Powering up a thruster panel on Jascon 31


Project: Jascon 31
Project no. W80083
Drawing: P08173
Date: March 23, 2011
Technician: F. Konijn, Electroproject Aandrijftechniek
Location: Amsterdam
Report: Powering up a thruster panel

This report is about powering up a thruster panel step by step. With this method every
step is under control.
Because drives have not been used during transportation of the vessel this method
gains confidence of operation. This method must be performed by an experienced
technician.

Under normal conditions it is not necessary to power up this way!

Overall Visual check


-. Visually check every panel for irregularities.
-. Make sure main switch is OPEN. No voltage on fuses 5F3 and 5F10.
-. Turn off 10F2. (control cabinet)
-. Measure with digital-multi-meter for short-circuits and earth faults on multiple points.
-. Close all cabinet doors.
-. Check main motor for free rotation.

Cooling system
-. Check for flow and temperature of ships cooling water for both drive cabinets and
main motor.
-. Check pre-pressure of both secondary cooling systems of each thruster system.
(must be at least 1,5 Bar)
-. Check supply (3x440Vac) and power up heat exchangers.

Electroproject Aandrijftechniek is een business unit van Cofely Experts bv.


Op met ons te sluiten overeenkomsten zijn uitsluitend van toepassing de algemene verkoop- en leveringsvoorwaarden voor metaal- en
elektrotechnische industrie uitgegeven door de vereniging FME/CWM gedeponeerd ter griffie van de arrondissementsrechtbank te ’s-Gravenhage op
19 oktober 1998. Deze voorwaarden zullen op verzoek worden toegezonden. Afwijkende bedingingen zijn slechts geldig indien wij uitdrukkelijk hebben
verklaard, daarmede akkoord te gaan.

Statutaire zetel Amsterdam, handelsregister 35013591 – BTW nr. NL 0035.11.194.B01


page 2. Powering up a thruster panel on Jascon 31

Power up
-. Check external supply(230Vac) 10F2. Power up and check consumers.
-. Open 5F15. Switch 23S2 'OPERATION' to Emergency.
-. Check main supply (3x690Vac). Power up main supply. Check voltage at 5F15.
-. Power up 5F15. Check lamp 'MAIN POWER SUPPLY AVAILABLE'.
-. Check EM-STOP functionality. (complete thruster system) Check Maintenance-
switch. Check lamp test.

-. CLOSE ALL CABINET DOORS

-. Push 'EMERGENCY COMMAND STOP' button approximately 2 seconds after


starting pre-charging with 'EMERGENCY COMMAND START' button.

-. DC voltage on display's of both AFE's (inside cabinet) should drop slowly after last
step.

-. Start pre-charging again with 'EMERGENCY COMMAND START'. Listen to 'klak-klak'


sound of contactors 18Q3 and 19Q3 closing. Drive is in 'RUN' state.

-. Speed up to low setpoint with 'EMERGENCY COMMAND SPEED HIGHER'


-. Check if motor blower is running. Check thruster motor for rotation behavior.
-. Check if heat exchangers are running. Monitor temperature (display) and flow.

-. Stop with 'EMERGENCY COMMAND STOP'.


-. Switch 23S2 'OPERATION' to NORMAL.

-. Thruster is now ready for operation from HRP panels.

Electroproject Aandrijftechniek is een business unit van Cofely Experts bv.


Op met ons te sluiten overeenkomsten zijn uitsluitend van toepassing de algemene verkoop- en leveringsvoorwaarden voor metaal- en
elektrotechnische industrie uitgegeven door de vereniging FME/CWM gedeponeerd ter griffie van de arrondissementsrechtbank te ’s-Gravenhage op
19 oktober 1998. Deze voorwaarden zullen op verzoek worden toegezonden. Afwijkende bedingingen zijn slechts geldig indien wij uitdrukkelijk hebben
verklaard, daarmede akkoord te gaan.

Statutaire zetel Amsterdam, handelsregister 35013591 – BTW nr. NL 0035.11.194.B01

Вам также может понравиться