Академический Документы
Профессиональный Документы
Культура Документы
0
Refinaria do Nordeste - RNEST Job S-01411
DK-2800 Lyngby, Denmark Hydrogen Generation Unit - U-35 Page 1 of 4
Clients Doc. No. I-FD-5290.00-2311-941-HTP-011
Specification
for
Chemicals
1. General Information
This specification covers the chemicals required within the HTAS battery limit of the
hydrogen plant.
2.1 Phosphate
2.2 Morpholine
Quality Commercial grade morpholine (tetrahydro-1,4 isoxazine) suitable
for boiler feed water conditioning. Sample and certified
specification to be submitted to the boiler vendors for approval.
The morpholine must not contain any sulphur or chlorine
compounds.
3.1 DMDS
Quality Commercial grade DMDS, max. 1% DMS
Consumption
Start-up (presulphiding new catalyst) 900 kg
Normal operation, max. 950 kg/year
Information contained herein is confidential and must not be used by or conveyed to any third party without our written authorisation - Haldor Topsøe A/S
1 Petrobras - Petróleo Brasileiro S.A. No. 4309671 Rev. 0
Refinaria do Nordeste - RNEST Job S-01411
DK-2800 Lyngby, Denmark Hydrogen Generation Unit - U-35 Page 3 of 4
Clients Doc. No. I-FD-5290.00-2311-941-HTP-011
3.2 Methanol
Quality: as per IMPCA’s specification
Consumption per:
Start-up (normal startup) 2200 kg
Start-up (with TK-250 presulphiding) 14000 kg
Shut-down 550 kg
Information contained herein is confidential and must not be used by or conveyed to any third party without our written authorisation - Haldor Topsøe A/S
1 Petrobras - Petróleo Brasileiro S.A. No. 4309671 Rev. 0
Refinaria do Nordeste - RNEST Job S-01411
DK-2800 Lyngby, Denmark Hydrogen Generation Unit - U-35 Page 4 of 4
Clients Doc. No. I-FD-5290.00-2311-941-HTP-011
4. Safety Instructions
Information contained herein is confidential and must not be used by or conveyed to any third party without our written authorisation - Haldor Topsøe A/S