FDR
Fire Damper for Rectangular and Circular Ducts

• Type-approved and compliant with the EN 1366-2 • Fire damper casing complying with the tightness
and EN 13501-3 standards. requirements for Class C, EN 1751.
• Design for installation in separating concrete and • Fire damper tightness meeting smoke damper
masonry walls and ceilings and lightweight requirement S of standard EN 1366-2.
plasterboard walls of fire compartments with fire • Suitability for use in ducts with a maximum
resistance class EIS 30 to EIS 120. pressure of 2800 Pa.
• Readiness for installation with all wall options as • Damper closing tests performed at 15 m/s duct
delivered – no additional frames needed. velocity.
• Manufactured in accordance with the ISO 9001
quality system. Product models and Accessories
• VTT, the Technical Research Centre of Finland, is
responsible for external quality control. • Models equipped with either manual or electric
• Installation in rectangular and circular ducts with actuators.
diameter 630 to 1000 mm.
• Available with motorised or manual actuator.
• Double sealing, ensuring that the blades are tight
when the fire damper is closed before and during a
fire.

FDR - Fire Damper for Rectangular and Circular Ducts


136
20/FDR/3500/0907/EN
DIMENSIONS

W/H: 200, 250, 300, 400, 500...1000


When the damper is installed on concrete and
masonry walls or ceilings, the size of the installation
hole is W/H + 100 mm.

When the damper is installed on lightweight walls, the


size of the installation hole is W/H + 110 mm.

FDR Ø BxH D-1 La Lb C L L+2xC

630 600x600 629 266 354 52 620 724


800 800x800 799 366 454 58 820 936
1000 1000x1000 999 466 554 58 1020 1136

Pressure drop and sound data

Sound power level Lw, in in each octave band is


computed bu adding the corresponding correction
factor, Kok, to the sound pressure level in the
selection chart according to the following equation.

Lw = LpA + Kok

The corresponding factor Kok is the average of the


FDR operating area.

f / [Hz] 125 250 500 1k 2k 4k 8k


kok 10 5 0 -3 -3 -11 -20
l / dB +/- 2 +/- 2 +/- 2 +/- 2 +/- 2 +/- 2 +/- 3

FDR - Fire Damper for Rectangular and Circular Ducts


137
20/FDR/3500/0907/EN
Material and finishing Function

The FDR fire damper casing, installation flange, and The FDR is a fire damper of class EIS 30 to EIS 120
installation frame are made of galvanised steel. The for circular or rectangular ducts, which prevents fire
closing blade is made of calcium silicate and equipped and smoke from spreading in ventilation ducts. The fire
with a flexible silicone seal as well as a graphite mass damper is equipped with either a motorised actuator
seal that expands at high temperatures. or manual actuation arrangement. Both actuators
have a visual position indicator. If the power in the
motorised actuator system is switched off, the blade
Product options and Accessories
closes automatically.

Actuators
Manual actuator, MA (spring return) Europe and Russia models:
In both actuator options, a fuse reacts to a rise in

Electrical actuators temperature, causing a spring-return blade to close.


The motorised fire damper is delivered complete with

Models for Europe and Russia: a spring-return actuator and a fuse that is activated at

Belimo BF24-T-2 HL, operating voltage AC/DC 24 V (72 72 ºC.

ºC, contains a microswitch), B1


Belimo BF230-T-2 HL, operating voltage AC 230 V (72 Sweden model:

ºC, contains a microswitch), B2 The electrical motor option is without thermal fuse
and shall be connected to an automatic alarm system.

Model for Sweden:


Belimo BF24 HL, operating voltage AC/DC 24 V (no The fire damper is made of fireproof materials. Once

fuse, contains a microswitch), B5 the fire damper has closed, the double sealing closes

Belimo BF230 HL, operating voltage AC 230 V (no the duct tightly, effectively preventing the spreading

fuse, contains a microswitch), B6 of flue gases in the ventilation ductwork. The flexible
seal of the double sealing system operates at lower

Accessories temperatures, while the graphite mass seal expands

Safety mesh on one side, N1 to insulate the system at temperatures above 150 ºC.

Safety mesh on both sides, N2


The FDR fire damper can be connected to the MSH

Manual actuator accessories control and testing system for fire dampers. The

Fuse release temperatures, FU = 50 ºC, 65 ºC, 72 ºC, MSH unit enables the use of smoke detectors in the

100 ºC ductwork or rooms. The FDR fire damper can also

Limit switches, open and closed position, MS be connected to other common building automation
systems.

