Central Data Bank


List of Building Materials

A. General

Department: Buildings

Type of building material: Structural Fixing

Applications: Drill-in/Cast-in Anchors

B. Acceptance criteria

Testing standards:
Testing of drill-in anchors and cast-in anchors should be in
accordance with BS 5080.

Conditions of Acceptance:
• The factor of safety of structural fixing systems (drill-in anchors
and cast-in anchors) shall not be less than 3.
• Structural fixing systems shall be properly installed and securely
fixed to the parent structure in accordance with the manufacturer’s
specifications/recommendations.
• Suitability of the structural fixing system in terms of fire
performance as well as any need for fire protection of the exposed
parts of the fixing system shall be considered individually.
• Where drill-in anchors are used for cladding works or for
supporting steel cantilevered canopy structures, strength tests on
a representative number of the drill-in anchors may be required.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Fischer Steel fischerwerke Artur Zinc-plated steel, or Drill-in anchors BS 5080: Parts 1 N/A University of Hong A-MIS-487, January 1991 18/01/2005 No-objection letter issued
Anchors Fischer GmbH & Co. stainless steel A4. subject to axial &2 Kong, Department A-MIS-488 in 1991.
001
KG tension and shear. of Civil &
Types EA M8, Structural Updated information on
M12 & M16 (See remarks) Engineering place of manufacture to be
provided by the
manufacturer.

The application of the


anchors is to be considered
individually with regard to
the fire resistance aspect.
BD-AF
Fischer Steel fischerwerke Artur Zinc-plated steel Drill-in anchors BS 5080: Parts 1 N/A University of Hong A-MIS-487, January 1991 18/01/2005 No-objection letter issued
002 Anchors Fischer GmbH & Co. subject to axial &2 Kong, Department A-MIS-488 in 1991.
KG tension and shear. of Civil &
Types FB 8/50, Structural Updated information on
10/50 & 12/50 (See remarks) Engineering place of manufacture to be
provided by the
manufacturer.

The application of the


anchors is to be considered
individually with regard to
the fire resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF
Hemax 820 Harris & Edgar Grade 303 austenitic Drill-in anchors BS 5080: Part 1: N/A John Laing RD/82/116/ST August 1982 18/01/2005 No-objection letter issued
003 Parallel Limited stainless steel fixed in concrete 1974 Research and in 1993.
Expansion base material and Development
Bolts (See remarks) subject to axial Limited. Updated information on
tension and shear. place of manufacture to
M8, M10, BS 5080: Part 2: Laing Technology be provided by the
1986 NAMAS TS931095 July 1993
M12, M16 & Details and load Group Limited manufacturer.
M20 capacities of the
anchors are as Structural applications
shown in which may be exposed to
appendix A to fire will be considered
BD’s letter Ref. individually.
BD
Tests for quality control
GR/SEG/AF(9)
and workmanship may
of 6 September
be required during
1993.
construction.
BD-AF
Hilti HHS Hilti (Hong Kong) Galvanized steel Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
004 Self-drilling Limited drill-in anchors in 1984.
Anchor * Test report could
(See remarks) not be retrieved. Updated information on
place of manufacture to
be provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF
Hilti HKD Hilti (Hong Kong) N/A Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
005 Anchor Limited drill-in anchors in 1984.
* Test report could
(See remarks) not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
BD-AF
Hilti HSA Stud Hilti (Hong Kong) N/A Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
006 Anchor Limited drill-in anchors in 1984.
* Test report could
(See remarks) not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF
Hilti HSA –303 Hilti Corporation Stainless steel grade Drill-in anchors BS 5080: Parts 1 N/A Hong Kong AN-1 January 1994 18/01/2005 No-objection letter issued
007 Stud Anchor 303 fixed in concrete &2 University, Civil in 1994.
(See remarks) base material and Engineering AN-2
M8, M10 & subject to axial Department Testing Updated information on
M12 tension and shear. Laboratory place of manufacture to be
provided by the
Details and load manufacturer.
capacities of the
anchors are as Structural applications
shown in which may be exposed to
appendices A & fire will be considered
B to BD’s letter individually.
Ref. (3) in BD
Tests for quality control
GR/SEG/AF(13)
and workmanship may be
of 1 March 1994.
required during
construction.

BD-AF Hilti HSC Hilti Galvanized steel Drill-in anchors BS 5080: Parts 1 HOKLAS Hong Kong AN56 May 1992 18/01/2005 No-objection letter issued
Safety Anchor Aktiengesellschaft fixed in concrete &2 University, Civil in 1993.
008 AN57 May 1992
base material and Engineering
AM8x40, (See remarks) subject to axial Department Testing Updated information on
AM8x50, AN82 June 1993 place of manufacture to be
tension and shear. Laboratory
AM10x40, provided by the
AM12x60, Details and load manufacturer.
IM8x40, capacities of the
IM10x50, anchors are as Structural applications
IM10x60 & shown in which may be exposed to
IM12x60 appendix A to fire will be considered
BD’s letter Ref. individually.
(15) in BLD(B)
Tests for quality control
GR/SEG/AF(6)
and workmanship may be
of 8 July 1993.
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF
Hilti HSL Hilti (Hong Kong) Grade 8.8 galvanized Heavy duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
009 Heavy Duty Limited steel drill-in anchors in 1984.
Anchor * Test report could
(See remarks) not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.

BD-AF Hilti HSL-TZ Hilti Corporation Zinc galvanized Drill-in anchors BS 5080: Parts 1 N/A University of Hong AN11 October 1991 18/01/2005 No-objection letter issued
Heavy Duty grade 8.8 steel subject to axial &2 Kong, Department in 1992.
010 (See remarks) AN24 December
Anchor tension and shear. of Civil &
Structural 1991 Updated information on
M8, M10, AN25 place of manufacture to be
Engineering
M12, M16 & provided by the
M20 manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF
Hilti HST-R Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Parts 1 N/A Hong Kong AN85 August 1993 18/01/2005 No-objection letter issued
011 Safety Anchor fixed in &2 University, Civil in 1993.
(See remarks)
uncracked Engineering AN86 September
M8, M10, concrete base Department Testing 1993 Updated information on
M12, M16, material and Laboratory place of manufacture to be
M20 & M24 subject to axial provided by the
tension and shear. manufacturer.

Details and load Structural applications


capacities of the which may be exposed to
anchors are as fire will be considered
shown in individually.
appendix A to
Tests for quality control
BD’s letter Ref.
and workmanship may be
(19) in BD
required during
GR/SEG/AF(6)
construction.
of 15 December
1993.

BD-AF Hilti HVA Hilti (Hong Kong) N/A Heavy duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
Adhesive Limited anchors in 1984.
012 * Test report could
Anchor (See remarks)
not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF
Ramset Ramset Fasteners N/A Heavy duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
013 Chemset (H.K.) Ltd. anchors in 1989.
Chemical * Test report could
(See remarks)
Anchor not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.

BD-AF Ramset Ramset Fasteners N/A Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
Dynabolt (H.K.) Ltd. anchors in 1989.
014 * Test report could
Anchor
(See remarks) not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
BD-AF
Ramset Ramset Fasteners N/A Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
015 Dynaset (H.K.) Ltd. anchors in 1989.
Anchor * Test report could
(See remarks)
not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Ramset Terrier Ramset Fasteners N/A Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
Self-drilling (H.K.) Ltd. anchors in 1989.
016 * Test report could
Anchor
(See remarks) not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
BD-AF
Ramset Trubolt Ramset Fasteners N/A Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
017 Anchor (H.K.) Ltd. anchors in 1989.
* Test report could
(See remarks)
not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Rawlplug Rawlplug Company Zinc plated, or Drill-in chemical BS5080 N/A Swedish National 87B1.1801 1988 18/01/2005 No-objection letter issued
Kemfix Ltd. stainless steel (grade anchors subject equivalent Testing Institute in 1994.
018
Chemical 303) to axial tension
Anchor (See remarks) and shear. Updated information on
place of manufacture to be
M8, M10, Load capacities provided by the
M12, M16, of the anchors are manufacturer.
M20 & M24 as shown in
appendix C to Structural applications
BD’s letter Ref. which may be exposed to
(19) in BD fire will be considered
GR/SEG/AF(10). individually.

Tests for quality control


and workmanship may be
required during
construction.
BD-AF
Rawlplug Rawlplug Company Zinc plated steel Drill-in anchors BS 5080 N/A Thornliebank N/A* N/A 18/01/2005 No-objection letter issued
019 Rawlbolt Ltd. subject to axial equivalent in 1994.
tension and shear. * Test report could
(See remarks)
M6, M8, M10, not be retrieved. Updated information on
M12, M16, Load capacities place of manufacture to be
M20 & M24 of the anchors are provided by the
as shown in manufacturer.
appendix A to
BD’s letter Ref. Structural applications
(19) in BD which may be exposed to
GR/SEG/AF(10). fire will be considered
individually.

