GAS/HEAVY-OIL DUAL BURNERS

GASTEC

Multiflam 170.1
Multiflam 200.1
G.N. 20÷300 mbar/ Heavy oil

LB 1348
LB 1348 Multiflam 170.1 / 200.1

TECHNICAL DATA

MODELS 170.1 200.1


Thermal power max. kW 1770 2150
kcal/h 1.526.000 1.853.450
Thermal power min. kW 342 414
kcal/h 295.000 356.900
Min. natural gas pressure mbar 40÷300 40÷300
Voltage 50 Hz V 230/400 230/400
Motor kW 3 4
Rpm N° 2800 2800
Fuel : Natural Gas (L.C.V. 8.570 kcal/Nm3),
Heavy oil (L.C.V. 9.800 kcal/kg max. visc 50°E at 50°C)

WORKING FIELDS
mbar 12

11

10

9
Pressure in the combustion chamber
Pressione in camera di combustione

8
M
7 U
LT
6
IF
LA
MULTIFLAM 170.1 M
5 20
0.
4 1
3

0
300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 kW

200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 2000 kcal/h
x 1000
Burner Output / Potenza

DIMENSIONS D'ENCOMBREMENT
A
E D - D1
B C L
I
F

SUNTEC

M
G
O

N
H

MODELS A B C D D1 E F G H I L M N O
Multiflam 170.1 860 385 475 340 540 660 250 398 283* 240 240 M14 125 250
Multiflam 200.1 880 405 475 346 546 660 270 398 283 240 240 M14 125 250
* Optional (only 170.1) D = Short head D1 = Long head

pag.2
LB 1348 Multiflam 170.1 / 200.1

ELECTRICAL CONNECTIONS
All burners factory tested at 400 V 50 Hz three-phase for motors and 230 V 50 Hz monophase with neutral for auxi-
liary equipment. If mains supply is 230 V 50 Hz threephase withuot neutral, change position of connectors on burner
as in fig. Protect burner supply line with safety fuses and any other devices required by safety standards obtaining in the
country in question.
CONNECTION TO THE GAS PIPELINE
Once connected the burner to the gas pipeline, it is necessary to control that this last is perfectly sealed. Also verify that
the chimney is not obstructed. Open the gas cock and carefully bleed the piping through the pressure gauge connector,
then check the pressure value trough a suitable gauge. Power on the system and adjust the thermostats to the desired
temperature. When thermostats close, the sealing control device runs a seal test of valves; at the end of the test the bur-
ner will be enabled to run the start-up sequence.

OPERATION OF BURNER WITH GAS


Before starting the burner, make sure it is mounted correctly. Then check connections are correct according to the dia-
gram and piping is appropriate to the system. Before connecting the burner to the electricity supply, make sure voltage
corresponds to burner plate data. The connection diagram and start-up cycle are shown separately. For wiring from
control box to burner, see the enclosed connection diagram. Pay particular attention to neutral and phase connections :
never exchange them!. Vent air and impurities of gas pipe. Check gas pressure conforms to the limits stated on the bur-
ner plate when connecting a master gauge to the test port provided on the burner. Blower motor starts and pre-purging
begins. Since pre-purging has to be carried out with the max. air delivery, the burner control circuit GAS OIL
turns the air damper to the max. delivery position by the air servocontrol in approximately 30 seconds
2 0 1
time. When the servocontrol is fully open, a signal to the electronic control unit starts the 66 seconds
pre-purge cycle. At the end of the prepurging time, the air servocontrol gets to the Low Flame posi-
tion so that burner ignition is ensured at min. output. Simultaneously the ignition transformer recei-
ves voltage and after 3 seconds (pre-ignition) opens the pilot gas valve. Fuel flows to the combustion
head and ignites. Two seconds after pilot gas valves have opened, the ignition transformer is excluded
from the circuit. In case of no ignition the burner goes to lock-out within two seconds. After 6 sec. open the working
gas valve, governed by the gas firing butterfly valve.Now the burner is operating at the min. firing rate (about 30% of
the max. firing rate). The air servocontrol runs at the Low Flame position and in case the temperature control has to be
set at the max. output it goes to a fully open position of air damper and butterfly valve. During the burner-off periods
the air damper closes up fully.

ADJUSTING THE COMBUSTION PROCESS


IMPORTANT: to obtain the right adjustment of the combustion and thermal capacity it is important to analyze the
reducts of combustion with the aid of suitable instruments. The combustion and thermal capacity adjustment is done
simultaneously, together with the analysis of the products of combustion, making sure that the measured values are sui-
table and that they comply with current safety standards. On this matter, please refer to the table and figure below.
THESE OPERATIONS MUST BE DONE BY PROFESSIONALLY-QUALIFIED TECHNICIANS.
30 1,3
Metano
AIR EXCESS (%)

CO2 9,6% 25 1,25


AIR FACTOR

CO <100 ppm 20 1,2


1,2 1,2
GPL 15 1,15
CO2 11,7%
10 1,1
CO <50 ppm 10 20 30 40 50 60 80 100 200 300 400 600 800 1000 2000
70 90 500 700 900
THERMAL POWER (kW)

pag.3
LB 1348 Multiflam 170.1 / 200.1

LANDIS & STAEFA, Model LFL1.622 OPERATING CYCLE


Ref. Description Duration
t1 Duration Waiting time for confirmation Operating cycle
Ciclo di in the event of
funzionamento
t2 of air pressure 8” CicloNormal operating
di funzionamento cycle
normale ignition failureNormal
in mancanza di fiamma operating cycle
all'accensione
t3 Preventilation time 66” t1 t2 t3 t1 t2 t3
t4 Safety time 2” Gas manostat
Pressostato gas
t5 Pressurizing time 4”
Time for enabling operation of the Motore Fan motor
ventilatore
main gas valve on minimum capacity 10”
Air Switch
Pressostato aria
t6 Time for enabling operation of the
Trasformatore t4 t4
main gas valve on maximum capacity 10” Ignition
di transformer
accensione

Gas valve
Valvola gas
The control box starts the burner t5 t6
Min/maxConsenso
fan, to carry out the prepurging of min./max. capacity
potenza
enabling device
the combustion chamber, and 100%
Serranda aria min
cheks the vent air pressure throu- Air damper 0
gh the air pressure switch. At the Gas damper
Serranda gas
end of prepurging, the ignition
Rivelazione
Flame detector
transformer cuts-in and generates di fiamma

a spark between the electrodes. At Cut-out pilot lamp


Spia di blocco

the same time the two gas valves


open (Vs safety valve and Vl working valve). The total safety, in case of missed ignition or casual burner's flame-out, is
granted by a ionisation probe which cuts-in and sets the burner shutdown within the safety time. In case of gas lack or a
major pressure drop, the minimum air pressure switch shuts down the burner.
LANDIS & STAEFA SQM 50.381A2 AIR DAMPER MOTOR
Remove cover to gain access to the adjusting cams.The cams are to be adjusted through the suitable key provided for.
Description:
Manual change
I - High flame operating opening position adjusting cam (Heavy-Oil /Gas)
II - Ignition flame opening position adjusting cam (Gas).
III - Low flame operating opening position adjusting cam (Gas)
IV - Low flame operating opening position adjusting cam ( Heavy-Oil))
V - Limit switch for 2nd stage’s solenoid valve(Heavy-Oil) opening release.
VI - Not used cam
VII - Not used cam
VIII - Not used cam

ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH


Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas nominal
45
40
50

35
30

N
feed pressure (i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; M
25
2,5

5
20

10
15

for L.P.G. nom. pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw
up cover M I

ADJUSTMENT OF THE AIR PRESSURE SWITCH L

Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by turning
regulator D to position 1. - Start the burner and keep in low flame running, while checking 2,7
2,4
3,0

2,1

that combustion is correct. Through a small cardboard, progressively obstruct the air intake
1,8

D
1,5

until to obtain a CO2 increase of 0,5÷0,8% or else, if a pressure gauge is available, connec- C
0,4
1,2

0,6
0,9

ted to pressure port E, until reaching a pressure drop of 1 mbar (10 mm of W.G.). - A
Slowly increase the adjustment value of the air pressure switch until to have the burner H
G
E
lockout. Remove the obstruction from the air intake, screw on the cover C and start the B
burner by pressing the control box rearm button.
F
Note: The pressure measured at pressure port E must be within the limits of the pressure switch working
range. If not, loose the locking nut of screw F and gradually turn the same: clockwise to reduce the pressure; coun-
terclockwise to increase. At the end tighten the locking nut.
pag.4
LB 1348 Multiflam 170.1 / 200.1

AIR AND GAS ADJUSTMENT

--
+

Part. 1

Part. 3

--
SELECTOR
COMMUTATORE
AUTO +
Part. 2
0

0 = operating
bloccaggio elements locked
degli apparati per ilin an intermediate
position
funzionamento in una posizione intermadia
= operation on maximum
funzionamento capacity
alla massima potenza
= operation
funzionamento alla minima
on minimum potenza
capacity
AUTO = automatic
funzionamento automatico
operation

ADJUSTING THE MINIMUM CAPACITY OF THE BURNER – AIR and GAS


Position the selector placed on the control panel on position 2 and proceed as follows:
Adjust the minimum gas flow rate using a suitable wrench, turn the butterfly valve until you reach the correct gas flow,
as established by analyzing the combustion process.

ADJUSTING THE MAXIMUM CAPACITY OF THE GAS


Position the selector, situated on the control panel, on position 1 and proceed as follows:
Adjusting the maximum gas flow rate (see figure on solenoid valve adjustments) or adjust the gas pressure in the gover-
nor.
ADJUSTING THE MAXIMUM AIR FLOW RATE
Adjusting the maximum air flow rate (see figure, detail 2). Loosen the nut holding the air damper transmission rod;
The correct air flow as established by analyzing the combustion process.

ADJUSTING THE INTERMEDIATE BURNER CAPACITY


Using the selector, start the servomotor (closing or opening) and position on 0 to stop the stroke; the adjustment is
made as outlined below. Repeat the operation for the other cam points.
Adjustment the intermediate gas flow rates (see figure, detail 3): - using a suitable Allen wrench, change the position of
the cam guide blade; if you screw it down, the flow rate is reduced; if you unscrew it, the flow rate increases.

CALCULATING THE BURNER CAPACITY e = Litres gas


To calculate the burner's capacity in kW, proceed as follows: Check the gas flow rate (in liters) on sec = Time in second
the counter and the time of the reading in seconds. G20 = 34,02
e x f = kW f G30 = 116
Proceed with the calculation using the following :
sec G31 = 88

pag.5
LB 1348 Multiflam 170.1 / 200.1

COMBUSTION ADJUSTMENT
WARNING: In order to have a correct combustion and thermal output adjustments, these must be carried out together
with a combustion analysis, to be executed through suitable devices, taking care that the values are the correct ones and
are in accordance with the local safety regulations. The adjustments must be carried out by qualified and skilled techni-
cians authorised by Ygnis.
REMOVING THE BLAST TUBE

POSITION OF ELECTRODES
3 ÷ 4 mm

5 ÷ 6 mm

FLAME DETECTION SYSTEM CHECK


Microamperometer
Microamperometro LANDIS
full scale
fondo scala1000
1000µA
µA LFL 1.622
UVFotocellula
CELL 22 23

min 70 µA

DESCRIPTION OF THE CONTROL PANEL OF THE BURNER

100
GAS HEAVY OIL

A
50

0
150
A - Reset key
B HEAVY OIL
B - Operating lamps (orange=heavy oil; green= gas; red= heater)
C - Selector switch:
AUTO

C GAS

AUX
O = Loking of devoices for operating at intermediate outputs
D = Operation at max. output
E = Operation at min. output
E AUTO = Automatic operation
G
D- ON/OFF switch
E- Fuse
F- Switch GAS / HEAVY OIL
G- Switch AUX heater

pag.6
LB 1348 Multiflam 170.1 / 200.1

HEAVY OIL FEEDING

1 - Inlet
2 - Return
3 - Bleed and pressure gauge port
4 - Vacuum gauge port
5 - Pressure adjustment
6 - Nozzle outlet

Oil temperature: Max. 120° in the pump


Inlet and return pressure: 3,5 bar max.
Suction height: 0,5 bar max. vacuum
0,4 bar advised to prevent air separation from oil

PUMP’S PRESSURE / OIL TEMPERATURE DIAGRAM


The gasification of volatile fractions in preheated heavy oil seems to be the main cause of premature fuel
pump wear. To avoid such a problem, adjust pump pressure according to the diagram hereinafter.
bar 5
pompa ( bar )

4
MAX
inlet pressure

3
minima

2
Pump
Pressione

0
50 100 MAX 150 C°
Temperatura olio
Oil temperature

pag.7
LB 1348 Multiflam 170.1 / 200.1

HEAVY OIL FEED SYSTEM

A
2
4 T

3
5

7 1 - Burner
2 - Tank
A 3 - Heater
Sez. A - A 4 - Thermostat
5 - Transfer pump
6 - Header
B 7 - Tank
8 - By-pass
9 - Pressure regulating valve
C

A - Isolation gasket
B - Heater
C - Pipe heavy oil
2
4 T

3
5

1
6

7
8

IMPORTANT: All fuel pipings are heated (see section A-A of the picture)

