
be considered and sufficient ballast 2. Each Elevation™ geofoam block shall be construction. Portions of blocks that are
provided over the blocks to prevent marked to include “Atlas EPS”, molded otherwise acceptable can be used as
uplift during the life of the structure. date, individual block identifier and desired by the contractor provided they
1.04 Quality Assurance ASTM D6817 type. comply with any other requirements of
A. Atlas EPS Pre-Certification – No 3. Additionally, for each load requiring a this specification.
Elevation™ geofoam shall be shipped prior 3rd party certification: 2. Any shipment of Elevation™ blocks,
to completion of pre-certification: a) Each Elevation™ geofoam block shall for which the representative samples
1. Atlas EPS shall provide evidence of 3rd be additionally stamped per UL fail to meet the parameters outlined
party certification against ASTM D6817, requirements. in this specification, are considered
including each of the following: b) Each lot of Elevation™ geofoam defective and shall be replaced by
a) Current certification by blocks on the initial project delivery the contractor with non-defective
Underwriters Laboratories specific load per ASTM D6817 type shall Elevation™ blocks at no additional
to ASTM D6817 (QORW.R16529). be sampled according to ASTM cost or time to the project owner.
b) UL Follow-Up Services Procedures D7557 and tested for compliance to
to assure compliance to ASTM Compressive Resistance minimum
D6817. value at 1% deformation per ASTM
EPS block (typical)

Vertical-face fill

1.05 Warranty ignition sources. project, including individual layers of


A. Physical Properties Warranty: Physical 3. P rojects that include petroleum concerns Elevation™ geofoam blocks in multiple-layer
properties shall be warranted to shall include a specification for a projects. The drawing shall include size,
ASTM D6817. puncture-free, low-vapor transmission type, location, connector plate location and
1. Warranty Period: 20 years rated product to protect Elevation™ orientation of all blocks.
beginning with date of substantial geofoam from petroleum products. C. Quality Assurance Submittals: Submit
project completion. 4. Due to the lightweight nature of the following:
B. Termite Preservative Warranty [where Elevation™ geofoam, it is the contractor’s 1. Evidence of Atlas EPS current UL ASTM
applicable]: Performance against termite responsibility to provide temporary D6817 certification, audit procedures
infestation resulting in significant ballast or protection during storage and and test reports verifying compliance of
degradation shall be provided. block placement. each type.
1. Warranty Period: 20 years C. Handling: Elevation™ geofoam may be cut, 2. Atlas EPS-signed certification letter to
beginning with date of substantial drilled, sawn, sanded, rasped, or otherwise supply specification compliant material.
project completion. handled similar to other construction 3. Copy of Atlas EPS test report for
1.06 Delivery, Storage & Handling materials, such as wood. Care should be used capturing compressive property
A. Delivery: Materials shall be delivered in handling to prevent damage to blocks. No performance.
labeled “Atlas EPS”, date of manufacture, heavy construction equipment or vehicles 4. Evidence of building authority-approved
lot #, material type and any marking shall be allowed directly on Elevation™ termiticide TalonGUARD EPS [when
required to assist in installing according to geofoam. Protective sheathing or planks required as part of the specifications].
shop drawings. should be placed on the blocks to allow light D. Warranties
rubber-tired equipment use.
B. Storage and Protection: Store materials 1. Copy of Elevation™ Physical
protected from exposure to harmful 1.07 Submittals Property Warranty.
environmental conditions. Prior to installation of the Elevation™ geofoam 2. Copy of Elevation™ TalonGUARD Termite
1. Avoid prolonged exposure to sunlight, blocks, contractor shall provide engineer: Resistance Warranty [when required as
cover with opaque tarp if stored outside A. Product Data: Submit Elevation™ geofoam part of project specifications].
for more than 30 days. data and installation instructions.
2. Elevation™ geofoam should not be B. Shop Drawings: Provide drawings with a
exposed to open flame or any other profile and section view of the proposed
PART 2 − PRODUCTS shall be filled with sand. 3.02 Installation
2.01 Manufacturers c) E levation™ geofoam blocks with A. General:
A. Atlas EPS, a division of Atlas Roofing excessive damage (i.e., exceeding 1. Install Elevation™ geofoam blocks to
Corporation–Elevation™ geofoam, Geoclips. the “moderate” category) shall be the lines and grades shown in the
1. Corporate office: 8240 Byron Center SW, replaced with blocks which meet the plans and as directed by the engineer.
Byron Center, MI 49315; Telephone: (800) damage criteria. The surface of a layer of blocks to
917-9138; Fax: (616) 878-9942; www. d) Elevation™ blocks not meeting the receive additional Elevation™ geofoam
atlaseps.com www.falcongeofoam. damage criteria may be cut to shall be constructed with a variation
com, multiple locations. eliminate the excessive damage in surface tolerance of no more than
and the remaining undamaged .5-inch any 10-foot interval. No gaps
2.02 Materials
portion of the block may be greater than 2 inches will be allowed
A. Elevation™ geofoam blocks: used within the fill, provided the on vertical joints. Cut and fit tightly
1. Elevation™ geofoam ASTM D6817 types undamaged portion of the block around projections and penetrations.
and physical properties: meets all other requirements. 2. Each subsequent layer of blocks shall

