Вы находитесь на странице: 1из 5

First International Power and Energy Coference PECon 2006 501

November 28-29, 2006, Putrajaya, Malaysia

Surface Potential Calculation for Grounding


Grids
Sherif Ghoneim', Holger Hirsch2, Ahdab Elmorshedy3, Rabah Amer4
l 2Institute of Power Transmission and Storage (ETS), University of Duisburg-Essen, Germany
3'4Faculty of Engineering, Cairo University,
.3
Egypt
'Email:, e;2 o .; 4rabah amer

The dissipation of the electrical current into the


Abstract: One of tasks of the grounding systems is soil is a well-known phenomenon which equations can
to maintain the voltage rise due to discharging be stated from Maxwell's Electromagnetic Theory [4].
fault current into grounding grids at the minimum Nevertheless, their application and resolution for the
value to insure the safety of public and personnel. computing of grounding grids of large installations in
The objective of the paper is to make a comparison practical cases present some difficulties.
between the addition of horizontal rods and First, no analytical solutions can be obtained for
vertical rods to the grounding grids to improve the most of real problems. On the other hand, the
performance of it. A Boundary Element Approach geometry of the grounding grids in main earthing
uses to get the numerical computation of systems (a mesh of interconnected bare conductors
grounding system analysis such as the equivalent with a relatively small ratio diameter-length) makes it
resistance and the distribution of potential on the very difficult to use standard numerical methods: The
earth surface due to fault currents. This study use of techniques commonly applied for solving
describes the importance of vertical ground rods boundary value problems in engineering, such as finite
not only decrease the grounding grid resistance but elements or finite differences, is indeed extremely
also reduce the step and touch voltages. costly since the discretization of the domain (the
ground excluding the electrode) is required. Therefore,
Index terms: Grounding grids, Boundary Element obtaining sufficiently accurate results should imply
method, Computer methods for grounding unacceptable computing efforts in memory storage
analysis, System protection. and CPU time.
In the last decades, some intuitive techniques for
grounding grid analysis such as the Average Potential
I. INTRODUCTION Method (APM) have been developed. A new
A safe grounding design has two main objectives: Boundary Element Approach has been recently
* To carry the electric currents into earth under presented [4-6] that includes the above mentioned
normal and fault conditions without intuitive techniques as particular cases. In this kind of
exceeding operating and equipment limits or formulation the unknown quantity is the leakage
adversely affecting continuity of service. current density, while the potential at an arbitrary
* To ensure that the person in the vicinity of point and the equivalent resistance for grounding grids
grounded facilities is not exposed to the must be computed subsequently.
danger of electric shock. Studying the effect of vertical grounding rods that
add to the grounding grid on earth surface potential
The problem under consideration is that the safety (ESP) is investigated in this paper. This study
values of the step and touch voltages for the human describes the importance of vertical grounding rods
that in the vicinity of the grounded facilities [1]. not only decrease the grounding grid resistance but
Ground grids are considered an effective solution also reduce the step and touch voltages.
for grounding systems for all sites which must be
protected from lightning strokes such as, II. METHOD OF CALCULATION
telecommunication towers, petroleum fields, The results in this paper are produced by the
substations and plants. Ground grids produce an equi- techniques that have been implemented in a computer
potential surfaces and should provide a very small aided design (CAD) system for grounding grids of
impedance but the ground grids are considered electrical substations called TOTBEM [4]. The
complex arrangement and many research efforts have problem focused in this paper is which the best, the
been made to explain the performance of grounding addition of vertical rods to the grounding grids or
impedance of its under lightning and fault horizontal rods to get the best performance of
conditions[2,3]. Vertical ground rods is connected to grounding grids.
the grid to have low values of ground resistance when The characteristics of the grid are 1OxI0 m2, the
the upper layer of soil in which the grid is buried, is of radius of the grid conductor ( r ) is 5 mm, the length of
much higher resistivity than that of the soil beneath. vertical rods ( Lvr ) is (land 2m), its radius of ( r, ) is
(5 and 8 mm) , the grid depth (h) is 0.5 m, the