Tests for quality control


and workmanship may be
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Rawlplug Rawlplug Company Zinc plated, or Drill-in anchors BS 5080 N/A Thornliebank N/A* N/A 18/01/2005 No-objection letter issued
Tufbolt Ltd. stainless steel (grade subject to axial equivalent * Test report could in 1993.
020
303 or 316) tension and shear. not be retrieved.
M6, M8, M10, (See remarks) Updated information on
M12, M16 & Load capacities place of manufacture to be
M20 of the anchors are provided by the
as shown in manufacturer.
appendix A to
BD’s letter Ref. Structural applications
(14) in BD which may be exposed to
GR/SEG/AF(10). fire will be considered
individually.

Tests for quality control


and workmanship may be
required during
construction.
BD-AF
Spit Fix Signode Hong Kong Stainless steel grade Drill-in anchors Testing methods HOKLAS Hong Kong A-MIS-477 August 1990 18/01/2005 No-objection letter issued
021 Anchor Ltd. 303 subject to axial were given in the University, Civil in 1990.
tension and shear. test reports. Engineering A-MIS-480 August 1990
(See remarks)
M10 & M12 Department Testing Updated information on
A-MIS-478 August 1990 place of manufacture to be
Laboratory
provided by the
A-MIS-481 August 1990
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF
Spit Fix Signode Hong Kong Grade 5.8 steel. Drill-in anchors Testing methods HOKLAS Hong Kong A-MIS-474 July 1990 18/01/2005 No-objection letter issued
022 Anchor Ltd. subject to axial were given in the University, Civil in 1990.
tension and shear. test reports. Engineering A-MIS-482 August 1990
(See remarks)
M16 Department Testing Updated information on
Laboratory place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Sunway Sunway Metal Stainless steel (SUS Drill-in anchors BS 5080: Part 1: N/A MateriaLab 910064t10008 January 1991 18/01/2005 No-objection letter issued
Anchor Bolt Manufactory 304) subject to axial 1974 Limited 901714t4858 in 1992.
023 August 1990
tension and shear.
Model (See remarks) Updated information on
SW-M-10 place of manufacture to be
Engineering PD/2257/89
provided by the
Materials Research January 1989
manufacturer.
& Laboratories
Ltd. Structural applications
BS 5080: Part 2:
July 1991 which may be exposed to
1986 SL0972 fire will be considered
individually.
OPP Testing
Services Ltd. Quality control procedures
for manufacturing of the
anchors should be in
accordance with the
Sunway’s Quality Control
Procedures (Revision A)
and the subsequent
amendment to the
sampling rate of the
pull-out and shear tests s,
submitted to BD on
28.8.92 and 22.10.92
respectively.

Tests for quality control


and workmanship may be
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Upat EXA Upat GmbH & Co. Stainless steel grade Drill-in anchors BS 5080: Parts 1 N/A University of Hong A-MIS-484 September 18/01/2005 No-objection letters issued
Express 303 for M6 subject to axial & 2, or otherwise Kong, Department A-MIS-485 1990 in 1990 and 1991.
024 (See remarks)
Anchor tension and shear. as stated in the of Civil and
Stainless steel grade test reports. Structural July 1991 Updated information on
AN5
M6 & M12 A1 for M12 Engineering place of manufacture to be
AN6
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
BD-AF
Upat EXA Upat GmbH & Co. Stainless steel grade Drill-in anchors BS 5080: Parts 1 HOKLAS Hong Kong AN64 September 18/01/2005 No-objection letter issued
025 Express A1-70 subject to axial &2 University, Civil 1992 in 1992.
(See remarks)
Anchor tension and shear. Engineering AN65
Department Testing Updated information on
M8 & M10 Details and load Laboratory place of manufacture to be
capacities of the provided by the
AN62
anchors are as manufacturer.
August 1992
shown in AN63
appendix A to Structural applications
BD’s letter Ref. which may be exposed to
(31) in BLD(B) fire will be considered
GR/SEG/AF(4). individually.

Tests for quality control


and workmanship may be
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Upat EXA Upat GmbH & Co. Zinc-plated steel, or Drill-in anchors BS 5080: Parts 1 N/A University of Hong AN5 July 1991 18/01/2005 No-objection letters issued
Express hot-dipped subject to axial &2 Kong, Department AN6 in 1991, 1992 and 1993.
026 (See remarks)
Anchor galvanized steel. tension and shear. of Civil and
Structural Updated information on
AN20 November
M6, M8, M10, Engineering place of manufacture to be
AN22 1991
M12, M16 & provided by the
M20 manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
BD-AF
Upat PSE Upat GmbH & Co. Zinc-plated steel Heavy duty BS 5080: Parts 1 N/A University of Hong AN5 July 1991 18/01/2005 No-objection letter issued
027 14/25 Anchor drill-in anchors &2 Kong, Department in 1991.
(See remarks)
subject to axial of Civil and AN6
M10 tension and shear. Structural Updated information on
Engineering place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
BD-AF
Upat PSE Upat GmbH & Co. Zinc-plated steel Heavy duty BS 5080: Parts 1 N/A University of Hong AN21 November 18/01/2005 No-objection letter issued
028 18/25 Anchor drill-in anchors &2 Kong, Department 1991 in 1992.
(See remarks)
subject to axial of Civil and AN23
M12 tension and shear. Structural Updated information on
Engineering place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Upat PSE Upat GmbH & Co. Zinc-plated grade 8.8 Heavy duty BS 5080: Parts 1 HOKLAS Hong Kong AN55 April 1992 18/01/2005 No-objection letter issued
24/25 Anchor steel drill-in anchors &2 University, Civil AN53 in 1992.
029 (See remarks) subject to axial Engineering
M16 tension and shear. Department Testing Updated information on
Laboratory place of manufacture to be
provided by the
manufacturer.

Structural applications
which may be exposed to
fire will be considered
individually.

Tests for quality control


and workmanship may be
required during
construction.
BD-AF
Upat PSE Upat GmbH & Co. Zinc-plated grade 8.8 Heavy duty BS 5080: Parts 1 HOKLAS Hong Kong AN55 April 1992 18/01/2005 No-objection letter issued
030 28/25 Anchor steel drill-in anchors &2 University, Civil in 1992.
(See remarks)
subject to axial Engineering AN53
M20 tension and shear. Department Testing Updated information on
Laboratory place of manufacture to be
provided by the
manufacturer.

Structural applications
which may be exposed to
fire will be considered
individually.

Tests for quality control


and workmanship may be
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Upat UKA-3 Upat GmbH & Co. Chemical anchor Chemical anchor BS 5080: Parts 1 N/A University of Hong A-MIS-486 September 18/01/2005 No-objection letters issued
EAP Chemical consists of a stainless with anchorage & 2, or otherwise Kong, Department A-MIS-487 1990 in 1990 and 1991.
031 (See remarks)
Anchor steel (grade 316) to be achieved by as stated in the of Civil and
threaded stud with the bond formed test reports. Structural Updated information on
M8, M10, M12 nut and washer and a by the cured Engineering place of manufacture to be
AN5
& M16 glass capsule chemical mortar provided by the
AN6
containing quartz between the stud manufacturer.
July 1991
aggregate, epoxy and the
The application is to be
acrylate resin and a surrounding
considered individually
small glass capsule concrete.
with regard to the fire
containing the
resistance aspect.
hardener.
BD-AF
Upat UKA-3 Upat GmbH & Co. Chemical anchor Chemical anchor BS 5080: Parts 1 HOKLAS Hong Kong AN54 April 1992 18/01/2005 No-objection letter issued
032 EAP Chemical consists of a with anchorage &2 University, Civil in 1992.
(See remarks)
Anchor zinc-plated steel to be achieved by Engineering AN52
(grade 5.8) threaded the bond formed Department Testing Updated information on
M20 & M24 stud with nut and by the cured Laboratory place of manufacture to be
washer and a glass chemical mortar provided by the
capsule containing between the stud manufacturer.
quartz aggregate, and the
Structural applications
epoxy acrylate resin surrounding
which may be exposed to
and a small glass concrete.
fire will be considered
capsule containing
individually.
the hardener.
Tests for quality control
and workmanship may be
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Upat USA Upat GmbH & Co. Stainless steel grade Drill-in anchors BS 5080: Parts 1 HOKLAS Hong Kong AN59 May 1992 18/01/2005 No-objection letter issued
Wedge Anchor A4 subject to axial &2 University, Civil AN60 in 1992.
033 (See remarks) tension and shear. Engineering
M8, M10 & Department Testing Updated information on
M12 Laboratory place of manufacture to be
provided by the
manufacturer.