pag.8
NOZZLE OUTPUT FOR HEAVY OIL
Pump pressure bar
GPH 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
0,60 2,5 2,6 2,7 2,9 3,0 3,1 3,2 3,3 3,4 3,4 3,5 3,6 3,7 3,8 3,9 4,0 4,0 4,1 4,2 4,3 4,3
0,65 2,7 2,8 3,0 3,1 3,2 3,3 3,4 3,5 3,6 3,7 3,8 3,9 4,0 4,1 4,2 4,3 4,4 4,4 4,5 4,6 4,7
0,75 3,1 3,3 3,4 3,5 3,7 3,8 3,9 4,0 4,2 4,3 4,4 4,5 4,6 4,7 4,8 4,9 5,0 5,1 5,2 5,3 5,4
0,85 3,5 3,7 3,8 4,0 4,1 4,3 4,4 4,6 4,7 4,8 4,9 5,1 5,2 5,3 5,4 5,5 5,6 5,8 5,9 6,0 6,1
1,00 4,2 4,4 4,6 4,8 5,0 5,1 5,3 5,5 5,6 5,8 5,9 6,1 6,2 6,4 6,5 6,6 6,8 6,9 7,0 7,2 7,3
1,10 4,6 4,8 5,0 5,2 5,4 5,6 5,8 6,0 6,2 6,3 6,5 6,7 6,8 7,0 7,1 7,3 7,4 7,6 7,7 7,8 8,0
1,20 5,0 5,2 5,5 5,7 5,9 6,1 6,3 6,5 6,7 6,9 7,1 7,2 7,4 7,6 7,7 7,9 8,1 8,2 8,4 8,5 8,7
1,25 5,2 5,5 5,7 5,9 6,2 6,4 6,6 6,8 7,0 7,2 7,4 7,5 7,7 7,9 8,1 8,2 8,4 8,5 8,7 8,9 9,0
1,35 5,6 5,9 6,1 6,4 6,6 6,9 7,1 7,3 7,5 7,7 7,9 8,1 8,3 8,5 8,7 8,9 9,0 9,2 9,4 9,5 9,7
1,50 6,2 6,5 6,8 7,1 7,3 7,6 7,8 8,1 8,3 8,5 8,8 9,0 9,2 9,4 9,6 9,8 10,0 10,2 10,4 10,6 10,7
1,65 6,9 7,2 7,6 7,9 8,2 8,5 8,7 9,0 9,3 9,5 9,8 10,0 10,2 10,5 10,7 10,9 11,1 11,3 11,5 11,8 12,0
1,75 7,3 7,7 8,0 8,3 8,6 8,9 9,2 9,5 9,8 10,1 10,3 10,6 10,8 11,1 11,3 11,5 11,8 12,0 12,2 12,4 12,6
2,00 8,3 8,7 9,1 9,5 9,8 10,2 10,5 10,8 11,1 11,4 11,7 12,0 12,3 12,6 12,9 13,1 13,4 13,6 13,9 14,1 14,4
2,25 9,4 9,9 10,3 10,7 11,1 11,5 11,9 12,3 12,6 13,0 13,3 13,6 13,9 14,3 14,6 14,9 15,2 15,4 15,7 16,0 16,3
2,50 10,4 10,9 11,4 11,9 12,3 12,7 13,2 13,6 14,0 14,3 14,7 15,1 15,4 15,8 16,1 16,4 16,8 17,1 17,4 17,7 18,0
3,00 12,5 13,1 13,7 14,3 14,8 15,3 15,8 16,3 16,8 17,2 17,7 18,1 18,5 19,0 19,4 19,8 20,2 20,5 20,9 21,3 21,7
3,50 14,6 15,3 16,0 16,6 17,3 17,9 18,5 19,0 19,6 20,1 20,6 21,2 21,7 22,1 22,6 23,1 23,5 24,0 24,4 24,9 25,3
4,00 16,6 17,4 18,2 18,9 19,6 20,3 21,0 21,6 22,3 22,9 23,5 24,1 24,6 25,2 25,7 26,2 26,8 27,3 27,8 28,3 28,8
4,50 18,7 19,6 20,5 21,3 22,1 22,9 23,7 24,4 25,1 25,8 26,4 27,1 27,7 28,4 29,0 29,6 30,2 30,7 31,3 31,8 32,4

pag.9
5,00 20,8 21,8 22,8 23,7 24,6 25,5 26,3 27,1 27,9 28,7 29,4 30,1 30,9 31,5 32,2 32,9 33,5 34,2 34,8 35,4 36,0
5,50 22,9 24,0 25,1 26,1 27,1 28,0 29,0 29,9 30,7 31,6 32,4 33,2 34,0 34,7 35,5 36,2 36,9 37,6 38,3 39,0 39,7
6,00 25,0 26,2 27,4 28,5 29,6 30,6 31,6 32,6 33,5 34,5 35,4 36,2 37,1 37,9 38,7 39,5 40,3 41,1 41,8 42,6 43,3
6,50 27,1 28,4 29,7 30,9 32,1 33,2 34,3 35,3 36,4 37,4 38,3 39,3 40,2 41,1 42,0 42,8 43,7 44,5 45,3 46,1 46,9
7,00 29,1 30,5 31,9 33,2 34,4 35,6 36,8 37,9 39,0 40,1 41,2 42,2 43,2 44,1 45,1 46,0 46,9 47,8 48,7 49,6 50,4
7,50 31,2 32,7 34,2 35,6 36,9 38,2 39,5 40,7 41,9 43,0 44,1 45,2 46,3 47,3 48,3 49,3 50,3 51,3 52,2 53,1 54,0
8,30 34,5 36,2 37,8 39,3 40,8 42,3 43,6 45,0 46,3 47,6 48,8 50,0 51,2 52,3 53,4 54,5 55,6 56,7 57,7 58,8 59,8
9,50 39,5 41,4 43,3 45,0 46,7 48,4 50,0 51,5 53,0 54,4 55,9 57,2 58,6 59,9 61,2 62,5 63,7 64,9 66,1 67,3 68,4
10,50 43,7 45,8 47,9 49,8 51,7 53,5 55,3 57,0 58,6 60,2 61,8 63,3 64,8 66,3 67,7 69,1 70,5 71,8 73,1 74,4 75,7
12,00 49,9 52,3 54,7 56,9 59,0 61,1 63,1 65,1 66,9 68,8 70,6 72,3 74,0 75,7 77,3 78,9 80,5 82,0 83,5 85,0 86,4
13,80 57,4 60,2 62,9 65,4 67,9 70,3 72,6 74,8 77,0 79,1 81,2 83,2 85,1 87,1 88,9 90,8 92,6 94,3 96,0 97,7 99,4
15,30 63,7 66,8 69,8 72,6 75,4 78,0 80,6 83,1 85,5 87,8 90,1 92,3 94,5 96,6 98,7 100,7 102,7 104,7 106,6 108,5 110,3
17,50 72,8 76,4 79,7 83,0 86,1 89,2 92,1 94,9 97,7 100,3 103,0 105,5 108,0 110,4 112,8 115,1 117,4 119,6 121,8 124,0 126,1
19,50 81,2 85,2 89,0 92,6 96,1 99,4 102,7 105,9 108,9 111,9 114,8 117,7 120,4 123,1 125,8 128,4 130,9 133,4 135,9 138,3 140,6
21,50 89,5 93,9 98,0 102,0 105,9 109,6 113,2 116,7 120,1 123,4 126,6 129,7 132,7 135,7 138,7 141,5 144,3 147,1 149,8 152,4 155,0
24,00 99,9 104,8 109,4 113,9 118,2 122,4 126,4 130,3 134,0 137,7 141,3 144,8 148,2 151,5 154,8 158,0 161,1 164,2 167,2 170,1 173,0
28,00 116,5 122,2 127,6 132,8 137,8 142,7 147,4 151,9 156,3 160,6 164,8 168,8 172,8 176,7 180,5 184,2 187,9 191,4 194,9 198,4 201,8
30,00 124,9 131,0 136,8 142,4 147,8 153,0 158,0 162,8 167,6 172,2 176,6 181,0 185,3 189,4 193,5 197,5 201,4 205,2 209,0 212,7 216,3
OUTPut Kg/h
LB 1348 Multiflam 170.1 / 200.1
LB 1348 Multiflam 170.1 / 200.1

