A B A B
D C D C
Coil Spring Spring
Exhaust
Exhaust
Air Air
Receiver receiver
Compressor Motor Compressor Motor
(a) (b)
Fig. 1.1 Operation of a solenoid valve (a) solenoid coil de-energised (b) solenoid coil energised
In Fig. 1.1 (a) the solenoid coil is de-energised and ports of the valve are connected as
shown by arrows. Port A is connected to exhaust while port B is connected to air receiver in
1
2 CONTROL OF MACHINES
which air is stored at a high pressure. The machine part connected to the piston will be in the
position as shown. This is due to air pressure acting on the right-hand side of the piston.
When the solenoid coil is energised, a spool will get shifted in the valve and now the
ports of the valve will get connected as shown by arrows in Fig. 1.1 (b). Port A gets connected
to pressurised air while port B gets connected to exhaust. The piston will thus move forward to
the extreme end due to air pressure on the left-hand side of the piston. In this arrangement
also, of course a motor is used as drive for the air compressor or the pump (if fluid is used) to
build up air or fluid pressure. Thus it is seen that a motor is the heart of all machinery whether
its output is used directly or indirectly. In this text the main emphasis is on the study of
control of motors. However some control circuits using solenoid valves will also be taken up.
Now we will proceed to discuss methods of control of motors.
dharm
d:\N-Mach\Mac1-1.pm5 2
INTRODUCTION TO CONTROL OF MACHINES 3
Fig. 1.2 Manual and Magnetic control of a small squirrel cage induction motor
In Fig. 1.3 it is seen that a coil is wound on the fixed core while the contacts are mounted
on the moveable core, called the armature. The contacts remain in the normal position as
shown in Fig. 1.3 (a) i.e., when the coil remains de-energised. The spring (S) keeps the main
and the auxiliary contacts in the position shown. In Fig. 1.3 (b) the contactor is shown with its
coil in energised condition. As soon as the coil is energised, the armature i.e., the movable core
is attracted towards the fixed core against the pressure of spring (S). The contacts thus change
their positions. The normally open main contacts close. Simultaneously auxiliary contacts also
change their positions. The normally open contacts close and normally close contacts open.
The main contacts are used for switching the power to the motor while auxiliary contacts are
used in the control circuit. When the coil is again de-energised armature comes back to its
original position due to the tension of the spring (S).
Now let us refer back again to the starting circuit of motor in Fig. 1.2 (b). In this figure
there are two separate circuits, i.e., the power circuit and the control circuit. Supply to the
control circuit is isolated from the main supply using a control transformer T1. Alternatively,
a phase and neutral can also be used for providing supply to the control circuit. The motor can
be switched ON and OFF with the help of push buttons. These push button switches require
small force to actuate their contacts. These contacts remain operated as long as pressure is
applied and they return to their normal position when pressure is released.
In this circuit when the ON-push button is pressed, contact P2 closes. Supply from
secondary terminal of the control transformer reaches the contactor coil through contacts, P1
(OFF-push button), P2, (ON-push button) and the over-load relay contact OL. The other terminal
of the coil is connected directly to the terminal b1 of the transformer. The coil is thus energised
dharm
d:\N-Mach\Mac1-1.pm5 3
4 CONTROL OF MACHINES
Normally closed
Auxiliary
contacts
Normally open
Normally
open
Main
contacts
Armature
Spring
Switch Switch
I
Supply Supply
(a) (b)
Fig. 1.3 Operation of an electromagnetic type contactor (a) coil de-energised (b) coil energised
and contactor closes its main contacts M1, M2, M3 and the auxiliary contact M4. Closing of
contact M4 bypasses ON-push button contact P2. Now if pressure on the ON-push button is
released contact P2 will open but supply to contactor coil M would reach through closed contact
M4 connected in parallel with contact P2. This contact M4 is known as holding or sealing contact.
A bimetallic thermal over-load is also shown connected in the power circuit. If motor draws
more current than its rated value, thermal relay contact OL opens and de-energises coil M.