Structural applications
which may be exposed to
fire will be considered
individually.

Tests for quality control


and workmanship may be
required during
construction.
BD-AF
HIT-C100 Hilti (Hong Kong) Modified epoxy Injection system N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
034 Injection Ltd. acrylate resin for grouting of in 1990.
System for adhesive deformed * Test report could
(See remarks)
Deformed reinforcement. not be retrieved. Updated information on
Reinforcement place of manufacture to be
provided by the
manufacturer.

The application of this


rebar system is to be
considered individually
with regard to the fire
resistance.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti Hilti Corporation Two-component Anchorage of BS 5080: Part 1: N/A Hong Kong MI-960181 June 1996 18/01/2005 No-objection letter issued
HIT-HY150 adhesive based on Y10 & Y16 1993 University, Civil MI-960182 in 1996.
035 (See remarks)
Rebar resin and deformed Engineering
Fastenings cementitious agents. reinforcement as Department Testing Updated information on
structural fixing Laboratory place of manufacture to be
in concrete base provided by the
material for Hong Kong manufacturer.
BS 5080: Part 2: MI-960178
internal building N/A University, Civil June 1996
1986 MI-960177 Structural applications
works only. Engineering
Department Testing which may be exposed to
Setting details, Laboratory fire will be considered
recommended individually.
load capacities
Tests for quality control
and the user
and workmanship may be
guide are as
required during
shown in
construction.
appendices A &
B to BD’s letter
Ref. (17) in BD
GR/SEG/ADH(1
)
BD-AF
Ramset Ramset Fasteners N/A Chemical N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
036 Chemset (H.K.) Ltd. injection system in 1989.
Injection for heavy duty * Test report could
(See remarks)
System anchor fixing. not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
N/A*
BD-AF Red Head Signode Hong Kong N/A Chemical N/A N/A N/A N/A 18/01/2005 No-objection letter issued
* Test report could
Epcon Ceramic Ltd. injection system in 1990.
037 not be retrieved.
6 Injection for anchor fixing.
System (See remarks) Updated information on
place of manufacture to be
M16 & M20 provided by the
manufacturer.

This anchor system is not


to be used for fire resisting
construction.
BD-AF
Halfen HTA Halfeneisen GmbH Channel: hot-dip Cast-in channels BS 5080: Part 1: HOKLAS Testconsult Far S/017/90/1 January 1991 18/01/2005 No-objection letter issued
038 Cast-in & Co. galvanized mild steel used as structural 1974, or East Ltd. in 1992.
Channel (See remarks) grade St 37-2, or fixings in otherwise as
stainless steel grade building works. stated in the test Updated information on
Type HTA A4 reports. place of manufacture to be
52/34 Details and load Wiss, Janney, provided by the
N/A Elstner Associates, WJE No. 880203 November
(52x34x5.2kg./ Bolt: grade 4.6 steel capacities of the manufacturer.
Inc. 1988
m [, with M10, cast-in channels
M12, M16 or are as shown in Structural applications
M20 bolts) appendix A to which may be exposed to
BD’s letter Ref. fire will be considered
(9) in BLD(B) individually.
GR/SEG/5/8(III).
Tests for quality control
and workmanship may be
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Halfen HTA Halfeneisen GmbH Channel: hot-dip Cast-in channels BS 5080: Part 1: HOKLAS Department of N/A April 1993 18/01/2005 No-objection letter issued
Cast-in & Co. galvanized mild steel used as structural 1974 Civil & Structural in 1994.
039
Channel grade St 37-2 fixings in Engineering, Hong
(See remarks) building works. Kong Polytechnic Updated information on
Type HTA Bolt: grade 4.6 steel, place of manufacture to be
50/30 or stainless steel Details and load provided by the
(50x30x3.4kg./ grade A4 capacities of the manufacturer.
BS 5080: Part 2: Department of N/A
m [, with M10, cast-in channels HOKLAS January 1994
1986 Civil & Structural Structural applications
M12, M16 or are as shown in
M20 bolts) appendix A to Engineering, Hong which may be exposed to
BD’s letter Ref. Kong Polytechnic fire will be considered
BD individually.
GR/SEG/5/8(III)
Tests for quality control
of 13 April 1994.
and workmanship may be
required during
construction.
BD-AF
Halfen HTA Halfeneisen GmbH Channel: hot-dip Cast-in channels BS 5080: Part 1: HOKLAS Testconsult Far S/017/90/1 January 1991 18/01/2005 No-objection letter issued
040 Cast-in & Co. galvanized mild steel used as structural 1974, or East Ltd. in 1992.
Channel (See remarks) grade St 37-2 fixings in otherwise as
building works. stated in the test Updated information on
Type HTA Bolt: grade 4.6 steel, reports. place of manufacture to be
40/22 or stainless steel Details and load Wiss, Janney, provided by the
N/A Elstner Associates, WJE No. 880203 November
(40x22x2.2kg/ grade A4 capacities of the manufacturer.
Inc. 1988
m[, with M10, cast-in channels
M12 or M16 are as shown in Structural applications
bolts) appendix A to which may be exposed to
BD’s letter Ref. fire will be considered
(9) in BLD (B) individually.
GR/SEG/5/8(III)
Tests for quality control
of 18 November
and workmanship may be
1992.
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Halfen HTA Halfeneisen GmbH Channel: hot-dip Cast-in channels BS 5080: Part 1: HOKLAS Department of N/A April 1993 18/01/2005 No-objection letter issued
Cast-in & Co. galvanized mild steel used as structural 1974, or Civil & Structural in 1993.
041
Channel grade St 37-2, fixings in otherwise as Engineering, Hong
(See remarks) stainless steel grades building works. stated in the test Kong Polytechnic Updated information on
Type HTA A2 or A4 reports. place of manufacture to be
38/17 Details and load provided by the
(38x17x1.8kg/ Bolt: grade 4.6 steel, capacities of the manufacturer.
m[, with M10, stainless steel grades cast-in channels Wiss, Janney,
N/A WJE No. 880203 November
M12 or M16 A2 or A4 are as shown in Elstner Associates, Structural applications
1988
bolts) appendix A to Inc. which may be exposed to
BD’s letter Ref. fire will be considered
(23) in BD individually.
GR/SEG/5/8(III)
Tests for quality control
of September
and workmanship may be
1993.
required during
construction.
BD-AF
Jordahl Anchor Jordahl Deutsche Channel: mild steel Anchor channels BS 5080: Part 1, HOKLAS Hong Kong AN62 June 1992 18/01/2005 No-objection letter issued
042 Channel Kahneisen grade St37-2 used as structural or otherwise as University, Civil in 1992.
Gesellschaft West fixings in stated in the test Engineering
Type JTA W GmbH. Bolt: grade 4.6 steel building works. reports. Department Testing Updated information on
54/40/4.0 or stainless steel Laboratory place of manufacture to be
(See remarks)
(54x40x5.19kg grade A4 Details and load provided by the
/m[, with Type capacities of the manufacturer.
B bolts of M10, anchor channels
M12, M16 or are as shown in Structural applications
M20]. appendix A to N/A 2..2/195414 March 1980 which may be exposed to
Institute for fire will be considered
BD’s letter Ref.
Material Testing individually.
(11) in BLD(B)
(BAM)
GR/SEG/AF(8)
Tests for quality control
of 9 November
and workmanship may be
1992.
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Jordahl Anchor Jordahl Deutsche Channel: mild steel Anchor channels BS 5080: Part 1, HOKLAS Hong Kong AN62 June 1992 18/01/2005 No-objection letter issued
Channel Kahneisen grade St37-2 used as structural or otherwise as University, Civil in 1992.
043
Gesellschaft West fixings in stated in the test Engineering
Type JTA W GmbH. Bolt: grade 4.6 steel building works. reports. Department Testing Updated information on
50/30/3.0 or stainless steel Laboratory place of manufacture to be
(50x30x3.2kg/ (See remarks) grade A4 Details and load provided by the
m[, with Type capacities of the manufacturer.
B bolts of M10, anchor channels
M12, M16 or are as shown in Structural applications
M20]. appendix A to 2..2/191531 which may be exposed to
N/A January 1979
Institute for fire will be considered
BD’s letter Ref.
Material Testing individually.
(11) in BLD(B)
(BAM)
GR/SEG/AF(8)
Tests for quality control
of 9 November
and workmanship may be
1992.
required during
construction.
BD-AF
Jordahl Anchor Jordahl Deutsche Channel: mild steel Anchor channels BS 5080: Part 1, HOKLAS Hong Kong AN62 June 1992 18/01/2005 No-objection letter issued
044 Channel Kahneisen grade St37-2 used as structural or otherwise as University, Civil in 1992.
Gesellschaft West fixings in stated in the test Engineering
Type JTA W GmbH. Bolt: grade 4.6 steel building works. reports. Department Testing Updated information on
40/22/2.5 or stainless steel Laboratory place of manufacture to be
(See remarks)
(40x22x2.04kg grade A4 Details and load provided by the
/m[, with Type capacities of the manufacturer.
C bolts of M10, anchor channels
M12 or M16] are as shown in Structural applications
appendix A to N/A 2..2/191531 January 1979 which may be exposed to
Institute for fire will be considered
BD’s letter Ref.
Material Testing individually.
(11) in BLD(B)
(BAM)
GR/SEG/AF(8)
Tests for quality control
of 9 November
and workmanship may be
1992.
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Jordahl Anchor Jordahl Deutsche Channel: mild steel Anchor channels BS 5080: Part 1, HOKLAS Hong Kong AN62 June 1992 18/01/2005 No-objection letter issued
Channel Kahneisen grade St37-2 or used as structural or otherwise as University, Civil in 1992.
045
Gesellschaft West stainless steel grade fixings in stated in the test Engineering
Type JTA K GmbH. A4 building works. reports. Department Testing Updated information on
38/17/3.0 Laboratory place of manufacture to be
(38x17x1.78kg (See remarks) Bolt: grade 4.6 steel Details and load provided by the
/m[, with Type or stainless steel capacities of the manufacturer.
H bolts of grade A4 anchor channels
M10, M12 or are as shown in Structural applications
M16]. appendix A to 2..2/191531 which may be exposed to
N/A January 1979
Institute for fire will be considered
BD’s letter Ref.
Material Testing individually.
(11) in BLD(B)
(BAM)
GR/SEG/AF(8)
Tests for quality control
of 9 November
and workmanship may be
1992.
required during
construction.
BD-AF
Jordahl Anchor Jordahl Deutsche Channel: mild steel Anchor channels BS 5080: Part 1, HOKLAS Hong Kong AN51 March 1992 18/01/2005 No-objection letter issued
046 Channel Kahneisen grade St37-2, used as structural or otherwise as University, Civil in 1992.
Gesellschaft West stainless steel grades fixings in stated in the test Engineering
Type JSA K GmbH. A4 or A2 building works. reports. Department Testing Updated information on
28/15/2.3 Laboratory place of manufacture to be
(See remarks)
(28x15x1.11kg Bolt: grade 4.6 steel Details and load provided by the
/m[, with Type or stainless steel capacities of the manufacturer.
D bolts of M6, grade A4 anchor channels
M8 or M10] are as shown in Structural applications
appendix A to N/A 2..2/191531 January 1979 which may be exposed to
Institute for fire will be considered
BD’s letter Ref.
Material Testing individually.
(11) in BLD(B)
(BAM)
GR/SEG/AF(8)
Tests for quality control
of 9 November
and workmanship may be
1992.
required during
construction.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF TRW Nelson TRW Nelson Stud Bars of diameters of Deformed anchor Steel bars were N/A MateriaLab 901865m10099 February 1991 18/01/2005 No-objection letter issued
Deformed Welding Division, 16mm and 19mm stud bars used as subjected to Limited in 1991.
047
Anchor Stud Control & Fasteners conforming to concrete tensile and bend
Bar Group ASTM-A-496. connectors in tests in Updated information on
building works. accordance with place of manufacture to be
Type D2L (See remarks) BS 4449: 1978. provided by the
manufacturer.
Tensile and shear
tests were also The application of the
conducted on anchors is to be considered
stud welded individually with regard to
samples. the fire resistance aspect.

