SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)

SAIC NUMBER DATE APPROVED QR NUMBER


SAUDI ARAMCO INSPECTION CHECKLIST
Prefab Buildings - Accessories and Installation Inspection SAIC-M-1033 18-May-05 CIVIL-
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.

LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.

SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?

SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Field weld connections were completed, tested and accepted through
A1 verification of the Weld Summary Report (SATR-W-2008) and the IFC IFC Drawings
Drawings.
Welding procedures and individual welders shall be qualified in
accordance with the requirements of ANSI/AWS D1.1 or AWS D1.3 for
sheet steel. All welding procedures and welding performance 12-SAMSS-014
A2
qualification records shall be made available to the Buyer's Inspector for Sec. 10.1.2
review. All welders must be properly qualified for the weld procedure of
the type of welding performed.

All fabricated structural steel shapes such as beams, columns, channels


12-SAMSS-014
A3 or tubes shall be either hot rolled, full penetration or double-sided fillet
Sec. 10.1.3
welded. Single-sided fillet welded structural shapes are not permitted.

Windows shall be designed and constructed for integral installation with 12-SAMSS-014
A4
the building system. Sec. 8.2

Window fasteners shall be non-corrosive and compatible with aluminum


12-SAMSS-014
A5 window members, trim, hardware, anchors and other components of
Sec. 8.2.2
window units.

Compression glazing strips and weather striping shall be molded EPDM,


12-SAMSS-014
A6 PVC, Polypropylene or nylon material suitable for the purpose for which it
Sec. 8.2.4
is used.

Joint caulking sealants shall remain permanently elastic, be non- 12-SAMSS-014


A7
shrinking and non-migrating. Sec. 8.2.6

Door leaves shall be a minimum of 45mm thick, full flush fabricated from
12-SAMSS-014
A8 Class G90 (Z275) zinc coated sheets or better with jamb extensions as
Sec. 8.3.1
required to provide secure attachment to the wall framing.

Each door leaf shall be provided with a three 114mm x 114mm 12-SAMSS-014
A9
galvanized steel, interlocking template butt hinges. Sec. 8.3.3

Door leaves shall be shop painted with one coat of primer or finished to 12-SAMSS-014
A10
match the walls. Sec. 8.3.4

Door Thresholds shall be extruded aluminum to provide a positive 12-SAMSS-014


A11
weather seal. Sec. 8.3.5

12-SAMSS-014
A12 All exit doors shall be a minimum of 915 mm wide by 2035 mm high.
Sec. 8.3.6

Equipment door leaves shall have steel framing and panels as specified
12-SAMSS-014
A13 for the walls and shall be adequately flashed and gasketed for weather
Sec. 8.4.1
tightness.

The leaves of sliding door's track and trolley shall be protected by a


12-SAMSS-014
A14 counter flashed hood; When closed the door shall form a weather seal
Sec. 8.4.2
with the building wall.

Page 1 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Prefab Buildings - Accessories and Installation Inspection SAIC-M-1033 18-May-05 Civil
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR

ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.

12-SAMSS-014
A15 All exterior doors shall have inside and outside locking devices.
Sec. 8.4.3

Overhead roll-up door assemblies shall include their door curtain, guides, 12-SAMSS-014
A16
counterbalances, hardware, operators and installation accessories. Sec. 8.5.1

Overhead roll-up door assemblies shall have a 3mm continuous rubber


12-SAMSS-014
A17 or neoprene sheet weather seal on metal pressure bars secured to inside
Sec. 8.5.6
of curtain coil hood.

Eave gutters shall be box shaped 0.8mm galvanized or aluminum-zinc 12-SAMSS-014


A18
coated steel supported every meter by straps 2.0mm's thick. Sec. 8.7.1

Downspouts shall be round or rectangular 0.5mm galvanized or


12-SAMSS-014
A19 aluminum-zinc alloy coated steel with a 450 elbow at the bottom and be
Sec. 8.7.2
attached to the building wall 3 meters maximum spacing.

Ventilators and roof openings shall be weather tight and shall be framed, 12-SAMSS-014
A20
braced and furnished with bird screens. Sec. 8.8

Louvers frames shall be fabricated from 1.22mm galvanized steel with 12-SAMSS-014
A21
blades made from 0.91mm galvanized steel. Sec. 8.9

Louvers are to be fixed sand trap type or adjustable by means of a crank, 12-SAMSS-014
A22
as specified in the purchase order. Sec. 8.9

REMARKS:

REFERENCE DOCUMENTS:
1- 12-SAMSS-014 -- Pre-Engineered Metal Buildings, 30 June 2002
2- AWS D1.1/D1.1M -- Structural Welding Code - Steel, January 2004
3- AWS D1.3 -- Structural Welding Code - Sheet Steel, 1 January 1998

Contractor / Third-Party Saudi Aramco


Construction Representative* PMT Representative
Work is Complete and Ready for Inspection: T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Inspector PID Representative


Performed Inspection Work / Rework May Proceed T&I Witnessed QC Record Reviewed Work Verified
Name, Initials and Date: Name, Initials and Date:

QC Supervisor Proponent and Others


Quality Record Approved: T&I Witnessed QC Record Reviewed Work Verified
Name, Organization,
Name, Sign and Date:
Initials and Date:

*Person Responsible for Completion of Quality Work / Test Y = YES N = NO F = FAILED

Page 2 of 4
SATR NUMBER DATE APPROVED DISCIPLINE
Re-Instatement Punch List Form SATR-A-2011 18-May-05 Civil
PROJECT TITLE WBS/BI/JO NUMBER CONTRACTOR/SUBCONTRACTOR

MCC No.: Test Packs No.


System Description:
ITEM Covered Originator / Completion Verified/
Description Remarks
No. Y N Agency Date Accept.

Page 3 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SATR NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
SATR-W-2008 18-May-05
Attachment 3
WELD SUMMARY SHEET

Shop
Field
Joint
No.
Drawing Line Spool Mat. Sch. Diam- Welder's NDE PMI/MPI PWHT Hardness
Item # Number No. Number Typ Thick. eter Code Test Remarks
ACC. REJ. ACC. REJ.
e

Page 4 of 4