K T- 1 0 0 ™ D o o r C o n t r o l l e r
In s t a l l a t i o n M a n u a l
Products names are trademarks or registered
trademarks of their owners.
DN5073-0307
Ta b le o f c o n te n t s
Section 3: Appendix 9
Typical KT-100 Wiring Diagram ............................... 9
KT-100 Compliance Notices ................................... 10
Troubleshooting Communication Problems ........ 10
KT-100 Controller Maintenance ............................. 11
Bi-annual test for battery ............................................11
Annual test for emergency lithium battery .................11
Mounting the KT-PC4204 ....................................... 11
Using the KT-100 with an external alarm panel ... 12
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
S e c ti o n 1 : K T-1 0 0 F e a t u re s
The KT-100 Door Controller contains all the intelligence and Downloadable firmware. The firmware program is
necessary inputs/outputs to manage one door; it is also easily stored in the controller’s flash memory; it can be easily updated
linked to a network controlling up to 32 doors. from the system’s workstation without changing the memory
The KT-100 Door Controller features include: chips.
Speed selection. The KT-100 automatically detects the loop Integration with a client alarm system. The KT-100
communication speed as set at the system workstation. Controller allows the ability to arm/disarm any client alarm
system. In addition, interfacing with an external alarm system
Trouble reporting. The KT-100 constantly supervises
allows the installer to assign the appropriate user permission to
power supply conditions and reports “Low power” status to the
arm or disarm the external alarm system. Optionally, adding a
system if power drops below 10.5VDC. The power output is
keypad will increase the security as cardholders will be required
protected against short-circuits and surges by a self-resetting
to enter a valid code in addition to presenting a valid card at the
PTC. The locking device is supervised for short to ground or
door reader. For details about using the KT-100 Controller to
open circuits. It also monitors all the equipment for any failure
interface another alarm panel, refer to “Using the KT-100 with
or tampering. Any abnormal condition is reported to the
an external alarm panel” on page 12.
software.
Te ch n i c a l Sp e c i fi c a t i o n s
Dimensions (H•W•D) 11.4 cm x 7.0 cm x 3 cm (4.5”; 2.75”; 1.25”), mounted in a standard single gang electrical box
without any additional enclosure
Operating temperatures / Humidity range From 20 C to 400 C (350 F to1100 F) / 0-95% (non-condensing)
Reader types Wiegand, proximity, bar code, magnetic, integrated keypad and others
Control relay outputs 2 relay outputs, 12VDC, 25mA max/each. Open collector to ground (use form C relays such as
Kantech/KT-RM1 if needed)
2 control relay outputs, 30VAC/DC, 50mA (max) each. Two Opto-isolated contacts per relay
Monitored input zones 4 monitored input zones, NO/NC, with or without end of line resistors
Auxiliary outputs (LED, BUZ) 2 outputs, open NPN collector for door access and status 25mA max, 12 DC each
Reader communication interface ANSI, SIA, ABA clock and data, Wiegand 5 conductor
Flash memory 64 K
Backup battery Lithium battery, up to 10 years retention (data and RTC operation)
Certifications / Listing FCC Part 15, Class B; CE approved (EN 55022, EN 50130-4)
3
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
4
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
S e c ti o n 2 : Mo u n t in g a n d Wi r in g t h e K T-1 0 0
D o o r C o n tr o ll e r
Step 1•Unpacking the KT-100 For details on installing the KT-PC4204, refer to “Mounting the
KT-PC4204” on page 11.
The KT-100 Controller has been designed to be mounted on a
wall in a single gang electrical box without any additional NOTE: If you are installing another type of power supply, please
enclosure. refer to the manufacturer’s instructions.
