GE Power Generation
GE Generators - An Overview
GE GENERATORS - AN OVERVIEW
J. J. Gibney, III
GE Industrial & Power Systems
Schenectady, NY
cooled units, through indirect hydrogencooled Totals 521 3,220 1,342 1,335 6,416
units to direct water-cooled units.
During the 1950s through the mid-1970s much
emphasis was placed on developing units to sup Figure 1. GE generator experience
port the rapid growth in unit ratings, which
increased from 100 MW to more than 1100 MW. paper will give an overview of each of these basic
It was during this time frame that such innovative design classifications.
design features as direct water-cooled armature
windings, gap-pickup rotor winding cooling,
Micapal II TM stator insulation, Class F rotor and DESIGN CONSIDERATIONS
stator insulation, advanced TetralocTM stator end- The design of synchronous generators is an
winding support systems, and the side ripple- optimization process. A generator design engi-
spring armature bar slot support structure were neer’s challenge is to develop a final design that,
developed. as best as is practical, optimizes the overall size,
In the early 1960s packaged gas-turbinedriven efficiency, performance capabilities and electrical
generators were introduced. These applications parameters, while maintaining mechanical, ther-
were characterized by the ambient-temperature- mal and magnetic limits. In addition, the designer
following nature of the gas turbine output and the must be aware of the need to minimize the overall
ability of the gas turbine to provide peaking capa- cost impact of the design.
bility for short periods. Generator designs were The development of modern analytical calcu-
developed which were tailored to gas turbine lation methods, including finiteelement analysis,
applications. As new gas turbines were intro- supplemented with the use of improved materi-
duced, or as older designs were uprated, genera- als, building upon component testing, has aided
tor designs were introduced to match the new gas the generator designer in the pursuit of an opti-
turbine ratings. mal design.
Over the course of the past decade, the empha-
sis in new electric power generation installations AIR-COOLED GENERATORS
has swung away from large units delivering major Air-cooled generators are produced in two
blocks of power to smaller units operated not only basic configurations: open ventilated (OV) and
by utilities, but by cogenerators or other smaller totallyenclosed water-to-air-cooled (TEWAC) . In
independent power production companies. In the OV design, outside air is drawn directly from
response to this change, GE is placing a major outside the unit through filters, passes through
emphasis on the design and development of gen- the generator and is discharged outside the gener-
erators suited to these applications. ator. In the TEWAC design, air is circulated within
Excluding marine service applications, GE cur- the generator passing through frame-mounted
rently has more than 6400 generators in service air-to-water heat exchangers.
(Figure 1) . These generators can be placed in three The recent emphasis in the marketplace on
major design classifications based on the cooling steam and gas turbinegenerators in the 20- to lOO-
medium used: air, hydrogen and liquid cooled. This MVA size has provided GE with the impetus to
GER-3688B
restructure its aircooled machines. A consequence account is the use of steam and water injection for
of the historical development of the turbinegener- NO, control. The output of the gas turbine can
ator market was that two lines of generators increase by 5% or more above its dry IS0 rating,
evolved, one for steam turbine applications and the depending on the level of steam or water injection
other for gas turbine applications, with little stan- required to meet the emission requirements. An
dardization between the designs. As GE embarked approach that results in the generator having suf-
on this design restructuring, it took the opportunity ficient capacity to match the gas turbine at the
to look at other issues which GE judged were criti- required NO, requirements has been factored
cal to its ability to maintain leadership in the design into the generator rating.
and manufacture of this size generator. Among
these issues were performance parameters, avail-
ability of features, cycle time and cost effectiveness. STANDARDS
All new designs will meet the requirements of
the applicable ANSI and IEC standards, as did the
MARKET NEEDS older designs.
The basic design of a generator, while influ-
enced primarily by material and electromagnetic
properties, is also impacted by market require- RELIABILITY
ments. Hence, customer discussions as well as Particular attention has been paid to known
recent market trends are used in the development problem areas based on inservice generator experi-
of a final generator design. Some of these include: ence. The new designs strive for a high level of relia-
winding temperature rise, industry standards, gen- bility and availability through attention to detail
erator ratings, etc. design and to the problems that have caused down-
time on older designs. In addition, the reliability of
the product will improve through design simplifica-
TEMPERATURE RISES tion and standardization, discussed below.