Quality control tests on


sufficient samples of
completed stud
connections may be
required to be conducted
at a HOKLAS accredited
laboratory.
BD-AF
Ramset Ramset Fasteners N/A Medium duty N/A N/A N/A N/A* N/A 18/01/2005 No-objection letter issued
048 Concrete Insert (H.K.) Ltd. anchors in 1989.
* Test report could
(See remarks)
not be retrieved. Updated information on
place of manufacture to be
provided by the
manufacturer.

The application is to be
considered individually
with regard to the fire
resistance aspect.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HSL-3 Hilti Corporation Galvanized grade 8.8 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 023097ST22409 2 January 2003 28/04/2005 The application is to be
Heavy Duty steel subject to axial 1993 Services Limited considered individually
049 Nuziders, Austria 023097ST22411 2 January 2003
Anchor tension and shear. with regard to the fire
resistance aspect.
M12 & M20
BS 5080: Part 2:
1986 023097ST22409( 2 January 2003
1)
2 January 2003
023097ST22411(1
)

BD-AF Hilti HSC-A Hilti Corporation Galvanized grade 8.8 Drill-in anchors BS 5080: Parts 1 N/A Hong Kong AN56 May 1992 28/04/2005 The application is to be
050 Safety Anchor Zhangjiang, China steel subject to axial &2 University, Civil considered individually
tension and shear. Engineering AN57 May 1992 with regard to the fire
M10x40 Department Testing resistance aspect.
AN82 June 1993
Laboratory

BD-AF Fischer FAZ Fischerwerke Artur Stainless steel A4 Drill-in anchors BS 5080: Part 1 HOKLAS Hong Kong SF-0052R7283 5 February 28/04/2005 The application is to be
051 16/25/146 Fischer GmbH & Co subject to axial Curtain Wall 2005 considered individually
Anchor Bolt KG tension and shear. Testing Centre Ltd. with regard to the fire
Waldachtal, resistance aspect.
M16 In house method N/A
Germany based on BS 5 February
5080: Part 2: SF-T0088R7283 2005
1986
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Anchors for BS 5080: Part 1: N/A Fugro Technical 042835ST41894A 2 November 28/04/2005 The application is to be
500 injection for chemical installation of 1993. Services Limited 2004 considered individually
052 Kaufering, Germany
adhesive with fastening with grade rubber fenders.. with regard to the fire
anchor rod SUS316 anchor rod. BS 5080: Part 2: 2 November resistance aspect, if
1986 042835ST41895A 2004 applicable.
M42

BD-AF Hilti HIT-HY Hilti Corporation Hybrid resin system Anchors for BS 5080: Part 1 N/A Hong Kong AN-44 15 March 1995 28/04/2005 The application is to be
053 150 injection Kaufering, Germany for fixing of fixing of outdoor University, Civil considered individually
adhesive with galvanized Grade ancillary Engineering with regard to the fire
Grade 460 460 rebar anchor. amenities. Department Testing resistance aspect, if
rebar of Laboratory applicable.
diameter of
16mm

BD-AF Hilti HIT-HY Hilti Corporation Hybrid resin system Anchors for In house method N/A Hong Kong Testing H06099M1487 17 November 28/04/2005 The application is to be
054 150 injection Kaufering, Germany for fixing of fixing of outdoor based on BS Co., Ltd. 1999 considered individually
adhesive with galvanized Grade ancillary 5080: Part 1 with regard to the fire
Grade 460 460 rebar anchor amenities. resistance aspect, if
rebar of applicable.
diameter of
32mm

BD-AF Hilti HDA-T Hilti Corporation Galvanized grade 8.8 Anchors for BS 5080: Part 2: N/A MateriaLab 000324ST00430( 19 April 2000 03/08/2005 The application is to be
055 self-undercut Liechtenstein steel shear 1986 Limited 1) considered individually
anchor connections with regard to the fire
000324ST00430( resistance aspect.
M10, M12, 3) 19 April 2000
M16 & M20
000324ST00430( 19 April 2000
5)
In-house method Fugro Technical 040547ST40553A
Services Limited 31 March 2004
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HSL-3 Hilti Corporation Galvanized grade 8.8 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 023097ST22410 2 January 2003 03/08/2005 The application is to be
Heavy Duty steel subject to axial 1993. Services Limited considered individually
056 Nuziders, Austria
Anchor tension and shear. with regard to the fire
BS 5080: Part 2: resistance aspect.
M16 1986 023097ST22410( 2 January 2003
1)

BD-AF Hilti HSL-3 Hilti Corporation Galvanized grade 8.8 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 023097ST22408 2 January 2003 03/08/2005 The application is to be
057 Heavy Duty Nuziders, Austria steel subject to axial 1993 Services Limited considered individually
Anchor tension and shear. with regard to the fire
BS 5080: Part 2: resistance aspect.
M10 1986 023097ST22408( 2 January 2003
1)
Ramset Fasteners
BD-AF Ramset Trubolt Grade 316 stainless Heavy duty BS 5080: Part 1: N/A A.E.S. Destructive GS03-0733 AMD Test date is 03/08/2005 The application is to be
(Aust) Pty Limited
058 stud anchor steel torque setting 1993 & Non-destructive No. 1 available but considered individually
T08090SS expansion anchor Testing Ltd. not the report with regard to the fire
Melbourne, BS 5080: Part 2:
subject to axial date resistance aspect.
M8x90 Australia 1986
tension and shear.

