Академический Документы
Профессиональный Документы
Культура Документы
Figure 1
1
Figure 2
Evidently, any number of similar sections can be wired in tandem in this manner, each
section correctly terminating the one before it, and each introducing a fixed amount of
attenuation. Any desired degree of attenuation may therefore be obtained by the use of
a sufficient number of repetitive sections, the characteristic impedance of the total
system being equal to that of a single section.
Figure 3
Example 1. Find the characteristic impedances of the three attenuating networks
drawn in Figure 3.
2
Here we use the formula R0 = R1 + 2 R1 R2
For (a) R0 = √{102 + (2 × 10 × 40)}
= √900 = 30 Ω
For (b) R0 = √{202 + (2 × 20 × 12.5)}
= √900 = 30 Ω
For (c) R0 = √{1202 + (2 × 50 × 120)}
= √26400 = 162.5 Ω
Attenuation Factor
For a single section pad, a desired characteristic impedance R0 may be obtained with
numerous combinations of R1 and R2; the examples (a) and (b) above, for instance,
both have a characteristic impedance of 30 ohms, but the section at (b) will be found
to provide a greater degree of attenuation than that at (a). The problem in the design
of an attenuator pad is, given R0 and the required attenuation, to find suitable values
for R1 and R2.
2
The attenuation may be expressed as a voltage ratio VS /VR , where Vs is the input, and
VR the output voltage, or quoted in decibels where:
Attenuation = 201og( VS /VR ) dB
or in terms of power: =10 log (Ps /PR ) dB
= 201og√( Ps /PR ) dB
whence, VS /VR = √( Ps /PR ) = N, which we will call the attenuation factor.
This relationship follows from the fact that if the section is symmetrical, that is, if the
terminals of the section are matched to equal impedances, then:
Therefore, for a pad in a symmetrical circuit, the attenuation factor N = VS /VR = IS /IR
but in an asymmetrical circuit the value N = √( Ps /PR) must be used.
Symmetrical T-pad
VS
For the symmetrical T-pad shown in Figure 4 let the attenuation N = V . With this
R
notation, attenuation is expressed as a whole number of 'times', not a fraction. We
have from the circuit:
Figure 4
VS
IS =
R0
V = VS − R1 I S
VS R
= VS − R1 = VS (1 − 1 )
R0 R0
R0 R R0
VR = V = VS (1 − 1 )( )
R1 + R0 R0 R1 + R0
R0 − R1 R0
= VS ( )( )
R0 R1 + R0
VS R + R1
=N= 0
VR R0 − R1
Equation 1
This formula gives us the attenuation factor in terms of R0 and R1. We require now to
derive expressions for R1 and.R2 in terms of N and R0. From Equation 1 above we
have, by cross multiplication:
3
Using these formulae, therefore, an attenuator can be designed to give the specified
attenuation and to be matched symmetrically into the circuit.
The calculated values for R1 and R2 have been inserted in the T-section of Figure 4
where the input and output impedances are R0.
20 log10N = 20
20
N = antilog10 [20 ] = antilog10 1.0 = 10
N−1
R1= R0[N + 1 ] = 600 × 9/11 = 491 Ω
2N
R2= R0[ 2 ] = 600 × 20/99 = 121 Ω
N −1
4
It should be particularly noted that the current supplied by the generator I will be the
same whether the attenuator network is in circuit or not, as the generator sees an
impedance of 600 Ω in either case and cannot distinguish between them. The current
in the load with the attenuator in circuit, however, is only I/5 as required; the
remaining 4/5I passes along the shunt arm. The distribution is indicated in the figure.
As the present network reduces the load current to 1/5 of its initial value, the insertion
of a second similar network will reduce the load current to 1/5 × 1/5 = 1/25 of the
initial current. (NOT 1/5 + 1/5 remember!). The generator will, of course, still see a
load resistance of 600 Ω as the second network, itself terminated by the 600 Ω load
resistance, will in turn terminate the first network with 600 Ω.
5
The symmetrical π attenuator