83-78-00-01

1/99

7800 Series
Burner Control

TOTAL BURNER
CONTROL
7800 SERIES

7800 SERIES
The latest in Flame Safeguard state-of-the-art technology
is the7800SERlES Burner Control. The Honeywell 17800
SERIES combines safety, comprehensive diagnostics,
communication and networking capabilities into one com-
pact and affordable microcomputer burner control. It can
do just about anything and everything you would like it to
do.

The 7800 SERIES works on a wide range of industrial


applications: burners, boilers, furnaces, ovens, kilns,
process heaters and more. The 7800 SERIES replaces
more than 400 Honeywell and competitive control types.
It offers you intelligent control anyway you want it: with or
without communications, with or without an expanded an-
nunciator, with or without a keyboard display module.
Whatever features you want from a burner control, just
ask. With the 7800 SERIES, the answer is...yes, it can.

COMMUNICATIONS INTERFACE
The 7800 SERIES can interface with compatible lBM®
equivalent personal computers at an onsite or remote
location through a communications interface.
Flame Safeguard Systems
Product Selection Matrix for CE Sequence Primary/Programmer
Relay Modules:
For 230 Vac nominal applications—
Fuel Burner Type Relay Module Type
Single Atmospheric EC7810
Single Atmospheric with fan EC7820
Combination or single On/Off Controlled Power Burner EC7830
Combination or single Full Modulation Power Burner EC7850

For 120 Vac nominal applications-


Fuel Burner Type Relay Module Type
Combination or single On/Off Controlled Power Burner RM7830
Combination or single Full Modulation Power Burner RM7850

Use the following pages to select the following required Use the following pages to select the following optional devices:
devices: Keyboard Display module, up to 1 mounted to relay module, remote
Relay Module, 1 per burner as desired
Subbase, 1 per relay module Communications, network and controlbus modules to service
Purge Timer Card, 1 per relay module selected relays
Flame Amplifier, 1 per relay module Miscellaneous, as required to complete installation
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC7810 PROGRAMMER RELAY MODULES:

SELECT A 220-240 VAC 50/60 HZ DESCRIPTION


1.) RELAY EC7810A1027 ONE IGNITION ATTEMPT
MODULE EC7810A1035 FIVE IGNITION ATTEMPTS

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 1 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 2 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 2 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7849A1015 1 SECOND FFRT NONE C7027, C7035
R7849A1023 2 SECOND FFRT NONE C7027, C7035
R7849B1013 1 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 2 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 2 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 1 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 2 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
5.) OPTIONAL O.S. NO. DESCRIPTION
COMPONENTS S7800A1001 ENGLISH LANGUAGE
S7800A1035 FRENCH LANGUAGE
KEYBOARD S7800A1043 GERMAN LANGUAGE
DISPLAY S7800A1050 ITALIAN LANGUAGE
MODULE S7800A1068 SPANISH LANGUAGE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
COMMUNICATIONS
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7800E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS
203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15515

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC7820 PROGRAMMER RELAY MODULES:

SELECT A 220-240 VAC 50/60 HZ DESCRIPTION


1.) RELAY EC7820A1026 ONE IGNITION ATTEMPT
MODULE EC7820A1034 FIVE IGNITION ATTEMPTS

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.)
SUBBASE Q7800B1003 BURNER/WALL MOUNT
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 1 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 2 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 2 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7849A1015 1 SECOND FFRT NONE C7027, C7035
R7849A1023 2 SECOND FFRT NONE C7027, C7035
R7849B1013 1 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 2 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 2 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 1 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 2 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
O.S. NO. DESCRIPTION
5.) OPTIONAL
S7800A1001 ENGLISH LANGUAGE
COMPONENTS
S7800A1035 FRENCH LANGUAGE
S7800A1043 GERMAN LANGUAGE
KEYBOARD S7800A1050 ITALIAN LANGUAGE
DISPLAY S7800A1068 SPANISH LANGUAGE
MODULE S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
COMMUNICATIONS QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7800E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS 203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15516

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC/RM7830 PROGRAMMER RELAY MODULES:

220-240 VAC 50/60 HZ 120VAC 50/60 HZ DESCRIPTION


SELECT A EC7830A1033 RM7830A1003 POST-PURGE 2 SECONDS
1.) RELAY EC7830A1041 RM7830A1011 POST-PURGE 30 SECONDS
MODULE EC7830A1066 RM7830A1029 POST-PURGE 15 SECONDS

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 1 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 2 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 2 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7849A1015 1 SECOND FFRT NONE C7027, C7035
R7849A1023 2 SECOND FFRT NONE C7027, C7035
R7849B1013 1 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 2 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 2 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 1 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 2 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
5.) OPTIONAL O.S. NO. DESCRIPTION
COMPONENTS S7800A1001 ENGLISH LANGUAGE
S7800A1035 FRENCH LANGUAGE
S7800A1043 GERMAN LANGUAGE
KEYBOARD
S7800A1050 ITALIAN LANGUAGE
DISPLAY
S7800A1068 SPANISH LANGUAGE
MODULE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS 203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)
M15517

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC/RM7850 PROGRAMMER RELAY MODULES:

220-240 VAC 50/60 HZ 120VAC 50/60 HZ DESCRIPTION


SELECT A EC7850A1064 DYNAMIC AIR DAMPER CHECK
1.) RELAY EC7850A1072 RM7850A1001 POST-PURGE 2 SECONDS
MODULE EC7850A1080 RM7850A1027 POST-PURGE 30 SECONDS
EC7850A1122 RM7850A1019 POST-PURGE 15 SECONDS

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 1 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 2 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 1 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 2 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 2 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7849A1015 1 SECOND FFRT NONE C7027, C7035
R7849A1023 2 SECOND FFRT NONE C7027, C7035
R7849B1013 1 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 2 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 2 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 1 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 2 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
OPTIONAL O.S. NO. DESCRIPTION
5.)
COMPONENTS S7800A1001 ENGLISH LANGUAGE
S7800A1035 FRENCH LANGUAGE
KEYBOARD S7800A1043 GERMAN LANGUAGE
DISPLAY S7800A1050 ITALIAN LANGUAGE
MODULE S7800A1068 SPANISH LANGUAGE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS 203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)
M15519

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC/RM7823 FLAME SWITCH RELAY MODULES:

SELECT A
1.) RELAY 220-240 VAC 50/60 HZ 120VAC 50/60 HZ
MODULE EC7823A1004 RM7823A1016

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
3.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
OPTIONAL O.S. NO. DESCRIPTION
4.) S7800A1001 ENGLISH LANGUAGE
COMPONENTS
S7800A1035 FRENCH LANGUAGE
S7800A1043 GERMAN LANGUAGE
KEYBOARD S7800A1050 ITALIAN LANGUAGE
DISPLAY S7800A1068 SPANISH LANGUAGE
MODULE S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS
203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)
M15520

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR RM7824A 24VDC PRIMARY CONTROL RELAY MODULES:

SELECT A
1.) RELAY RM7824A1006 24VDC
MODULE

O.S. NO. DESCRIPTION


2.) SELECT A Q7800A1005 PANEL MOUNT
SUBBASE Q7800B1003 BURNER/WALL MOUNT
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7824C1002 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7024E, F
3.) A FLAME R7848A1008 3.0 SECOND FFRT NONE C7015
AMPLIFIER R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015

O.S. NO. DESCRIPTION


SELECT S7800A1001 ENGLISH LANGUAGE
4.) OPTIONAL S7800A1035 FRENCH LANGUAGE
COMPONENTS S7800A1043 GERMAN LANGUAGE
S7800A1050 ITALIAN LANGUAGE
KEYBOARD S7800A1068 SPANISH LANGUAGE
DISPLAY S7800A1118 KATAKANA (JAPANESE) LANGUAGE
MODULE S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
QS7800A1001 CONTROLBUS MODULE, STANDARD
COMMUNICATIONS QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
MISCELLANEOUS 204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15521

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC/RM7885 SEMI-AUTOMATIC PRIMARY RELAY MODULES:

SELECT A
1.) RELAY 220-240 VAC 50/60 HZ 120VAC 50/60 HZ DESCRIPTION
MODULE EC7885A1011 RM7885A1015

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.)
SUBBASE Q7800B1003 BURNER/WALL MOUNT
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
3.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
O.S. NO. DESCRIPTION
4.) OPTIONAL
S7800A1001 ENGLISH LANGUAGE
COMPONENTS
S7800A1035 FRENCH LANGUAGE
S7800A1043 GERMAN LANGUAGE
KEYBOARD S7800A1050 ITALIAN LANGUAGE
DISPLAY S7800A1068 SPANISH LANGUAGE
MODULE S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS
QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS 203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15522

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR RM7888A SPECIAL FUNCTION PRIMARY CONTROL RELAY MODULES:

SELECT A
1.) RELAY 120VAC 50/60 HZ DESCRIPTION
MODULE RM7888A1019

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.)
SUBBASE Q7800B1003 BURNER/WALL MOUNT
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

SELECT O.S. NO. DESCRIPTION CHECKING USE WITH


3.) A FLAME R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT O.S. NO. DESCRIPTION


4.) OPTIONAL S7800A1001 ENGLISH LANGUAGE
COMPONENTS S7800A1035 FRENCH LANGUAGE
S7800A1043 GERMAN LANGUAGE
KEYBOARD S7800A1050 ITALIAN LANGUAGE
DISPLAY S7800A1068 SPANISH LANGUAGE
MODULE S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS 203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15523

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC/RM7890 PRIMARY CONTROL RELAY MODULES:

220-240 VAC 50/60 HZ 120VAC 50/60 HZ DESCRIPTION


EC7890A1011 RM7890A1015
RM7890A1031 30 SECOND PFEP
SELECT A EC7890B1010 RM7890B1014 WITH SHUTTER DRIVE
1.) RELAY RM7890C1005 STANDING PILOT APPLICATIONS WITH FLAME RODS ONLY
MODULE RM7890D1004 INFRARED HEATER ONLY 15 OR 30 PREF

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.)
SUBBASE Q7800B1003 BURNER/WALL MOUNT
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
3.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**
* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
O.S. NO. DESCRIPTION
4.) OPTIONAL
S7800A1001 ENGLISH LANGUAGE
COMPONENTS
S7800A1035 FRENCH LANGUAGE
S7800A1043 GERMAN LANGUAGE
KEYBOARD S7800A1050 ITALIAN LANGUAGE
DISPLAY S7800A1068 SPANISH LANGUAGE
MODULE S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS
203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15524

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR EC/RM7895 FULL FUNCTION PRIMARY RELAY MODULES:

INTERMITTENT PILOT
220-240 VAC 50/60 HZ 120VAC 50/60 HZ DESCRIPTION
SELECT A EC7895A1010 RM7895A1014
1.) RELAY RM7895A1048 EARLY SPARK TERMINATION
MODULE RM7895B1013 DYNAMIC AIRFLOW SWITCH CHECK

INTERRUPTED PILOT
EC7895C1000 RM7895C1012
RM7895C1020 EARLY SPARK TERMINATION
RM7895D1011 DYNAMIC AIRFLOW SWITCH CHECK
RM7895E1002 INFRARED HEATER APPLICATIONS, 15/30 SECOND PFEP
RM7895F1001 DYNAMIC AIRFLOW SWITCH CHECK, INFRARED
HEATER APPLICATIONS, 15/30 SECOND PFEP

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
OPTIONAL O.S. NO. DESCRIPTION
5.)
COMPONENTS S7800A1001 ENGLISH LANGUAGE
S7800A1035 FRENCH LANGUAGE
KEYBOARD S7800A1043 GERMAN LANGUAGE
DISPLAY S7800A1050 ITALIAN LANGUAGE
MODULE S7800A1068 SPANISH LANGUAGE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
MISCELLANEOUS 203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15525

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR RM7838A SEMI-AUTOMATIC INDUSTRIAL PRIMARY RELAY MODULE:

SELECT A
1.) RELAY 120 VAC 50/60 HZ DESCRIPTION
MODULE RM7838A1014 INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
OPTIONAL O.S. NO. DESCRIPTION
5.)
COMPONENTS S7800A1001 ENGLISH LANGUAGE
S7800A1035 FRENCH LANGUAGE
KEYBOARD S7800A1043 GERMAN LANGUAGE
DISPLAY S7800A1050 ITALIAN LANGUAGE
MODULE S7800A1068 SPANISH LANGUAGE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
COMMUNICATIONS QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
MISCELLANEOUS 203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)
M15527

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR RM7838B SEMI-AUTOMATIC INDUSTRIAL PROGRAMMER RELAY MODULE:

SELECT A 120 VAC 50/60 HZ DESCRIPTION


1.) RELAY RM7838B1013 SEMI-AUTOMATIC PROGRAMMER WITH
MODULE S7800A1001 KEYBOARD DISPLAY STANDARD

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.)
SUBBASE Q7800B1003 BURNER/WALL MOUNT
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
PURGE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**
* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
O.S. NO. DESCRIPTION
5.) OPTIONAL
S7800A1001 ENGLISH LANGUAGE
COMPONENTS
S7800A1035 FRENCH LANGUAGE
KEYBOARD S7800A1043 GERMAN LANGUAGE
DISPLAY S7800A1050 ITALIAN LANGUAGE
MODULE S7800A1068 SPANISH LANGUAGE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
COMMUNICATIONS Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS 203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)

M15528

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR UL/CSA RM78XXG, M PROGRAMMER RELAY MODULE:

SELECT A 120VAC 50 HZ 120VAC 60 HZ DESCRIPTION


1.) RELAY RM7800G1000 RM7800G1018 MODULATING BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY
MODULE MODULE STANDARD
RM7840G1006 RM7840G1014 MODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE
RM7800M1003 RM7800M1011 ON-OFF BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULE
STANDARD
RM7840M1009 RM7840M1017 ON-OFF BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
O.S. NO. DESCRIPTION
5.) OPTIONAL
S7800A1001 ENGLISH LANGUAGE
COMPONENTS
S7800A1035 FRENCH LANGUAGE
KEYBOARD S7800A1043 GERMAN LANGUAGE
DISPLAY S7800A1050 ITALIAN LANGUAGE
MODULE S7800A1068 SPANISH LANGUAGE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
COMMUNICATIONS Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS REMOTE DISPLAY MOUNTING BRACKET
203765
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)
M15529

65-0198—2
7800 SERIES BURNER CONTROL

PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE:

SELECT A 120VAC 50/60 HZ DESCRIPTION


1.) RELAY RM7800E1010 ENERGY SAVING PURGE, S7800A1001 KEYBOARD DISPLAY STANDARD
MODULE RM7840E1016 ENERGY SAVING PURGE WITHOUT KEYBOARD DISPLAY
RM7800L1012 S7800A1001 KEYBOARD DISPLAY STANDARD
RM7840L1018 WITHOUT KEYBOARD DISPLAY
RM7800L1053 INTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD
RM7840L1026 INTERMITTENT PILOT WITHOUT KEYBOARD DISPLAY

O.S. NO. DESCRIPTION


SELECT A Q7800A1005 PANEL MOUNT
2.) Q7800B1003 BURNER/WALL MOUNT
SUBBASE
Q7800B1011 BURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO. DESCRIPTION O.S. NO. DESCRIPTION


SELECT A ST7800A1005 TIMING: 2 SECOND ST7800A1070 TIMING: 2.5 MINUTE
3.) PURGE ST7800A1013 TIMING: 7 SECOND ST7800A1088 TIMING: 4 MINUTE
CARD ST7800A1021 TIMING: 10 SECOND ST7800A1096 TIMING: 6 MINUTE
ST7800A1039 TIMING: 30 SECOND ST7800A1104 TIMING: 9 MINUTE
ST7800A1047 TIMING: 40 SECOND ST7800A1112 TIMING: 12 MINUTE
ST7800A1054 TIMING: 60 SECOND ST7800A1120 TIMING: 15 MINUTE
ST7800A1062 TIMING: 90 SECOND ST7800A1138 TIMING: 22 MINUTE
ST7800A1146 TIMING: 30 MINUTE