BD-AF Hilti HSL-GR Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Part : N/A ETS-Testconsult FDA50383 26 May 2005 03/08/2005 The application is to be
059 Heavy Duty Nuziders, Austria subject to axial 1993 Limited considered individually
Anchor tension and shear with regard to the fire
BS 5080: Part 2: resistance aspect.
M12/25 1986 FDA50429 8 June 2005
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Fischer FZA Fischerwerke Artur Stainless steel A4 Drill-in anchors In house method HOKLAS Castco Testing BD/MISCEL 29 April 2004 26/10/2005 The application is to be
18x100 M12 Fischer GmbH & Co subject to axial based on HKHA Centre Ltd. 240427-1 considered individually
060
D/20 A4 KG tension and shear. MTS with regard to the fire
Anchor Bolt (2000/2002) resistance aspect.
Waldachtal, Specification and
M12 Germany BS 5080: Part 1:
1993 BD/MISCEL
240910-1
In house method Castco Testing
based on BS N/A Centre Ltd. BD/MISCEL
5080: Part 2: 240910-2
1986
BD/MISCEL
13 September
240910-3
2004
BD/MISCEL
240910-4

BD/MISCEL
240910-5

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Anchors for BS 5080: Part 1: N/A Fugro Technical 020323ST20500 Report certified 26/10/2005 The application is to be
061 500 injection for fixing of installation of 1993 Services Limited on 13 June considered individually
adhesive with Kaufering, Germany galvanized Grade balustrade (not 2002. with regard to the fire
Grade 460 460 rebar anchor. for fire resisting resistance aspect, if
rebar of construction) applicable.
diameter of
12mm

BD-AF Fischer EA M6 Fischerwerke Artur Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A Hong Kong Testing I001503M00354 7 March 2003 26/10/2005 The application is to be
062 A4 Anchor Fischer GmbH & Co subject to axial 1993 Co., Ltd. considered individually
Bolt KG tension and shear. with regard to the fire
In house method Castco Testing resistance aspect.
M6 Ningbo, China based on BS Centre Ltd. BD/MISCEL 14 July 2005
5080: Part 2: 250712-9
1986
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Jordahl Anchor Deutsche Kahneisen Channel: hot-dip Anchor channels BS 5080: Part 1: UKAS CERAM Building SW032.02 21 March 2002 26/10/2005 The application is to be
Channel Gesellschaft mbH galvanized mild steel used as structural 1993 Technology considered individually
063
grade St 37-2 fixings in with regard to the fire
Type JTA W Berlin, Germany building works. National Centre for resistance aspect.
53/34 with Bolt: grade 4.6 steel CNAL Quality BETC-CL1-2005- 23 March 2005
Type B bolts of Supervision and 54 Shear load capacity shall
M16 or M20 Test of Building be limited to not
Engineering exceeding the tensile load
capacity.

BD-AF Hilti HSL-3 Hilti Corporation Galvanized grade 8.8 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 023097ST22412 2 January 2003 26/10/2005 The application is to be
064 Heavy Duty steel subject to axial 1993. Services Limited considered individually
Anchor Nuziders, Austria tension and shear. with regard to the fire
BS 5080: Part 2: resistance aspect.
M24 1986 023097ST22412( 2 January 2003
1)

BD-AF Hilti HSL-3 Hilti Corporation Galvanized grade 8.8 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 023097ST22407 2 January 2003 26/10/2005 The application is to be
065 Heavy Duty steel subject to axial 1993. Services Limited considered individually
Anchor Nuziders, Austria tension and shear. with regard to the fire
BS 5080: Part 2: resistance aspect.
M8 1986 023097ST22407( 2 January 2003
1)

BD-AF Hilti HDA-TR Hilti Corporation A4-80 stainless steel Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50469 9 June 2005 03/02/2006 The application is to be
066 self-undercut subject to axial 1993 Limited considered individually
anchor Liechtenstein tension and shear. with regard to the fire
BS 5080: Part 2: resistance aspect.
M16x190/40 1986 FDA50399 30 May 2005

BD-AF Ramset Ramset Fasteners Zinc-plated steel of Steel threaded BS 5080: Part 1: N/A ETS-Testconsult FDA51110 24 November 03/02/2006 The application is to be
067 ChemSet (Aust) Pty Limited grade 5.8 studs grouted 1993 Limited 2005 considered individually
CS12160 Stud with chemical with regard to the fire
Anchor grouted Melbourne, Australia injection mortar. BS 5080: Part 2: 24 November resistance aspect.
1986 FDA51111 2005
in EPCON G5

M12x80mm
embedment
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HSA-R Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50772 6 September 03/02/2006 The application is to be
stud anchor subject to axial 1993 Limited 2005 considered individually
068 Liechtenstein tension and shear. with regard to the fire
M10 BS 5080: Part 2: 30 August resistance aspect.
1986 FDA50730 2005

BD-AF MKT Wedge Metall-Kunststoff- Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 993114ST10286(4 31 March 2001 21/04/2006 The application is to be
069 Anchor subject to axial 1993 Services Limited ) considered individually
B8-10/75 Technik GmbH & tension and shear. 31 March 2001 with regard to the fire
Co. KG BS 5080: Part 2: 993114ST10286(5 resistance aspect.
Weilerbach, 1986 )
Germany
BD-AF Hilti HIT-HY Hilti Corporation Hybrid resin system Injection system BS 476: Part 20: UKAS Warrington Fire WFRC No. 25 September 21/07/2006 The assessment report no.
070 150 Kaufering, Germany for making 1987 Research Centre C121086 2002 WFRC No. C121086 is
nominal valid until 1 October 2007.
anchorage
connections of Load carrying capacity of
Grade 460 rebars the injection system for
of diameters up rebar fixing under the
to 25mm in effects of fire should be
reinforced assessed with an
concrete appropriate factor of safety
elements up to 4 compatible with the
hrs. FRP. structural design of the
parent structure.

Reference can also be


made to ref. BD-FP 054
under the .
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection system BS 476: Part 20: UKAS Warrington Fire WFRC No. 25 September 21/07/2006 The assessment report no.
500 for making 1987 Research Centre C121086 2002 WFRC No. C121086 is
071 Kaufering, Germany nominal valid until 1 October 2007.
anchorage
connections of Load carrying capacity of
Grade 460 rebars the injection system for
of diameters up rebar fixing under the
to 40mm in effects of fire should be
reinforced assessed with an
concrete appropriate factor of safety
elements up to 4 compatible with the
hrs. FRP. structural design of the
parent structure.

Reference can also be


made to ref. BD-FP 055
under the .

BD-AF Macsim Wedge Macsim Fastenings Grade 316 stainless Drill-in anchors BS 5080: Part 1: N/A Hong Kong Testing M019206M02093 22 May 2006 20/10/2006 The application is to be
Anchor Pty Ltd. steel subject to axial 1993 Co., Ltd. considered individually
072 M019206M02597 27 June 2006
38S10100 Australia tension and shear. with regard to the fire
BS 5080: Part 2: resistance aspect.
M10 1986

BD-AF Ramset TRIGA SPIT Zinc plated grade 8.8 Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50179 3 March 2005 20/10/2006 The application is to be
Z Heavy Duty France steel subject to axial 1993 Limited considered individually
073 FDA50180 3 March 2005
Anchor tension and shear. with regard to the fire
V12-18/25 BS 5080: Part 2: resistance aspect.
1986
M12
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Ramset TRIGA SPIT Zinc plated grade 8.8 Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50313 23 April 2005 20/10/2006 The application is to be
Z Heavy Duty steel subject to axial 1993 Limited considered individually
074 France FDA50569 21 July 2005
Anchor tension and shear. with regard to the fire
V16-24/25 BS 5080: Part 2: resistance aspect.
1986
M16

BD-AF MKT Wedge Metall-Kunststoff- Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 012720ST21677 17 September 20/10/2006 The application is to be
Anchor B6 subject to axial 1993 Services Limited 2002 considered individually
075 Technik GmbH &
(setting depth tension and shear. with regard to the fire
/embedded Co. KG BS 5080: Part 2: resistance aspect.
1986 012720ST21677(
length: 50mm)
Weilerbach, 1) 17 September
Anchor Germany 2002
diameter: 6mm