CHECKS TO BE MADE TO ENSURE A PROPER INSTALLATION:


Before proceeding with the filling of the fuel system and subsequent burner start up, it is advisable to carry
out the following checks:
- Power line must be adequate to system’s adsorbed load
- Fuses must be adequate to the system’s load
- Boiler’s thermostats must have been properly connected
- Voltage and frequency must be within the specified limits
- Fuel type must be the one specified by the burner manufacturer
- Feed piping section must be adequate to the requested fuel flow rate
- Filters, cocks as well as fittings must have been properly installed
- Blast tube length must be the one specified by the boiler manufacturer
- Nozzle’s flow rate of the burner must be adequate to boiler’s output

fig. A fig. B

OPERATION OF BURNER WITH HEAVY OIL


When all the controls, as shown in previous paragraphs, have been accomplished, it will be possible to pro-
ceed with the burner start up.
- Switch-on the burner. When reaching the preset temperature on the working thermostat, and with boiler’s
thermostat closed, the control box starts the fan, the fuel pump and the ignition transformer. At the same
time, the balancing resistors are activated, to keep fuel temperature into the heater at a constant value.
- It begins, in this way, the combustion chamber prepurging, as well as the fuel circulation in the whole cir-
cuit, so as to obtain an uniformity of temperature which allows a correct flowing of the same. The fuel pres-
sure, during prepurging, shall be around 16÷18 bar. If not, adjust the pressure to the specified
GAS OIL
value through the regulator “D”, purposely installed on the heating circuit (see figure).
2 0 1
- At the end of the prepurging, the control box shut off the solenoid valve “O” while opening
the 1st stage valve (for example valve “A”), allowing the burner ignition in Low Flame.
Afterwards, it will be opened the 2nd stage valve “B” which, while allowing the fuel flowing
through both nozzles, permit the burner’s High Flame ignition, i.e. at the full power.
- In order to have a correct combustion, adjust the combustion air flow for both Low and High flame.
During flow rate adjustement, it is possible to manually switch from Low Flame to High Flame and viceversa,
through the LOW/HIGH manual switch. When all adjustments are made, leave the switch in II (HIGH)
position.
- The fuel pressure during burner’s working shall be set to 23 bars.

pag.10
LB 1348 Multiflam 170.1 / 200.1

ADJUSTEMENT OF PUMP PRESSURE


+
-

WARNING: For a correct working of the pump, verify what follows:

Pump : SUNTEC E4NC 1069 / SUNTEC E6NC 1069


Oil temperature at the pump: Max. 120 °C
Maximum allowable pressures: Max. 3,5 bar on inlet

ADJUSTMENT OF FUEL THERMOSTATS


The working resistor thermostat must be set to 120 °C, while the safety one to 160 °C. Said adjustments can
be slightly modified following the type of fuel and particular uses.

A - Termostato di sicurezza / Safety thermostat


Thermostat de sécurité / Termóstato de seguridad (160° C).
B - Termostato di lavoro / Working thermostat
Thermostat de travail / Termóstato de trabajo (120° C).
C - Termostato di livellamento / Levelling thermostat
Thermostat de nivellement / Termóstato de nivelación (130° C).
D - Termostato di min. temperatura olio combustibile
Heavy oil min. temp. thermostat / Thermostat de température minimale du
fioul lourd / Termóstato de minima fuel pesado (90° C).

Pocket for levelling thermostat

Pocket for thermometer


Pocket for safety thermostat

Pocket for working thermostat Pocket for min. temp. thermostat

pag.11
PREPURGING PHASE

A
LB 1348 Multiflam 170.1 / 200.1

N
D

Legend :
A. Low Flame solenoid valve (N.C.)
B. High Flame solenoid valve (N.C.) H G
D. Fuel flow adjuster in prepurging . E I
E. Heater
F. Anti-gas valve
G. Resistors
H. Filter
I. Fuel pump
N. Manometer
O. Solenoid valve (N.O.)
N.C. = Norm. closed
N.O. = Norm. open
LB 1348 Multiflam 170.1 / 200.1

Low Flame

High Flame

pag.13
LB 1348 Multiflam 170.1 / 200.1

CLEANING AND MAINTENANCE OF FILTERS MOUNTED ON THE PREHEATER

REMOVING OF THE FILTER


1. Switch-off the burner.
2. Loosen screw B and drain part of the fuel from the heater, until the fuel level drop below the filter.
3. Unscrew and pull out the stem filter A from its seat.
4. Clean the filter and reassemble the parts as shown by the picture, then fit it in its own seat.
It is advisable to replace all filter and valve gaskets whenever they are removed.
Note that when the burner is working the heater has a pressure of abt. 23 bar, and that it becomes very
dangerous to carry out said operations with the burner running.

