Date: 24-Sep-10

Job discription:

The proposed industrial shead of size 60'x40' in banglore


with 15 tonn crane capacitywith 15 tonn crane capacity

Type of building: Portal frame

Length of building L = 18.288 m


Width of building W = 12.192 m
Height (to the eaves) h = 9.143 m
Height (to the ridge) H = 10.776 m
Roof angle θ = 15.3 Degree

Loading:
Dead load IS 875 (Part 1)-1987
Self weight of the structure
Roof sheeting = 10 kg/m2
False ceiling = 0 kg/m2
Services = 10 kg/m2
Others = 0 kg/m2

Live load = 75 kg/m2 IS 875 (Part 2)-1987

Crane load
Capacity of crane = 15 Tons (Client requirement)
Weight of crane = 14 Tons Appropriate
Reaction on gantry girder = 22 Tons weight of double
girder EOT crane
Wind load IS 875 (Part 3)-1987
Location Banglore
Basic wind speed Vb = 33 m/s
Probability factor k1 = 1 Category 2 Class A Table 1, Page 11
Terrain,height and structure
size factor k2 = 1 Table 2, Page 12
Topography factor k3 = 1 Clause5.3.3,Page 12
Design wind speed Vz = Vb k1 k2 k3
= 33 m/s
Design wind pressure pz = 0.6 Vz 2

= 653.4 N/m2
= 0.6534 kN/m2
External pressure coefficient (Cpe) for walls of rectangular clad building Table 4
h/W = 0.750 Angle A B C D
L/W = 1.500 0 0.7 -0.25 -0.6 -0.6
90 -0.6 -0.6 0.7 -0.25
External pressure coefficient (Cpe) for pitched roof of rectangular clad building Table 5
h/W = 0.750 Angle Wind 0o Wind 90o
θ = 15 EF GH EG FH
-1.1 -0.6 -0.8 -0.6
Internal pressure coefficient (Cpi) = ± 0.5 Openings between 5% to 20% Clause6.2.3,Page 27

Wind coefficient for walls of rectangular clad building


Wind load 0o (Cpe+Cpi)
C
-0.6 -1.1

A B
® ® + ¬ 0.5 ® = ® ®
0.7 -0.25 0.2 -0.75

¯
-0.6 ¯ -1.1 ¯
D

Wind load 0o (Cpe-Cpi)


C
-0.6 -0.1
¯
A B
® ® + ® -0.5 ¬ = ® ¬
0.7 -0.25 1.2 0.25

-0.6 ¯ -0.1 ¯
D

Wind load 90o (Cpe+Cpi)


C
0.7 ¯ 0.2 ¯

A B
¬ ® + ¬ 0.5 ® = ¬ ®
-0.6 -0.6 -1.1 -1.1

¯
-0.25 ¯ -0.75 ¯
D

Wind load 90o (Cpe-Cpi)


C
0.7 ¯ 1.2 ¯
¯
A B
¬ ® + ® -0.5 ¬ = ¬ ®
-0.6 -0.6 -0.1 -0.1

-0.25 ¯ 0.25
D
Wind load 180o (Cpe+Cpi)
D
-0.6 -1.1

B A
¬ ¬ + ¬ 0.5 ® = ¬ ¬
-0.25 0.7 -0.75 0.2

¯
-0.6 ¯ -1.1 ¯
C

Wind load 180o (Cpe-Cpi)


D
-0.6 -0.1
¯
B A
¬ ¬ + ® -0.5 ¬ = ® ¬
-0.25 0.7 0.25 1.2

-0.6 ¯ -0.1 ¯
C

Wind load 270o (Cpe+Cpi)


D
-0.25 -0.75

B A
¬ ® + ¬ 0.5 ® = ¬ ®
-0.6 -0.6 -1.1 -1.1

¯
0.7 0.2
C

Wind load 270o (Cpe-Cpi)


D
-0.25 0.25 ¯
¯
B A
¬ ® + ® -0.5 ¬ = ¬ ®
-0.6 -0.6 -0.1 -0.1

0.7 1.2
C
Wind coefficient for pitched roof of rectangular clad building

Wind load 0o (Cpe+Cpi)

-1.1 -0.6 -1.6 -1.1


E G + =

F H
-1.1 -0.6 -1.6 -1.1
0.5

Wind load 0o (Cpe-Cpi)