BD-AF Hilti HDA-TR Hilti Corporation A4-80 stainless steel Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50476A 28 October 22/01/2007 The application is to be
self-undercut subject to axial 1993 Limited 2005 considered individually
076 Liechtenstein
anchor tension and shear. with regard to the fire
BS 5080: Part 2: 30 May 2005 resistance aspect.
M12x125/30 1986 FDA50397

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part 1: N/A ETS-Testconsult FDA61247 6 September 22/01/2007 The application is to be
500 injection for chemical adhesive anchor 1993 Limited 2006 considered individually
077 Kaufering, Germany
adhesive with fastening with grade subject to axial with regard to the fire
HAS ER M20 A4 stainless steel rod. tension and shear. BS 5080: Part 2: 6 September resistance aspect.
1986 FDA61253 2006
rods

BD-AF Hilti HIT-HY Hilti Corporation Hybrid resin system Injection BS 5080: Part 1: N/A ETS-Testconsult FDA61313 15 September 22/01/2007 The application is to be
150 injection for fixing grade 5.8 adhesive anchor 1993 Limited 2006 considered individually
078 Kaufering, Germany
adhesive with galvanized steel rod. subject to axial with regard to the fire
HAS-E M20 tension and shear. BS 5080: Part 2: 15 September resistance aspect.
1986 FDA61318 2006
rods.
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HSL-GR Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50435 8 June 2005 22/01/2007 The application is to be
Heavy Duty subject to axial 1993 Limited considered individually
079 Nuziders, Austria
Anchor tension and shear. with regard to the fire
BS 5080: Part 2: resistance aspect.
M16/25 1986 FDA50431 8 June 2005

BD-AF Hilti HSA-R Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50774 6 September 22/01/2007 The application is to be
stud anchor subject to axial 1993. Limited 2005 considered individually
080 Liechtenstein tension and shear with regard to the fire
M12 BS 5080: Part 2: 30 August resistance aspect.
1986 FDA50732 2005

BD-AF Hilti HSA-R Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A ETS-Testconsult FDA50780 6 September 22/01/2007 The application is to be
stud anchor subject to axial 1993. Limited 2005 considered individually
081 Liechtenstein tension and shear. with regard to the fire
M16 BS 5080: Part 2: 30 August resistance aspect.
1986 FDA50734 2005

BD-AF Hilti HST-R Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Part : N/A ETS-Testconsult FDA51018 9 November 22/01/2007 The application is to be
stud anchor subject to axial 1993 Limited 2005 considered individually
082 Liechtenstein tension and shear with regard to the fire
M16 BS 5080: Part 2: 14 November resistance aspect.
1986 FDA51078 2005

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part : N/A ETS-Testconsult FDA61246 6 September 22/01/2007 The application is to be
500 injection for chemical adhesive anchor 1993 Limited 2006 considered individually
083 Kaufering, Germany
adhesive with fastening with grade subject to axial with regard to the fire
HAS ER M16 A4 stainless steel rod. tension and shear. BS 5080: Part 2: 6 September resistance aspect.
1986 FDA61252 2006
rods
Reference List of Structural Fixing
BD-AF

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF MKT Wedge Metall-Kunststoff- Hot dip galvanized Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 053357ST51586 9 February 22/01/2007 The application is to be
Anchor B8 Technik GmbH & steel subject to axial 1993 Services Limited 2006 considered individually
084
(setting depth Co. KG tension and shear. with regard to the fire
/embedded BS 5080: Part 2: 9 February resistance aspect.
Weilerbach, 1986 053357ST51586 2006
length: 55mm)
Germany (1)
Anchor
diameter: 8mm

BD-AF MKT Wedge Metall-Kunststoff- Hot dip galvanized Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 053357ST51595 9 February 22/01/2007 The application is to be
Anchor B10 Technik GmbH & steel subject to axial 1993 Services Limited 2006 considered individually
085
(setting depth Co. KG tension and shear. with regard to the fire
/embedded BS 5080: Part 2: 9 February resistance aspect.
Weilerbach, 1986 053357ST51595 2006
length: 60mm)
Germany (1)
Anchor
diameter:
10mm

BD-AF MKT Wedge Metall-Kunststoff- Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 993114ST10286 26 March 2001 22/01/2007 The application is to be
Anchor subject to axial 1993 Services Limited considered individually
086 Technik GmbH & 11 August 2003
B10-20/90 tension and shear. with regard to the fire
Co. KG BS 5080: Part 2: resistance aspect.
1986 993114ST10286
Weilerbach,
(1)C
Germany
BD-AF MKT Wedge Metall-Kunststoff- Stainless steel A4 Drill-in anchors BS 5080: Part 1: N/A Fugro Technical 993114ST10286 11 August 2003 22/01/2007 The application is to be
Anchor subject to axial 1993 Services Limited (2)B considered individually
087 Technik GmbH & 11 August 2003
tension and shear. with regard to the fire
B12-15/110 Co. KG BS 5080: Part 2: 993114ST10286 resistance aspect.
1986 (3)B
Weilerbach,
Germany
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HSL-GR Hilti Corporation Stainless steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA50394A 24 May 2005 25/04/2007 The application is to be
Heavy Duty subject to axial 1993 Limited considered individually
088 Nuziders, Austria
Anchor tension and shear. with regard to the fire
BS 5080: Part 2: N/A FDA50425 26 May 2005 resistance aspect.
M10 1986

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA61247 29 August 25/04/2007 The application is to be
500 injection for chemical adhesive anchor 1993 Limited 2006 considered individually
089 Kaufering, Germany
adhesive with fastening with grade subject to axial with regard to the fire
HAS ER M20 A4 stainless steel rod. tension and shear. BS 5080: Part 2: N/A FDA61253 29 August resistance aspect.
rods 1986 2006

BD-AF Ramset ITW Red Head Epoxy injection Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA70419A 28 February 25/04/2007 The application is to be
EPCON G5 system for fastening adhesive anchor 1993 Limited 2007 considered individually
090 Illinois, USA
injection grout of M16 A4-80 subject to axial with regard to the fire
with M16 stainless steel anchor tension and shear. BS 5080: Part 2: N/A FDA70388A 28 February resistance aspect.
A4-80 stud 1986 2007
Stainless steel
Anchor Stud

BD-AF Ramset ITW Red Head Epoxy injection Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA70317B 13 February 18/10/2007 The application is to be
EPCON G5 system for fastening adhesive anchor 1993 Limited 2007 considered individually
091 Illinois, USA
injection grout of M30 Grade 8.8 subject to axial with regard to the fire
with M30 anchor stud tension and shear. BS 5080: Part 2: N/A FDA70316B 13 February resistance aspect.
Grade 8.8 1986 2007
Anchor Stud

BD-AF Ramset Trubolt Ramset Fasteners Grade 316 stainless Heavy duty BS 5080: Part 1: HOKLAS ETS-Testconsult FDA51140A 22 Nov 2005 18/10/2007 The application is to be
FDA60635 17 May 2006
T10090SS (Aust) Pty Limited Steel torque setting 1993 Limited considered individually
092
(M10 x90mm) expansion anchor with regard to the fire
& T12140SS Melbourne, Australia subject to axial BS 5080: Part 2: N/A resistance aspect.
1986 FDA60637 17 May 2006
(M12x140mm) tension and shear FDA60638 17May 2006

BD-AF Ramset ITW Red Head Epoxy injection Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA50334 16 April 2005 18/10/2007 The application is to be
EPCON G5 system for fastening adhesive rebar 1993 Limited considered individually
093 Illinois, USA 16 April 2005
injection grout of Y32 and Y40 rebar subject to axial with regard to the fire
with Y32 and tension only N/A FDA50335 resistance aspect.
Y40 rebar
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HSA-R Hilti Corporation Stainless Steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA50776 27 July 2005 18/10/2007 The application is to be
Stud Anchor subject to axial 1993 Limited considered individually
094 Schaan,
M8 tension and shear. with regard to the fire
Liechtenstain BS 5080: Part 2: N/A FDA50728 8 August resistance aspect
1986
2005

BD-AF Hilti HSC-IR Hilti Corporation Stainless Steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA51054 27 October 18/10/2007 The application is to be
2005
Safety Anchor Internal Thread subject to axial 1993 Limited considered individually
095 Guangdong, China
M10 tension and shear. 8 November with regard to the fire
BS 5080: Part 2: N/A FDA51035 resistance aspect
1986 2005

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection system BS 5080: Part 1: N/A Fugro Technical 020323ST20493 12 June 2002 21/1/2008 The corresponding fire
500 for making 1993. Services Limited assessment report no. WF
096 Kaufering, Germany 020323ST20500
nominal 166402 is valid until 1
anchorage November 2012
020323ST20501
connections of
Grade 460 rebars Load carrying capacity of
020323ST20510
of diameters up the injection system for
to 40mm in 020323ST20538 rebar fixing under the
reinforced effects of fire should be
concrete 020323ST20593 assessed with an
elements up to 2 appropriate factor of safety
hrs. FRP. 020323ST20607 compatible with the
structural design of the
parent structure.