In the early 1970s GE introduced insulation sys-
tems capable of operating at class F temperatures
(155 C, 311 F) for the life of the generator. This PRODUCT
enabled a significant uprating of generator designs STANDARDIZATION
(about 10%) with a minimal increase in cost. To Standardization of the product line has signifi-
capitalize on this technical capability, GE designed cant benefits both to the user and to the manufac-
generators with Class F insulation and Class F rises.
turer. From the user’s viewpoint, the standardiza-
Many such generators built by GE are in service
tion of the product line translates into a simpler
and operating successfully at Class F temperatures.
machine with fewer unique parts, easier spare
However, the trend in recent specifications has
parts access and the reliability benefit of a larger
been toward Class F insulation systems operating at
fleet of identical machines, with the rapid identifi-
Class B temperatures. In order to be responsive to
cation of any performance problems that this
these requirements, the new designs will operate at
brings. The benefits to the manufacturer are that,
Class B temperatures according to ANSI and IEC
with fewer unique parts to track and check, fewer
standards.
different assemblies to build and fewer drawings
to keep up to date, the job of building a highqual-
GENERATOR RATINGS ity machine becomes simpler.
In a rapidly developing technology, such as that Standardization is being implemented at three
of the combustion turbine, it is inevitable that the levels. At the highest level, the number of differ-
output of a given gas turbine frame size will be ent designs can be reduced by careful selection of
increased from time to time. This has required generator ratings and the use of common designs
redesign of the generator to keep pace with the for gas and steam turbines. At the time the
rise in turbine output. The ratings of the genera- redesign project was begun, there were 17 unique
tors designed to match the gas turbine frame sizes air-cooled generator designs between 12 MVA and
have been set so that the generator will meet or 100 MVA. With careful choice this has been
exceed the gas turbine capability over the full reduced to six basic electromagnetic designs.
operating temperature range, taking into account The second level of standardization is illustrat-
the expected turbine upratings duriiig the life- ed in Figure 2. This shows the high level of stan-
time of the design. dardization achieved in covering the basic config-
Another important consideratioil that affects urations of the generator for the Frame 6 gas
the generator rating which must be taken into turbine (designated 6A3), 50 Hz or 60 Hz, open
2
GER-3688B
Design Option
6A3
5oHz
6OHz 6OHZ
Generator Component TEWAC ov TEWAC ov
BSBSBSBS
Frame.. ............................................... . .. . ,
Core.. ............................................... . . .. . . . .
Base .................................................
................................................. .
. .
. .
. .
. l .
. l
B - Brushless Excitation
* .%me Canp~nent Applied to Deoign Option
S - Static Excitation
GT164SOA
ventilated (OV) or totally enclosed (TEWAC) , and addition, while the gas turbines are the primary
brushless or static excitation. For example, the sta- application of the new air-cooled generators, they
tor frame, core and base, and the rotor forging can and have been applied with steam turbine
and rotor copper cross section are identical for drives as well (Figure 3).
any combination of these features. The only dif- The most detailed level of standardization is
ference between the 50-Hz stator and the 60-Hz with hardware such as fasteners and small compo
stator is the different stator bar. Everything else is nents. A carefully constructed list of preferred
the same. This component standardization can be hardware has been developed and the number of
extended to other ratings when the same compo different nuts, bolts and similar items has been
nent is used for two different machines. For exam- drastically reduced.
ple, the generator base is the same for the Frame The impact of standardization is illustrated in
5 generator as it is for the Frame 6 generator. In Figure 4, which shows the reduction in the num-
ber of parts and drawings required to build a sin-
I- ,
OLD DESIGN NEW DESIGN
REL. # OF
PARTS 1.0 0.6
REL. # OF
DRAWINGS 1.0 0.7
GT19263 GT1649’
Figure 3. Air-cooled steam turbine generator Figure 4. Impact of standardization
3
GER-3688B
gle new design as compared to its predecessor. configuration, a large range of design alternates
When these gains are compounded by the was considered, and the final choice of design
reduced number of unique designs, there is a pro reflects the optimization of the types of considera-
found effect on the productivity and quality of the tion described herein.
manufacturing operation.