BURNER MOUNTING

pag.14
LB 1348 Multiflam 170.1 / 200.1

SETTING PARAMETERS
When the burner is ignited all displays of the regulator light up. The set point display will blink for about 10 seconds. The value
in the upper field of the display (red) indicates the actual value. The value in the lower field of the display (green) indicates the set
point currently programmed.
CHANGING THE SET POINT
To change the set point, proceed as follows: - Press the PGM button to access the user level. SP1* will appear in the lower display
- Change the value of set point SP1 using the t and s keys.▼e ▲. - After a 2 second delay the value set is stored automatically – To
return to normal display press EXIT.
EXIT
* The value of SP1 depends on the value set previously in configuration level C111.
SETTING PID PARAMETERS
PID parameters are factory set to standard mean values. The operation of the regulator can be self-adapted to suit the system by
activating the “tunE” function. The regulator will set the PID parameters automatically. To activate the “tunE” function proceed
as follows: - With the burner in operation, press PGM + ▼. - the caption “tunE*” will blink in the display. – When “tunE” stops
blinking, the self-adaptation routine has been completed. - Confirm the computed parameters by pressing the ▲ key for 2 seconds.
* The “tunE” function cannot be activated in Manual mode, or when the burner is off.
The PID parameters can be corrected manually from the parameters level, working on the proportional band Pb1, the derivati-
ve action time dt and the integral action time rt.
To change parameters Pb1, dt and rt, proceeds as follows: - Press the PGM button to access the parameters level. - To move from
one parameter to the next, press PGM . - When Pb1 is displayed, the value can be increased or decreased using the s and t keys. -
Confirm the changed parameters by pressing PGM. PGM - If confirmation is not given within 2 seconds the value will be stored auto-
matically. - Press PGM to access the next parameter. - When dt is displayed, repeat the procedure described above. - Press PGM
to access the next parameter. - When rt is displayed, repeat the procedure above. - To return to normal display press EXIT.EXIT
DIFFERENTIAL SETTING FOR IGNITION AND SHUTOFF
The regulator allows the selection of an adjustable switching differential that establishes burner ignition and shutoff values.
HYS1 indicates the lower ignition limit, below which the regulator switches the burner to maximum power. HYS3 indicates
the upper shutoff limit, above which the regulator switches the burner off. To set HYS1 and HYS3 proceed as follows: - Press
the PGM key to access the parameters level. - To move from one parameter to the next, press PGM . - When HYS1 is displayed
(burner ignition differential-stage II), increase or decrease the value using the ▼ and ▲ keys. - Confirm the changed parameters by
pressing PGM.
PGM - If confirmation is not given within 2 seconds the value will be stored automatically. - Press PGM to access the
next parameter. - When HYS2 is displayed (burner shutoff differential-stage II), repeat the procedure described above. - Press
PGM to access the next parameter. - When HYS3 is displayed (upper shutoff differential) repeat the procedure described above.
- To return to normal display press EXIT.
EXIT
MANUAL/AUTOMATIC MODE
To access “MANUAL” mode, press and hold EXIT for at least 5 seconds. Manual mode can only be selected when the burner is
in operation. It is deactivated automatically when the burner shuts off. When the LED above the hand symbol is alight, the regu-
lator is in manual mode and the position of the servocontrol can be changed using the ▼ and ▲ keys. The LEDS on the front of
the regulator indicate whether the servocontrol OPEN or CLOSE command is currently active. Pressing the ▼ key the servocon-
trol OPENS. Pressing the ▲ key the servocontrol CLOSES. To select automatic mode press and hold EXIT for at least 5 seconds.
The LED above the hand symbol goes out and the regulator reverts to automatic.
CLIMATIC COMPENSATION
The RWF 40 regulator can be set with the set point interlocked to the external probe. To select this operating mode, proceed as
follows: - Connect the required probe as in the wiring diagram. - Change the regulator settings. When using an external probe
the regulator must be set as follows: - Press the PGM key to access the configuration level. When the caption C111 (XXXX) is
displayed, use the ▲ key to access the second figure (XXXX). Use the ▼ key to select the type of probe (XX3X). - Confirm the
change of parameters by pressing PGM.
PGM If this is not done within 2 seconds, the value is stored automatically - Press PGM to
access the configuration level. When the display reads C112 (XXXX), use the ▲ key to access the second figure (XXXX). Press the
▼ key to set the type of probe (XX3X). - Confirm the changed parameters by pressing PGM.PGM - If confirmation is not given
within 2 seconds the value will be stored automatically.
- To return to normal display press EXIT.
EXIT To establish the heating curve, proceed as follows:
- Press PGM to access the parameters level. - Press PGM to move from one parameter to the next. - When the letter H is
displayed (heating curve gradient), increase or decrease the value using the ▼ and ▲ keys. - Confirm the changed parameters by
pressing PGM.
PGM - If confirmation is not given within 2 seconds the value will be stored automatically.
- To return to normal display press EXIT.
EXIT

pag.15
LB 1348 Multiflam 170.1 / 200.1

PARAMETERIZATION
160
4
3.8
140 3.6
3.4
3.2
120 3
Boiler temperature set point (iC)

2.8
2.6

Heating curve gradient (H)


100 2.4
SPH 2.2
2
80 1.8
1.6
1.4
60 1.2
SPL 1
0.8
40 0.6
0.4
0.2
20

0
20 15 10 5 0 -5 -10 -15 -20
17.5 12.5 7.5 2.5 -2.5 -7.5 -12.5 -17.5
External temperature (iC)

PROBE CONNECTION DIAGRAMS


Cod. S721 Connection for probe Cod.
QAE2..(passive probe) Cod. RWF 40 S720/1
Water probe S731 G+ G- M1 U1
Configuration code S731/1
C111 = 9XXX S731/2 1 2 3 4
S731/3
S731/4 GL M U1
OBE620-P..
RWF 40
G1+ M1 Connection for probe Connection for probe
QBE620-P..(active probes) QAC22 (passive probe)
1 2 3 4 Configuration code Configuration code
C111 = GXXX C111 = XX3X
S731 - 0…4 bar / 0…400 kPa C112 = XX1X
B M
QAE22A QBE620-P4
S731/1 - 0…10 bar / 0…1 MPa RWF 40
QBE620-P10
B9 M9
S731/2 - 0…16 bar / 0…1.6 Mpa
Connection for probe QBE620-P16
FT-TP/..(passive probe) S731/3 - 0…25 bar / 0…2.5 MPa 1 2 3 4
(Degusa probe) QBE620-P25
Cod. Configuration code S731/4 - 0…40 bar / 0…4 MPa B M
S704 C111 = 5XXX QBE620-P40 QAC2..

pag.16
LB 1348 Multiflam 170.1 / 200.1

C111 – C112 INPUT CONFIGURATION INDICATIONS

Analog input 1 (actual value) Analog Input 3 (external temperature)


Pt1000, 2-wire, Landis & Staefa IEC 751 No function (probe not active) 0
5
FT-TP/… (passive probe) External probe Pt 1000, 2-wire,
1
QAC22 (passive probe)
Ni1000, 2-wire, Landis & Staefa
QAE2 … (passive probe - water probe) 9
Standard Signal DC 0…10 V QBE620P…
(active probe - pressure probe) G

AUXILIARY CONTACT, TYPE OF REGULATOR, SET POINT “SP1”


BLOCK C112. Parameter configuration
Set point “SP1”
Set point SP1 - data input from keys 0
Set point SP1 - interlocked to external probe (configure) 1

ERROR/FAULT INDICATION
NUMBERS BLINKING IN DISPLAY
- Situation - The number 1999 blinks in the display as the actual value, with the
set point value displayed normally.
- Cause - The real value is not being measured. This means that the upper or lower
limit of the measurement range on analog input 1 (real value) has been exceeded.
- Remedy - Check the electrical connections and the state of the probe. If the probe
is faulty, the regulator will not indicate the real value of the physical quantity
monitored. This will result in automatic shutdown (failsafe), deactivation of the
self-adapt function and inhibition of manual operation. The response of the
auxiliary contact will depend on the configuration of parameter C113.

- Situation - The number 1999 blinks in the display as the actual value, with tA
showing in the set point field.
- Cause - The external temperature is not being measured. This means that the
upper or lower limit of the measurement range on analog input 3 (real value) has
been exceeded.
- Remedy - Check the electrical connections and the state of the probe. If the probe
is faulty, the regulator will not indicate the real value.

- Situation - The number 1999 blinks in the display as the actual value, with SP .E
showing in the set point field.
- Cause - The external set point value is not being measured. This means that the
upper or lower limit of the measurement range on analog input 2 (real value) has
been exceeded.
- Remedy - Check the electrical connections and the external set point signal. If the
probe is faulty, the regulator will not indicate the real value of the physical quantity
monitored. This will result in automatic shutdown (failsafe), deactivation of the
self-adapt function and inhibition of manual operation.

pag.17
LB 1348 Multiflam 170.1 / 200.1

WHEN REPLACEMENT IS NECESSARY, PROCEED AS SHOWN IN FIGURES A-B-C BELOW


A B C

Insert the RWF 40 regulator through the relative opening in the electrical panel (A).
Insert the fixing anchors and screws into the slots, and secure the unit to the panel (B).
To open the regulator, squeeze the cover from the ends as shown, and lift out (C).