O.S. NO. DESCRIPTION CHECKING USE WITH


SELECT R7847A1025 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
4.) A FLAME R7847A1033 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS
AMPLIFIER R7847A1074 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847A1082 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847B1023 0.8 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1031 3.0 SECOND FFRT AMPLICHECK™ FLAME ROD, PHOTOCELLS
R7847B1064 0.8 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*
R7847B1072 3.0 SECOND FFRT NONE FLAME ROD, PHOTOCELLS*, C7012A, C
R7847C1005 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7012E, F**
R7848A1008 3.0 SECOND FFRT NONE C7015
R7848B1006 3.0 SECOND FFRT AMPLICHECK™ C7015
R7849A1015 0.8 SECOND FFRT NONE C7027, C7035
R7849A1023 3.0 SECOND FFRT NONE C7027, C7035
R7849B1013 0.8 SECOND FFRT AMPLICHECK™ C7027, C7035
R7849B1021 3.0 SECOND FFRT AMPLICHECK™ C7027, C7035
R7861A1026 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7861A1034 0.8 SECOND FFRT DYNAMIC SELF-CHECK C7061A**
R7886A1001 3.0 SECOND FFRT DYNAMIC SELF-CHECK C7076A, D**
* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).
** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

SELECT
OPTIONAL O.S. NO. DESCRIPTION
5.) S7800A1001 ENGLISH LANGUAGE
COMPONENTS
S7800A1035 FRENCH LANGUAGE
KEYBOARD S7800A1043 GERMAN LANGUAGE
DISPLAY S7800A1050 ITALIAN LANGUAGE
MODULE S7800A1068 SPANISH LANGUAGE
S7800A1118 KATAKANA (JAPANESE) LANGUAGE
S7800A1126 PORTUGUESE LANGUAGE
S7800B1009 CHINESE LANGUAGE

O.S. NO. DESCRIPTION


Q7700A1014 NETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.
EXTERNAL MODEM REQUIRED.
COMMUNICATIONS Q7700B1004 NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZ
EXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.
QS7800A1001 CONTROLBUS MODULE, STANDARD
QS7800B1000 CONTROLBUS MODULE, MULTI DROP
QS7800C1009 CONTROLBUS MODULE, DATA ACQUISITION MODULES
QS7800D1008 CONTROLBUS MODULE, ARMSTRONG
QS7850E1007 CONTROLBUS MODULE, PULSAFEEDER
QS7850A1006 CONTROLBUS MODULE, GENERAL PURPOSE INTERFACE
ZM7850A1001 COMBUSTION SYSTEM MANAGER® SOFTWARE
ZM7850B1000 SYSNET INTEGRATION SOFTWARE
S7810A1009 DATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)
S7810B1007 DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO. DESCRIPTION


S7820A1007 REMOTE RESET MODULE
S7830A1005 EXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)
203541 DATA CONTROLBUS CONNECTOR, 5-WIRE
MISCELLANEOUS
203765 REMOTE DISPLAY MOUNTING BRACKET
221729 DUST COVER, RELAY MODULE
204718A KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR
204718B KEYBOARD DISPLAY MODULE COVER, CLEAR
204718C KEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH
RESET BUTTON
205321B FLUSH DISPLAY MOUNTING KIT
221818A EXTENSION CABLE, DISPLAY 5FT (1524MM)
221818C EXTENSION CABLE, DISPLAY 10FT (3048MM)
M15530

65-0198—2
7800 SERIES Relay Modules

RM7888A Semi-Automatic Industrial Primary Control


Microprocessor-based integrated APPROVAL BODIES:
burner control for industrial process Underwriters Laboratories Inc. Component Recognized.
semi-automatically fired gas, oil, Factory Mutual Approved.
coal, or combination fuels for single Canadian Standards Association certified.
and multiple burner applications. APPROXIMATE DIMENSIONS: 5 in. [127 mm] wide; 5 in. [127 mm]
Provides level of safety, functional ca- high; 5-1/4 in. [133 mm] deep with Q7800A Subbase, 6-3/32 in.
pability and features beyond conven- [155 mm] deep with Q7800B Subbase.
tional controls. WEIGHT: 1 lb., 10 oz. [737 grams].
OPERATING AMBIENT TEMPERATURE RANGE: –40 F to +140 F
● Functions include automatic burner [–40 C to +60 C].
startup sequencing, five user select- ELECTRICAL RATINGS:
able run sequences, four line-voltage sequence control inputs, Voltage and Frequency: 120 Vac (+10/–15%), 50 or 60 Hz (±10%).
flame supervision, system status indication, system or self-diag- REQUIRED COMPONENTS:
nostics and troubleshooting. Q7800A or B Universal Wiring Subbase. R7847, R7848,
● Requires a relay module, subbase, and amplifier for operation. R7849, R7861, or R7886 Plug-in Flame Signal Amplifier.
● Options include PC interface, keyboard display module, DATA OPTIONAL COMPONENTS:
CONTROLBUS MODULE™, remote display mounting, first- A78001002 Tester.
out expanded annunciator, and COMBUSTION SYSTEM Q7700A1014 Communications Interface Base Unit.
MANAGER™ software. QS7800A1001 Communications Interface ControlBus Module.
● Use with master system control which determines purge timing S7800A1001 Keyboard Display Module.
and confirms air supply and air flow. S7810A1009 DATA CONTROLBUS MODULE™.
● Nonvolatile memory retains history files and sequencing status S7820A1007 Remote Reset Module.
after power loss. S7830A1005 Expanded Annunciator.
● Optional remote reset capability. ZM7850A1001 COMBUSTION SYSTEM MANAGER™ (CSM™).
● Five LEDs provide sequence information. 123514A Rectifying Flame Simulator.
● Interchangeable plug-in flame amplifiers. 203541 ControlBus 5-Wire Electrical Connector.
● Local or remote annunciation of operation and fault information. 203659 Ultraviolet Flame Simulator.
203765, 205321B, 204718A,B Remote Display Mounting
Brackets.
203968A Remote Display Power Supply (13 Vdc) Plug-in.
221818A Sixty-inch Extension Cable Assembly.
221818C 120 inch Extension Cable Assembly.
SEQUENCE TIMING FOR NORMAL OPERATION:

Pilot Flame Main Flame


RM7888A Sequence Initiate Standby Purge Establishing Period Establishing Period Pilot Relight Run
Pilot: PV Return 10 sec. a b 10 sec. 15 sec. 5 sec. to infinity a
Pilot: MV LoFire —
DSI Normal 4 sec. — —
DSI High/Low Stepfire — —
DSI On/Off Stepfire — —
a
STANDBY and RUN can be an infinite time period.
b
PURGE time is determined by the system master controller.

Order Number Description

RM7888A1027 Semi-automatic relay module, 50/60 Hz.


Primary Relay Modules—Automatic

NOTE: CONTROLS FOR USE IN 7800 SERIES BURNER CONTROL SYSTEMS ARE AVAILABLE ONLY THROUGH
AUTHORIZED HONEYWELL 7800 SERIES DISTRIBUTORS.
For the name of your nearest authorized Honeywell 7800 SERIES Distributor, please call 1-800-345-6770, ext. 2040.

NV17890A, B, C, D/EC7890A, B Primary Controls


Microprocessor-based integrated primary burner control for automatically fired gas, oil, coal or combina-
tion fuel single burner applications.
WEIGHT: 1 lb., 13 oz.
OPERATING AMBlENT TEMPERATURE RANGE: – 40 F to
+140 F [– 40 C to + 60 C].
ELECTRICAL RATINGS:
Voltage and Frequency: 120 Vac (+10/ -15%), 50/60 Hz
(±10%) RM7890A,B,C,D.
220-240 Vac (+10/ -15%), 50/60 Hz (±10%)
EC7890A,B.
REQUIRED COMPONENTS:
R7847, R7848, R7849, R7861, or R7886A Flame Signal
Amplifiers.
Q7800 Universal Wiring Subbase.
● Functions include automatic burner sequencing, flame OPTIONAL COMPONENTS:
supervision, system status indication, system or self- Communciations (see Communications Section).
diagnostics and troubleshooting. S7800A Keyboard Display Module.
S7810A DATA CONTROLBUS MODULE™.
● Five LEDs provide sequence information. S7820A Remote Reset Module.
● Selectable recycle or lockout on loss of flame. S7830A First-out Expanded Annunciator Module.
● Shutter drive output (RM7890B) for use with Dynamic REPLACEMENT PART: 221729 Dust Cover.
Self-Check flame detectors.
● Access for external electrical voltage checks. SEQUENCE TIMING FOR NORMAL OPERATION:

● Interchangeable plug-in flame amplifiers. Pilot F l a m e


Model Establishing
● Nonvolatile memory retains history files and sequence Number Initiate Standby Period (PFEP) Run
status after loss of power. RM7890A/ 10 sec. a b
4 or 10 sec. a
● Compatible with existing Honeywell flame detectors. EC7890A
RM7890B/ 10 sec. a 4 or 10 sec. a
EC7890B
RM7890C 10 sec. a Not Applic. a
RM7890D 10 sec. a 15/30 sec. a
APPROVAL BODIES: RN17890 a b
STANDBY & RUN can be an infinite time period. RM7890A1031—30 PFEP
Underwriters Laboratories Inc. listed, File No. MP268,
Guide No. MCCZ.
Canadian Standards Association certified, LR9S329-3. Order Number Description Replaces a
Factory Mutual approved.
RM7890A1015/ Automation primary relay RA890F,
IRI acceptable. EC7890A1011 module, 50/60 Hz G, H
Federal Communications Commission: Part 15, Class
B-Emissions. RM7890A1031/ Automatic primary relay RA890F,
module, 30 sec . PFEP G, H
RM7890B1014/ Automatic primary relay RA890F,
DIMENSIONS: 5 in. [127 mm] wide, 5 in. [127 mm] high, EC7890B1010 module, shutter drive, 50/60 G, H
3-1/32 in. [77 mm] deep. Hz
RM7890C1005 Automatic primary relay
module, 60 Hz, standing
pilot
RM7890D1004 Automatic primary relay
module, 60 Hz for direct
spark infrared heater
application, Flame rods only
a
To replace RA890F, select R7847A Flame Signal Amplifier. To replace
RA890G, select R7849A Flame Signal AMplifier. To replace RA890H,
select R7847B Flame Signal Amplifier. Check timings for application
requirements.
Primary Relay Modules—Automatic
RM7895A, B, C, D, E, F/EC7895A, C Primary Controls

Microprocessor-based DIMENSIONS: 5 in. (127 mm) wide, 5 in. (127 mm) high,
integrated primary burner 3-1/32 in. (77 mm) deep.
control for automatically fired WEIGHT: 1 lb., 13 oz.
gas, oil, coil, or combination OPERATING AMBlENT TEMPERATURE RANGE: –40°F to
fuel single burner +140°F (–40°C to +60°C).
applications.
ELECTRICAL RATINGS:
Voltage and Frequency: 120 Vac (+10/-15%), 50/60 Hz
(±10%) RM7895A, B, C, D, E, F.
220 to 240 Vac (+10/-15%), 50/60 Hz (±10%) EC7895A, C.
● Functions include automatic burner sequencing, flame
REQUIRED COMPONENTS:
supervision, system status indication, system or self-
Q7800 Universal Wiring Subbase.
diagnostics and troubleshooting. R7847, R7848, R7849, R7861, or R7886 Flame Signal
● Five LEDs provide sequence information.
Amplifiers.
● Selectable recycle or lockout on loss of flame or airflow. ST7800 Plug-in Purge Timers.
● Access for external electrical voltage checks.
● Interchangeable plug-in flame amplifiers.
OPTIONAL EQUIPMENT:
● Nonvolatile memory retains history files and lockout status Communications (see Communications Section).
after loss of power.
S7800 Keyboard Display Module
● Delayed main valve on RM7895C, D. S7810 DATA CONTROLBUS MODULE™.
● Airflow switch check feature on RM7895B, D.
S7820 Remote Reset module
● Compatible with existing Honeywell flame detectors.
S7830 First-out Expanded Annunciator.
APPROVALS: ACCESSORIES:
RM7895—
123514A Rectifying Flame Simulator.
Underwriters Laboratories Inc. Listed: File No. MP268, 203541 ControlBus 5-Wire Electrical Connector.
Guide No. MCCZ. 203659 Ultraviolet Flame Simulator.
Canadian Standards Association Certified: LR95329-3. 203765, 205321B, 204718A, B, C Remote Display Mounting
Factory Mutual Approved: JIOW7A4.AF. Brackets.
Industrial Risk Insurers Acceptable. 203968A Remote Display Power Supply (13 Vdc) Plug-in.
Federal Communications Commission: Part 15, Class B— 221729A Dust Cover.
Emissions. 221818A 60-inch Extension Cable Assembly.
Control Safety Devices Acceptable: CSD-1. 221818C 120-inch Extension Cable Assembly.
EC7895—
Factory Mutual Approved. REPLACEMENT PART: 221729 Dust Cover.

Flame Establishing Period Airflow Switch Delay


Model Number Initiate Standby Purge Pilot Main Check (AFSC) Main Valve
RM7895A/EC7895 10 sec. a b 4 or 10 sec. No No No
A
RM7895BEC7895 10 sec. a b 4 or 10 sec. No Yes No
B
RM7895C 10 sec. a b 4 or 10 sec. 10 sec. No Yes
RM7895D 10 sec. a b 4 or 10 sec. 10 sec. Yes Yes
RM7895E 10 sec. a b 15 or 30 sec. No No No
RM7895F 10 sec. a b 15 or 30 sec. No Yes No

Order Number Description Replaces c


RM7895A1014 Intermittent primary relay module without AFSC, 50/60 Hz R7795A, B
EC7895A1010 Intermittent primary relay module without AFSC, 50/60 Hz
RM7895A1048 Intermittent primary relay module without AFSC, 50/60 Hz R7795A, B
Termination of spark upon detection of flame
RM7895B1013 Intermittent primary relay module with AFSC, 50/60 Hz R7795E, F
EC7895C1000 Intermittent primary relay module with AFSC, 50/60 Hz
RM7895C1012 Interrupted primary relay module without AFSC, 50/60 Hz R7795C, D
RM7895C1020 Interrupted primary relay module without AFSC, fixed 10 sec. PFEP, R7795C, D
termination of spark upon detection of flame, 50/60 Hz
RM7895D1011 Interrupted primary relay module with AFSC, 50/60 Hz R7795G, H
RM7895E1002 Intermittent primary relay module with AFSC, 50/60 Hz for direct spark
infrared heater, flame rods only
RM7895F1001 Intermittent primary module with AFSC, 50/60 Hz for direct spark
infrared heater, flame rods only
a b
STANDBY and RUN can be an infinite time period. PURGE will be determined by which ST7800 Purge card is selected.
C
To replace R7795A C, E, F, select R7849A FIame Signal Amplifier. To replace R7795B, D, F, H, select R7847A Flame signal Amplifier.
Primary Relay Modules—Automatic
RM7824 Primary Controls

24 Vdc microprocessor-based TIMING SEQUENCE:


integrated burner control for Model Initiate Standby Pilot Flame Run
automatically fired gas, oil, or Number Establishing
combination fuel single burner Period (PFEP)
applications. Provides level of
safety, functional capability RM7824A 10 sec. a 4 or 10 sec. a
and features beyond the a
STANDBY and RUN can be an infinite time period.
capacity of conventional
controls. REQUIRED COMPONENTS:
Q7800A, B Universal Wiring Subbase.
R7824C1002 Dynamic Self-Check Amplifier 3.0 sec. FFRT
For use with R7824C Amplifier with C7024E, F Flame used with C7024E, F.
Detectors and R7848A, B with C7015A Flame Detectors. R7848A1008 Infrared or C7015A Infrared Flame Detector
Functions include automatic burner sequencing, flame 3.0 sec. FFRT used with C7015A.
supervision, system status indication, system or self- F7848B1006 Dynamic AmpIi-Check® 3.0 sec. FFRT used
diagnostics and troubleshooting. with C7015A.
Five LEDs provide sequence information.
Selectable recycle or lockout on loss of flame airflow. ACCESSORIES:
Shutter drive output for use with dynamic self-check Flame 123514A Rectifying Flame Simulator.
detectors. 203541 ControlBus 5-Wire Electrical Connector.
Access for external electrical voltage checks. 203659 Ultraviolet Flame Simulator.
Plug-in flame amplifier. 203765, 205321B, 204718A, B, C Remote Display
Nonvolatile memory retains history files and lockout status Mounting Brackets.
after loss of power. 203968A Remote Display Power Supply (13 Vdc) Plug-in.
204718A NEMA 4 Weatherproofing Kit for S7800.
APPROVALS: 204718B NEMA 1 Weatherproofing Kit for S7800.
Underwriters Laboratories Inc. Component Recognized: 221729A Dust Cover.
File No. MP268, Guide No. MCCZ. 221818A 60-inch Extension Cable Assembly to remote
Canadian Standards Association Certified: LR95329-3. mount S7800.
Federal Communications Commission: Part 15, Class B— 221818C 120-inch Extension Cable Assembly.
Emissions.
DIMENSIONS, APPROXIMATE: REPLACEMENT PART: 221729 Dust Cover.
5 in. (127 mm) wide, 5 in. (127 mm) high, 5-1/4 in. (133
mm) deep with subbase.
WEIGHT: 1 lb., 13 oz. (0.8 kg) with dust cover.
TEMPERATURE RATINGS:
Ambient: –40°F to +140°F (–40°C to +60°C).