Reference can also be


made to ref. BD-FP 077
under the .

BD-AF Hilti HSL-G-R Hilti Corporation Stainless Steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA50466A 28 October 21/1/2008 The application is to be
Heavy Duty subject to axial 1993 Limited 2005 considered individually
097 Nuziders, Austria
Anchor tension and shear. with regard to the fire
M20/30 BS 5080: Part 2: N/A FDA50433 8 June 2005 resistance aspect
1986
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Fischer Anchor Fischerwerke Artur Stainless Steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS Castco Testing I001503M00355 7 March 2003 31/1/2008 The application is to be
FBN-Bolt (A4) Fischer GmbH & Co subject to axial 1993 with Centre Ltd. BD/MISCEL 4 March 2006 considered individually
098
M8/48, KG tension and shear. modification for 260301-1 with regard to the fire
M10/50, M8, M10 resistance aspect
M12/70 Waldachtal, Germany I001503M00355 7 March 2003
& M16/84 In-house method BD/MISCEL 3 November
based on BS HOKLAS 251027-8 2005
5080: Part 1:
1986 for M12, BD/MISCEL
M16 270228-2 10 May 2007
BD/MISCEL 7 June 2007
BS 5080: Part 2: N/A 270228-6
1986 for M12
BD/MISCEL 2 October 2004
In-house method N/A 240930-2
BD/MISCEL 15 June 2005
based on BS
5080: Part 2: 250512-12
1986 for M8,
M10, M16

BD-AF Fischer Anchor Fischerwerke Artur Stainless Steel A4 Drill-in anchors In-house method HOKLAS Castco Testing BD/MISCEL 10 May 2007 31/1/2008 The application is to be
FAZ-Anchor Fischer GmbH & Co subject to axial based on BS Centre Ltd. 270228-1 considered individually
099
Bolt (A4) M8 KG tension and shear. 5080: Part 1: with regard to the fire
1993 BD/MISCEL resistance aspect
Waldachtal, Germany 270228-4 7 June 2007
N/A
BS 5080: Part 2:
1986

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA61082 10 August 25/04/2008 The application is to be
500 injection for chemical adhesive anchor 1993 Limited 2006 considered individually
100 Kaufering, Germany
adhesive with fastening with grade subject to axial with regard to the fire
HAS-ER M24 A4 stainless steel rod. tension and shear. BS 5080: Part 2: N/A FDA61314 30 September resistance aspect.
rods 1986 2006
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Upat EXA Fischerwerke Artur Zinc-plated steel, or Drill-in anchors BS 5080: Parts 1 N/A University of Hong AN5 July 1991 22/7/2008 It should be read in
Express Fischer GmbH & Co hot-dipped subject to axial &2 Kong, Department AN6 conjunction with BD-AF
101
Anchor KG galvanized steel. tension and shear. of Civil and 026
Structural AN20
M8 Waldachtal, November Note on change of
Engineering AN22
Germany 1991 manufacturer.

(See remarks)

BD-AF Hilti HKD-SR Hilti Corporation Stainless Steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA50718A 9 September 22/7//2008 Overall FOS shall not be
Push-in Anchor subject to axial 1993 Limited 2005 less than 3.0.
102 Nuziders, Austria
M10 A4 tension and shear. Manufactured shall be
BS 5080: Part 2: 20 September consulted in this aspect for
1986 N/A FDA50790A 2005 design.

The application is to be
considered individually
with regard to the fire
resistance aspect

BD-AF Fischer Anchor Fischerwerke Artur Hot-dipped Drill-in anchors BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 27 September 22/7/2008 Recommended load for
FBN M10/15 Fischer GmbH & Co galvanized steel subject to axial 1993 Centre Ltd. 240925-1 2004 design shall be determined
103
fvz KG tension and shear. from dividing the
BS 5080: Part 2: BD/MISCEL 28 September characteristic load by a
Waldachtal, Germany 1986 N/A 240923-9 2004 FOS 3.0.

The application is to be
considered individually
with regard to the fire
resistance aspect
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 10 May Recommended load for
BD-AF Fischer Anchor Fischerwerke Artur Stainless Steel A4 Drill-in anchors 22/7/2008
1993 Centre Ltd. 270412-4 2007 design shall be determined
FAZ-Bolt (A4) Fischer GmbH & Co subject to axial
104 BS 5080: Part 2: N/A BD/MISCEL 7 June from dividing the
M10, M12, KG tension and shear.
1986 270228-3 2007 characteristic load by a
M16, M20 &
Waldachtal, Germany FOS 3.0.
M24
BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 16 December
1993 Centre Ltd. 251208-5 2005 The application is to be
BS 5080: Part 2: N/A BD/MISCEL 7 June considered individually
1986 270228-7 2007 with regard to the fire
resistance aspect
BS 5080: Part 1: HOKLAS Hong Kong SF – 0052R7283 5 February
1993 Curtain Wall 2005
BS 5080: Part 2: N/A Testing Centre Ltd SF – T0088R7283 5 February
1986 2005

BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 10 May


1993 Centre Ltd. 270412-5 2007
BS 5080: Part 2: N/A BD/MISCEL 4 June
1986 270412-7 2007

BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 10 May


1993 Centre Ltd. 270412-6 2007
BS 5080: Part 2: N/A BD/MISCEL 4 June
1986 270412-8 2007
BD-AF Ramset Trubolt Ramset Fasteners Grade 316 stainless Heavy duty BS 5080: Part 1: HOKLAS ETS-Testconsult FDA60636 24 May 2006 22/7/2008 The application is to be
T16175SS (Aust) Pty Limited Steel torque setting 1993 Limited considered individually
105
(M16 expansion anchor with regard to the fire
x125mm) Melbourne, Australia subject to axial BS 5080: Part 2: resistance aspect.
1986 N/A FDA60639 24 May 2006
tension and shear

BD-AF Ramset ITW Red Head Epoxy injection Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA50330 (for 23 April 2005 22/7/2008 The application is to be
EPCON G5 system for fastening adhesive anchor 1993 Limited Y12) considered individually
106 Illinois, USA
injection grout of Y12 & Y16 high subject to axial with regard to the fire
with Y12 & yield dowel bar tension only FDA 50331(for resistance aspect.
Y16) 23 April 2005
Y16 high yield
dowel
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Fischer Anchor Fischerwerke Artur Hot-dipped Drill-in anchors BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 21 September 22/10/2008 Recommended load for
FBN M12/15 Fischer GmbH & Co galvanized steel subject to axial 1993 Centre Ltd. 240917-6 2004 design shall be determined
107
fvz KG tension and shear. from dividing the
BS 5080: Part 2: BD/MISCEL 28 September characteristic load by a
Waldachtal, Germany 1986 N/A 240923-10 2004 FOS 3.0.

The application is to be
considered individually
with regard to the fire
resistance aspect

BD-AF Hilti HIT-HY Hilti Corporation Hybrid resin system Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA61360 22 September 22/10/2008 The application is to be
150 injection for fixing grade 5.8 adhesive anchor 1993 Limited 2006 considered individually
108 Kaufering, Germany
adhesive with galvanized steel rod. subject to axial with regard to the fire
HAS-E M16 tension and shear. BS 5080: Part 2: 22 September resistance aspect.
1986 N/A FDA61367 2006
rods.

BD-AF Hilti HCS M8 Hilti Corporation A2 – 304 stainless Cast-in socket BS 5080: Part 1: HOKLAS ETS-Testconsult FDA60243 7 March 2006 22/10/2008 The application is to be
x 40 Cast-in steel used as structural 1993 Limited considered individually
109 Kaufering, Germany
Socket fixing for M8 with regard to the fire
bolt/ threaded rod BS 5080: Part 2: resistance aspect.
1986 N/A FDA60239 7 March 2006
for fastening of
cladding. Tests for quality control
and workmanship may be
required during
construction.

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part 1: HOKLAS Qualitech Testing 20080730-BD-PL- 1 August 2008 23/1/2009 The application is to be
500 injection for chemical adhesive anchor 1993 & Consultancy 02 considered individually
110 Kaufering, Germany
adhesive with fastening with grade fixed on Limited. with regard to the fire
HAS-ER M8 A4 stainless steel rod. brickwork BS 5080: Part 2: 20080730-BD-S-0 resistance aspect.
1986 N/A 4 1 August 2008
and M10 rods subject to axial
tension and shear.

