Application
Dimensions
Power cables for power networks, Eland Part Number No. of Cores x Nominal Diameter Nominal Weight
Nominal Cross
underground and in cable ducting. Sectional Area
Under Armour Over Armour Overall
# x mm² mm kg/Km
Standards
BS6622 A9M11KV01050* 1 x 50 21.7 24.9 28.5 1200
A9M11KV01070* 1 x 70 23.0 26.2 30.0 1500
Conductor A9M11KV01095* 1 x 95 24.7 27.9 31.7 1600
Class 2 stranded plain copper conductor to BS A9M11KV01120* 1 x 120 26.7 29.9 33.9 2100
EN 60228:2005 (previously BS6360)
A9M11KV01150* 1 x 150 27.5 31.5 35.7 2500
A9M11KV01185* 1 x 185 29.3 33.3 37.5 2900
Conductor Screen
Semi-conducting material A9M11KV01240* 1 x 240 31.6 35.6 40.0 3600
A9M11KV01300* 1 x 300 34.6 38.6 43.0 4300
Insulation A9M11KV01400* 1 x 400 37.0 41.0 45.8 5200
XLPE (Cross-Linked Polyethylene) A9M11KV01500* 1 x 500 40.5 45.5 50.5 6500
Type GP8 to BS7655
A9M11KV01630* 1 x 630 44.6 49.6 54.8 8000
Correction Factors
Air
25°C 30°C 35°C 40°C 45°C 50°C 55°C
Temperature
Correction
1.00 0.96 0.92 0.88 0.83 0.78 0.73
Factor
Ground
10°C 15°C 20°C 25°C 30°C 35°C 40°C
Temperature
Correction
1.03 1.00 0.97 0.93 0.89 0.86 0.82
Factor
Ground
Thermal 0.9 1.0 1.2 1.5 2.0 2.5 3.0
Resistivity
Correction
1.06 1.04 1.00 0.92 0.82 0.74 0.68
Factor
Depth of
0.80 1.00 1.25 1.50 1.75 2.00 2.50
Laying m
Correction
1.00 0.97 0.95 0.94 0.93 0.91 0.90
Factor
The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable
dimensions may vary due to manufacturing tolerances.
For all your cable needs sales@eland.co.uk www.eland.co.uk tel +44 (0)207 241 8787 fax +44 (0)207 241 8700