Compressive be offset 90 degrees from the direction
Flexural Oxygen Block
Type Resistance @ 1%
Strength (min) Index (min) Density (min)
of placement of the previous layer or
Deformation (min) otherwise staggered for increased
EPS 15 3.6 psi 25.0 psi 24.0 0.90 pcf stability of the system.
EPS 19 5.8 psi 30.0 psi 24.0 1.15 pcf 3. Secure layers 2 and above with
EPS 22 7.3 psi 40.0 psi 24.0 1.35 pcf
connector plates, using quantity and
pattern recommended by manufacturer
EPS 29 10.9 psi 50.0 psi 24.0 1.80 pcf
on shop drawings to prevent blocks
EPS 39 15.0 psi 60.0 psi 24.0 2.40 pcf from shifting during the backfill stage.
EPS 46 18.6 psi 75.5 psi 24.0 2.85 pcf 4. For projects requiring a load
distribution slab over the top
2. E levation™ geofoam shall not contain 2.03 Accessories surface of Elevation™ geofoam, it is
Formaldehyde, CFCs, HCFCs or other A. Elevation™ geofoam Connector Plates permissible to use rebar supports
volatile components. (Geoclips): (dobies) to support the reinforcing
3. All blocks shall be shop-trimmed as 1. Elevation™ geoclips shall be galvanized steel during concrete placement.
necessary so all surfaces are smooth steel multi-barbed connectors. Each 5. In areas where utilities are placed in
and flat, are within tolerances of +/- connector shall have a lateral holding Elevation™ geofoam, provide space to
0.5% of respective height, width and strength of 60 lbs minimum when accommodate pipe, structures and
length dimensions. Additional field and/ tested with ASTM D6817 type EPS22 conduit system and flowable fill.
or shop cutting or trimming may be Elevation™ geofoam. Install connector
required and shall be done with a saw plates as directed on shop drawings.
or hot wire cutter.
4. Damage to Elevation™ geofoam shall be PART 3 − EXECUTION
corrected as follows: 3.01 Preparation
a) Slight damage (<0.12 cubic feet with A. Clear debris and dewater site as needed.
no linear dimension > 1 ft may be left Grade according to elevations shown on
in place as-is. plans; the finish grade shall be smooth
b) Moderate damage (<0.35 cubic feet and free from holes or protruding objects.
with no linear dimension >3.3 ft) Cover graded area to receive Elevation™
geofoam blocks with sand or other
drainage layer.

ATLAS EPS MANUFACTURING PLANTS ATLAS ROOFING


8240 Byron Center Road SW East – Byron Center, MI – Tel: (800) 917-9138 2000 RiverEdge Parkway
Byron Center, MI 49315 Central – Perryville, MO – Tel: (800) 888-2332 Suite 800
Tel: (800) 917-9138 West – Tijuana, MX – Tel: (866) 811-9517 Atlanta, GA 30328
Fax: (800) 626-9942

©2010 Atlas Roofing Corporation. Atlas EPS is a division of Atlas Roofing. Elevation is a trademark of Atlas Roofing Corporation. A EPS 2010-XX-XXXX