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA61084 10 August 23/1/2009 The application is to be
500 injection for chemical adhesive anchor 1993 Limited 2006 considered individually
111 Kaufering, Germany
adhesive with fastening with grade subject to axial with regard to the fire
HAS-ER M33 A4 stainless steel rod. tension and shear. BS 5080: Part 2: 24 August resistance aspect.
1986 N/A FDA61168 2006
rods
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Ramset Ramset Fasteners Grade304 stainless Cast-in insert BS 5080: Part 1: HOKLAS ETS-Testconsult FDA81285 20 October 23/1/2009 The application is to be
Concrete Insert (Aust) Pty Limited Steel used as structural 1993 Limited 2008 considered individually
112
CIM10SS fixing for M10 with regard to the fire
Melbourne, Australia bolt/ threaded rod BS 5080: Part 2: 20 October resistance aspect.
1986 N/A FDA81277 2008
for fastening
Tests for quality control
and workmanship may be
required during
construction.

BD-AF Nelton Tanchor Shanghai Sishun Galvanized mild steel Cast-in channel BS 5080: Part 1: HOKLAS Fugro Technical 082615ST 9 December 23/1/2009 The application is to be
Channel – Industry & Trade Co. with inserted 1993 Service Ltd. 80814 2008 considered individually
113 Channel: Grade
HBC-52/26(30 Ltd. T-bolt subject to with regard to the fire
03) with T-bolt Q235B axial tension and BS 5080: Part 2: 082615ST 9 December resistance aspect.
Shanghai, China N/A
HB-M16 shear 1986 80814(1) 2008
Anchor stud : Grade Tests for quality control
Q195 and workmanship may be
required during
T-bolt : Grade 8.8
construction.

BD-AF Ramset ITW Red Head Acrylic chemical Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA81100 (for M8 4 September 23/1/2009 The application is to be
EPCON A7 injection for A4 adhesive anchor 1993 Limited in tension) 2008 considered individually
114 Illinois, USA
Injection stainless steel anchor stud subject to with regard to the fire
Adhesive with bolt axial tension and BS 5080: Part 2: FDA 81101(for 4 September resistance aspect.
1986 N/A M16 in tension) 2008
shear
M8 A4-80 Stud
and M16 FDA81280 (for 20 October
A4-80 Stud M8 in shear 2008

FDA 81283(for 20 October


M16 in shear) 2008
Reference List of Structural Fixing

Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Ramset TRIGA SPIT A4 Stainless Steel Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA81424 (for 25 November 23/1/2009 The application is to be
Z-A4 Heavy subject to axial 1993 Limited M8 in tension) 2008 considered individually
115 France
Duty Anchor tension and shear. with regard to the fire
M8, M10, M12 BS 5080: Part 2: FDA61177 (for 24 August resistance aspect.
1986 N/A M10 in tension) 2006
& M16

V8-12/25 FDA61178 (for 24 August


V10-15/25 M12 in tension) 2006
V12-18/25
FDA61179 (for 24 August
E16-24/25
M16 in tension) 2006

FDA81425 (for 25 November


M8 in shear) 2008

FDA61180 (for 24 August


M10 in shear) 2006

FDA61181 (for 24 August


M12 in shear) 2006

FDA61182 (for 24 August


M16 in shear) 2006

BD-AF Fischer Anchor Fischerwerke Artur Hot-dipped Drill-in anchors BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 21 September 30/4/2009 Recommended load for
FBN M8/10 Fischer GmbH & Co galvanized steel subject to axial 1993 Centre Ltd. 240917-4 2004 design shall be determined
116
fvz KG tension and shear. from dividing the
BS 5080: Part 2: BD/MISCEL 21 February characteristic load by a
Waldachtal, Germany 1986 N/A 250219-1 2005 FOS 3.0.

The application is to be
considered individually
with regard to the fire
resistance aspect
Reference List of Structural Fixing
Ref. Product Name of Material Application Compliance Details of Test or Assessment Report Date of Remarks /
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
Laboratory Laboratory / Assessment
(City and
Accreditation Assessing Report
Country)
Body Organization
BD-AF Hilti HVU Hilti Corporation Urethane Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA61170A 30 August 30/4/2009 The application is to be
adhesive methacrylate resin for adhesive anchor 1993 Limited 2006 considered individually
117 Kaufering, Germany
capsule with chemical fastening subject to axial with regard to the fire
HAS-ER- M24 with grade A4 tension and shear. BS 5080: Part 2: 22 September resistance aspect.
1986 N/A FDA61366 2006
anchor rod stainless steel anchor
rod

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA61245 6 September 12/8/2009 The application is to be
500 injection for chemical adhesive anchor 1993 Limited 2006 considered individually
118 Kaufering, Germany
adhesive with fastening with grade subject to axial with regard to the fire
HAS-ER M12 A4 stainless steel rod. tension and shear. BS 5080: Part 2: 6 September resistance aspect.
1986 N/A FDA61251 2006
rods

BD-AF Fischer Anchor Fischerwerke Artur Hot-dipped Drill-in anchors BS 5080: Part 1: HOKLAS Castco Testing BD/MISCEL 17 January 12/8/2009 Recommended load for
FBN M16/25 Fischer GmbH & Co galvanized steel subject to axial 1993 Centre Ltd. 250112-52 2005 design shall be determined
119
fvz KG tension and shear. from dividing the
BS 5080: Part 2: BD/MISCEL 17 January characteristic load by a
Waldachtal, Germany 1986 N/A 250115-1 2005 FOS 3.0.

The application is to be
considered individually
with regard to the fire
resistance aspect

BD-AF Hilti HSC-IR Hilti Corporation Stainless Steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA51056 14 November 4/11/2009 The application is to be
2005
Safety Anchor Internal Thread subject to axial 1993 Limited considered individually
120 Guangdong, China
M12 tension and shear. 14 November with regard to the fire
BS 5080: Part 2: N/A FDA51037 resistance aspect
1986 2005

BD-AF Hilti HSC-IR Hilti Corporation Stainless Steel A4 Drill-in anchors BS 5080: Part 1: HOKLAS ETS-Testconsult FDA51053 14 November 22/2/2010 The application is to be
2005
Safety Anchor Internal Thread subject to axial 1993 Limited considered individually
121 Guangdong, China
M8 tension and shear. 14 November with regard to the fire
BS 5080: Part 2: N/A FDA51034 resistance aspect
1986 2005

BD-AF Hilti HIT-RE Hilti Corporation Epoxy resin system Injection BS 5080: Part 1: HOKLAS ETS-Testconsult FDA61172 24 August 3/5/2010 The application is to be
500 injection for chemical adhesive anchor 1993 Limited 2006 considered individually
122 Kaufering, Germany FDA61174
adhesive with fastening with grade subject to axial with regard to the fire
HAS-ER A4 A4 stainless steel rod. tension and shear. BS 5080: Part 2: resistance aspect.
1986 N/A FDA61171
M30 and M39
stainless steel FDA61169
anchor rod
Reference List of Structural Fixing
Ref. Product Name of Material Application Compliance Date of Remarks /
Details of Test or Assessment Report
No. Category Posting on Comments
Name Manufacturer Testing CDB
and Place of Standard
Name of Name of Report No. Date of Test /
Manufacture
(City and Laboratory Laboratory / Assessment

Country) Accreditation Assessing Report


Body Organization
BD-AF Sampag TSA Sampag Anchoring Galvanized Cast-in channel BS 5080: Part 1: HOKLAS Castco Testing BD 0091007-12 to 14 July 2009 25/8/2010 The application is to be
Anchor Systems Ltd. hot-rolled carbon with inserted 1993 Centre Ltd 16 considered individually
123 14 October
Channel 41/25 Hong Kong, China steel T-bolt subject to with regard to the fire
with 2Nos axial tension and BS 5080: Part 2: BD 0090710-1 to 5 2009 resistance aspect.
Channel: Grade 1986 N/A
Grade 4.6 ZP shear
S235JRG2 to BD0090710-16 to Tests for quality control
M16 T-bolt &
EN10025 20 and workmanship may be
Anchor
Channel 51/31 required during
Anchor stud : Grade BD 0091007-17 to
with 2Nos construction.
S235JRG2 to 21
Grade 4.6 ZP
EN10025
M20 T-bolt BD 0090710-6 to
T-bolt : Grade 4.6 to 10
EN ISO 898-1 Zinc
BD 0090710-11 to
Plated
15