One of the potential adverse effects of stan-
dardization can be a loss of flexibility to meet an
STATOR DESIGN
individual customer’s needs. This has been The stator frame is divided onto an inner and an
addressed first by building into the design those outer section, both of which mount on a single
features that are frequently specified. An example base fabrication. The inrrer frame is a very simple
is the use of stainless steel oil feed piping. This fea- structure designed to support the stator core and
ture is not requested by every customer, but it is winding while providing some guidance to the air
asked for often enough such that it is easier to flow in the machine. The stator core, made from
build every unit with the stainless steel piping. The grainoriented silicon steel for low loss and high
second way in which individual needs have been permeability, is mounted rigidly in the inrrer frame.
met is through “standard options.” These are pre- Isolation of the core vibration from the remainder
engineered options commonly requested for of the structure is accomplished through the use of
which drawings have been prepared ahead of flexible pads between the feet on the inner frame
time. and the base structure. The combined core and
These options can be readily incorporated in inner frame are designed to have a four-nodal natu-
the machine, within normal material procure- ral frequency well removed from 100 Hz or 120 Hz,
ment and manufacturing cycles. An additional and tests on the assembled inner frame confirmed
group of options is available that have not been the predicted natural frequencies.
pre-engineered due to the low frequency of The outer frame is a simple fabricated enclo-
request. These are available but with longer lead sure, which supports either the air inlets and
times since the necessary engineering work must silencers if the unit is open ventilated (Figure 5)
be accommodated. or the roof and cooler enclosure if the unit is
totally enclosed, water-to-air-cooled. The outer
frame further acts as an air guide to complete the
DESIGN AND ventilation paths and as a soundproof enclosure
CONSTRUCTION FEATURES to keep noise levels low. Since the rotor is pedestal
The design teams involved were organized with mounted, the end shields are very simple struc-
representation from all the major business func- tures. As with the inner frame, the outer frame
tions, and members of the design teams visited was designed to be free of resonances below 80
some representative customers to better under- Hz, and again, tests of the completed structure
stand user needs. In this way, the technical confirmed the design analysis.
requirements of the designs were influenced by The entire generator is mounted on a single
the needs of all the functions involved in the fabricated base, which supports the pedestals, the
design, manufacture, marketing and maintenance inrrer and outer frames, and the brush rigging or
of the generator. Features were incorporated into the exciter. The base contains piping for oil sup
the design specifically to aid producibility. Visits to plies, conduit for wiring and a number of compo
and discussions with potential vendors influenced nents associated with the main leads, such as light-
the design of components both for improved per- ning arresters and surge capacitors. The structural
formance and to suit vendors’ capabilities. Careful vibration of the base was also confirmed by test to
cost comparisons were made of alternative design be well away from any frequency of concern.
approaches to ensure that the final configuration The stator winding is a conventional lapwound
was cost effective. design. The insulating materials are those used
since the early 1930s thus maintaining the proven
reliability record. The materials are all designed
ELECTROMAGNETIC DESIGN and tested to provide reliable performance at
To achieve the reliability objectives of the pro Class F temperatures for the life of the machine.
ject, no new electromagnetic design limits have The stator bar copper is stranded and insulated
been used. The designs are based on proven tech- with Class F materials and is Roebelled for mini-
nology used in generators already in service. mum losses. The ground wall insulation is Micapal
Where appropriate, the technology used in larger HT, a proven Class F system (Reference 1). This is
units has been drawn upon to improve the a resin-rich tape system, with the volatiles removed
designs of these machines. In reaching the final under vacuum, which is then cured under pres-
4
GER-3688B
JGEWERMRI
,YR-:
sIL:zlc4
I
1; .:* I
I I GENERATOR
AIR
lNLET
GENERAlOR CGMPIRTYEN,
GT18560
Figure 5. Generator packaging
\RTD OR
FILLER
GLASS TAPE -E
ARMOR I SIDE RIPPLE
SPRING
TOP RIPPLE j
SPRING
f
FILLER/ J \ WEDGE
GT18494A-1
Figure 6. Stator slot section
GER-3688B
! - STATOR
FLANGE
i r BINDING
/ ’ BAND
I ;I SUPPORT
STAT01
KEYBA.. \
TION
STATOR
PUNCHINGS--,
\
VENTILATION - . .. ..