ELECTRICAL RATINGS:
Power Supply: 24 Vdc, +7%, –8%.
Load: 500 VA maximum.

SEQUENCE TIMING FOR NORMAL OPERATION OF THE PRIMARY RELAY:


Pilot Flame
Device Initiate Standby Establishing Period Run
* *
RM7824A1006 10 sec. 4 or 10 sec.

*STANDBY and RUN can be an infinite time period.

AMPLIFIER:
Order Number Description

R7824C1002 Amplifier for Primary Relay Module - 24 Vdc Input - used with C7024E, F
R7848A1008 Amplifier for Primary Relay Module - 3.0 FFRT- used with C7015A
R7848B1006 Amplifier for Primary Relay Module - 3.0 FFRT - AmpIi-Check®
Primary Relay Modules—Semi-Automatic

RM7823A/EC7823A Primary Flame Switch


Microprocessor-based integrated flame switch for detecting a flame using rectification, ultraviolet (UV) or
infrared (IR) source.

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) high, 5 in.


(127 mm) wide, 5-1/4 in. (133 mm) deep with Q7800A
Subbase, 6-3/32 in. (155 mm) d e e p w i t h Q 7 8 0 0 B
Subbase.
WEIGHT: 1 lb., 13 oz. (0.8 kg).
TEMPERATURE RATINGS:
Ambient: –40°F to +140°F (–40°C to +60°C).
ELECTRICAL RATINGS:
Power Supply: EC7823—220/240 Vac (+10%/-15%), 50/60
● Can be fitted with any 7800 Series Amplifier to provide Hz (±10%); RM7823—120 Vac (+10%/-15%), 50/60 Hz
relay action from two single pole, double throw (spdt) (±10%).
relays when flame is present or not present. REQUIRED COMPONENTS:
● RM7823A is a flame detector relay only. Suitable primary Q7800A, B Universal Wiring Subbases.
control must be used to provide safe-start check, safety R7847, R7848, R7849, R7861, or R7886 Flame Signal
lockout, load switching and other functions required in Amplifiers.
flame safeguard systems. OPTIONAL COMPONENTS:
● Three LEDs to indicate power, flame and alarm. Communications (see Communications Section).
● Access for external electrical voltage checks. S7800 Keyboard Display Module.
● Nonvolatile memory. S7810 DATA CONTROLBUS MODULE™.
● Shutter drive output. S7820 Remote Reset Module.
● Compatible with existing Honeywell flame detectors. ACCESSORIES:
123514A Rectifying Flame Simulator.
APPROVALS: 203541 ControlBus 5-Wire Electrical Connector.
RM7823A— 203659 Ultraviolet Flame Simulator.
Underwriters Laboratories Inc. Listed: File No. MP268, 203765, 205321B, 204718A, B, C Remote Display
Guide No. MCCZ. Mounting Brackets.
Canadian Standards Association Certified: LR9S329-3. 203968A Remote Display Power Supply (13 Vdc) Plug-in.
Factory Mutual Approved: JIOX4A5.AF. 221729A Dust Cover.
Industrial Risk Insurers Acceptable. 221818A 60-inch Extension Cable Assembly.
Federal Communications Commission: Part 15, Class B— 221818C 120-inch Extension Cable Assembly.
Emissions. REPLACEMENT PART: 221729 Dust Cover.
EC7823A—
Factory Mutual Approved: Repent No. JI1V94A0.AF. Order
Industrial Risk Insurers Acceptable. Number Voltage Switching Replaces a
Federal Communications Commission: Part 15, Class B—
Emissions. RM7823A1016 120 Vac, Two spdt R7023B, C
50/60 Hz

EC7823A1004 220-240 Vac, Two spdt —


50/60 Hz
a
To replace R7023B, select R7847 Flame Signal Amplifier. To
replace 7023C, select R7849 Flame Signal Amplifier.
Primary Relay Modules—Semi-Automatic

RM7885A/EC7885A Semi-Automatic Primary Control


Microprocessor-based integrated burner control for industrial semi-automatically fired, gas, oil, coal, or
combination fuel single burner applications.

REQUIRED COMPONENTS:
Q7800A, B Universal Wiring Subbases.
R7847, R7848, R7849, R7861, or R7886 Flame Signal
Amplifiers.
OPTIONAL COMPONENTS:
Communications (see Communications Section).
S7800 Keyboard Display Module.
S7810 DATA CONTROLBUS MODULE™.
S7820 Remote Reset Module.
● Functions include flame supervision, system status S7830 First-out Expanded Annunciator.
indication, system or self-diagnostics and troubleshooting. ACCESSORIES:
● Adaptable to continuous firing, high-low or modulating 123514A Rectifying Flame Simulator.
firing rate for semi-automatic burner sequencing. 203541 ControlBus 5-Wire Electrical Connector.
● Operates with the following: 203659 Ultraviolet Flame Simulator.
◆ Torch-ignited main burner or torch-ignited pilot using 203765, 205321B, 204718A, B, C Remote Display
S445A Start-Stop Station, or conventional knee or foot Mounting Brackets.
operated station. 203968A Remote Display Power Supply (13 Vdc) Plug-in.
◆ Direct-ignition oil burner or electrically ignited pilot, 221729A Dust Cover.
using S445A Start-Stop Station. 221818A 60-inch Extension Cable Assembly.
● Five LEDs provide sequence information.
221818C 120-inch Extension Cable Assembly.
● Nonvolatile memory.
● Flame signal check during standby. TIMING SEQUENCE:
● Shutter drive output.
Model Number Initiate Standby Ignition Run
● Compatible with existing Honeywell flame detectors.
● Terminal provided for external alarm to sound on flame EC7885A; RM7885A 10 sec. a b a
failure. a
STANDBY and RUN can be an infinite time period.
b
APPROVALS: lGNITION is the time the Start switch is pushed and is limited
RM7885A— to 15 minutes.
Underwriters Laboratories Inc. Listed: File No. MP268,
Guide No. MCCZ. Order
Canadian Standards Association Certified: LR95329-3. Number Description Replacesa
Factory Mutual Approved: JIOX4A5.AF.
Industrial Risk Insurers Acceptable. EC7885A1011 Semi-automatic primary control. R485
Federal Communications Commission: Part 15, Class B—
Emissions. RM7885A1015 Semi-automatic primary control. R485
EC7885A— a
To replace R485, select R7847 Flame Signal Amplifier.
Factory Mutual Approved only.
DIMENSIONS, APPROXIMATE:
5 in. (127 mm) high, 5 in, (127 mm) wide, 3-1/2 in. (77
mm) deep.
WEIGHT: 1 lb., 13 oz. (0.8 kg).
TEMPERATURE RATINGS:
Ambient: –40°F to +140°F (–40°C to +60°C).
ELECTRICAL RATINGS:
Power Supply: EC7885A—220/240 Vac (+10%, –15%),
50/60 Hz (±10%); RM7885A—120 Vac (+10%, –15%),
50/60 Hz (±10%).
Primary Relay Modules—Semi-Automatic

RM7838A Semi-Automatic Industrial Primary Control

Microprocessor-based integrated DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.


burner control for industrial semi- (127 mm) high, 5-1/4 in. (133 mm) deep with Q7800A
automatically fired gas, oil, coal, Subbase, 6-3/32 in. (155 mm) deep with Q7800B
or combination fuel single burner Subbase,
applications. Provides level of WEIGHT: 1 lb., 10 oz. (0.7 kg).
safety, functional capability and TEMPERATURE RATINGS:
features beyond conventional Ambient: –40°F to +140°F (–40°C to +60°C).
controls. ELECTRICAL RATINGS:
Power Supply: 120 Vac (+10%/–15%), 50/60 Hz (±10%).
REQUIRED COMPONENTS:
Q7800A, B Universal Wiring Subbases.
● Functions include purge, burner pilot startup, flame R7847, R7848, R7849, R7861, or R7886 Flame Signal
supervision, system status indication, system or self- Amplifiers.
diagnosis and troubleshooting. ST7800 Plug-in Purge Timer Card.
● Delays admission of fuel to combustion chamber until pilot OPTIONAL COMPONENTS:
flame has been proven and then monitors the flame Communications (see Communications Section).
through the run period while providing system status S7800 Keyboard Display Module.
indication. S7810 DATA CONTROLBUS MODULE™.
● Includes Keyboard Display Module. S7820 Remote Reset Module.
● Five LEDs provide sequence information. S7830 First-out Expanded Annunciator.
● Intermittent pilot valve. ACCESSORIES:
● Interchangeable plug-in flame amplifier. 123514A Rectifying Flame Simulator.
● Access for external electrical voltage checks. 203541 ControlBus 5-Wire Electrical Connector.
● Nonvolatile memory retains history files and lockout status 203659 Ultraviolet Flame Simulator.
after loss of power. 203765, 205321B, 204718A, B, C Remote Display
● Selectable pilot flame establishing period. Mounting Brackets.
● Provides application flexibility and optional communication 203968A Remote Display Power Supply (13 Vdc) Plug-in.
interface capability. 221729A Dust Cover.
● Compatible with existing Honeywell flame detectors. 221818A 60-inch Extension Cable Assembly.
221818C 120-inch Extension Cable Assembly.
APPROVALS:
Underwriters Laboratories Inc. Listed: File No. MP268, TIMING SEQUENCE:
Guide No. MCCZ. Model Initiate Standby Purge Pilot Flame Run
Canadian Standards Association Certified: LR95329-3. Number Establishing
Factory Mutual Approved: Report No. JI1V9A0.AF. Period (PFEP)
Industrial Risk Insurers Acceptable.
Federal Communications Commission: Part 15, Class B— RM7838A 10 sec. a b 4 or 10 sec. a
Emissions. a
STANDBY and RUN can be an infinite time period.
Control safety Devices Acceptable: CSD-1. b
PURGE will be determined by ST7800A Plug-in Purge Timer
Card.

Order
Number Description Replaces

RM7838A1014 Semi-automatic industrial primary R4138A, C


relay module with display.
Primary Relay Modules—Semi-Automatic

RM7838B Semi-Automatic Programmer

Microprocessor-based integrated DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.


burner control with pilot hold (127 mm) high, 5-1/4 in. (133 mm) deep with Q7800A
function for industrial semi- Subbase; 6-3/32 in. (155 mm) deep with Q7800B
automatically fired gas, oil, coal, Subbase.
or combination fuel single burner
applications. Provides level of WEIGHT: 1 lb., 10 oz. (0.7 kg).
safety, functional capability and
features beyond conventional TEMPERATURE RATINGS:
controls. Ambient: –40°F to +140°F (–40°C to +60°C).

ELECTRICAL RATINGS:
● Functions include automatic modulated high fire and low Power Supply: 120 Vac (+10%, –15%), 50/60 Hz (±10%).
fire proven purge, burner pilot start up with pilot valve hold,
special pilot valve hold from the Run condition, flame REQUIRED COMPONENTS:
supervision, system status indication, system or self- Q7800A, B Universal Wiring Subbases.
diagnostics and troubleshooting. R7847C, R7861, or R7886 Flame Amplifiers.
● Access for external electrical voltage checks. ST7800 Plug-in Purge Timer Card.
● Application flexibility and communication interface
capability. OPTIONAL COMPONENTS:
● Five LEDs provide sequence information. Communications (see Communications Section).
● Five function Run/Test Switch. S7810 DATA CONTROLBUS MODULE™.
● Interchangeable plug-in flame amplifiers. S7820 Remote Reset Module.
● Local or remote annunciation of operation and fault S7830 First-out Expanded Annunciator.
information.
● Nonvolatile memory retains history files and lockout status ACCESSORIES:
after loss of power. 123514A Rectifying Flame Simulator.
● Compatible with existing Honeywell flame detectors. 203541 ControlBus 5-Wire Electrical Connector.
● Includes Keyboard Display Module. 203659 Ultraviolet Flame Simulator.
● Use with R7847C or R7886A Plug-in Flame Signal 203765, 205321 B, 204718A, B, C Remote Display
Amplifiers. Mounting Brackets.
203968A Remote Display Power Supply (13 Vdc) Plug-in.
APPROVALS: 221729A Dust Cover.
Underwriters Laboratories Inc. Listed: File No. MP268, 221818A 60-inch Extension Cable Assembly.
Guide No. MCCZ. 221818C 120-inch Extension Cable Assembly.
Canadian Standards Association Certified: LR95329-3.
Factory Mutual Approved: Report No. Jl1V9AO.AF.
Industrial Risks Insurers Acceptable.
Federal Communications Commission: Part 15, Class B—
Emissions.
Control Safety Devices Acceptable: CSD-1.

SEQUENCE TIMING FOR NORMAL OPERATION:


Device Initiate Standby Purge Pilot Flame Establishing Main Flame Establishing Run
Period (PFEP) Period (MFEP)
RM7838B 10 sec. a b 4 sec. or 10 sec. 10 sec.c a
a
STANDBY and RUN can be an infinite time period.
b
PURGE will be determined by which ST7800A Plug-in Purge Timer Card is selected.
b
lmmediate or deferred main flame.

Order Number Description

RM7838B1013 Enhanced semi-automatic industrial primary relay module with display; 50/60 Hz.
Programmers

RM7840 Programmer

Microprocessor-based integrated DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.


burner control for automatically (127 mm) high, 5-1/4 in. (133 mm) deep with Q7800A
fired gas, oil, coal, or combination Subbase; 6-3/32 in. (155 mm) deep with Q7800B
fuel single burner applications. Subbase.
Provides safety, functional WEIGHT: 1 lb., 13 oz. (0.8 kg).
capability and features beyond
conventional controls. TEMPERATURE RATINGS:
Ambient: –40°F to +140°F (–40°C to +60°C).
ELECTRICAL RATINGS:
● Functions include automatic burner sequencing, flame
Power Supply: 120 Vac (+10%/–15%), 50/60 Hz (±10%).
supervision, system status indication, system or self-
diagnostics and troubleshooting. REQUIRED COMPONENTS:
● Access for external electrical voltage checks. Q7800A, B Universal Wiring Subbases.
● Application flexibility and communication interface R7847, R7848, R7849, R7861, or R7886 Flame Signal
capability. Amplifiers.
● Five LEDs provide sequence information. ST7800 Plug-in Purge Timer Cards.
● Five function Run/Test Switch.
● Interchangeable plug-in flame amplifiers. OPTIONAL COMPONENTS:
● Local or remote annunciation of RM7840 operation and Communications (see Communications Section).
fault information. S7800 Keyboard Display Module.
● Nonvolatile memory retains history files and lockout status S7810 DATA CONTROLBUS MODULE™.
after loss of power. S7820 Remote Reset Module.
● Compatible with existing Honeywell flame detectors. S7830 First-out Expanded Annunciator.
ACCESSORIES:
APPROVALS: 123514A Rectifying Flame Simulator.
Underwriters Laboratories Inc. Listed: File No. MP268,
203541 ControlBus 5-Wire Electrical Connector.
Guide No. MCCZ. 203659 Ultraviolet Flame Simulator.
Canadian Standards Association Certified: LR95329-3.
203765, 205321B, 204718A, B, C Remote Display
Factory Mutual Approved: Report No. JI1V9AO.AF.
Mounting Brackets.
Industrial Risks Insurers Acceptable.
203968A Remote Display Power Supply (13 Vdc) Plug-in.
Federal Communications Commission: Part 15, Class B—
221729A Dust Cover.
Emissions. 221818A 60-inch Extension Cable Assembly.
Control Safety Devices Acceptable: CSD-1. 221818C 120-inch Extension Cable Assembly.

TIMING SEQUENCE:
Model Initiate Standby Purge Pilot Flame Establishing Main Flame Establishing Run Postpurge
Number Period (PFEP) Period (MFEP)d
RM7840E a 10 sec. b c 4 or 10 sec. 10 or 15 sec. b 15 sec.
RM7840G 10 sec. b c 4 or 10 sec. 10, 15, or Intermittent b 15 sec.
RM7840L 10 sec. b c 4 or 10 sec. 10, 15, or Intermittent b 15 sec.
RM7840M 10 sec. b c 4 or 10 sec. 10 sec. or Intermittent b 15 sec.
a
Energy Saving Prepurge.
b
STANDBY and RUN can be an infinite time period.
c
PURGE is determined by ST7800 Plug-in Purge Timer Card selected.
d
The MFEP will be determined by terminal used, configuration jumper, or jumper wire addition. See instruction sheet.