De-energisation of coil opens the contacts M1, M2, M3 and M4. Supply to motor stops and holding
of control supply through M4 is also broken. Motor can also be stopped by pressing the OFF-
push button. When OFF-push button contact P1 opens, coil M is de-energised and thus holding
of supply through contact M4 is broken. Motor can be switched on again by pressing the ON-
push button. This circuit that we have discussed is also known as direct-on-line starting of
motors. This is the simplest control circuit in the field of industrial control.
dharm
d:\N-Mach\Mac1-1.pm5 4
INTRODUCTION TO CONTROL OF MACHINES 5
• Magnetic control permits installation of power contacts close to motor whereas the
actuating control device i.e., a push button switch could be located away from the motor
in a position most convenient to the operator.
• Magnetic control provides safety to the operator as remote operation described above
minimises the danger to the operator of coming into accidental contact with live parts
or being exposed to power arc and flashes at the main contacts.
• The most important advantage of magnetic control is the elimination of dependence on
operators’ skill for control of motor performance. Current and torque peaks could be
limited thus resulting in less wear and less maintenance.
• Magnetic control also makes interlocking (to be discussed later) between various
operations of a multi motor drive easy. The various operations can be performed in the
desired sequence automatically.
• With the demand for more production in industry, it became necessary to automise the
machinery to meet the challenge. Today in our industrial plants most of the machines
are automatic. Once the machine is started most of the operations are carried out
automatically.
dharm
d:\N-Mach\Mac1-1.pm5 5
6 CONTROL OF MACHINES
much advancement in the field of computers this static control is also becoming obsolete as
more and more machines are now being controlled by programmable controllers. Inspite of all
these developments as far as single motor control or a machine having few operations is
concerned, the magnetic control using contactor and relay will continue to be in use because it
is the simplest and cheapest method of control for such applications.
dharm
d:\N-Mach\Mac1-1.pm5 6
INTRODUCTION TO CONTROL OF MACHINES 7
and, therefore, M remains de-energised. When the switch, S is closed supply reaches terminal
3 through the normally closed overload relay contact OL and thus the coil M is energised. The
motor gets supply because of closing of the main contacts of the contactor (not shown in the
figure). This control circuit just developed is known as two wire control. In this type of control
circuit, however, the motor would automatically start when power supply to the motor is restored
after a failure. This type of control is only useful for starting of motors at remote places, e.g.,
starting of water pump for filling an over-head tank. Here the advantage is that the operator
is not required to switch on the motor when power supply is restored after a failure. This type
of control may however be dangerous in industries and can cause accidents due to sudden
restarting of motors on restoration of power supply. Thus the control circuit of Fig. 1.5 has
very limited application due to safety reasons.
Now let us develop a control circuit using push button switches. The normally open
contacts of these push buttons remain closed as long as the button is kept pressed by hand.
Each push button has one normally open (NO) and one normally closed (NC) contact. To use a
push button as stop (OFF) switch, the normally closed (NC) contact is generally used and for
start (ON) operation the normally open contact (NO) is generally used. In Fig. 1.6 the stop and
start push buttons and the over-load relay control contact have been connected in series with
the contactor coil.
Under normal conditions as the STOP-push button contact is normally closed supply
would reach upto terminal 2. When START-push button is pressed supply would reach the
contactor coil and hence the contactor would get energised. The coil will remain energised as
long as the START-push button is held pressed. As soon as the pressure on the START-push
button is released, the supply is cut off at terminal 3 and the coil is de-energised. To develop
the circuit further i.e., to ensure that the coil remains energised permanently once the push
button is pressed, we connect an auxiliary contact M1 of contactor M in parallel with the push
button as shown in Fig. 1.6 (b). When the coil M is energised, along with the main contacts the
auxiliary contact M1 also closes. The supply from terminal 2 now has two parallel paths i.e.,
one through the closed contact of the START-push button and the other through the closed
contact M1. Thus even when the pressure on the START-push button is released, supply reaches
coil M through closed contact M1. Thus supply to coil M is held (or sealed) through its own
dharm
d:\N-Mach\Mac1-1.pm5 7
8 CONTROL OF MACHINES
1 1 1
2 2 2 5
M1 M1
Start Start Start
3 3
3
4 4 4
Indication
M M M lamp
0 0 0
(a) (b) (c)
contact M1. When it is desired to stop the motor, the STOP-push button is pressed and therefore
its normally closed contact opens and the coil M gets de-energised. De-energisation of coil M
also opens its sealing contact M1. Thus when the pressure on the STOP-push button is released
the coil does not get energised as both the parallel paths i.e., of the START-push button and
that of contact M1 are open. To start the motor again the START-push button has to be pressed.