Before installing the KT-100 Door Controller: Step 4•Installing the KT-100 Unit
1. Unpack the KT-100 Controller package. The following
items are required to install the KT-100:
The following diagram illustrates a typical door
layout:
• KT-100 Controller with accessory kit (included),
• PC4204 DC Power Supply with battery backup (suggested,
not included),
• AC transformer; Input: 120 or 230 VAC, 50-60 Hz:
Output: 16 VAC, 40VA, class 2 (not included)
• One 12-volt lead-acid battery 7A/h (not included)
• Ground clamp (not included).
2. Verify the content for any missing item/part or damaged
component. Any missing or damaged item should be
reported immediately.
5
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
entry and to prevent “door open too long” or “door left open” To connect the door locking device:
alarms. 1. Connect the negative wire from the door strike to the NO
Door contact. When the door is locked, the access output and optionally, the door magnetic lock to the NC
output.
controller supervises the door contact and will report a “door
forced open” alarm if the door is opened without the use of a 2. Connect the positive wire to the +12 VDC output.
card. When the door is unlocked, the condition of the door PWR OUT
LOCK
contact is still supervised but no alarms are generated. 12VDC
6
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
KT-100
ENTRY READER EXIT READER
OUTPUTS
BUZ
Additional Zone Inputs BLUE BLUE
LED
Door Contact (Z3 & Z4) BROWN BROWN
GRN
EXIT
CARD READERS
WHT
GREEN GREEN
WHITE WHITE
GRN
ENTRY
NC or NO Dry contact RED RED
WHT
Controller defined withou
PWR
BLACK BLACK
End of Line Resistor
+5V
PWR OUT
500mA Max
+ -
12VDC
IOProx IOProx
NOTE:
AUX
Z4
• The 12 VDC auxiliary power can also be used to power low
AUX
Z3
INPUTS
current audible devices usually located at the controlled
COM
door. Auxiliary outputs can be connected to readers & local
DOOR REX
Z2
Z1
warning devices to be used for visual and audible signals.
T.REX
-
+
POWER
12VDC
+
TAMPER
Optional The KT-100 provides two opto-isolated contacts (R1 & R2) and
5,6K End of Line Resistor
two control outputs (R3 & R4). R1 & R2 can be used as either
as dry contacts.
• R1 & R2: maximum voltage = 30 volts AC/DC; maximum
current = 100 mA total; (R1 & R2).
2. Connect resistors (included with KT-100) for all inputs • R3 & R4: maximum voltage = 12 volts DC; maximum cur-
5.6K ohm (if selected). rent (each relay) 25 mA
NOTE: Use a KT-RM1 (optional) to switch larger currents or volt-
NOTE: Inputs can be defined with none or one end-of-line resis-
ages or to supply a dry contact.
tor according to parameters defined in your EntraPass Special
Edition software.
Relays Outputs
procedure for proper power connection. Up to 2 Internal
Equivalent
readers can be connected to a KT-100. They can be Circuits
+ -
750mA Max
+
500mA Max
- -
NO
-
NC +5V WHT GRN WHT GRN LED BUZ
7
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
The normally closed tamper switch is connected to an input. It To link KT-100 Door Controllers:
is recommended to choose an unused input (3 or 4) as tamper 1. Connect the RS-485 cable to X1+, X1- and GND.
input.
• If you are not using the USB-485 or VC-485: connect a 120
1. Install the KT-100TAMP tamper switch in the MUSB ohm end-of-line resistor at the interface of the first and last
box as illustrated below. KT-100 (X- & X+).
KT-100
RELAYS INPUTS
R1 R2 R3 R4 Z1 Z2 Z3 Z4
DOOR REX COM AUX AUX
TAMPER
NOTE: After you have completed all the necessary steps, you
SWITCH
may power the KT-100 by connecting the AC power and the bat-
TAMPER
ARM
MUSB
BOTTOM
tery.