Order Number Description Replaces


a
RM7840E1016 Relay module with ESP ; without display; 50/60 Hz
RM7840G1006 Relay module without display; 50 Hz R4140G
RM7840G1014 Relay module without display; 60 Hz R4140G
RM7840L1018 Relay module without display; 50/60 Hz R4140L

RM7840L1026 Relay module without display; Intermittent pilot; 50/60 Hz R4140L


RM7840M1009 Relay module without display; 50 Hz R4140M
RM7840M1017 Relay module without display; 60 Hz R4140M
a
ESP—Energy Saving Prepurge.
Programmers

RM7800E, G, L, M Programmers

Microprocessor-based inte- DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.


grated burner control for auto- (127 mm) high, 5-1/4 in. (133 mm) deep with Q7800A
matically fired gas, oil, coal, or Subbase; 6-3/32 in. (155 mm) d e e p w i t h Q 7 8 0 0 B
combination fuel single burner Subbase.
applications. Provides safety,
WEIGHT: 1 lb., 10 oz. (0.7 kg).
functional capability and
features beyond conventional TEMPERATURE RATINGS:
controls. Ambient: –40°F to +140°F (–40°C to +60°C).
ELECTRICAL RATINGS:
● Functions include automatic burner sequencing, flame Power Supply: 120 Vac (+10%/–15%), 50/60 Hz (±10%).
supervision, system status indication, system or self- REQUIRED COMPONENTS:
diagnostics and troubleshooting. Q7800A, B Universal Wiring Subbases.
● Access for external electrical voltage checks. R7847, R7848, R7849, R7861, or R7886 Flame Signal
● Application flexibility and communication interface Amplifiers.
capability. ST7800 Plug-in Purge Timer Card.
● Five LEDs provide sequence information.
● Five function Run/Test Switch. OPTIONAL COMPONENTS:
● Interchangeable plug-in flame amplifiers. Communications (see Communications Section).
● Local or remote annunciation of operation and fault infor- S7810 DATA CONTROLBUS MODULE™.
mation (optional). S7820 Remote Reset Module.
● Nonvolatile memory retains history files and lockout status S7830 First-out Expanded Annunciator.
after loss of power.
ACCESSORIES:
● Compatible with existing Honeywell flame detectors.
123514A Rectifying Flame Simulator.
● Includes Keyboard Display Module.
203541 ControlBus 5-Wire Electrical Connector.
203659 Ultraviolet Flame Simulator.
APPROVALS:
203765, 205321B, 204718A, B, C Remote Display
Underwriters Laboratories Inc. Listed: File No. MP268,
Mounting Brackets.
Guide No. MCCZ.
203968A Remote Display Power Supply (13 Vdc) Plug-in.
Canadian Standards Association Certified: LR95329-3.
221729A Dust Cover.
Factory Mutual Approved: Report No. JI1V9AO.AF.
221818A 60-inch Extension Cable Assembly.
Industrial Risks Insurers Acceptable.
221818C 120-inch Extension Cable Assembly.
Federal Communications Commission: Part 15, Class B—
Emissions.

TIMING SEQUENCE:
Model initiate Standby Purge Pilot Flame Establishing Main Flame Establishing Run Postpurge
Number Period (PFEP) Period (MFEP)d

RM7800E a 10 sec. b c 4 or 10 sec. 10 or 15 sec. b 15 sec.


RM7800G 10 sec. b c 4 or 10 sec. 10, 15, or Intermittent b 15.sec.
RM7800L 10 sec. b c 4 or 10 sec. 10, 15, or Intermittent b 15.sec.
RM7800M 10 sec. b c 4 or 10 sec. 10 sec. or Intermittent b 15 sec.
a
Energy Saving Prepurge.
b
STANDBY and RUN can be an infinite time period.
c
PURGE will be determined by which ST7800A Plug-in Purge Timer Card is selected.
d
The MFEP will be determined by terminal used, cinfiguration jumper, or wire addition. See instruction sheet.

Order Number Description Replaces


RM7800E1010 Automatic programming control with ESPa and display; 50/60 Hz BC7000L; PM720L
RM7800G1000 Automatic programming control with display; 50 Hz BC7000L; PM720G
RM7800G1018 Automatic programming control with display; 60 Hz BC7000L; PM720G
RM7800L1012 Automatic programming control with display; 50/60 Hz BC7000L; PM720L
RM7800L1053 Automatic programming control with display, intermittent pilot; 50/60 Hz BC7000L; PM720L
RM7800M1003 Automatic programming control with display; 50 Hz BC7000L; PM720M
RM7800M1011 Automatic programming control with display; 60 Hz BC7000L; PM720M
a
ESP—Energy Saving Prepurge.
Integrated Burner Control

NEW!
EC7810, EC7820 Integrated Burner Control

Microprocessor-based integrated ELECTRICAL RATINGS:


burner control for automatically Power Supply: 220-240 Vac (+10%/–15%), 50/60 Hz
fired gas, oil, coal, or combination (±10%).
fuel single burner atmospheric Power Dissipation: 10W maximum.
(EC7810A) or atmospheric with Connected Load: 2000 VA maximum total.
fan (EC7820A) applications. Pro- Fusing: 20A maximum type FRN or equivalent.
vides automatic burner sequenc- DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.
ing, flame supervision, system (127 mm) high, 5-1/4 in. (133 mm) deep with Q7800A
status indication, system or self- Subbase; 6-3/32 in. (155 mm) deep with Q7800B
diagnostics, and troubleshooting. Subbase.
WEIGHT: 1 lb., 10 oz. (0.7 kg).
● Access for external electrical voltage checks. TEMPERATURE RATINGS:
● Application flexibility and communication interface Operating: –40°F to +140°F (–40°C to +60°C).
capability. Shipping: –40°F to +150°F (–40°C to +66°C).
● Four LEDs provide sequence information.
● Five function Run/Test Switch. HUMIDITY RATINGS: 85% RH continuous, noncondensing.
● Interchangeable plug-in amplifiers.
● Local or remote annunciation of operation and fault infor- VIBRATION: 0.5G environment
mation (optional). REQUIRED COMPONENTS:
● Nonvolatile memory retains history files and lockout status Q7800A, B 22-Terminal Wiring Subbase.
after loss of power. R7824, R7847, R7848, R7849, R7861, or R7886 Flame
● Compatible with existing Honeywell flame detectors. Amplifier.
APPROVALS: ST7800A Plug-in Purge Timer.
Underwriters Laboratories Inc. Listed: File No. MP268, OPTIONAL COMPONENTS:
Guide No. MCCZ. Personal Computer Interface.
Canadian Standards Association Certified: LR95329-3. S7800A Keyboard Display Module (KDM).
Factory Mutual Approved: Report No. JI1V9A0.AF. S7810A Data ControlBus Module™.
IRI: Acceptable. S7820 Remote Reset Module.
FCC: Federal Communications Commission: Part 15, ZM7850A Combustion System Manager™.
Class B—Emissions. 221818A 60-inch Extension Cable Assembly.
221818C 120-inch Extension Cable Assembly.
221729C Dust Cover.
204718C NEMA 4 Cover Assembly with Reset for S7800A.

SEQUENCE TIMING FOR NORMAL OPERATION:


Model Initiate Standby Purge Pilot Flame Main Flame Run Postpurge
Number Establishing Period Establishing Period
(PFEP) (MFEP) a

EC7810A1022 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.

EC7810A1035 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.

EC7820A1026 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.

EC7820A1034 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.


a
The MFEP will be determined by terminals used, configuration jumper, or jumper wire addition. See instruction sheet.
b
STANDBY and RUN can be an infinite time period.
c
PURGE will be determined by which ST7800A Purge Timer Card is selected.

Order Number Description Comments

EC7810A1022 Automatic Primary Relay Module for single atmospheric burner, 220-240, 50/60 Hz 1 ignition attempt

EC7810A1035 Automatic Primary Relay Module for single atmospheric burner, 220-240, 50/60 Hz 5 ignition attempts

EC7820A1026 Automatic Primary Relay Module for single atmospheric burner with fan, 220-240, 50/60 Hz 1 ignition attempt

EC7820A1034 Automatic Primary Relay Module for single atmospheric burner with fan, 220-240, 50/60 Hz 5 ignition attempts
Integrated Burner Control

NEW!
EC7830, RM7830, EC7850, RM7850 Integrated Burner Control
Microprocessor-based integrated ELECTRICAL RATINGS:
burner control for automatically Power Supply: RM7830A and RM7850A—120 Vac
fired gas, oil, coal, or combination (+10/–15%), 50/60 Hz (±10%); EC7830A and
fuel single burner full modulation EC7850A—220-240 Vac (+10/–15%), 50/60 Hz (±10%).
(EC/RM7830A) or on/off (EC/ Power Dissipation: 10W maximum.
RM7850A) applications. Provides Connected Load: 2000 VA maximum total.
automatic burner sequencing, Fusing: 20A maximum type FRN or equivalent.
flame supervision, system status DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.
indication, system or self- (127 mm) high, 5-1/4 in. (133 mm) deep with Q7800A
diagnostics, and troubleshooting. Subbase; 6-3/32 in. (155 mm) deep with Q7800B
Subbase.

● Access for external electrical voltage checks. WEIGHT: 1 lb., 10 oz. (0.7 kg).
● Application flexibility and communication interface TEMPERATURE RATINGS:
capability. Operating: –40°F to +140°F (–40°C to +60°C).
● Five LEDs provide sequence information. Shipping: –40°F to +150°F (–40°C to +66°C).
● Five function Run/Test Switch.
● interchangeable plug-in amplifiers. HUMIDITY RATINGS: 85% RH continuous, noncondensing.
● Local or remote annunciation of operation and fault infor-
mation (optional). VIBRATION: 0.5G environment
● Nonvolatile memory retains history files and lockout status REQUIRED COMPONENTS:
after loss of power. Q7800A, B 22-Terminal Wiring Subbase.
● Compatible with existing Honeywell flame detectors. R7824, R7847, R7848, R7849, R7861, or R7886 Flame
APPROVALS: Amplifier.
RM7830A and RM7850A— ST7800A Plug-in Purge Timer.
Underwriters Laboratories Inc. Listed: File No. MP268, OPTIONAL COMPONENTS:
Guide No. MCCZ. Q7700 Network Interface Unit.
Canadian Standards Association Certified: LR95329-3. S7800A Keyboard Display Module (KDM).
Factory Mutual Approved: Report No. JI1V9A0.AF. S7810A Data ControlBus Module™.
Industrial Risk Insurers Acceptable. S7820 Remote Reset Module.
FCC: Federal Communications Commission: Part 15, ZM7850A Combustion System Manager™.
Class B—Emissions. 221818A 60-inch Extension Cable Assembly.
EC7830A and EC7850A— 221818C 120-inch Extension Cable Assembly.
Factory Mutual Approved. 221729C Dust Cover.
204718A NEMA 4 Cover Assembly for S7800A.
204718C NEMA 4 Cover Assembly with Reset for S7800A.

SEQUENCE TIMING FOR NORMAL OPERATION:


Model Initiate Standby Purge Pilot Flame Main Flame Run Postpurge
Number Establishing Period Establishing Period
(PFEP) (MFEP) a
EC7830A1033 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 2 sec.
EC7830A1041 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 30 sec.
EC7830A1066 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 15 sec.
RM7830A1003 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 2 sec.
RM7830A1011 3 or 5 sec. b c 3 sec. 4 or7 sec. b 30 sec.
RM7830A1029 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 15 sec.
EC7850A1064 2 sec. b c 3 sec. 6 or 7 sec. b d
EC7850A1072 2 sec. b c 3 sec. 6 or 7 sec. b 2 sec.
EC7850A1080 2 sec. b c 3 sec. 6 or 7 sec. b 30 sec.
EC7850A1122 2 sec. b c 3 sec. 6 or 7 sec. b 15 sec.
RM7850A1001 2 sec. b c 3 sec. 6 or 7 sec. b 2 sec.
RM7850A1019 2 sec. b c 3 sec. 6 or 7 sec. b 15 sec.
RM7850A1027 2 sec. b c 3 sec. 6 or 7 sec. b 30 sec.
a
The MFEP will be determined by terminals used, configuration jumper, or jumper wire addition. See instruction sheet.
b
STANDBY and RUN can be an infinite time period.
C
PURGE will be determined by which ST7800A Purge Timer Card is selected.
d
Dynamic damper check.
7800 SERIES Required Components

Q7800A,B 22-Terminal Universal Wiring Subbases


Universal burner, panel or wall mount subbases for RM78xx and EC78xx SERIES relay modules and
S7830A Expanded- Annunciator.

APPROVAL BODIES:
Underwriters Laboratories Inc. component recognized
(Q7800A).
Underwriters Laboratories Inc. listed (Q7800B).
Canadian Standards Association certified.

DIMENSIONS:
Q7800A: 4-31/32 in. [126 mm] wide, 4-31/32 in. [126 mm] high,
1-13/32 in. [36 mm] deep.
Q7800B: 4-31/32 in. [126 mm] wide, 4-31/32 in. [126 mm] high,
● Makes electrical connections for 7800 SERIES relay mod- 2-7/32 in. [56 mm] deep.
ules or S7830A Expanded Annunciator through bifurcated REPLACEMENT PART: 221779 Electrical Access Slot Covers.
contacts.
Order
● Provides terminals for field wiring.
Number Description
● Q7800B has knockouts provided in back, top and bottom for Q7800A1005 Universal wiring subbase, panel mounting.
conduit connections.
● Twenty-two terminals. Q7800B1003 Universal wiring subbase, burner/wall mounting.

Q7800B1011 Universal wiring subbase, burner/wall mounting.

R7847, R7848, R7849, R7861, R7886 Flame Signal Amplifiers


Solid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flame
when used with RM78xx and EC78XX SERIES relay modules.
R7847C Dynamic Self-Check Rectification Amplifier,
R7861A Dynamic Self-Check Ultraviolet Amplifier, and
R7886A Dynamic Self-Check Ultraviolet Amplifier test
electronic components in the flame detection system
10 to 12 times per minute; 7800 SERIES relay module
locks out on safety shutdown with flame detection
system failure.
APPROVAL BODIES:
Flame failure response time of 0.8 or 3 seconds. Underwriters Laboratories Inc. listed.
Canadian Standards Association certified.
Flame signal strength ranges from 0.0 to 5.0 Vdc. Factory Mutual approved.
Plug-in to 7800 relay module through printed circuit board Industrial Risks Insurers acceptable.
edge card connector keyed for proper orientation.
DIMENSIONS: 3-9/16 in. [91 mm] wide, 3-3/8 in. [85 mm] high,
Flame signal test jacks to measure amplifier flame signal 7/8 in. [23 mm] deep.
voltage. WEIGHT: 2.5 oz.
R7847B, R7848B, R7849B Dynamic AMPLI-CHECK™ cir- OPERATING AMBlENT TEMPERATURE RANGE: – 40 F to
cuitry tests flame amplifier during burner operation; 7800 +140 F [–40 C to + 60 C].
SERIES relay module locks out on safety shutdown with OPTIONAL COMPONENTS:
amplifier failure. 123514A Rectification Flame Simulator.
203659 Ultraviolet Flame Simulator.
7800 SERIES Required Components
R7847, R7846, R7649, R7886 continued
FLAME DETECTION SYSTEMS
Plug-in Flame Signal Amplifiers Applicable Flame Detectors
Order Self- Flame Failure
Number Type Color Checking Response Time Fuel Type Models
R7824C1002 Rectifi- Green Dynamic 3.0 sec. Gas, oil, Ultraviolet (Purple C7024E, F.
cation SELF CHECK coal Peeper)
R7847A1025 No 1.0 sec. or Gas Rectifying Flame Rod C7004, C7007, C7011d,
R7847A1074f 0.8 sec.g Holder Complete assemblies:
C7008, C7009, Q179.
R7847A1033 2.0 sec. or Gas, oil, Ultraviolet (Purple C7012A, C.
R7847A1082f 3.0 sec.g coal Peeper)

R7847B1023c Dynamic 1.0 sec. or Gas Rectifying Flame Rod C7004, C7007, C7011d,
AMPLI- 0.8 sec.g Holder Complete assemblies:
R7847B1064f
CHECK™ C7008, C7009, Q179.
R7847B1031c 2.0 sec. or Oil Rectifying Flame Rod C7004, C7007, C7011d,
R7847B1072f 3.0 sec.g Holder, Photocelle, Complete assemblies:
or Ultraviolet (Purple C7008, C7009, Q179,
Peeper) C7003, C7010, C7013,
C7014, C7012A, C.
R7847C1005b Dynamic Gas, oil, Ultraviolet (Purple C7012E, F.
SELF CHECK coal Peeper)
R7848A1008 Infrared Red No Infrared (Lead C7015.
Sulfide)
R7848B1006 Dynamic C7015.
AMPLI-
CHECK™
R7849A1015 Ultra-- Purple No 1.0 sec. or Gas, oil Ultraviolet C7027, C7035, C7044a
violet 0.8 sec.g (Minipeeper)
R7849A1023 2.0 sec. or
3.0 sec.g
R7849B1013 Dynamic 1.0 sec. or
AMPLI- 0.8 sec.g
CHECK™
R7849B1021 2.0 sec. or
R7861A1026 Dynamic 3.0 sec.g C7061.
SELF CHECK
R7861A1034 0.8 sec. or
1.0 sec.g
R7886A1001 Blue 2.0 sec. or Gas, oil, Ultraviolet (Adjustable C7076A, D.
3.0 sec.g coal Sensitivity)
aR7849A and C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once every
twenty-four hours. Appliances with burners that remain on for twenty-four hours continuously or longer should use C7061A Flame
Detector with R7861A Amplifier.
bCircuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner
operation and shuts down burner if detection system fails.
cCircuitry tests flame signal amplifier at least 12 times a minute during burner operation and shuts down burner if amplifier fails.
dSee instructions for holder.
eUse only Honeywell Photocell, part number 38316.
fFor use with C7012A, C parallel detectors, or flame rod applications with leadwire lengths greater than 50 feet.
gThe 7800 Series amplifiers have been modified as of 1/15/98 to provide 0.8 sec/1.0 sec, or 2.0 sec/3.0 sec.