It is therefore seen that unlike the control circuit of Fig. 1.5, here the control circuit does not
get energised when the power supply gets restored after a failure. Thus the danger of motors
getting restarted on restoration of power supply is eliminated. In case of over loading of the
motor the over-load relay contact opens and supply is disconnected at terminal 4 thereby de-
energising the contactor and subsequently stopping the motor. Even if the over-load protective
device is of auto reset type i.e., if its contact closes when the bimetallic elements cool down the
motor would not start on its own. However, in the two wire control circuit as in Fig. 1.5, if the
overload relay is of auto reset type the motor would restart automatically. Thus the motor may
get damaged due to repeated on-off on over loading. The control, we have just discussed in Fig.
1.6, is known as three wire control. This designation is given because in this control circuit,
three wires lead from a pilot device to the starter. The term two wire and three wires are used
as they describe the simplest application of the two types. Actually in control circuits any
number of wires can start from a pilot device in a three wire control. The control contact M1
used in parallel with the START-push button is called the holding contact or sealing contact.
The name is so because it holds/seals the contactor coil in the energised condition even when
START-push button switch is released. The step in further development of the circuit is to
have a ‘motor ON’ indication. An auxiliary contact M2 of contactor M is connected in series
with supply wire 1 to feed an indicator lamp terminal. Its other terminal being connected to
the neutral as shown in Fig. 1.6 (c).
1.6.2 Remote Control Operation of a Motor
In further development of circuit of Fig. 1.6 (c) it may be desired that starting and stopping of
the motor should also be possible from a distant place (remote place) while the starter being
dharm
d:\N-Mach\Mac1-1.pm5 8
INTRODUCTION TO CONTROL OF MACHINES 9
1 1
P1 P3 P1 P3 P5
2 5 2 5 9
P4
P2 A1 B1 P2 A1 P4 B1 P6 C1
3 6 3 6 10
A2 A3
11
B2
7
12
4 7 4 8 13
A B A B C
0 0
(a) (b)
dharm
d:\N-Mach\Mac1-1.pm5 9
10 CONTROL OF MACHINES
A has started. It should however be possible to stop the motor independently. The first step
would be to develop the starters of motor A and motor B independently as shown in Fig. 1.8.
In order that contactor B should energise only when contactor A is energised we will
have to insert a normally open contact of contactor A in series with the contactor coil B after
terminal 6 as shown in Fig. 1.8 (b). As shown in the figure a normally open contact A2 has been
connected after wire No. 6. Thus when contactor A is not energised the contact A2 will be open.
If we press the push button P4 the supply will reach upto terminal 6 only. The contactor coil B
can be energised only when contactor A is energised i.e., only when its contact A2 is closed.
If in the above circuit it is further required that a motor C should run only if both motors
A and B are running, we will be able to get this function by connecting normally open contacts
of contactor A and B in series with the coil of contactor C. This development is also shown in
Fig. 1.8 (b). When push button P6 is pressed the supply will reach coil of contactor C at terminal
13, only if contacts A3 and B2 are closed i.e., only when both contactors A and B are energised.
When either of the two motors is not running motor C can not be started.
REVIEW QUESTIONS
1. State the disadvantages of using manual control for control operations of electrical motors.
2. Name the devices which led to the use of automatic control for motors.
3. State the advantages of magnetic control over manual control.
4. What is the difference between semi-automatic and automatic control?
5. What will happen if the plunger of a contactor is prevented from completing its stroke?
6. When will a contactor coil take maximum current and why?
7. Under what conditions static control is preferred against magnetic control?
8. Explain why magnetic control is used for control having few operations.
9. State the difference between a two wire and a three wire control.
10. When the plunger of a contactor is in closed position the coil current is:
(a) maximum
(b) minimum
(c) zero.
11. When the contactor coil is de-energised:
(a) the contacts remain closed
(b) are held closed by mechanical latch
(c) gravity and spring tension open the contacts.
12. The purpose of using over load protection in a motor is to protect the motor from:
(a) sustained overcurrent
(b) over voltage
(c) short circuit
(d) all the above.