MUSB
COVER
8
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
S e c ti o n 3 : A p p e n d ix
Typical KT-100 Wiring Diagram
NC Dry contact
Controller defined without
T.REX
End of Line resistor
NO Dry contact
+
POWER
C1
Entry Reader
NC1 NO1
BUZZER
-
OUTPUTS
BUZ
AUX
Z4
+
Door Contact
AUX
LED
Z3
INPUTS
BLUE
COM
GRN
EXIT
Optional Exit Reader BROWN
CARD READERS
WHT
DOOR REX
Z2
GREEN
GRN
Z1
ENTRY
WHITE
WHT
a nd (2) Th is d evice must accept any interf erence
receive d, including int erfe ren ce that may cause
R4
ACCESS CONTROLLER
RED
PWR
+5V
R3
BLACK
RELAYS
NC
-
LOCK
R2
un desired operation.
IOProx Card
NO
KT-100
-
Reader
PWR OUT
500mA Max
+ -
12VDC
R1
750mA Max
X-
PWR IN
RS-485
+ -
12VDC
12 Volts DC
X+
Open-Collector
Opto-Isolated Contact
25 mA Max.
120 Volts AC/DC
100 mA Max. Load Negative
Positive
Electrical Mag-Lock
RS485 Network 12 Volts DC 250 mA MAX.
to others KT-100s (IF NOT USED, CONNECT A 1000 OHMS
or RESISTOR BETWEEN NC AND +12V)
+12VDC to PC Workstation
via USB/485 interface
120/230 VOLTS
16V 40VA
60/50 HERTZ
CLASS 2
(WIRE-IN)
4 Relays Module PC4204
NUT
WASHER
CASE
SCREW
Sealed Acid-Lead
12 Volts Battery EARTH
7 A/H GROUND
KANTECH # KT-BD7-12
9
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
Jumper
RELAYS INPUTS
R1 R2 R3 R4 Z1 Z2 Z3 Z4
DOOR REX COM AUX AUX
10
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
Jumper
WASHER
CASE
SCREW
Input: 120 or 230 VAC
Output: 16VAC/40VA
CLASS 2 (WIRE-IN)
To the KT100 controllers
(1.5 amps max.)
SEALED ACID-LEAD
12 V BATTERY
7A/H MAXIMUM
KANTECH # KT-BD7-12
EARTH GROUND
11
K T - 1 0 0 I n s t a l l a t i o n M a n u a l
Using the KT-100 with an external alarm • The KT-100 output (Relay 3, in the example) is used as
an arm/disarm request of the third party alarm system. This
panel output is pulsed once to arm or disarm the alarm system
according to the current arming state.
To interface the KT-100 to an external alarm • The KT-100 output (Relay 4, in the example) is con-
panel: nected to a local bell or to warn the alarm panel of an
1. Connect the KT-100 two inputs (zone 3 and 4) to the abnormal condition from the door.
external alarm status relay (PGM1 and PGM2) • Optionally, one KT-100 input zone can be defined as an
2. Connect the KT-100 two outputs (Relay 3 and 4) to the arming/disarming request input for the external alarm
external alarm system arming status inputs (input 3 and panel. In this case, the arming/disarming request will
input 4). These will be used to arm/disarm the external depend on the door or external alarm. For example, an arm-
alarm system as illustrated below. ing/disarming request may be triggered by an access
request, a code entered on the keypad and/or a schedule,
• The KT-100 Input (Input 3, in the example) is used to
depending on the door status (open or closed) and the alarm
indicate the arming state of the client party alarm system.
system status (armed or disarmed).
An abnormal status indicates to the KT-100 that the exter-
nal alarm system is armed. NOTE: For details about interfacing the KT-100 Door Controller
• The KT-100 input (Input 4, in the example) is used to with an external alarm system, please contact Customer Sup-
indicate the alarm state of the external alarm. An abnormal port.
status tells the KT-100 that the external alarm system is in
alarm.
1 2 3
4 5 6
7 8 9
#
* 0
12
Kantech Systems
Tel: +1(978) 731-6252 • Toll Free: North America: 1 888 222-1560 • Fax: +1(978) 731-7759
Web Site: www.kantech.com
E-mail: techlink@tycoint.com