FLAME FAILURE RESPONSE TIME ON RM or EC78XX DEVICES


Relay Module Flame Failure Response Time (FFRT)
0.8 or 1.0 sec 2.0 or 3.0 sec
EC/RM7810, 7820, 7830, 7850 1.0 2.0
EC/RM7823, 7885, 7890, 7895, 7896, 0.8 3.0
7888, 7838, 7800, 7840
RM7824 NA 3.0
7800 SERIES Required Components

ST7800A Plug-In Purge Timer Card


Provides prepurge timing for select RM78xx and EC78xx SERIES relay modules.

Order Number Prepurge Timing Used With


ST7800A1005 2 seconds RM7800, RM7838, RM7840, RM7888, RM7895,
ST7800A1013 7 seconds EC7800, EC7810, EC7820, EC7830, EC7840, EC7850, EC7888,
ST7800A1021 10 seconds EC7895 Relay Modules.
ST7800A1039 30 seconds
ST7800A1047 40 seconds
ST7800A1054 60 seconds
ST7800A1062 90 seconds
ST7800A1070 2.5 minutes
ST7800A1088 4.0 minutes
ST7800A1096 6.0 minutes
ST7800A1104 9.0 minutes
ST7800A1112 12.0 minutes
ST7800A1120 15.0 minutes
ST7800A1138 22.0 minutes
ST7800A1146 30.0 minutes

S7810A DATA CONTROLBUS MODULE™


Supports remote mounting of S7800 Keyboard Display Module, personal computer communications
interface and remote reset.
OPERATING AMBIENTTEMPERATURE RANGE: –40 F to
+140 F [–40 C to +60 C].
ELECTRICAL RATINGS: 13 Vdc peak full-wave rectified
(+20/–15%).
OPTIONAL COMPONENTS: 203968A Remote Display Power
Supply, plug-in.
REPLACEMENT PART:
203541 ControlBus 5-Wire Electrical Connector.
● Use with remotely mounted S7800 Keyboard Display
Module. Order
Number Description Used With
● Installs directly on the front of 7800 SERIES relay modules.
S7810A1009 Remote mounting of 7800 SERIES Relay
● Provides communications bus interface and remote reset.
keyboard display mod- Modules.
ule, personal computer
DIMENSIONS: 4-27/32 in. [123 mm] wide, 2-29/32 in. communications inter-
[73 mm] high, 29/32 in. [23 mm] deep. face and remote reset.
WEIGHT: 4 oz.
7800 SERIES Optional Components
S7800A Keyboard Display Module
Provides current status of burner sequence, timing information, hold information and lockout in-
formation, as well as selectable or preemptive messages.
Canadian Standards Association certified.
Factory Mutual approved.
Industrial Risks Insurers acceptable.
Federal Communications Commission, Part 15, Class B.

DIMENSIONS: 4-27/32 in. [123 mm] wide, 2-29/32 in.


[73 mm] high, 29/32 [23 mm] deep.
WEIGHT: 4 OZ.
Application flexibility. OPERATING AMBlENT TEMPERATURE RANGE: –40 F to
+140 F [–40 C to +60 C].
Communication interface capability. ELECTRICAL RATINGS:
Dependable long-term operations provided by microcompu- Voltage and Frequency 13 Vdc peak fullwave rectified
ter technology. (+20/–15%)

First out annunciation and system diagnostics provided by 2 OPTIONAL COMPONENTS:


row by 20 column Vacuum Fluorescent Display (VFD). S7810A1009 DATA CONTROLBUS MODULE.
203541 ControlBus 5-Wire Electrical Connector.
Local or remote annunciation of operation and fault
203765 Remote Display Mounting Bracket.
information.
203968A Remote Display Power Supply (plug-in).
Optional first out expanded annunciation with 24 limit and 203969A Remote Display Power Supply (screw terminal).
interlock LEDs enhances keyboard display module infor- 221818A Extension Cable Assembly to remote mount
mation. keyboard display module. 60 inch cable.
Provides burner controller data. 221818C Extension Cable Assembly.
120 inch cable.
Remote reset.
Report generation. Order Number Description Used With
S7800A1001 English Language RM7800, RM7823, RM7824,
APPROVAL BODIES: Keyboard RM7838, RM7840, RM7885,
Underwriters Laboratories Inc. listed. Display RM7888, RM7890, RM7895
Module Relay Modules
EC7810, EC7820, EC7823,
EC7830, EC7850

S7800A1035 French Language


Keyboard
Display
Module
S7800A1043 German Language
Keyboard
Display
Module
S7800A1050 Italian Language
Keyboard
Display
Module
S7800A1068 Spanish Language
Keyboard
Display
Module

S7800A1118 Katakana
(Japanese)
Language
Keyboard
Display
Module

S7800A1126 Portuguese
Language
Keyboard
Display
Module
S7800B1009 Chinese Language
Keyboard
Display
Module - Remotely
Mounted
7800 SERIES Optional Components

S7820A Remote Reset Module


Serves as link between remote reset pushbutton and relay module. Allows RM78xx and EC78xx
SERIES relay modules to be reset from a remote location.
DIMENSIONS: 4-27/32 in. [123 mm] wide, 2-29/32 in.
[73 mm] high, 29/32 in. [23 mm] deep.
WEIGHT 3 oz.
OPERATING AMBlENT TEMPERATURE RANGE: –40 F to
+140 F [–40 C to +60 C].
REPLACEMENT PART: 203541 ControlBus 5-Wire Electrical
Connector.

● Allows resetting of 7800 SERIES relay module by a remote Order


reset pushbutton up to 1000 feet away. Number Description Used With
● Installs directly on the front of 7800 SERIES relay module. S7820A1007 Remote reset module 7800 SERIES relay modules
to reset 7800 SERIES
relay module.

S7830A First-Out Expanded Annunciator


Microprocessor-based expanded annunciator to support the RM78xx and EC78XX SERIES relay
modules for first-out annunciation, sequencing, system or self-diagnostics and troubleshooting.
● On/Off status of limits and interlocks.
● RS485 connection to 7800 SERIES relay module.
● Used with Q7800A,B subbases; 7800 SERIES relay
modules.

APPROVAL BODIES:
Underwriters Laboratories Inc. listed.
Canadian Standards Association certified.
Twenty-six Light Emitting Diodes (LEDs).
Order Electrical
Twenty-two LEDs to annunciate Limits and Interlocks. Number Dimensions Weight Input
Four LEDs to annunciate Power, Current Status, First-out S7830A1005 5 in. [127 mm] wide, 1 lb., 13 oz. 120 Vac,
Status and System Lockout. 5 in. [127 mm] high, [829 g]. 50/60 Hz
3-1/32 in. [77 mm]
Enhances S7800A Keyboard Display Module sequence deep.
hold and lockout messages.
Q7700A, B Network Interface Unit

FEATURES
● Connect up to six BCS 7700 controls, Armstrong
TrapScan TM systems, Pulsafeeder PULSAtrolTM
systems. up to 900 QM40XX Data Acquisition Modules,
and up to 222 multi-dropped 7800 SERIES devices or
combinations of the systems.
● Local and remote annunciation of BCS 7700,7800
SERIES safety shutdowns and Armstrong TrapScan TM,
Pulsafeeder PULSAtrolTM and QM40XX Data
Acquisition Alarms.
● Autodial-out on BCS 7700,7800 SERIES, Armstrong
TrapScan lM, Pulsafeeder PULSAtrolTM, and QM40XX
Data Acquisition Alarms for up to three telephone
numbers.
● Personal computer user-friendly, menu driven,
Microsoft® Windows™ software-based user interface.
● On-line data logging.
● Modular construction.
● Access controlled with password protection.
● Light Emitting Diode (LED) status interface.
● 19,200 selectable baud personal computer/printer
inteface.
● 19,200 selectable baud modem interface. Interfaces
with Hayes-compatible modems.
Q7700B ● Fault-dating and time -stamping internal software
clock.
● Dial-out override for maintenance-induced alarms.
● Dedicated RS-232 external modem port.
● Universal power supply (Q7700B only).

APPLICATION ● SYSNet TM compatible.

The Q7700A,B Network Interface Unit provides local and


remote monitoring and diagnostics of the BCS 7700, 7800
SERIES, Armstrong TrapScanTM, Pulsafeeder PULSAtrolTM
and QM40XX Data Acquisition devices with an lBM®
equivalent personal computer. The Q7700 also provides local
and remote configuration and control of BCS 7700,
Pulsafeeder PULSAtrol™, or QM40XX Data Acquisition
devices.
APPROVAL BODIES: ACCESSORIES:
Underwriters Laboratories Inc. component recognized. QM4520A: RS-232C to RS-485 Converter.
Canadian Standards Association certified. QS7800B: ControlBus™ Module for multi-drop 7800
Factory Mutual approved. Series.
Industrial Risk Insurers acceptable. QS7800C: ControlBus™ Module for QM40XX Data
Federal Communications Commission: Part 15, Class A - Acquisition modules.
Emissions. QS7800D: ControlBus™ Module for Armstrong Trap
Canadian Department of Communications certified. Scan™.
QS7800E: ControlBus™ Module for Pulsafeeder
OPERATING AMBlENT TEMPERATURE RANGE: 32 F to PULSAtrol™.
130 F [0 C to 54 C]. ZM7850A: Combustion System Manager® Software for
HUMIDITY: 85% relative humidity continuous, noncondensing. personal computer.
ZM7850B: SYSNet™ Operator Interface Software for
COMPONENTS: personal computer.
221237 Cover Assembly, Baser Unit. 200603: ControlBus™ Module Electrical Connector.
221240 Cover Assembly, Electrical Enclosure. 202433: Slot Inserts, ControlBusTM Slots.
202433 Slot Inserts, ControlBus Slots. 221237/1698: Cover Assembly, Base Unit.
200603 ControlBus Module 3-Wire Electrical Connector. 221240/1698: Cover Assembly, Electrical Enclosure.
203541 ControlBus Module 5-Wire Electrical Connector. Null Modem Adaptor (obtain locally).
QS7700A Communications Interface ControlBus Module 209164: Power Supply, panel mounting, 85 to 132 Vac
(BCS7700). or 170 to 264 Vac input voltage, switchable; 1.4A
QS7800A Communications Interface ControlBus Module maximum input current; 24 Vdc (±10%) output
(7800 SERIES). voltage; 3A maximum output current.
QS7850A General Purpose Interface ControlBus Module. 209162 Power Supply, DIN-Rail mounting, 110 Vac
input voltage; 225mA input current; 24 Vdc (±1%)
output voltage; 1A output current.
209163 Power Supply, DIN-Rail mounting, 220 Vac
input voltage; 225mA input current; 24 Vdc (±1%)
output voltage; 1A output current.
208670; IEC 120V power cord for universal power
supply (obtain other plug configuration locally).
208289: Universal Power Supply, 100 to 250 Vac,
50/60 Hz.

Order Electrical Electrical Signal Direct Terminal


Number Dimensions Weight Ratings Connectors Characteristics Hookup
Q7700A1014 9 in. [229 mm] wide, 4 Ibs., Voltage and Frequency: RS232C Port 25 Selectable baud RS232C Connection,
8 in. [203 mm] high, 10 oz. 120 Vac (+10/-15%),60 “D” pin connector; rate up to 19,200 PINS. 1 Ground:
4-7/8 in. [123 mm] Hz (±10%) ControlBus Local Protective.
deep. Communication: RS485 communications. 2 Transmit Data (TD).
Remote 3 Receive Data (RD).
5 lbs., 100-250 Vac, 50/60 Hz communications 7 Ground: Signal.
Q77C0B1004 requires an external
13 oz. Power Supply (part
number 208289 included) modem.
SPECIFICATIONS
Models:
Q7700A,B Network Interface Unit:
Q7700A1014 Network Interface Unit, 120 Vac only.
Q7700B1004 Network Interface Unit with Universal 100 to
250 Vac power supply.

NOTE: 208670 Power Cord provided with 208289 Universal


100 to 250 Vac Power Supply is equipped with a
standard U.S. 120 Vac plug. Adapter plugs for other
power systems, if needed, can be obtained locally.

Electrical Ratings:
Voltage and Frequency:
Q7700A: 120 Vac (+10%/-15%), 50/60 Hz.
Q7700B: 100 to 250 Vac, 50/60 Hz.

Universal Power Supply (Q7700B only):


Rated Voltage: 100 to 250 Vac, 50/60 Hz.
Rated Input: 0.7A to 0.3A.
Secondary Voltages: +5V, +12V, -12V.
Secondary Current: 4.0A, 1.0A, 0.6A maximum.

Electrical Connectors:
RS-232C port, 25 D pin connector for local
communications.
RS-232 port, 9 D pin connector for remote
communications.

Environmental Ratings:
Ambient Temperature:
Fig. 1. Network Interface unit dimensions in in. (mm).
Operating: 32°F to 130°F (0°C to 54°C).
Storage: -30°F to +150°F (-34°C to 66°C).
Weight:
Q7700A: 4 lb, 5 oz unpacked, without ControlBus TM
Humidity:
Modules.
Operating, 85 percent relative humidity, continuous,
Q7700B: 5 lb. 13 oz unpacked, including power supply
noncondensing.
and cord, without ControlBus TM Modules.
Vibration:
Approvals:
Continuous 0.5G.
Underwriters Laboratories Inc: File No. MP268, Guide No.
MCCZ2.
Enclosure:
Canadian Standards Association: LR95329.
NEMA 1.
Factory Mutual: J.1. 2Q2A5.AF.
Dimensions:
See Fig. 1.
7800 SERIES Communications

QS7800A/QS7850A Communications Interface ControlBus Module


AllOWS remote monitoring and diagnostics of the RM78xx and EC78xx SERIES relay
modules with an lBM® compatible personal computer.
DIMENSIONS: 4-21/32 in. [118 mm] wide, 3-29/32 in. [99 mm]
high, 1 in. [25 mm] deep.
WEIGHT 8 oz.
OPERATING AMBIENT TEMPERATURE RANGE: 32 F to 130
F [0 C to 54 C].
ENCLOSURE: NEMA 1
ELECTRICAL RATING: RS485 ControlBus. Current Draw:
7 mA.
● Provides local and remote annunciation of 7800 SERIES
OPTIONAL COMPONENT:
faults.
200603 ControlBus Module 3-Wire Electrical Connector.
● QS7850A provides open protocol communications

with third party systems.


