Академический Документы
Профессиональный Документы
Культура Документы
VAV BOX
REHEAT
SELECTION
KRUEGER
EXCELLENCE IN AIR DISTRIBUTION
Page # 1
VAV Box Reheat Guidelines Revised 05/01/02
VAV terminals provide a measured quantity of The need to rapidly warm a space following a
conditioned air to a space, in response to a night setback has another set of requirements.
control signal from a thermostat or room sensor. Air needs to be heated as rapidly as possible,
This air may be tempered with a reheat coil, with a maximum of mixing, without too much
plenum air, or both. The means and selection of regard for occupant comfort. This requires both a
parameters for this reheat leads to much of the high delta-t and a high airflow. Note: The hotter
complexity and questions in selecting and the air temperature, the longer it will take to heat
specifying VAV terminals. Selection of the reheat the room, for a given heat delivery rate!
design parameters requires both an
understanding of the limitations of the reheat coil This is due to stratification of hot air at the
(hot water or electric) and the means of air ceiling. The maximum design discharge
distribution, if problems in the installation are to temperature is probably 120F. This is the limit for
be avoided. electric heater units, set by the National Electric
Code. In addition, insulation adhesives are
Overview: typically designed around this expected air
Reheat is provided to terminal VAV units temperature. If fan powered units have a plenum
primarily to allow for individual room controlled inlet located water coil, caution must be used to
heat to perimeter zones. With fan terminals, this not overheat the downstream fan motor, limiting
concept uses heated plenum air, supplied coil discharge temperatures to less than 110F.
through ceiling diffusers, to offset skin load The engineer therefore needs to ensure that both
heating demands. Single duct terminals, occupied heating and morning warm-up
however, reheat cooled primary air to offset situations are covered in his design with proper
perimeter heating requirements, which may be stages of electric heat or proportional water coil
wasteful of energy, especially when the same air valves.
handler is using chilled air for interior zones
which require year round cooling. Fan terminals The reheating of cold primary air seems, on the
require some energy to run the fans, however, so surface, to be a wasteful practice in terms of
the use of fan powered units is not without some optimum utilization of energy resources. There
penalties. In mild climates, the trade-off between are many situations, however, where it is not
equipment first costs and operating costs may only necessary, but also beneficial to do so, and
lead to the selection of single duct reheat units can save considerable energy. These include:
as the most economical solution.
1.) Providing comfort with a great diversity
The ASHRAE Fundamentals Handbook of loads: When both heating and cooling is
(Chapter 31) states that discharging air at a required from a single air handler, due to
temperature more than 15F above the room (90F climate and building design factors, reheat is
in a 75F room) will likely result in significant often an economical solution. As it is only
unwanted air temperature stratification. In used in a few locations, and only part of the
addition, ASHRAE Standard 62 (Indoor Air time, the energy penalty for reheat is
Quality) is being modified to require increased minimal.
outside air when heating from the ceiling. This is 2.) Supplementing baseboard perimeter heat:
because hot air tends to stay at the ceiling, and Baseboard heating systems can be the most
may 'short-circuit' directly back to the room effective means of offsetting perimeter
exhaust without mixing in the room. Indeed, heating demand loads. At times, however,
using the newly released ASHRAE 129 test peak heating demand loads may exceed the
procedure for Air Change Effectiveness, mixing installed baseboard capacity and
effectiveness values as low as 20% (or lower) supplemental overhead heat can be
have been observed, when the supply to room supplied.
differential exceeds 15F. Calculations will show 3.) Maintaining minimum ventilation rates:
that in most cases, it only requires 85F air to The benefit of an installed re-heat coil in non-
handle a typical winter design perimeter load at 1 perimeter zones becomes apparent when
cfm/SqFt. air supply rate (the airflow rate we minimum ventilation rates exceed the cooling
recommend for both good ventilation mixing and demand. This happens when the quantity of
comfort). supply air to a space required to provide
proper ventilation exceeds that required to
Page # 2
VAV Box Reheat Guidelines Revised 05/01/02
offset local heat sources, such as when the method #2). This often requires adjusting the
ratio of occupants to equipment (which heating CFM to achieve the desired room BTUH
requires little ventilation air) shifts towards at a discharge air temperature that will promote
occupants, as in conference rooms. In these good room air distribution and ventilation mixing.