DUCT
BETWEEN BAR
FILLER
_----
\ ‘- GLASS
.------
WFDCXS -‘-\ \
\
?
\ M&END
ROVING
TIES
\
BLOCK ’ BINDING
(FINGER) RAND
GTlW!SA
6
Fan
Fan
Ring
GTlWX
/:YIR 1 1
OUTLE
1 AIR
FILTER
s,,k%ls~
‘Is =--=
1 $r II -f-- JI -J-
I
I INLET
* SILENCEAS
I j 1
GENERmJR
4 I / A,R
INLET
tie --....’
‘i -- -- ..--
I i '/%ki I 'I Lg.& t BEARING
t .-- 7;: - -.
I- DRIVE ’ -_, ‘;;ib- l-y;dA -* _- 1 IA
GEAR i,r: i+.
“: i I;
.I 1,
1. -- ;;;T-g*1, p!JJ--~7+sJ,,~ H I-- ‘:Ag
t I rlj’ .-, _IJ’
. imm,
‘-‘I ,: 1 K.‘&-;/y
’ ; +,I,-’
&mms SW& !
TR;:;aEFls
^:;g$g=
^.._^r..l
GT18561
core. The rotor winding, which is a directlycooled required on longer rotors, several wedges are used
radial flow design, is self-pumping and does not in each slot. The rotor slot insulation, turn insula-
rely on the fan for air flow. The overall ventilation tion and other materials in contact with the wind-
pattern is shown in Figure 9. ing are full Class F materials and have proven reli-
The rotor winding fits in a rectangular slot ability through use on other generator designs.
(Figure 10) and is retained by a full-length wedge
on the shorter machines. Where cross slots are
7
GER-3688B
COll Wedge
Measured Vibration
creepage BlWk Journal Probe Mils Peak-to-Peak (MM)
Location
and Orientation Broadband Filtered - l/Rev
Field COll
Turn l”S”latlOn
Turbine End Horizontal 0.90 (.023) 0.37 (.009)
GI1lU!M
Figure 10. Section through coil slot Figure 12.6A3 journal vibration maximum val-
ues observed for all speed and operat-
PACKAGING DESIGN ing conditions
The objective in the packaging design has been all the expected performance requirements
to reduce the number of sections (Figure 5) to throughout the load range. Some of the key test
simplify the structure and to improve the piping objectives are listed in Figure 11.
and wiring design for fewest parts and ease of Loss measurements confirmed the prediction
assembly. The lesser number of package sections of generator efficiency at the generator rated out-
leads to a stronger structure, but, more important- put, and heat runs both in the factory and under
ly, results in fewer feet of joint through which load confirmed that the generator would meet
unfiltered air can leak, thus aiding cleanliness in both NASI and IEC standards for Class B tempera-
the generator. Depending on the design, a num- ture rise.
ber of components have been relocated from the At the design stage, a great deal of attention
auxiliary cubicle into the base, simplifjring the was focused on achieving a smooth running rotor.
design of the auxiliary cubicle. Components in the Figure 12 shows the levels measured on a 6A3 at
base are low-maintenance items, and are accessible the site. These levels are significantly lower than
through covers in the collector compartment. those required by API, and also are much lower
A great deal of attention has been paid to cus- than those in a recently issued draft international
tomer requirements in this area, as the prefer- standard (7919/3). The API requirements for sep
ences of individual users frequently require pack- aration margins of rotor lateral critical speeds
aging changes. Ease of addition or removal of from operating speeds were also fully met.
features and hardware is critical to meeting these A noise survey was conducted during startup of
needs within the normal cycle times. the first 6A3, using the sound intensity method
which compensates for ambient noise effects. The
average generator near-field sound pressure was
TESTING determined from the measurements to be 85.7
Extensive prototype testing of each of the new dBA, which is very satisfactory, and compares
designs, both in the factory and under load at a favorably with the design target of 85 dBA.