Electrical
● Provides user interface to personal computer.
Order Connectors
● Modular construction, NEMA #1 rated enclosure.
Number Included Used With
APPROVAL BODIES: QS7800A1001 ControlBus three-prong 7800 SERlES relay
Underwriters Laboratories Inc. component recognized, electrical connector. modules.
File No. MP268, Guide No. MCCZ2. QS7800B1000 Network Interface 7800 SERIES Relay
Canadian Standards Association certified, LR80141. ControlBus Module for Modules S7810
Federal Communications Commission, Part 15, Class Multi-dropping up to 31 Network Interface
A-Emissions, Part 68; registered. multi-dropped .7800
Series.
FCC Registration Number HS92SJ-10735-D-T-E.
Canadian Department of Communications certified. QS7850A1006 ControlBus three-prong Provides open com-
electrical connector. munication with third
party systems.
QS7800C1009 ControlBus three-prong SYSNet TM Data
electrical connector. Acquisition Modules.
QS7800D1008 Control Bus three-prong Armstrong
electrical connector. International
Trapscan TM Trap
Monitoring System.
QS7800E1007 ControlBus three-prong Pulsafeeder
electrical connector. PULSAtrol™ Surface
Blowdown System.

ZM7850A Combustion System ManagerTM Software


The ZM7850 is support software for connecting BCS and fault reporting for up to 6,000 individual burner/boiler
7700, RM78xx, and EC78xx SERIES controls with an controls.
lBM® or equivalent personal computer running Microsoft
Windows™ 3.0 or greater. It is a graphical, mouse-driven Order Description
software package that is easy to use and understand. It Number
provides data logging, remote interrogation, remote set
point adjustment of non-safety parameters (BCS 7700 ZM7850A1001 Combustion System Manager
only), history, real-time graphics, and control point
ZM7850B1000 SYSNet™ Software to monitor Honeywell BBC
trending. Pulsafeeder Controls, Armstrong Traps & Adam
Data Acq. modules. Microsoft windows based.
Touch screen compatible faceplates, dynamic
graphics, instrumentation & multi-media.
A matrix listing the O. S. numbers obsoleted and their modified replacements if listed
below:

Amplifiers Modified
Obsoleted Replacement
R7847A1058 R7847A1025
R7847A1066 R7847A1033
R7847A1090 R7847A1074
R7847A1108 R7847A1082
R7847B1049 R7847B1023
R7847B1056 R7847B1031
R7847B1080 R7847B1064
R7847B1098 R7847B1072
R7849A1049 R7849A1015
R7849A1056 R7849A1023
R7849B1039 R7849BI013
R7849B1047 R7849B1021
R7861A1000 R7861A1034
R7861A1018 R7861A1026

A7800A Tester
Provides quick operational check of the 7800 SERIES System components.
REQUIRED COMPONENTS:
203579A Configuration plug for RM7800/RM7840.
203579B Configuration plug for RM7838A.
203579C Configuration plug for RM7838B.
203579D Configuration plug for RM7885.
203579E Configuration plug for RM7890.
203579F Configuration plug for RM7895.
203579G Configuration plug for RM7823.

OPTIONAL COMPONENTS:
123514A Rectification Flame Simulator.
203659 Ultraviolet Flame Simulator.
W136A Test Meter.
● Function switches and selectors simulate interlocks and
control functions that allow 7800 SERIES devices to oper- REPLACEMENT PARTS: 192128 Panel fuse, 1.0A.
ate through sequences.
● Indicator lamps represent outputs as activated. Order Number Application
A7800A1002 Operational tests of 7800 SERIES relay mod-
OPERATING AMBlENT TEMPERATURE RANGE: 0 F to 120 F ules.
[–18 C to 49 C].
ELECTRICAL RATING: 120 Vac, 50/60 Hz.
7800 SERIES Accessories

Accessories

203968A
221729A

Description/Title Part Number Used With

ControlBus Module Electrical Connector 200603 QS7800

Electrical Access Slot Covers 221779 Q7800

Dust Cover 221729A RM7800, RM7823, RM7824,


RM7838, RM7840, RM7885,
RM7888, RM7890, RM7895,
EC7810, EC7820, EC7823,
EC7830, EC7850 with S7800A

ControlBus 5-Wire Electrical Connector 203541

Remote Display Mounting Bracket 203765

Remote Display Power Supply (Plug-in) 13 Vdc 203968A

Extension Cable Assembly for Remote Mounting


Keyboard Display Module-60 in. Cable Length 221818A
120 in. Cable Length 221818C

NEMA 4 Cover Assembly with Waterproof Gasket 204718A

NEMA 4 Cover Assembly with Waterproof Gasket 204718C


and provides remote reset of the 7800 series
device

Flush Mounting Bracket 205321B


Gas Burner Controls—Combination
Intermittent Pilot Applications
VR8304 Intermittent Pilot Dual Automatic Valve Combination Gas
Control
Combination gas control for use in Meet codes requiring dual safety shutoff.
24 Vac, gas-fired, intermittent pilot Standard and slow opening natural gas models include natural to
appliances with capacities from 30 LP gas conversion kit; LP to natural gas conversion kit also
to 415 cfh. available.
All adjustments, wiring connections and pilot outlet are acces-
Controls include safety shutoff, sible from top of control.
manual valve, two automatic oper- Adjustable servo regulator effectively maintains almost constant
ators, pressure regulator and pilot gas output pressure under wide fluctuations in gas supply pres-
adjustment. sure.
Use with S86F, H; S860D; Compatible with ECO connector.
S8600F,H; S8610 and S90A,B Con- ON-OFF lighting sequence.
trol Modules.
Compact size. VR8304 controls replace the following Honeywell and competitive
Provide two automatic valves. combination gas controls for applications requiring a minimum
Solenoid operated first automatic valve opens on thermostat call capacity of 30 cfh and a maximum capacity of 415 cfh.
for heat; closes when call for heat ends. Diaphragm-operated —Honeywell VR8440 and VR8204
second automatic valve opens under control of regulator; closes —White Rodgers 36E36/38
if gas or power supply is interrupted. —Robertshaw 7100DER (700-070)

Typical wiring connections in 24V system with S8610.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ALTERNATE LIMIT CONTROLLER LOCATION.

MAXIMUM CABLE LENGTH 3ft. (0.9 m).

CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.

REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS REMOVED AND VENT DAMPER
WIRING HARNESS IS INSTALLED; THEN MODULE WILL OPERATE ONLY WHEN VENT DAMPER IS CONNECTED.

REMOVE JUMER AND CONNECT SENSE TERMINAL ON TWO ROD APPLICATION ONLY.

lF THE EVENT DAMPER IS CONNECTED, WIRE 24V TERMINAL AS SHOWN. CONNECT VENT DAMPER
CABLE IN PLACE OF PLUG SHIPPED WITH THE S8610U. M8150
Gas Burner Controls—Combination
VR8304 continued

APPROVALS: VR8304 dimensions in in. (mm).


American Gas Association Design Certified: File No. L2025007.
Canadian Gas Association Design Certified: File No. L2025007.
MOUNTING: 0 to 90 degrees in any direction from upright position
of gas control knob, including vertically.
BODY PATTERN: Straight-through with 1/2 x 1/2 in., 1/2 x 3/4 in., and
3/4 x 3/4 in. inlets and outlets.
PILOT GAS OUTLET: Compression fitting for 1/4 in. OD tubing.
PRESSURE TAPPING: 1/8 in. NPT with plug.
PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.
TEMPERATURE RATINGS:
Ambient: VR8304H: 0 F to 175 F (–18 C to +79 C).
VR8304K,M,P: –40 F to +175 F (–40 C to +79 C).
ELECTRICAL RATINGS:
Power Supply: 24 Vac, 60 Hz.
Electrical Connections: 1/4 in. male quick-connects.
THERMOSTAT HEAT ANTICIPATOR SETTING: 0.7A.

* TRADELINE models.
Capacity
A.G.A. Pressure Regulator Type Type of
Inlet- Certified a Setting
Order Outlet of Pressure
Number Size (in.) cfh m3/hr in. wc kPa Gas Regulator Includes

a
Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressure
drop).
b
Use of 3/4 x 1/2 in. reducer bushing reduces capacity to 270 cfh (7.6 m3/hr).
c
Step pressure is not adjustable.
Gas Burner Controls—Combination
VR8204 Intermittent Pilot Dual Automatic Valve Combination Gas
Controls
Combination gas controls for use in PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.
24 Vac, gas-fired, intermittent pilot ap- PILOT GAS OUTLET: Compression fitting for 1/4 in. OD tubing.
pliances with capacities from 20 to TEMPERATURE RATINGS:
200 cfh. Ambient: VR8204A,C,H: 0 F to 175 F (–18 C to +79 C).
VR8204M: –40 F to +175 F (–40 C to +79 C).
Controls include manual valve, two au- ELECTRICAL RATINGS:
tomatic operators, servo pressure regu- Power Supply: 24 Vac, 60 Hz.
Iator and pilot adjustment. Electrical Connections: 1/4 in. male quick-connects.
Use with S86F,H; S8600F,H and S8610 THERMOSTAT HEAT ANTICIPATOR SETTING: 0.5A.
Control Modules.
Compact size. See VR8304 for typical wiring connections.
Provide two automatic valves.
Solenoid operated first automatic valve opens on thermostat call
for heat; closes when call for heat ends. Diaphragm operated VR8204 dimensions in in. (mm).
second automatic valve opens under control of regulator; closes
if gas or power supply is interrupted.
Meet codes requiring dual safety shutoff.
Standard and slow opening natural gas models include natural to
LP gas conversion kit; LP to natural gas conversion kit also
available.
All adjustments and wiring connections are accessible from top of
control.
ON-OFF lighting sequence.

VR8204 controls replace the following Honeywell and competitive


combination gas controls for applications requiring a minimum
capacity of 20 cfh and a maximum capacity of 200 cfh.
—Honeywell VR8440
—White Rodgers 36E36/38
—Robertshaw 7100DER (700-070)

APPROVALS:
American Gas Association Design Certified: File No. L2025006.
Canadian Gas Association Design Certified: File No. L2025006.
MOUNTING: 0 to 90 degrees from the upright position of gas control
knob, including vertically.
BODY PATTERN: Straight-through with 1/2 in. inlets and outlets.
PRESSURE TAPPING: 1/8 in. NPT with plug.

Capacity Pressure Regulator Type of


A.G.A. Certifieda Setting Type of Pressure
Inlet-Outlet
Order Number Size (in.) cfh m 3 /hr in. wc kPa Gas Regulator Includes
Gas Burner Controls—Combination
VR8204 continued

Capacity, Pressure Regulator


A.G.A. Certifieda Setting Type of
Inlet-Outlet Type of Pressure
3
Order Number Size (in.) cfh m /hr in. wc kPa Gas Regulator Includes

a
Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressure
drop).
b
Use of 1/2 x 3/8 in. reducer bushing reduces capacity to 130 cfh (3.7 m3/hr).
c
Step pressure is not adjustable.
Gas Burner Controls—Combination
VR4304 Intermittent Pilot Dual Automatic Valve Combination Gas
Control
Combination gas control for use in VR4304 control replaces the following Honeywell combination gas
120 Vac, gas-fired, intermittent pilot controls for 120 Vac applications requiring a minimum capacity of
appliances with capacities from 30 30 cfh and a maximum capacity of 415 cfh.
to 415 cfh. —Honeywell VR4440 and VR4204

Control includes manual valve, two NOTE: Conduit cover (included) must be used if control is not
automatic operators, pressure regu- mounted in appliance.
lator and pilot adjustment.
Compact size. APPROVALS:
Provides two automatic valves. American Gas Association Design Certified: File No. L2025007.
Solenoid operated first automatic Canadian Gas Association Design Certified: File No. L2025007.
valve opens on thermostat call for MOUNTING: 0 to 90 degrees in any direction from upright position of
heat; closes when call for heat ends. Diaphragm-operated sec- gas control knob, including vertically.
ond automatic valve opens under control of regulator; closes if BODY PATTERN: Straight-through with 3/4 x 3/4 in. inlet and outlet.
gas or power supply is interrupted. PILOT GAS OUTLET: Compression fitting for 1/4 in. OD tubing.
Meets codes requiring dual safety shut-off. PRESSURE TAPPING: 1/8 in. NPT with plug.
Includes natural to LP gas conversion kit. PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.
All adjustments, wiring connections and pilot outlet are acces- TEMPERATURE RATINGS:
sible from top of control. Ambient: –40 F to 175 F (–40 C to +79 C).
Adjustable servo regulator effectively maintains almost constant ELECTRICAL RATINGS:
gas output pressure under wide fluctuations in gas supply Power Supply: 120 Vac, 60 Hz.
pressure. Electrical Connections: 1/4 in. male quick-connects; 24 in.
ON/OFF lighting sequence. (610 mm) Ieadwires.
THERMOSTAT HEAT ANTICIPATOR SETTING: 0.13A.
Typical wiring for 120V control in intermittent ignition system.

*TRADELINE model.

Inlet- Capacity Pressure Regulator Type Type of


Order Outlet A.G.A. Certifieda Setting of Pressure
Number Size (in.) cfh m3/hr in. wc kPa Gas Regulator Includes

8.5 Nat. Standard 393691 Natural to LP gas conversion


*VR4304M4519 3/4 x 3/4 300 3.5 0.9
kit.
a
Capacities based on 1,000 Btu/ft.3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressure
drop).
Gas Burner Controls—Combination
Hot Surface/Direct Spark Applications
VR8305 Direct Ignition Dual Automatic Valve Combination Gas
Controls
Combination gas control for use APPROVALS:
with hot surface/direct spark sys- American Gas Association Design Certified: File No. L2025007.
tems in 24 Vac, gas-fired appli- Canadian Gas Association Design Certified: File No. L2025007.
ances, with capacities from 30 to
415 cfh.
VR8305 dimensions in in. (mm).
Controls include manual valve, two
automatic operators, and pressure
regulator.
Use with S89C,E,F and S87 series 5
and later.
Compact size.
Provide two automatic valves.
Solenoid-operated first automatic valve opens on thermostat call
for heat; closes when call for heat ends. Diaphragm-operated
second automatic valve opens under control of regulator; closes
if gas or power supply is interrupted.
Meet codes requiring dual safety shut-off.
All adjustments, wiring connections and pilot outlet are acces-
sible from top of control.
Adjustable servo regulator effectively maintains almost constant
gas output pressure under wide fluctuations in gas supply pres-
sure.
ON-OFF lighting sequence.

VR8305 controls replace the following Honeywell and competitive


combination gas controls for applications requiring a minimum
capacity of 30 cfh and a maximum capacity of 415 cfh.
—Honeywell VR8450 and VR8205
—White Rodgers 36E36/38 and 36C68
—Robertshaw 7200DER

Typical wiring connections for 24V system with S89/S890.


Gas Burner Controls—Combination
VR8305 continued

MOUNTING: 0 to 90 degrees in any direction from upright position TEMPERATURE RATINGS:


of gas control knob, including vertically. Ambient:
BODY PATTERN: Straight-through with 1/2 x 3/4 in. inlets and outlets. VR8305H: 0 F to 175 F (–18 C to +79 C).
PRESSURE TAPPING: 1/8 in. NPT with plug. VR8305M,P: –40 F to +175 F (–40 C to +79 C).
PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure. ELECTRICAL RATINGS:
Power Supply: 24 Vac, 60 Hz.
Electrical Connections: 1/4 in. male quick-connects.
THERMOSTAT HEAT ANTICIPATOR SETTlNG: 0.7A.

Inlet- Capacity, Pressure Regulator Type of


Outlet A.G.A. Certifieda Setting Type of Pressure
Order Number Size (in.) cfh m 3 /hr in. wc kPa Gas Regulator Includes
VR8305H4005 3/4 x 3/4 300 8.5 3.5 0.9 Nat. Slow- —
opening
Standard One 3/4 x 1/2 in. reducer
VR8305M3506 1/2 x 3/4 270 7.6 bushing b; 393691 Natural
to LP gas conversion kit.
VR8305P2208 1/2 x 1/2 240 6.8 1.2 Stepc; 0.34 Stepc; Step-
3.5 full rate 0.9 full rate opening
VR8305P2224 4.0 Stepc; 1.0 Stepc; LP
10.0 full rate 2.5 full rate
VR8305P4204 3/4 x 3/4 300 8.5 1.2 Step c; 0.3 Step c; Nat.
3.5 full rate 0.9 full rate
VR8305P4212 2.5 Stepc; 0.62 Stepc; LP
10.0 full rate 2.5 full rate
VR8305P4279 0.9 Stepc; 0.22 Stepc; Nat.
3.5 full rate 0.9 full rate
a
Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 Sp gr natural gas at 0.25 kPa pressure
drop).
b
Use of 3/4 x 1/2 in. reducer bushing reduces capacity to 270 cfh (7.6 m3/hr).
c
Step pressure is not adjustable.