-1.1 -0.6 -0.6 -0.1

E G + =
¯
¯

F H
¯
¯

-1.1 -0.6 -0.6 -0.1


-0.5

Wind load 90o (Cpe+Cpi)

-0.8 -0.8 -1.3 -1.3

E G + =

F H
-0.6 -0.6 -1.1 -1.1
0.5

Wind load 90o (Cpe-Cpi)

-0.8 -0.8 -0.3 -0.3

E G + =
¯
¯
F H

¯
-0.6 -0.6 -0.1 -0.1
-0.5

Wind coefficient for pitched roof of rectangular clad building

Wind load 180o (Cpe+Cpi)

-0.6 -1.1 -1.1 -1.6

H F + =

G E
-0.6 -1.1 -1.1 -1.6
0.5

Wind load 180o (Cpe-Cpi)

-0.6 -1.1 -0.1 -0.6

H F + =
¯
¯

G E
¯

-0.6 -1.1 -0.1 -0.6


-0.5

Wind load 270o (Cpe+Cpi)

-0.6 -0.6 -1.1 -1.1

H F + =

G E
-0.8 -0.8 -1.3 -1.3
0.5

Wind load 270o (Cpe-Cpi)

-0.6 -0.6 -0.1 -0.1

H F + =
¯
¯
G E

¯
¯
-0.8 -0.8 -0.3 -0.3
-0.5

Load calculation for application in Analysis model:

Spacing of purlin as per analysis model = 1.051 m


Spacing of columns in eaves end = 4.5 m
Spacing of columns in gable end = 4 m

Load 1: Dead load


Self weight of the structure = Calculated by analysis software
UDL on purlin, roof sheet = 0.105 kN/m
False ceiling = 0.000 kN/m
Services = 0.105 kN/m
Others = 0.000 kN/m
0.210

Load 2: Live load


UDL on purlin, due to live load = 0.788 kN/m

UDL on columns in kN/m


Load 3: Load 4:
Wind load 0o (Cpe+Cpi) Wind load 0o (Cpe-Cpi)
###

###

###

###

0.294 -1.103 1.764 0.368

® ® ® ¬
0.588 -2.205 3.528 0.735
###

###

###

###

¯ ¯

Load 5: Load 6:
Wind load 90o (Cpe+Cpi) Wind load 90o (Cpe-Cpi)
###

###

###

###

¯ ¯
-1.617 -1.617 -0.147 -0.147

¬ ® ¬ ®
-3.234 -3.234 -0.294 -0.294
###

###

###

###
¯

Load 7: Load 8:
Wind load 180o (Cpe+Cpi) Wind load 180o (Cpe-Cpi)
###

###

###

###
-1.103 0.294 0.368 1.764

¬ ¬ ® ¬
-2.205 0.588 0.735 3.528
###

###

###

###
¯ ¯

Load 9: Load 10:


Wind load 270o (Cpe+Cpi) Wind load 270o (Cpe-Cpi)
###

###

###

###

¯
-1.617 -1.617 -0.147 -0.147

¬ ® ¬ ®
-3.234 -3.234 -0.294 -0.294
###

###

###

###
UDL on purlins in kN/m
Load 3: Load 4:
Wind load 0o (Cpe+Cpi) Wind load 0o (Cpe-Cpi)

-1.09876 -0.7554 -0.41203 -0.06867

-1.09876 -0.7554 -0.41203 -0.06867

Load 5: Load 6:
Wind load 90o (Cpe+Cpi) Wind load 90o (Cpe-Cpi)

-0.89274 -0.89274 -0.20602 -0.20602

-0.7554 -0.7554 -0.06867 -0.06867

Load 7: Load 8:
Wind load 180o (Cpe+Cpi) Wind load 180o (Cpe-Cpi)

-0.7554 -1.09876 -0.06867 -0.41203

-0.7554 -1.09876 -0.06867 -0.41203

Load 9: Load 10:


Wind load 270o (Cpe+Cpi) Wind load 270o (Cpe-Cpi)

-0.7554 -0.7554 -0.06867 -0.06867

-0.89274 -0.89274 -0.20602 -0.20602


.This spread sheet was created on September 2010 ,With reference to IS875-1987
.shall be used for wind load coefficient calculation
.Calculates coefficient for rectangular clad building with pitched roof only
.Yellow coloured cells to be filled by the user
.The forces should be with load factor 1
.Revised on