FDR - Fire Damper for Rectangular and Circular Ducts


138
20/FDR/3500/0907/EN
Installation

Installation on masonry walls Installation on lightweight plasterboard walls


When the fire damper is installed on concrete When the fire damper is installed on lightweight
and masonry walls and ceilings between fire plasterboard walls between fire compartments,
compartments, the blade shaft is always horizontal. an opening for the fire damper must be left on the
An opening is always left in the separating element plasterboard in which the installation frame (included
for the fire damper, and the product is subsequently in the delivery) is first mounted. The blade shaft must
grouted into this. always be horizontal. To make installation easier, the
To make installation easier, all products come with fire damper comes with an installation flange, which
an installation flange, which is used to fasten the fire is used to fasten the fire damper to, e.g., the steel
damper to the concrete surface with screws before frame of the panel wall. The space between the fire
grouting. damper and the installation frame is filled with a fire
During installation, the fire damper and actuator must prevention mastic. During installation, the fire damper
be protected with, e.g., a plastic cover. and actuator must be protected with. e.g., a plastic
The correct operation of the fire damper must be cover. The correct operation of the fire damper must
ensured before and after grouting. be ensured after application of the fire prevention
When the damper is installed for concrete and mastic.
masonry walls and ceilings, the size of the installation For lightweight walls, the size of the installation hole
hole is W/H + 100 mm. is W/H+110 mm; consult the section ‘Documents /
Installation Instructions’ for the size of the installation
holes.

Detailed installation instructions, as well as an


installer’s installation certificate form, are supplied
with each product. See also the section ‘Documents /
Installation Instructions’.

Electric actuator wiring diagram Manual actuator wiring diagram (limit switches,
~ ~
MS)
- + - +

1 2 S1 S2 S3 S4 S5 S6 1 2 S1 S2 S3 S4 S5 S6

<5 < 80 <5 < 80


K1 K1 K1

Tf1 Tf2 Tf3 LED BAE72B-S

BF24-HI BF24-T HI Damper open Damper drives Damper closed


BF230-HI BF230-T HI
K1:13/14 closed K1: 13/14 open K1: 13/14 open
21/22 open 21/22 closed 21/22 closed

K2: 13/14 open K2: 13/14 open K2: 13/14 closed


21/22 closed 21/22 closed 21/22 open

FDR - Fire Damper for Rectangular and Circular Ducts


139
20/FDR/3500/0907/EN
Suggested specifications

A fire damper of class EIS 30 to EIS 120 shall have The fire damper shall be suitable for vertical and
a double sealing solution that ensures fire-gas horizontal installation on concrete and masonry walls
resistance at all temperatures when the fire damper is and on ceilings or lightweight plasterboard walls
closed. between fire compartments (EIS 30 to EIS 120).
In motorised models, the fuse shall be activated at 72 The technical properties of the type-approved fire
°C (E and R models). damper shall conform to the EN 1366-2 and EN
In the manually operated system, the fuse activation 13501-3 standards.
temperature corresponds to the specifications (50, 65, The internal quality control of the fire damper
72, 100 °C). manufacturer shall be based on the ISO 9001
The fuse shall be located inside the damper, and it quality system system, and the operations of the
shall be possible to replace it from the outside. manufacturer shall be subject to external third-party
The fire damper shall have means for external opening quality control.
/ triggering of the release and closing. The fire damper
shall include a position indicator.

Product code

S = Model Specifics and Accessories


E Europe
S Sweden RE = Release type
R Russia MA Spring release
B1 BF24-T-2 HL fuse 72 °C (E and R
A = Type of duct connections models)
R Rectangular B2 BF230-T-2 HL fuse 72 °C (E and R
A Duct connection 630 models)
B Duct connection 800 B5 BF24 HL, no fuse (S model)
C Duct connection 1000 B6 BF230 HL, no fuse (S model)

W = Width FU = Fuse release temperature (°C)


A = R: 200, 250, 300, 400, 500, 600, 700, 50 °C, 65 °C, 72 °C, 100 °C
800, 900, 1000
A = A: 600 AC = Accessories
A = B: 800 MS Limit switches
A = C: 1000 N1 Safety mesh, 1 side, installed in
actuator side
H = Height N2 Safety mesh, 2 sides
A = R: 200, 250, 300, 400, 500, 600, 700,
800, 900, 1000 Code example
A = A: 600
A = B: 800 FDR/E-R-200-200, RE=MA, FU=72
A = C: 1000

FDR - Fire Damper for Rectangular and Circular Ducts