VR8205 Direct Ignition Dual Automatic Combination


Gas Controls
Combination gas controls for use APPROVALS:
with hot surface/direct spark sys- American Gas Association Design Certified: File No. L2025006.
tems in 24 Vac, gas-fired appliances Canadian Gas Association Design Certified: File No. L2025006.
with capacities from 20 to 200 cfh. MOUNTING: 0 to 90 degrees in any direction from the upright
position of the gas control knob, including vertically.
Controls include manual valve, two
automatic operators and servo
pressure regulator. VR8205 dimensions in in. [mm].
Compact size.
Use with S87C,D and S89E,F Con-
trol Modules.
Provide two automatic valves.
Solenoid operated first automatic valve opens on thermostat call
for heat; closes when call for heat ends. Diaphragm operated
second automatic valve opens under control of the regulator;
closes if gas or power supply is interrupted.
Meet codes requiring dual safety shutoff.
Standard and slow opening natural gas models include natural to
LP gas conversion kit; LP to natural gas conversion kit also
available.
Adjustments and wiring connections are accessible from top of
the control.
ON-OFF lighting sequence.
VR8205 controls replace the following Honeywell and competitive
combination gas controls for applications requiring a minimum
capacity of 20 cfh and a maximum capacity of 200 cfh.
—Honeywell VR8450
—White Rodgers 36E36/38

continued next page


Gas Burner Controls—Combination
VR8205 continued

BODY PATTERN: Straight-through. ELECTRICAL RATINGS:


PRESSURE TAPPING: 1/8 in. NPT with plug. Power Supply: 24 Vac, 60 Hz.
PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure. Electrical Connections: 1/4 in. male quick-connects.
TEMPERATURE RATINGS: THERMOSTAT HEAT ANTICIPATOR SETTING: 0.5A.
Ambient: 0 F to 175 F (–18 C to +79 C).

Typical wiring connections for 24V system with S89C.

POWER SUPPLY. PROVIDE DISCONNECT MEANS CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG T0
AND OVERLOAD PROTECTION AS REQUIRED. TRANSFORMER.
MAKE SURE L1 AND L2 ARE NOT REVERSED:
THIS WOULD PREVENT FLAME DETECTION. SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.

ALTERNATE LIMIT CONTROLLER LOCATION.

*TRADELINE model.
Inlet- Capacity Pressure Regulator Type Type of
Outlet A.G.A. Certifieda Setting of Pressure
Order
Number Size (in.) cfh m 3 /hr kPa Gas Regulator Includes
in. wc

a
Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressure
drop).
b
Use of 1/2 x 3/8 in. reducer bushings reduces capacity to 130 cfh (3.7 m3/hr).
c
Step pressure is not adjustable.
d
Lockout time required for module is 8.5 seconds.
Gas Burner Controls—Combination
VR4305 Direct Ignition Dual Automatic Valve Combination Gas
Control
Combination gas control for use with TEMPERATURE RATINGS:
hot surface/direct spark systems in 120 Ambient: –40 F to +175 F (–40 F to +79 C).
Vac, gas-fired appliances, with capac- ELECTRICAL RATINGS:
ities from 30 to 415 cfh. Power Supply: 120 Vac, 60 Hz.
Electrical Connections: 1/4 in. male quick-connects; 24 in.
● Controls include manual valve, two (610 mm) leadwires.
automatic operators and pressure THERMOSTAT HEAT ANTICIPATOR SETTING: 0.13A.
regulator.
● Compact size.
● Provides two automatic valves. Typical wiring for 120V control in direct ignition system.
● Solenoid operated first automatic
valve opens on thermostat call for heat;
closes when call for heat ends. Dia-
phragm-operated second automatic valve opens under control of
regulator; closes if gas or power supply is interrupted.
● Meets codes requiring dual safety shut-off.
● Includes natural to LP gas conversion kit.
● All adjustments, wiring connections and pilot outlet are acces-
sible from top of control.
● Adjustable servo regulator effectively maintains almost constant
gas output pressure under wide fluctuations in gas supply pres-
sure.
● ON/OFF lighting sequence.

VR4305 controls replace the following Honeywell combination gas


controls for applications requiring a minimum capacity of 30 cfh and
a maximum capacity of 415 cfh.
—Honeywell VR4450 and VR4205

NOTE: Conduit cover (included) must be used if control is not


mounted in the appliance.

APPROVALS:
American Gas Association Design Certified: File No. L2025007.
Canadian Gas Association Design Certified: File No. L2025007.
MOUNTING: 0 to 90 degrees in any direction from upright position of POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
gas control knob, including vertically.
BODY PATTERN: Straight-through with 3/4 x 3/4 in. inlet and outlet. ALTERNATE LIMIT CONTROLLER LOCATION. M3088

PRESSURE TAPPING: 1/8 in. NPT with plug.


PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.

*TRADELINE model.
Capacity Pressure Regulator Type of
a

Intlet-Outlet A.G.A. Certified Setting


Type of Pressure
Order Number Size (in.) cfh m /hr3
in. wc kPa Gas Regulator Includes
*VR4305M4532 3/4 x 3/4 300 8.5 3.5 0.87 Nat. Standard 393691 Natural to LP conversion kit;
390427 pipe bushing.
a
Capacities based on 1,000 Btu/ft.3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressure
drop).
Gas Burner Controls—lgnition Controls
S9301 Integrated Boiler Control
Provides control of a high efficiency gas boiler with a combus- ● Four LED lights indicate operating mode and help identify the
tion air blower and a combination hot surface igniter/flame problem source during troubleshooting.
sensor. ● Keyed plugs for wiring connections.

S9301 provides: NOTE: For use in residential boilers only; not for use with a vent
Sequencing of ignition and burner operation. damper.
Two additional trials for ignition if initial Iightoff is unsuccessful.
Wiring terminal board for all electrical connections. IMPORTANT: This control is configured for application to specific
Control of circulator pump and combustion blower motors. appliance models. It is intended for direct replacement of OEM
Monitoring of Aquastat and auxiliary limits to ensure proper water installed controls only; see order table. Do not attempt to apply
temperature and of the air proving switch to ensure proper this control except as a direct replacement for the specific Honey-
sequencing of combustion air before the ignition sequence starts. well models noted in the order table below.
Continued circulator pump operation during lockout as long as
thermostat calls for heat. Order Number Replaces Application
S9301A1027 S9301A1001 High efficiency gas boiler.
S9301A1027

S8610U Universal Intermittent Pilot Module


Field service replacement for APPROVALS:
most Honeywell, Robertshaw, American Gas Association Design Certified.
Johnson, and UTEC (HSC) in- Canadian Gas Association Design Certified.
termittent pilot ignition mod- Underwriters Laboratories Inc. Component Recognized.
ules. Provides electronic con- TEMPERATURE RATINGS:
trol of most intermittent pilot Ambient: –40 F to +165 F (–40 C to +74 C).
ignition systems used on gas- FLAME FAILURE RESPONSE TIME: 0.8 sec. at 1.0 µA flame current.
fired furnaces, boilers and ELECTRICAL CONNECTIONS: 1/4 in. male quick-connect terminals,
other heating appliances. including ignition terminal (3/16 in. male quick-connect sense
terminal).
Provides ignition sequence, flame monitoring and safety shutoff ELECTRICAL RATINGS:
for intermittent pilot central furnaces and heating appliances. Power Supply: 24V (nominal), 60 Hz.
Provides 100 percent pilot gas shutoff if pilot fails to light; after Current: 0.2A
6-minute delay, trial for ignition is repeated. Ignition trial/delay Spark Generator Output: 13 kV peak at 25 pf load.
sequence is repeated until the appliance lights or call for heat is Contact (at 24 Vac):
removed.
For use with natural or LP gas. Running Inrush
For use in single rod or dual rod/remote sense applications. Pilot 1.0A 10.0A
Includes relay contacts for use with any intermittent pilot gas Main 2.0A 20.0A
control string with maximum 1.0A pilot or 2.0A main valve rating;
Honeywell VR8204, VR8304 or VR8345M combination gas con- NOTE: Maximum ambient temperature is 175 F (79 C) if main valve
trol recommended. relay load is 1.0A or less.
Functional equivalent of S86, S8600, S8610 and S90 modules.
Includes spark cable adapters to allow field replacement of both THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus pilot valve
Honeywell and competitive controls without replacing existing rating plus main valve rating.
spark cable. ACCESSORIES:
394800-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-
Replaces most of the following intermittent pilot modules: connect on module end; Rajah connector receptacle,
—Honeywell S86, S90, S8600 and S8610 90 deg. rubber boot on igniter end.
—Robertshaw SP715, SP715A, SP735, SP735A, SP735L 394801-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-
—Johnson GSA, G60, G65, G67, G600, G770 connect on module end; Rajah connector receptacle, straight
Refer to S8610 specification sheet for a complete list of model rubber boot on igniter end.
numbers.

● SUPER TRADELINE model.


Shutoff
Order Number Time Description
S8610U1003 90 sec. max. 100 percent pilot gas shutoff and lockout on loss of pilot flame. Includes remote reset, and automatic
vent damper plug. For use in systems with combination igniter-sensor (single rod or sense) or separate
igniter and sensor (dual rod or remote sense).
Gas Burner Controls—Ignition Controls
S8610; S8670 Intermittent Pilot Modules
Provide electronic control of in- TEMPERATURE RATINGS:
termittent pilot ignition systems Ambient: –40 F to +165 (40 C to +74 C).
used on gas-fired furnaces, FLAME FAILURE RESPONSE TIME: 0.8 sec. at 1.0µA flame current.
boilers and other heating ELECTRICAL CONNECTIONS: 1/4 in. male quick-connect terminals,
appliances. including ignition terminal.
ELECTRICAL RATINGS:
● Provide ignition sequence, Power Supply: 24V (nominal), 60 Hz.
flame monitoring and safety Current: 0.2A.
shutoff for intermittent pilot central furnaces and heating Spark Generator Output: 13 kV peak at 25 pf load.
appliances. Contacts:
● Functional equivalent of S86, S860 and S90 modules.
● Include spark cable adapter to allow field replacement of S86, Running Inrush
S860 and S90 without replacing existing spark cable. Pilot 1.0A 10.0A
● Include relay contacts for use with any intermittent pilot gas con- Main 2.0A 20.0A
trol string with maximum 1.0A pilot and 2.0A main valve rating;
Honeywell VR8204, VR8304 or VR8440 combination gas control NOTE: Maximum ambient temperature is 175 F (79 C) if main valve
recommended. relay load is 1A or less.
● S8610F is for use with natural gas only; modules do not provide
100 percent pilot gas shutoff if pilot fails to light. THERMOSTAT HEAT ANTICIPATOR SETTlNG: 0.2A plus pilot valve
● S8610H; S8670D are for use with natural or LP gas; modules rating plus main valve rating.
provide 100 percent pilot gas shutoff and lockout if pilot fails to ACCESSORIES:
light. 394800-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-
connect on module end; Rajah connector receptacle, 90 deg.
See Honeywell to S8610 Intermittent Pilot Modules Cross Reference rubber boot on igniter end.
for a list of Honeywell intermittent pilot modules that S8610F,H; 394801-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-
S8670D replace. connect on module end; Rajah connector receptacle, straight
rubber boot on igniter end.
APPROVALS:
American Gas Association Design Certified.
Canadian Gas Association Design Certified.
Underwriters Laboratories Inc. Component Recognized.

Order Number Lockout Time Description


S8610F1008 None. Continuous trial for ignition. Non-100 percent shutoff if pilot fails to light. For use in systems with combina-
tion igniter-sensor.
S8610H1004 15 sec. max. 100 percent pilot gas shutoff and lockout if pilot fails to light. Includes remote
a
reset. For use in systems with combination igniter-sensor.
S8610H1020 15 sec. max.
S8670D1000 90 sec. max. 100 percent pilot gas shutoff and lockout if pilot fails to light. Includes remote
reset. For use in systems with combination igniter-sensor where prepurge
cycle is desired (45 second prepurge timing).
a
Includes automatic vent damper plug for D892 Vent Damper.
Gas Burner Controls—Ignition Controls
Honeywell to S8610 Intermittent Pilot Modules Cross Reference
Existing Model Number Replacement Model Number Existing Model Number Replacement Model Number
S86A1001, S86A1019, S8610U1003, S8610F1008 S8600F1042 S8610U1003, S8610F1008
S86A1027, S86A1035, S8600H1006 S8610U1003
S86B1009, S86B1017,
S8600H1014 S8610H1004
S86B1025
S8600H1022 S8610U1003
S86C1007, S86C1015 S8610U1003
S8610H1004 S8600H1048, S8600H1055 S8610U1003
S86C1023
S8610U1003 S8600H1063 S8610H1004
S86C1031, S86C1049,
S86C1056, S86D1005 S8600H1071 S8610U1003
S86D1013 S8610H1004 S8600H1089 S8610U1003
S86D1021 S8610U1003 S8600H1097 S8610U1003
S86E1002, S86E1010, S8610U1003, S8610F1008 S8600H1105 S8610U1003 a
S86E1028, S86E1036 S8600M1005, S8600M1013 S8610U1003
S86E1044, S86E1051 S8610U1003 S8610A1009 S8610U1003
S86E1069, S86E1077, S8610U1003, S8610F1008 S8610B1007, S8610B1015 S8610U1003
S86E1101, S86E1119,
S8610C1005 S8610U1003
S86E1127, S86F1000,
S86F1018, S86F1026, S8610F1008 S8610U1003, S8610F1008
S86F1042, S86F1059, S8610F1016 S8610U1003
S86F1067, S86F1075
S8610F1024 S8610U1003, S8610F1008
S86F1083, S86F1091 S8610U1003
S8610F1032 S8610U1003
S86G1008, S86G1016 S8610U003
S8610H1004 S8610H1004
S86G1024 S8610H1004
S8610H1012 S8610U1003
S86G1032, S86G1057, S8610U1003
S8610H1020 S8610H1020
S86G1073, S86H1006
S8610H1038, S8610H1046 S8610U1003
S86H1014 S8610H1004
S8610H1053 S8610U1003
S86H1022, S86H1048, S8610U1003
S86H1089, S86H1097, S8610H1061 S8610H1004
S86H1105 S8610H1079 S8610U1003
S86H1113 S8610H1004 S8610M1003 S8610U1003
S86H1121 S8610U1003 S8610M1011 S8610H1004 b
S86H1139 S8610H1020 S8610M1029 S8610U1003
S86H1147 S8610U1003 S8610U1003 S8610U1003
S90A1005 S8610U1003 S8620C1003 S8610H1004 b
S9OB1003, S90B1011 S8610U1003 S8620C1011 S8610H1020 b
S860C1000, S860D1009 S8670D1000 S8620H1002 S8610U1003
S8600A1001 S8610U1003 S8620H1010 S8610H1004
S8600B1009 S8610U1003 S8620H1028 S8610U1003
S8600C1065 S8610U1003 S8660D1002, S8670D1000, S8670D1000
S8600F1000 S8610U1003, S8610F1008 S8670D1018
S8600F1034 S8610U1003 S8670E1007 S8670D1000 b
a
S8610U1003 does not have meter shunt.
b
Replacement control does not have continuous rety.
Gas Burner Controls—Ignition Controls
Y8610F and U Universal Retrofit Intermittent Pilot Gas
Burner Ignition Systems
Each Y8610 system includes:
—S8610F or U Intermittent Pilot Module.
—VR8204 or VR8304 Intermittent Pilot Dual Valve Combination Gas
Control with an ON-OFF manual valve, pressure regulator and two
automatic main gas valve operators. Includes reducer bushings.
—393691 LP Gas Conversion Kit with Y8610U.
—392431 Igniter-Sensor Assembly. Includes ceramic-insulated
Kanthal rod that attaches to the existing pilot burner in place of the
thermocouple.
—394800-30 Ignition Cable. 30 in. (762 mm) cable with connectors.
—393690-14 Flange Assembly with Y8610U. Includes 3/4 in. straight
flange with O ring, 9/64 hex screws and wrench.
—Wiring Harness. 30 in. (762 mm) wiring harness with 1/4 in. quick-
connect terminals.
—Reducer bushings for gas control.
—Adhesive mounting tape for S8610.
—Miscellaneous installation hardware—screws, solderless con-
nectors, ground rod and adapter.