MAINTENANCE
ANNUAL CHECK
The burner (combustion head, electrodes, etc.) must be checked regularly by an authorized technician, once or twice
a year, depending on how much it is used. Before proceeding withe the maintenance check-up on the burner, it is
advisable to check the general condition of the burner and take the following steps: Disconnect the burner (remove
the plug).
- Close the gas shut-off cock.
- Remove the cover from the burner, clean the fan and air intake.
- Clean the combustion head and check the position of the electrodes.
- Re-install the parts.
- Check the seal on the gas connectors.
- Check the state of the flue.
- Start the burner.
- Check the combustion parameters

BEFORE TAKING ANY ACTION, CHECK:


- that there is power in the circit and the burner is connected;
- that the gas pressure is right and the gas shut-off cock is open;
- that the control systems are properly connected. If all these conditions have been satisfied, start the burner by pres-
sing the reset button. Check the burner cycle.

IF THE BURNER FAILS TO START:


check the switch, the thermostats, the motor and the gas pressure, fuses burnt, resistors failure, heater thermostats open.

IF THE BURNER PROCEEDS WITH PREVENTILATION BUT CUTS OUT AT THE END OF THE CYCLE:
check the air pressure and the fan. Check the air pressure switch, UV cell failure, premature ignition due to oil leakage
from solenoid valve.
IF THE BURNER PROCEEDS WITH PREVENTILATION BUT DOES NOT LIGHT:
check the installation and position of the electrodes. Electrodes dirty. Nozzles clogged. Check the ignition cable.
Check the ignition transformer. Check the safety device. Eccles of combustion air related to nozzles flow rate.

IF THE BURNER LIGHTS BUT CUTS OUT AFTER THE SAFETY INTERVAL:
check that the phase and neutral wires are connected correctly.
Check the gas solenoid valve. Check the UV cell. Check the safety device. The oil pressure during prepurging is too low.
Filters clogged. Nozzles are too worn. The oil temperature is too low (flame jumps). Eccles of combustion air related to nozzles flow
rate

IF THE BURNER LIGHTS BUT CUTS OUT AFTER OPERATING FOR A FEW MINUTES:
check the pressure regulator and gas filter. Check the gas pressure with a pressure gauge. Check the detector value (at
least 70 µA).

pag.18
LB 1348 Multiflam 170.1 / 200.1

PARAMETERS

Parameter Display (passive probe) (passive probe) (active probe)


QAE22 FT-TP/1000 QBE620-P...
Limit value of limit comparator AL 0 0 0
Switching differential for limit comparator HYSt 0 0 0
Proportional band Pb.1 8 8 1
Derivative time dt 20 20 3
Integral action time rt 80 80 15
Dead band (neutral zone) db 0.5 0.5 0.5
Actuator running time (sec.) tt 12 12 12
Switch-on threshold burner / stage II HYS1 -2 -2 -0.2
Switch-off level stage II HYS2 0 0 0
Upper switch-off threshold HYS3 5 5 0.5
Response threshold q 0 0 0
Heating curve slope H 2 2 2
Parallel displacement P 0 0 0

CONFIGURATION

Parameter Display setting


(passive probe) (active probe) QBE620-P...
QAE22 FT-TP/1000 -P4 -P10 -P16 -P25 -P40
Analog input 1, 2 and 3; setpoint
changeover / shift C111 9030 5030 G000 G000 G000 G000 G000
Limit comparator; controller type;
setpoint 1; locking C112 0010 0010 0010 0010 0010 0010 0010
Unit address; decimal place / unit,
signal for out-of-range C113 0110 0110 0110 0110 0110 0110 0110
Measured value range start analog
input 1 SCL 0 0 0 0 0 0 0
Measured value range
analog input 1 SCH 100 100 4 10 16 25 40
Measured value range
analog input 2 SCL2 0 0 0 0 0 0 0
Measured value range
analog input 2 SCH2 0 0 0 0 0 0 0
Lower setpoint limit SPL 60 60 0 0 0 0 0
Upper setpoint limit SPH 88 88 4 10 16 25 40
Actual value correction,analog input 1 OFF1 0 0 0 0 0 0 0
Actual value correction,analog input 2 OFF2 0 0 0 0 0 0 0
Actual value correction,analog input 3 OFF3 0 0 0 0 0 0 0
Filter time constant for digital filter, dF1 1 1 0 0 0 0 0
analog input 1