customer’s site, has proven that the designs meet
CURRENT STATUS
Electrical Testing
Three new machines have been designed to
l Excitation Requirements
l Short Circuit Ratio
match the GE Frame 5,6 and ‘7 gas turbines. More
l Temperatures
than 130 generators of these new designs have
been shipped through the end of 1992, with
Mechanical Testing approximately one-half in service.
l Rotor Vibration
The air-cooled generator product line is contin-
l Stator Frame Vibration
uing to evolve. The generator that is being
l Noise
applied with the LM6000 aeroderivative gas tur-
l Stator Winding Vibration
l Ventilation
bine (Figure 13) was tested and shipped in 1992.
Its basic configuration is open ventilated (with a
TEWAC option), brushless exciter, pedestal-
GT22940
mounted bearings, on a “single-lift” base, rated 60
Figure 11. Factory and load test objectives
GER-3688B
RDC26475-2 GO2A-00.044
Approx.
Relative Relative Rel Heat
Spectfic Relative Practical Removal
FluId HEat Denstty Vol Flow Abihty
GT21022A
RDC26126.21-3
Figure 14. Air, hydrogen, water heat removal
comparison Figure 16.7F generator
MVA at 0.8 pf. In 1993, a 160 MVA, 50-Hz air- below, while direct water cooling of armature
cooled generator, to be used primarily with the windings is applied to units above 250 MVA. This
frame 9E gas turbine, will be tested as well. division results from design optimization. While it
is possible to apply water cooling on machines
rated below 250 MVA, the cost/performance ben-
HYDROGEN-COOLED efit suffers. Water cooling adds manufacturing
GENERATORS complexity, as well as requires the need for an
auxiliary water cooling and deionizing skid, plus
As the rating of steam turbines rose in the associated piping, control and protection features.
1930-1950 time frame, it became clear that in At higher ratings, the cost of this complexity is off-
order to keep the size, weight, ability to ship and set by the advantage of producing a generator of
cost of a generator within reason, a more optimal significantly smaller size than a comparable con-
cooling medium needed to be used. Hence the ventionallycooled generator.
introduction of hydrogen. Hydrogen-cooled generator construction
How well the armature winding of a generator (Figure 15)) except for the frame, is very similar
is cooled has a significant influence on the overall to that of air-cooled generators. The stator slot
size of a synchronous generator. The cooling of and end winding support designs are essentially
the armature winding is dependent on a number like those shown in Figures 6 and ‘7. Most designs
of factors: cooling medium (air, hydrogen, water) ; use direct radial flow cooling similar to that
insulation thickness; and overall electrical losses shown in Figure 10. The stator frame, on the
(12R + load loss). As Figure 14 shows, relative heat other hand, because of the need to contain 30
removal capability improves from air to hydrogen, psig (2.07 bar) to 45 psig (3.10 bar) hydrogen,
with increased hydrogen pressure, and even more uses thick plate cylindrical construction. End
significant with the use of water cooling. shields are appropriately more rugged, and con-
Conventional hydrogen cooling can be utilized on tain a hydrogen seal system to minimize leakage.
generators rated approximately 300 MVA and Conventional hydrogen cooling, while available
9
GER-3688B
- /
G02A-00-043 POP35782
?OO systarri
Faults
Xela~rvai
FGiZO ioao Cycrlng
Normar
f-1hom?ai Expanslan)
Fiunnmg
FBC%S
1 -
i
L-. ---L ..-.--.-L-.-L-
7 102 d 4 1010 30’2
Total ~*~~~ of Cycles
w a .3t?-bar 4ime Span
GO4A-00-019 GT21019
Figure 18. Hollow copper strand construction Figure 20. Cyclic duty on stator winding in
30 years
for generators rated below 100 MVA, is most rated units. These present unique design require-
often applied to steam-turbinedriven units above ments must be addressed if high reliability and
100 MVA, as well as with the frame 9 and 7F long life of the equipment is to be maintained.
(Figure 16) and frame 7FA and 9F gas turbines.