Complete kits for converting conventional standing pilot sys- ELECTRICAL RATINGS:
tems to intermittent pilot systems. For use with 24 Vac gas-fired Power Supply: 24 Vac (nominal), 60 Hz.
atmospheric furnaces, boiler and heating appliances. Current: 0.7A (includes both module and gas control).
THERMOSTAT HEAT ANTICIPATOR SETTING—0.7A plus current
● Y8610F kits are for use with natural gas only: continue trial for ratings of other devices in thermostat control circuit.
ignition until the pilot lights or the system is shutdown manually.
● Y8610U kits are for use with natural or LP gas: provides 100 Compatible with all open-close switch type 24 Vac thermostats
percent pilot gas shutoff if pilot fails to light; after 6-minute delay, capable of supplying rated voltage and current to the module. Also
trial for ignition is repeated. Ignition trial/delay sequence is repeat- compatible with Honeywell electronic thermostats that directly
ed until the appliance lights or call for heat is removed. switch the ignition module.

● SUPER TRADELINE model.


Inlet-
Outlet Temperature Ratings
Order Capacity Type
Number Includes ( B t u h )c Size (in.) F C of Gas
Y8610F5003 S8610F1008 a Control Module and 150,000 1/2 x 1/2 0 to 175 –18 to +79 Natural
VR8204A2142 Combination Gas Control
● Y86103003 S8610U1003 b,d Control Module and 270,000 1/2 x 3/4 –40 to +175 –40 to +79 Natural
VR8304M3558 Combination Gas Control, or LP
two 3/4 x 1/2 in. reduce bushings.
a c
With non-100 percent shutoff. 0.64 sp gr Nat. gas at 1 in. wc (0.25 kPa) pressure drop.
b d
With 100 percent pilot gas shutoff and lockout, 90 second maxi- Includes automatic vent damper plug.
mum timed trial for ignition.
Gas Burner Controls—lgnition Controls
S8910U Universal Hot Surface Ignition Module
Provides operating control of a WIRING: Use existing appliance wiring. If repair or replacement of
direct ignition system using a leadwires is required, follow instruction on appliance label. Use
120 Vac hot surface igniter. included quick-connect terminals and wiring adapters according
to instructions.
● Provides easy field-replacement ELECTRICAL RATINGS:
of a wide range of hot surface Important: The S8910U is for use only in 60 Hz systems.
ignition modules manufactured Power Supply: 24V, 60 Hz.
by Honeywell, Robertshaw and Valve Contacts: 2A max.
White-Rodgers. Refer to the Current Draw: 0.4A plus valve load.
product specification sheet for specific models that can be Hot Surface Igniter Voltage: 120 Vac, 60 Hz.
replaced by the S8910U. Igniter Contacts: 5A at 120 Vac.
● For 120 Vac (up to 5.0A) hot surface igniter (Norton 201/271 or PREPURGE: 32 seconds.
equivalent). IGNITER WARMUP: 34 seconds.
● For local (single rod) or remote (dual rod) rectification type flame BETWEEN TRIAL PURGE: 96 seconds (3 trial mode only).
sensing. FLAME FAILURE RESPONSE TIME: 1.5 seconds maximum.
● Contains easy-to-use instructions plus the accessories required IGNITION SEQUENCE: The number of trials for ignition and trial time
to adapt the existing hot surface ignition module. is determined by the selection tab. If a selection tab is not in-
stalled, the module will operate at four seconds trial time and one
!WARNING ignition trial.
EXPLOSION HAZARD, CAN CAUSE INJURY OR EQUIPMENT
SELECTION TAB SPECIFICATIONS:
DAMAGE.
The S8910U can be used only for direct replacement of specific Trial Time Number of
installed models. Check the product specification sheet and the Selection Tab (seconds) Ignition Trials
cross-reference (page 77) before replacing an existing hot surface
module with the S8910U. If the existing module is not listed, do not A 4 1
use the S8910U to replace it. Always use the selection tab specified B 4 3
in the product specification sheet for the existing module being C 7 1
replaced. Replacement of an unlisted module or use of a selection
tab other than specified can result in appliance malfunction. D 7 3

APPROVALS: ● SUPER TRADELINE model.


American Gas Association Certified: Report no. C3090002.
Canadian Gas Association Certified: Report no. C3090002. Order Number Application
TEMPERATURE RATINGS: ● S8910U1000 For direct replacement of a wide range of hot
Ambient: –40 F to +175 F (–40 C to +79 C). surface ignition modules manufactured by
HOT SURFACE IGNITER OR IGNITER-SENSOR: Norton Model 201 Honeywell, White Rodgers and Robertshaw.
or 271 or equivalent. Refer to the product specification sheet and the
SENSOR: Separate sensor required for remote sense applications. Cross-Reference (page 77) for specific models
that can be replaced by the S8910U.
Gas Burner Controls—lgnition Controls
S89C,D,G,H,J; S890 Hot Surface Ignition Modules
Provide electronic control of 120V hot APPROVALS:
surface ignition systems used in fur- American Gas Association Design Certified.
naces, boilers and other heating Canadian Gas Association Design Certified.
appliances. Underwriters Laboratories Inc. Component Recognized.
TEMPERATURE RATINGS:
● S89C,G,J; S890G are for systems with Ambient: –40 F to +175 F (–40 C to +79 C).
combination igniter-sensor; S89D,H and FLAME FAILURE RESPONSE TIME: 2 seconds maximum with
S890H are for systems with separate igni- 2.5 µA flame signal.
ter and sensor. ELECTRICAL RATINGS:
● Use with Norton 201 Hot Surface Igniters Power Supply: Requires two power supply connections: 24 and
or equivalent. 120 Vac, 50/60 Hz.
● Lockout after one (S89C,D) or three Current: 2.2A maximum at 24 Vac; 5.0A maximum at 120 Vac.
(S89G,H; S890G,H) trials for ignition if main burner fails to ignite. Valve Contacts: 2.0A maximum at 24 Vac.
● Reset from thermostat after lockout. Igniter Contacts: 5.0A maximum at 120 Vac.
● S89G,H; S890G,H have 30 second between trial purge time. WIRING CONNECTIONS:
24 Vac—3/16 in. male quick-connects.
Other components needed to complete the system (order sep- 120 Vac—1/4 in. male quick-connects.
arately): Sense Terminals (S89D,H; S890H only)—1/4 in. male quick-
—VR845, VR854, VR8540, V845, V854, VR8205 or VR8305 Combi- connects.
nation Gas Control, or any dual valve rated 1.0A or less. IGNITER WARMUP PERIOD: 34 seconds, nominal.
—24V Transformer. THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus gas con-
—24V Thermostat. trol current.
—Hot surface igniter: Norton Model 201 or equivalent.
—Q354 Flame Sensor for all D and H models.
—High temperature limit controller.

Order Number Application Lockout Timing


S89C1087 For use in hot surface ignition systems to control hot surface igniter and flow of gas 6 sec.
in appliances; provides single trial for ignition.
S89C1095 15 sec.
S89C1103 4 sec.
S89D1002 For use in hot surface ignition systems to control hot surface igniter and flow of gas 6 sec.
in appliances; provides single trial for ignition; requires separate flame sensor.
S89G1005 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.
in appliances; provides three trials for ignition. Not for use in atmospheric burner
S89G1013 systems. 6 sec.
S89G1021 11 sec.
S89H1003 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.
in appliances; provides three trials for ignition; requires separate flame sensor. Not
S89H1011 for use in atmospheric burner systems. 6 sec.
S890G1003 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.
in appliances; provides three trials for ignition. Use in systems with combination
S890G1011 igniter-sensor where a prepurge cycle is desired. Includes 30 seconds 6 sec.
S890G1029 minimum/37 seconds maximum (34 seconds nominal) prepurge. 11 sec.

S890H1002 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.
in appliances; provides three trials for ignition; requires separate flame sensor.
S890H1010 6 sec.
Use in systems where prepurge cycle is desired. Includes 30 seconds
S890H1028 minimum/37 seconds maximum (34 seconds nominal) prepurge. 11 sec.

S89J1008 For use in hot surface ignition systems to control hot surface igniter and flow of gas 6 sec.
in appliances; provides single trial for ignition. Use in systems with combination
igniter-sensor. Provides 4 second maximum ignition activation period.
S89J1016 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.
in appliances; provides single trial for ignition. Use in systems with combination
igniter-sensor. Provides 2 second maximum ignition activation period. Includes
plug for vent damper.
Gas Burner Controls—lcmition Controls
S89E,F Direct Spark Ignition Modules
Provide electronic control of direct —VR8205 or VR8305 Combination Gas Control, or any 24 Vac dual
spark ignition systems, with external valve rated at 2.0A or less and designed for DSI applications.
spark transformers, used on gas-fired
furnaces, boilers, conversion burners APPROVALS:
and other heating appliances. American Gas Association Design Certified.
Canadian Gas Association Design Certified.
● Control ignition sequence and gas Underwriters Laboratories Inc. Component Recognized.
control operation in direct spark ignition TEMPERATURE RATINGS:
systems. Ambient: –40 F to +175 F (–40 C to +79 C).
● Control separate 120 Vac spark gener- FLAME FAILURE RESPONSE TIME: 2 seconds maximum.
ator that provides high voltage potential ELECTRICAL RATINGS:
for main burner ignition. Power Supply: Requires two power supply connections: 24 and
● Lockout after one trial for ignition if main burner fails to ignite. 120 Vac, 50/60 Hz.
● Reset from thermostat after lockout. Current: 2.2A maximum at 24 Vac; 1.5A maximum at 120 Vac.
● Use separate electrodes for spark ignition and flame sensing. Valve Contacts: 2.0A maximum at 24 Vac.
● Use any 24 Vac combination gas control designed for direct spark Spark Generator Relay Contacts: 1.5A at 120 Vac, 50/60 Hz.
applications and rated at 2.0A or less. ELECTRICAL CONNECTIONS:
24 Vac—1/4 in. male quick-connects.
Other components needed for a complete DSI system (order 120 Vac—12 in. (305 mm) color-coded leadwires.
separately): THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus gas con-
—120 Vac spark generator with 1.5A or less current draw. trol current.
—Q347 Spark Igniter.
—Q354 Flame Sensor.

Order Lookout
Number Timing Application Use With

S89E1058 4 sec. For use in direct spark ignition systems on gas-fired VR8205 or VR8305 Combination Gas Con-
atmospheric and power burners; provides safe start trol, or any dual valve rated 2.0A or less for
S 8 9 E 1 0 6 6a 4 sec. DSI applications.
check before ignition.
S89E1074 11 sec.

S89F1098 4 sec. For use in direct spark ignition systems on gas-fired


a
atmospheric and power-burners; provides safe start
S89F1106 4 sec. check and 30 second purge period prior to ignition.
a
Labels applied upside down for inverted mounting.

S87 Direct Spark Ignition Modules


Provide electronic control of direct spark —24 Vac thermostat.
ignition systems used on gas fired —High limit temperature controller.
furnaces, boilers, and other heating —24V transformer.
appliances.
APPROVALS:
● Control ignition sequence and gas con- American Gas Association Design Certified.
trol operation. Canadian Gas Association Design Certified.
● Generate high voltage potential for main Underwriters Laboratories Inc. Component Recognized.
burner ignition. TEMPERATURE RATINGS:
● Lockout after one trial for ignition if main Ambient: –40 F to +175 F (–40 C to +79 C).
burner fails to ignite. FLAME FAILURE RESPONSE TIME: 0.8 sec. max.
● Reset from thermostat after lockout. ELECTRICAL RATINGS:
● Use modules (except S87C) with any combination gas control Power Supply: 24 Vac, 60 Hz.
designed for direct spark applications and rated at 2.0A or less. Current: At 24 Vac input 2.2A maximum.
Contacts: Valve (S87B,D,J,K)—2.0A at 24 Vac.
Other components needed for a complete DSI system (order sep- Contacts: Alarm (S87B,D)—0.5A maximum at 24 Vac.
arately): ELECTRICAL CONNECTIONS: 1/4 in. male quick-connects for sys-
—Q347 Spark Igniter. tem; 1/4 in. diameter stud base for ignition cable.
—Q354 Flame Sensor (S87C,D,K systems only). THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus gas con-
—VR8205 or VR8305 Combination Gas Control, or any 24 Vac dual trol current.
valve rated at 2.0A or less and designed for DSI applications;
S87C requires a Honeywell combination gas control designed for
DSI applications.
Gas Burner Controls—Ignition Controls
S87 continued

Order Number Lockout Time Application Use With


S87B1008 6 sec. Uses a single electrode for spark ignition and Q347B Spark Igniter.
flame sensing. Includes optional alarm output.
S87B1016 11 sec.
S87B1024 21 sec.
S87B1065 4 sec.
S87C1006 6 sec. Uses separate electrodes for spark ignition Q347A Spark Igniter and Q354A
and flame sensing. For use only with Honey- Flame Sensor.
S87C1014 11 sec. well gas controls designed for DSI application.
S87C1022 4 sec. For direct replacement of S825C.
S87C1030 21 sec.
S87D1004 6 sec. Uses separate electrodes for spark ignition Q347A Spark Igniter and Q354A
S87D1012 11 sec. and flame sensing. Includes optional alarm Flame Sensor.
output. For direct replacement of S825C,D.
S87D1020 4 sec.

S87D1038 21 sec.
S87J1000 4 sec. Uses a single electrode for spark ignition and Q347B Spark Igniter.
flame sensing. Includes a 30 second (mini-
S87J1018 6 sec. mum) delay for use with system prepurge.
S87J1026 11 sec.
S87J1034 21 sec.
S87K1008 4 sec. Uses separate electrodes for spark ignition Q347A Spark Igniter and Q354A
and flame sensing. Includes a 30 second (mini- Flame Sensor.
S87K1016 6 sec. mum) delay for use with system prepurge.
S87K1024 11 sec.
S87K1032 21 sec.

Q345A Igniter-Sensor
Nonprimary-aerated combination pilot burn- *TRADELINE models.
er and igniter. Used with the S86, S860,
Order Tip Type Mounting
S8610 or S8670 in intermittent pilot systems. Includes
Number Style of Gas Bracket
● Includes pilot burner with bracket, ceramic- *Q345A1305 Nat. B 1/4 in. cc
insulated Kanthal flame rod/spark igniter, inlet fitting
and ground strap. and mounting
adaptor.
TEMPERATURE RATINGS:
At electrode tip—1775 F (968 C) max.
At ceramic insulator—1250 F (677 C) max.
*Q345A1313 Nat. B

Mounting dimensions in in. (mm) and bracket type for Q345A.

*Q345A1321 Nat. B
Gas Burner Controls—Ignition Controls
Q347A Spark Igniter
Produces spark for direct ignition of main ELECTRICAL CONNECTIONS: 1/4 in. diameter stud for ignition
burner. cable.
MOUNTING: One 3/16 in. (5 mm) slot, three 3/16 in. (5 mm) untapped
● Includes inner Kanthal electrode with ce- screw holes.
ramic insulator, bracket and Kanthal
ground strap. Order Ground Strap
● Use with S87C,D,K; S89E, F and Q354A. Number Orientation Electrode Lengtha

TEMPERATURE RATINGS: Q347A1004 Standard 2-1/32 in. (52 mm)


At electrode tip—1775 F (968 C) max. Q347A1012 90 degree right angle 2-1/32 in. (52 mm)
At ceramic insulator—1250 F (677 C) max. a
SPARK GAP: 5/32 in. (4 mm). Bracket to tip.

Q354A Flame Rectification Sensor


Detects the presence of a main ELECTRICAL CONNECTIONS: One 1/4 in. (6 mm) quick-connect
burner flame. terminal.
MOUNTING: One 3/16 in. (5 mm) slot, three 3/16 in. (5 mm) untapped
● Includes Kanthal rod supported screw holes.
by ceramic insulator and mount-
ing bracket. Flame Rod Length
● Use with S825, S87C,D,K or
Order Number in. mm
S89E,F.
Q354A1000 2.5 64
TEMPERATURE RATINGS: Q354A1018 6 152
At electrode tip—1775 F (968 C) max.
At ceramic insulator—1250 F (677 C) max.

Ignition System Cables


Order Number Description Use With
392125—1 25 in. (635 mm) ignition cable; right angle boot/terminal at igniter end, straight S86 Family; S87 Family.
boot/terminaI at module end.
392125—2 36 in. (914 mm) ignition cable; right angle boot/terminal at igniter end, straight
boot/terminal at module end.
392437—5 36 in. (914 mm) high temperature ignition cable; right angle terminal at igniter end,
straight boot/terminal at module end.
393044 30 in. (762 mm) wiring harness; with 1/4 in. quick-connect terminals. S8600 Family.
394800-30 30 in. (762 mm) ignition cable; 90 degree boot on igniter end.
394803-2 36 in. cable with high temperature boot 750 F (400 C) on igniter end.
394801-30 30 in. (762 mm) ignition cable; straight boot on igniter end.
4074EPM Ignition cable adapter; connects S8600 family of ignition modules to existing cables
for S86 systems.