pag.19
Multiflam 170.1 / 200.1 43

42

35
39
40 38
4 37

7 6 5
36
32
34
44
31
65
LB 1348 Multiflam 170.1 / 200.1

15 29 2

28 27 41
45

66 13
30
14
54
17
R
19 DE
FIN

56
21
55
25
24 57
23

pag.20
26
22 16
18 1
20
8
10
9

64 11

60
63 62 61 59 58

53

47

50
46
48
51

2
52
3
51

12
LB 1348 Multiflam 170.1 / 200.1

N° DESCRIPTION Multiflam 170.1 Multiflam 200.1


300 mbar 300 mbar
code code
1 - AIR PRESSURE SWITCH DUNGS LGW10 A2P Q120 Q120
2 - PRESSURE GAUGE BFT01105/001 BFT01105/001
3 - AIR INTAKE SET GRPA100 GRPA100
4 - COVER BFC09204/038 BFC09204/038
5 - GLASS BFC02004 BFC02004
6 - PEED WINDOM FRAME BFC02006 BFC02006
7 - MOTOR 3000 W M146/017 -
4000 W - M127/017
8 - FAN 280 x 140 BFV10301/001 BFV10301/001
9 - AIR CONVEYOR BFC08252/201 BFC08252/201
10 - FAN SCOOP - BFC08056/001
11 - AIR INTAKE BFC04154/038 BFC04154/038
12 - AIR INTAKE PIPE BFS02208/201 BFS02208/201
13 - CONTROL BOX BASE LANDIS A401 A401
14 - CONTROL BOX LANDIS LFL1.622 A113 A113
15 - IGNITION TRANSFORMER BRAHMA T8 13000/35 T101 T101
16 - REMOTE CONTROL SWITCH AEG LS4K.10 R621/1 R621/1
AEG LS11K.00 R621/4 R621/4
17 - REMOTE CONTROL SWITCH (MOTOR) BF16.10 R617/1 R617/1
18 - REMOTE CONTROL SWITCH (PUMP) AEG LS05.10 R621 R621
19 - MOTOR THERMAL RELAY (MOTOR) AEG 8-12,5A - R521/5
20 - MOTOR THERMAL RELAY (PUMP) AEG 1,7-2,4A - R521/2
21 - THERMOMETER IMIT sc.0-200 R301/2 R301/2
22 - GAS/HEAVY OIL SWITCH cod.360000001 R1020/1 R1020/1
23 - MAIN SWITCH cod.40100I1509 R1020 R1020
24 - MANUAL / AUTOMATIC SELECTOR R1020/5 R1020/5
25 - LAMP ORANGE E1510/1 E1510/1
GREEN 319017030S E1507/2 E1507/2
RED 319010010S E1507
26 - FUSE SUPPORT FUSIT FH-B528 E802/2 E802/2
27 - RELAY BASE Finder 5534 R906 R906
28 - RELAY Finder 5534 R712 R712
29 - UV CELL LANDIS QRA A205 A205
30 - IGNITION CABLE BFE01403/1 BFE01403/1
BFE01403/2 BFE01403/2
31 - IGNITION ELECTRODES SET E612 E612
32 - PIPE TC BFT14002/101
TL BFT14002/201
33 - ROD
34 - FIRING HEAD GAS
35 - FIRING HEAD HEAVY OIL TC BFT15055/102 BFT15055/102
TL BFT15055/202 BFT15055/202
36 - FRONT DISC BFD03021
37 - ROD NOZZLE HOLDER TC GRSP003 GRSP003
TL GRSP004 GRSP004
38 - NOZZLE HOLDER BFT15006 BFT15006
39 - OIL VALVE PARKER SCEM 120.8AR JB 18 V175/7 V175/7
40 - COIL PARKER V516/7 V516/7
41 - INNER ASSEMBLY
42 - BLAST TUBE TC BFB07030/103
TL BFB07030/203
43 - BLAST TUBE END BFB07030/4
44 - GASKET ISOMART BFG04006 BFG04006
45 - ANTIJAMMING FILTER S132/4 S132/4
46 - AIR DAMPER MOTOR LANDIS SQM50.381A2 M212/9 M212/9
47 - WIELAND PLUG 6 pin E226 E226
48 - WIELAND SOCKET 6 pin E226/1 E226/1
49 - OIL PUMP SUNTEC E 6NC 1069 P107 P107
50 - COUPLING MP501/4 MP501/4
51 - HOSES TN 18X1500 S902 S902
52 - OIL FILTER 70501/03 - S107/5
53 - PUMP MOTOR SIMEL 550 W - M147/81
54 - MANOMETER S601/1 S601/1
55 - OIL VALVE PARKER SCEM 120.8AR JB 18 V175/7 V175/7
56 - COIL PARKER V516/7 V516/7
57 - THERMOSTAT IMIT TR2 40/200 R801/2 R801/2
58 - FILTER BFP01114 BFP01114
59 - HEATER 9000 W R122 -
10500 W - R123
60 - OIL TANK BFP01033/017 BFP01033/017
61 - SILENCER - GRSIL03
62 - GAS VALVE BRAHMA EG12SR V142/1 V142/1
63 - COIL BRAHMA EG12SR V209 V209
64 - GAS PIPE EMISUPER S942/1 S942/1
65 - GAS PIPE EMICASA S942/2 S942/2
66 - MODULATING UNIT LANDIS RWF 40 E1215 E1215
TC = SHORT HEAD TL = LONG HEAD
pag.21
00 01 02 03 04 05 06 07 08 09
PAGINA DI
LANDIS LFL 1.622 LANDIS SQM 50.381A2 LANDIS RWF 40
M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 31 32 1
1/2
L N Q Y1 Y2 Q13 Q14 G+ G- M1 U1 G1+ B9 M9 D1 GND
N 11 1 21 12 2 22 13 3 23 14 4 24 15 5 25 16 6 26 17 7 27
A A
SAMA
YVGP
-
UV KA4
TV 0 3
ABCD

1 2
+
LB 509

B B

SA GAS-OIL

GAS NAFTA
HLR SPA HLgas KA1 YVO1 YVna HLnafta KA2 KA3 STmin STR 95
YVO2
T T
T P P
P FMV
96

COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE.


C C

STRL STL
T
LOAD T P
L1 N T1 T2 S3

pag.22
95 P
Z
LINE
FMP
96
FU

A T RMINE DI LEGGE E' VIETATO RIPRODURRE O


R S T NO KMP R S T NO KMV R S T NO
R S T NO

FU L1 N T1 T2 S3
D SAL D
KMRLA KMRLI FMP FMV KA
SARA

SPGmin YVGS YVG1


T
P

PREDISPOSIZIONE
CONTROLLO DI TENUTA
PREDISPOSED
LEKAGE CONTROL
BLUE
YELLOW-GREEN
BLACK
BROWN

PREVU POUR LE
R S T N R S T N 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 CONTROLE D'ETANCHEITI
PREDISPOSICION
CONTROL DE ESTANQUIDAD

Q
E E
R S T R1 S1 T1 1 2 U V W
U V W
50 Hz 400 V
MP M PE
3 MV M SA
3 R
R S T
GL M U1
S
R1 S1 T1 SAMA
QBE620-P
T COLLEGAMENTO CENTRALINA
400V 400V N DI EMULSIONE AQUAMATIC COMMUTATORE MANUALE-AUTOMATICO
Q CONNECTION TO SWITCH MANUAL-AUTOMATIC

PROPRIETA' RISERVATA DELLA DITTA


L1 N L2 INTERRRUPTEUR MANUEL-AUTOMATIQUE
AQUAMATIC EMULSIFIER 0
230V 230V STC T 3
P 1 2 CONMUTADOR MANUAL-AUTOMATICO
CONNEXION A
50 Hz 400 V
R
L'EMULSEUR AQUAMATIC
400V pos 0 : ARRESTO / STOP
S HLB RP RA RA CONEXION AL
STS pos 1 : ALTA FIAMMA/HIGH FLAME/2e ALLURE/ALTA LLAMA
T
EMULSIFICADOR AQUAMATIC
T
P
N
pos 2: BASSA FIAMMA/LOW FLAME/1e ALLURE/BAJA LLAMA

PE pos 3: AUTOMATICO/AUTOMATIC/AUTOMATIQUE
REV 7.0

DENOMINAZIONE MOTORIDUTTORE

IND.MOD. DATA-FIRMA DESCRIZIONE MODIFICA S.p.A.


MULTIFLAM 200.1 AB/MODULAIR LANDIS SQM 50.381A2
SOST.IL DISEGNATO 04-03-2004 APPARECCHIATURA CONTROLLO DI TENUTA SIST. RIVELAZ. CODICE IND.MODIFICA

DATA
DATA
UFF.TECNICO-SETTORE ELETTRICO

FIRMA
FIRMA
SOST.DA CONTROLLATO 11-03-2004 LANDIS LFL 1.622 PREDISPOSTO UV BEM44.004
00 01 02 03 04 05 06 07 08 09
00 01 02 03 04 05 06 07 08 09
PAGINA DI