cases, the required quantity of ventilation air This action is seldom performed, but should be.
may sub-cool the zone. The user inputs the room temperature and the
room load (not coil load), and the program
A slight amount of controlled reheat can calculates the necessary airflow at the selected
prevent this sub cooling. The alternative, leaving air temperature. With today’s DDC
reducing supply air temperature at the air controls, or with a parallel fan terminal, this
handler, may result in other spaces that reheat airflow setting is easy to establish.
cannot be cooled at design maximum
airflows, and also tends to increases space
relative humidity. Water coil issues:
4.) Controlling Humidity with sub cooling:
Humidity control can be enhanced using
Mixed air temperature: Mixed air temperature
reheat coils, just as for ventilation
(the combination of primary and induced air
requirements. When the local humidity is too
temperatures) is dependent on the coil location.
high, then drier cooler air can be added, and
The KSelect calculates the entering air
then slightly reheated to avoid sub cooling.
temperature for water coils. It also uses a
calculation to determine unit leaving air
Hot Water Heat: temperature on parallel boxes with a plenum inlet
The Krueger selection programs (The Krueger located coil (See below).
stand alone VAV box coil selection program and
the KSelect VAV terminal selection program) are Series Fan boxes: As the coil is always on the
very powerful tools, with many options, but discharge, the mixed air quantity (and the coil
cannot defy the basic laws of physics, entering air temperature) is based on the fan
(regardless of what is specified). Unlike custom cfm. The coil entering air temperature is
air handlers, the fin spacing, circuiting, and tube calculated based on the minimum primary at one
spacing are fixed for VAV box coils. This means temperature and the induced airflow (which is the
that there is only one solution for a given gpm, # fan cfm less the minimum primary) at another
of rows and airflow rate, for a given coil size. temperature. With series flow units, the coil
leaving air temperature and the box leaving air
When selecting a coil, one can pick only one are the same.
independent variable, with different parameters
for increasing the number of rows, gpm, etc. Parallel fan boxes: With some parallel fan
There are 6 different calculation paths included powered units, the coil location may be on the
in both programs. The selection of the best path plenum inlet so the coil entering air is always the
almost always requires a discussion with the plenum air temperature. There is mixing after the
engineer. If given a schedule to meet that is coil, however. The units discharge air
based on a coil other than Krueger’s it is temperature is therefore a mix of primary air,
necessary to know which item on the provided typically at the minimum primary air flow rate,
schedule is to be met. While this should probably and plenum air heated by the coil, at the fan air
be the BTUH, it is often the gpm (which is flow rate.
apparently set in concrete due to prior pump
selection), etc. Both scheduled gpm and BTUH Most parallel units have the coil on the
cannot be met, unless the Krueger coil is the discharge. This may be required when the
basis of design. Pick one! required coil leaving temperature exceeds 120F,
and there is a danger of ‘cooking’ the fan motor,
As discussed earlier, the coil leaving air and is usually the result of a relatively high
should be fixed so as to not exceed ASHRAE’s primary air minimum combined with a high
recommended 90F maximum (Chapter 31, heating demand. In this case, the coil acts like a
Fundamentals Handbook) except in unoccupied series fan box, except the air flow in heating
morning warm-up, for effective air distribution in mode is the sum of the primary (typically at a
the room (this is the default calculation method, minimum setting), plus the fan cfm.
Page # 3
VAV Box Reheat Guidelines Revised 05/01/02
Page # 4
VAV Box Reheat Guidelines Revised 05/01/02
Page # 5