Insulation
HYDROGEN/WATER-COOLED The stator insulation material used in modern
GENERATORS GE water-cooled generators consists of an epoxy-
Even more compact generator designs are mica-based system called Micapal. Micapal I was
achievable through the use of direct water cooling introduced in 1954, partially as a solution to tape
of the generator armature winding (Figure 17). migration and girth cracking problems associated
These designs employ hollow copper strands with the then almost universally applied asphalt-
(Figure 18) through which deionized water flows. insulation-based system.
The cooling water is supplied via a closed-loop In 1975, an improved epoxy-mica system was
auxiliary-base-mounted skid. The cool water introduced (Micapal II). This all-mica paper insu-
enters the winding through a distribution header lation has improved mechanical toughness (15%)
on the connection end of the generator and the and voltage endurance (12%). While these prop
warm water is discharged in a similar manrrer on erties were developed to meet the requirements
the turbine end of the generator (Figure 19). of very large ratings, the application of Micapal II
The armature voltage and current of hydro- on small and midsize units permits further opti-
gen/watercooled generators are significantly high- mization opportunities. Micapal II has excellent
er than those of air- or hydrogencooled units. As a thermal cycling capability, and is particularly suit-
result, the insulation voltage stress and forces on ed for the daily start/stop duty required of many
the armature windings can be several orders of units today.
magnitude larger than those experienced on lower-
10
GER-3688B
11
GER-3688B
INSULATING
CREEPAGE BLOCK INLET WEDGE
I WARM GAS
OUT
r OUTLET
8,
WEDGE
COOL GAS IN \
D COPPER CHANNEL
SUB-DIVIDED
FIELD CONDUCTOR
\- SLOT INSULATION
\
‘. TURN INSULATION
GT17110A
12
GEK3688B
‘)“A
CI I”
c-,.“.(.*rln~
““I l”“C,“l
Copper Temperature
Temperature Rise From Bottom A
OF OC
/ A
140 60
II \I
/’ -’
122 50
-
104 40
t I T
Rotor
Baftle
I
GTZlOZOA
Figure 25. Diagonal-flow cooling field winding temperature profile
Rotor Balance
One of the most critical rotor manufacturing
requirements, after all the parts are accurately
machined and carefully assembled, is the final bal-
ance operation. This ensures that the rotor vibra-
tion will be within acceptable limits and that the
rotor remains straight within very close tolerances
at all running speeds up to and including the
maximum specified overspeed.
The design work initially includes the accurate
calculation of all shaft stiffness and critical speeds. To
correct for the double frequency vibrations which
would otherwise occur, cross slots of appropriate
Figm-e 26. Arrangement of locking key and depth and number are specified in the pole centers
shrink fit of most twopole rotors to equalize the bending stiff-
ness between the direct and quadrature axes.
the ring material must be nonmagnetic to mini- Provisions are incorporated for making balance
mize the end leakage flux and reduce heating of weight corrections. Each GE hydrogencooled gen-
the core end structure. erator field is supported in its own pair of bearings.
For many years, nonmagnetic retaining rings Balancing and overspeed testing are per-
have been made from an 18Mn-5Cr steel alloy. formed in GE’s factory balance facility. A high-
However, it was not until the mid-1970s that the speed multiplane modal balancing procedure is
susceptibility of 185 retaining rings to stress-corro used. This procedure is done to ensure minimum
sion cracking became known. As a result of coop- vibration levels at every speed up to the maxi-
erative programs with retaining ring suppliers, a mum specified overspeed.
different alloy, 18Mn-18Cr (originally proposed by
GE), was selected as a better retaining ring materi-
al. This material has the required properties, CONCLUSION
including high resistance to stress-corrosion crack-
ing in the types of environments of which rings While this paper has focused mainly on the
may be exposed during the service life of the gen- “flange-to-flange” generator, the successful opera-
erator. GE now supplies 18-l 8 retaining rings on tion of a steam or gas turbine generator involves
its generators. other systems as well. Discussion of excitation,
lube oil, hydrogen and stator cooling water sys-
tems, as well as generator protection and opera-
tion, can be found in other GE publications.
13
GER-3688B
REFERENCE
0 1994 GE Company