Q INTERRUTTORE GENERALE CON FUSIBILE KA3 RELE' HLBT LAMPADA DI BLOCCO TERMICO
MAIN SWITCH WITH FUSE RELAY THERMAL LOCK-OUT LAMP
2/2
INTERRUPTEUR GENERAL AVEC FUSIBLE RELAIS LAMPE DE THERMAL DE SECURITE
REGOLAZIONE CAMME PER MULTIFLAM 200.1
INTERRUPTOR GENERAL CON FUSIBLE RELE' ESPIA DE BLOQUEO RELE TERMICO
Z FILTRO ANTIDISTURBO KA4 RELE' YVGP ELETTROVALVOLA GAS PILOTA
A ANTJAMMING FILTER RELAY PILOT FLAME SOLENOID GAS VALVE A
FILTRE ANTIPARASITES RELAIS ELECTROVANNE GAZ PILOTE
FILTRO DE PROTECION ANTIDISTURBIO RELE' ELECTROVALVULA GAS PILOTO
FU FUSIBILE KMP CONTATTORE MOTORE VENTILATORE I II III IV V VI VII VIII
FUSE REMOTE CONTROL SWITCH (FAN MOTOR)
FUSIBLE CONTACTEUR MOTEUR VENTILATEUR 0 0 0 0 0
FUSIBLE TELERRUPTOR MOTOR VENTILATOR
FU FUSIBILE KMV CONTATTORE MOTORE VENTILATORE
FUSE REMOTE CONTROL SWITCH (FAN MOTOR)
FUSIBLE CONTACTEUR MOTEUR VENTILATEUR
FUSIBLE TELERRUPTOR MOTOR VENTILATOR
KA RELE' SAL INTERRUTTORE DI LINEA
RELAY WORKING SWITCH
RELAIS INTERRUPTEUR DE LIGNE
RELE' INTERRUPTOR DE LINEA
B B
MV MOTORE VENTILATORE SPA PRESSOSTATO ARIA (60∞) I: CAMMA DI REGOLAZIONE ARIA MASSIMA FIAMMA GAS-NAFTA
MOTOR FAN AIR PRESSURE SWITCH (15∞) II: CAMMA DI REGOLAZIONE ARIA ACCENSIONE GAS
MUTEUR VENTILATEUR PRESSOSTAT AIR (40∞) III: CAMMA DI REGOLAZIONE ARIA BASSA FIAMMA LAVORO GAS
MOTOR VENTILADOR PRESOSTATO AIRE (42∞) IV: CAMMA DI REGOLAZIONE BASSA FIAMMA LAVORO NAFTA
(52∞) V: CAMMA APERTURA ELETTROVALVOLA SECONDA FIAMMA NAFTA
RA RESISTENZA AUSILIARIA STC TERMOSTATO CALDAIA
AUXILIARY RESISTOR BOILER THERMOSTAT (0∞) VI: CAMMA NON UTILIZZATA
RESISTANCE AUXILIAIRE THERMOSTAT CHAUDIERE (0∞) VII: CAMMA NON UTILIZZATA
RESISTENCIA AUXILIARIA TERMOSTATO CALDERA (0∞) VIII: CAMMA NON UTILIZZATA

COMUNICARE A TERZI IL CONTENUTO DEL PRESENTE.


LB 509

RP RESISTENZA POMPA STR TERMOSTATO DI SICUREZZA RESISTENZE


PUMP RESISTOR RESTOR SAFETY TERMOSTAT
RESISTANCE POMPE TERMOSTAT DE SECURITE RESISTANCES
RESISTENCIA BOMBA TERMOSTATO DE SEGURIDAD RESISTENCIAS
SA SONDA ATTIVA STS TERMOSTATO DI SICUREZZA
USIN GATTIVE SAFETY THERMOSTAT
C SONDE SCTIVE THERMOSTAT DE SECURITE C
SONDA SCTIVA TERMOSTATO DE SEGURIDAD
TV TRASFORMATORE SAMA COMMUTATORE MANUALE-AUTOMATICO
IGNITION TRANSFORMER SWITCH (MANUAL-AUTOMATIC))
TRANSFORMATEUR D'ALLUMAGE INTERRUPTEUR MANUEL-AUTOMATIQUE
TRANSFORMADOR CONMUTADOR MANUAL-AUTOMATICO
UV FOTOCELLULA SARA INTERRUTTORE RESISTENZE AUSILIARIE
UV CELL AUX HEATER SWITCH

pag.23
CELLULE UV INTERRUPTEUR DES RESISTACES AUXILIAIRES
FOTOCELULA INTERRUPTOR RESISTENCIA AUXILIAR
FMV RELE' TERMICO MOTORE POMPA YVG1 ELETTROVALVOLA GAS DI PRIMA FIAMMA
MOTOR PUMP THERMAL RELAY FIRST STAGE GAS SOLENOID VALVE
RELAIS THERMIQUE MOTEUR POMPE ELECTROVANNE GAZ PETITE ALLURE

A TERMINE DI LEGGE E' VIETATO RIPRODURRE O


RELE' TERMICO MOTOR BOMBA ELECTROVALVULA GAS DE 1^ LLAMA
D FMV RELE' TERMICO MOTORE VENTILATORE YVGS ELETTROVALVOLA GAS DI SICUREZZA D
MOTOR THERMAL RELAY (FAN MOTOR) EXTRA SAFETY GAS SOLENOID VALVE
RELAIS THERMIQUE MOTEUR VENTILATEUR ELECTROVANNE GAZ DE SECURITE
RELE' TERMICO MOTOR VENTILADOR ELECTROVALVULA GAS DE SEGURIDAD
HLgas LAMPADA GAS YVna ELETTROVALVOLA NORMALMENTE APERTA
1.ST FLAME LAMP NORMALLY OPEN SOLENOID VALVE
LAMPE DE 1^ ALLURE ELECTROVANNE NORMALEMENT AUVERT
ESPIA DE 1^ LLAMA ELECTROVALVULA NORMALMENTE ABIERTA

.
HLnafta LAMPADA NAFTA YVO1 ELETTROVALVOLA OLIO DI PRIMA FIAMMA
2.ST FLAME LAMP FIRST STAGE HEAVY OIL SOLENOID VALVE
LAMPE DE 2^ ALLURE ELECTROVANNE 1∞ ALLURE
ESPIA DE 2^ LLAMA ELECTROVALVULA FUEL PESADO DE 1^ LLAMA
HLB LAMPADA DI BLOCCO YVO2 ELETTROVALVOLA OLIO DI SECONDA FIAMMA
LOCK-OUT LAMP SECOND STAGE HEAVY OIL SOLENOID VALVE
LAMPE DE SECURITE ELECTROVANNE 2∞ ALLURE
E ESPIA DE BLOQUEO ELECTROVALVULA FUEL PESADO DE 2^ LLAMA E

HLR LAMPADA RESISTENZE KMRLA CONTATTORE RESISTENZE DI LAVORO


RESISTOR LAMP WORKING RESISTOR SWITCH
TEMOIN RESISTENCES INTERRUPTEUR DES RESISTANCES DE TRAVAIL
INDICADOR RESISTENCIAS INTERRUFTOR DE LAS RESISTENCIAS DE TRABAJIO
KA1 RELE' SPGmin PRESSOSTATO GAS DI MINIMA

PROPRIETA' RISERVATA DELLA DITTA


RELAY GAS PRESSURE SWITCH MIN
RELAIS PRESSOSTAT GAZ PRESSION MIN
RELE' PRESOSTATO GAS DE MINIMA POT.
KA2 RELE' KMRLI CONTATTORE RESISTENZE DI LIVELLAMENTO
RELAY LEVELLING RESISTOR SWITCH
RELAIS INTERRUPTEUR DES RESISTANCES DE NIVELLEMENT
RELE' INTERRUFTOR DE LAS RESISNCIAS DE NIVELACION

DENOMINAZIONE MOTORIDUTTORE

IND.MOD. DATA-FIRMA DESCRIZIONE MODIFICA S.p.A.


MULTIFLAM 200.1 AB/MODULAIR LANDIS SQM 50.381A2
SOST.IL DISEGNATO APPARECCHIATURA CONTROLLO DI TENUTA SIST. RIVELAZ. CODICE IND.MODIFICA

DATA
DATA
UFF.TECNICO-SETTORE ELETTRICO

FIRMA
FIRMA
SOST.DA CONTROLLATO LANDIS LFL 1.622 PREDISPOSTO UV BEM44.004