INSTRUCTIONS
Universal Air Shield/
Flange Mount Assembly
Q1115

DESCRIPTION
The Q1115 Universal Air Shield/Flange Mount Assembly
is a dual purpose device. As an air shield, it provides a
constant flow of clean air across the outside surface of
the detector window, thereby reducing contamination
buildup and extending maintenance intervals.

The flange mount on the Q1115 allows the detector to


be mounted directly to a duct or wall. It is compatible
with standard Det-Tronics UV or IR detectors and is rec-
ommended for use in applications where high levels of
airborne contaminants are present in the environment.

The assembly is available in aluminum or stainless steel


and attaches directly to the detector housing without the
use of tools. It is also easily removed when performing
detector maintenance. See Figure 1 for dimensions.
Connection to the compressed air supply is provided
The use of the Q1115 does not interfere with:
using a quick connect coupling. The recommended
– detector mounting
tubing is 1/4 inch O.D. parflex nylon with a minimum
– detector cone of vision
wall thickness of 0.035 inch. The air pressure should be
– manual or automatic oi testing of the detector.
between 5 and 15 psi.
The Q1115 is rated for 0°F to +150°F (-18°C to +66°C).
However, if the air inlet fitting (designed for plastic tub-
ing) is replaced with a standard elbow fitting (designed 3.5 2.4
(8.9) (6.1)
for metallic piping), the temperature range can be
expanded to -40°F to +257°F (-40°C to +125°C).

AIR SUPPLY
4.7
(11.9)
NOTE
Instrument grade air is required. Filtration should
be used to ensure that the air is dry and oil free.
The presence of oil in the air supply must be avoid-
ed, since it can accumulate on the detector viewing
window and reduce the sensitivity of the detector. A2043

In addition, oil can clog the sintered metal ring and


reduce the effectiveness of the air shield. Figure 1—Dimensions of Q1115 in Inches (Centimeters)

©Detector Electronics Corporation 2001 3/01 95-8467


INSTALLATION PROCEDURE 11. Apply power to the detection system and turn on the
air supply.

Air Shield without Duct Mount Duct Mount Installation

1. Remove power from the detection system. NOTE


The use of flexible conduit is required to allow easy
2. Remove the lens cap assembly (detector housing removal of the detector for maintenance purposes.
with lens cap attached) from the detector base (turn
counterclockwise). See Figure 2. 1. Mount the retainer ring and spacer ring (IR detec-
tors only) on the detector housing following steps 1
3. Remove the clamp ring from the air shield assembly. to 6 in the “Air Shield without Duct Mount” section
above.
4. For an IR detector, place the spacer ring on the
detector housing. For a UV detector, the spacer 2. Using Figure 3 as a template, cut out the mounting
ring is not used and should be discarded. holes in the duct or wall.

5. Place the retainer ring on the detector housing. Be 3. Mount the air shield to the duct or wall. A rubber or
sure that the side with the groove faces the lens neoprene gasket (not provided) can be placed
cap. (The spacer ring, if used, fits inside the between the air shield and mounting surface if
groove.) needed.

6. Re-install the lens cap assembly on the detector 4. Clean the detector viewing window and o i ring
base. using the procedure described in the “Maintenance”
section.
7. Clean the detector viewing window and o i ring
using the procedure described in the “Maintenance” 5. Insert the detector lens cap into the air shield.
section.
6. Place the clamp ring over the air shield and lock the
8. Place the air shield on the detector lens cap. assembly securely in place.

9. Place the clamp ring over the air shield and lock the 7. Attach the air supply to the air shield.
assembly securely in place.
8. Apply power to the detection system and turn on the
10. Attach the air supply to the air shield. air supply.

LENS CAP

CLAMP RING

AIR SHIELD
RETAINER RING

AIR DIFFUSER RING

DETECTOR HOUSING

SPACER RING
(IR DETECTORS ONLY)
Oi RING
NOTES: 1. IR DETECTOR SHOWN.
2. SPACER RING NOT USED
WITH UV DETECTOR. AIR INLET
A2022

Figure 2—Exploded View of Air Shield and Detector

2
MAINTENANCE 4. Thoroughly clean the detector viewing window with
a clean cloth and Det-Tronics window cleaner.

Air Shield NOTE


If paint overspray or similar contaminants are pre-
No routine maintenance is required. However, as con- sent in the environment, the use of solvents may
taminants accumulate on the sintered metal diffuser ring be required to clean the detector viewing window.
over time, the effectiveness of the air shield will be After cleaning the viewing window with a solvent,
reduced. To replace the ring, remove the gasket and always use Det-Tronics window cleaner and a
unscrew the retainer from the inside of the air shield. clean cloth to remove any solvent or other residue.
Replace the diffuser ring and reassemble the air shield.
5. Clean the oi ring. If the inner reflective surface can-
not be restored, the ring must be replaced. It is
Detector Window and oi Ring essential for the ring to be highly reflective to ensure
proper operation of the oi system.
If the detector indicates an oi fault, the detector window
and oi ring must be cleaned. The following procedure 6. Re-install the oi ring. Be sure that the opening in
is recommended for cleaning the detector viewing win- the oi ring:
dow and oi ring: — is not aligned with the test lamp(s) on the sensor
module
1. Secure output loads (or place the controller in the — is positioned downward to prevent buildup of
TEST or BYPASS mode). dirt or moisture.

2. Remove the air shield assembly from the detector. 7. Re-install the air shield.

3. Remove the oi ring from the detector. 8. Return the system to normal operation.

3.5 INCH DIA.

3.2 INCH BOLT CIRCLE

1.7 INCH DiA.

0.2 INCH DIA. (3)

Figure 3—Template for Duct Mount Installation

3 95-8467
RECOMMENDED SPARE PARTS

Part Number Description


004289-001 Sintered metal air diffuser ring
002519-001 oi ring for UV detector
003525-001 oi ring for IR detector
001680-001 Window cleaner

ORDERING INFORMATION
One air shield assembly is needed for each UV or IR
detector.

For assistance in ordering a system to meet the needs


of a specific application, please contact:

Detector Electronics Corporation


6901 West 110th Street
Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491
Fax: (952) 829-8750
Web site: www.detronics.com