1-4244-0273-5/06/$20.00 ©2006 IEEE


502

resistivity of the soil (p) is 100 Q.m, and the total voltage is defined as the maximum touch voltage to be
ground potential rise (GPR) is defined as 1. The found within a mesh of a ground grid. The maximum
grounding resistance has two components: the touch voltage is the difference between the GPR and
dissipation resistance which is the resistance of the the lowest potential in the grid boundary [7]. The
ground between the ground electrode and reference maximum percentage value of Vto011h is given by
ground and the resistance of the metal parts of the
ground electrode and the grounding conductor. The Vtuh00:::::Vgrid
Vtoucho gri
Vmin
m "o
x 100 (1)
last resistance is usually much smaller than the Vgrid
dissipation resistance, then the ground resistance is Where, Vgrid is the ground potential rise (GPR), which
equal to the dissipation resistance only. equal the equivalent resistance of grid multiplies in the
fault current and Vmin is the minimum surface
If potential in the grid boundary.
The step voltage is the difference in surface
-Vg= GP
potential experienced by a person bridging a distance
of 1 m with his feet without contacting any other
grounded object [7]. Furthermore, the maximum step
voltage of a grid will be the highest value of step
voltages of the grounding grid. The maximum step
voltage can be calculated by using the slope of the
secant line.
Figures 3. a, b and c. illustrate the fact that the
number of meshes has a significant effect in reducing
Fig. 1. Illustration of the grounding system (Vg is the the touch and step voltage. The surface potential in
ground potential rise (GPR), If is the fault current, Vt case of 36 meshes grid is much flatter than that grid
is the touch voltage, Vs is the step voltage and h is the with 4 and 16 meshes and hence the values of step and
burial depth of the grid). touch voltages are lowest. Also it is shown in figure 4
that an increase in the number of meshes makes the
if curve of earth surface potential much flatter and then a
reduction in the grid resistance, touch and step
voltages, also it is seen that the max touch voltage
moves towards the corner mesh in the grid.

(c) ~~~~~~~(d) I)
.1 4

Fig. 2. Different configurations of grids. (a) 4 meshes.


(b) 16 meshes. (c) 36 meshes. (d) 4 meshes with
vertical rods.
III. COMPUTATION RESULTS
In this section, the 3D graphs explain the earth Fig 3.a. 4 meshes.
surface potential along diagonal profile for the square
grid with different number of meshes.
It is clear that the ground potential rise (GPR) as
well as distribution of the earth surface potential .
-

(ESP) during the current flow in the grounding system -1.

are important parameters for the protection against


electric shock. The distribution of the earth surface
potential helps to determine the step and touch
voltages, which are very important for human safe.
By definition, the touch voltage is the difference /,
between the ground potential rise (GPR) and the
q00\ . , 1 (t
surface potential at the point where a person is
standing while at the same time having his hands in
contact with a grounded structure, and the mesh Fig. 3.b. 16 meshes.
503

addition of vertical rods plays an important part to get


the same results and decreases the cost of design.
No of meshes 36 4
I-
F.1 No. of vertical rods 0 9
Vertical rods length (m) 0 2
V, Total grid length (m) 140 78
Resistance (Q) 4.26 4.29
GPR (V) at 100 A 426 429
Max touch voltage 0/, GPR 25.0 31.1
Max touch voltage (V) 106.5 133.419
Max step voltage 00 GPR 16 16

Table 1
Fig. 3.c. 36 meshes.
450 -wthout rods
-wth rods
400
1 Mesh
1 4 Mesh y350
16 Mesh
36 Mesh C.3
.;z 300
u
P- C)
P-. 250-
.ct u
0
5 Iz!.-o 200-
;z
V.
c)
7s
150 -
PsH
v:
44 100
50

-20 -10 0 10 20
-20 -10 0 10 20 Distance from the center of grid (m) "

Distance from the center of grid (m) Diagonal Profile".


"Diagonal Profile".

Fig. 5. Effect of the vertical rods on the earth surface


Fig. 4. Effect of the number of meshes on the earth potential at the same fault current. (16 meshes)
surface potential.

IV. EFFECT OF GROUND RODS 450


Ground rods are one of the most important 400
solutions when the upper layer of the soil in which the
grid is buried, is higher resistivity than that of the
down layer. 4-y
ct ~~~300-
This section discusses the effect of ground rod
characteristics (length and radius of the rod) on earth _ / 'tt250
surface potential. It is clear from figures 5, 6 and 7
that the ground rods cause a reduction in the earth
ci
~~~200
surface potential, moreover the reduction of the grid 150
resistance, but no significant change in the earth ct
surface potential when the ground rod radius 100
-Lvr =2 m
increases.
50 -Lvr =1
The following table 1 explains that an addition of m

ground rods with 2m lengths to the 4 meshes ,,

grounding grid for the case of study gives nearest -20 -10 0 10 20
results when add the horizontal conductors to the same Distance from the center of grid (m) "

grid. The difference in the max touch voltage between Diagonal Profile".
the two cases is 26.919 V but the difference in the
total length of conductors is 62 m as shown from the
table and hence, an increase in the cost of design Fig. 6. Effect of the vertical rod length on the earth
occurs when add horizontal rods. Therefore the surface potential at the same fault current. (16 meshes)
504

VII.ACKNOWLEDGEMENT
450 -rvr= 0.008 m The authors gratefully acknowledge the help in
-rvr= 0.005 m the grounding analysis of Prof. Ignasi Colominas from
the Civil Engineering School of the University of La
350
Coruna (Spain).
300
0 250 VIII. REFERENCES
0ta) 200
150 [1] S. Benda, "Earthing and Bonding in Large
100 Installations", ABB Review, No. 5, pp. 22-29,
50 1994.
As [2] R. Verma and D. Mukhedkar, "Fundamental
-20 -10 0 10 20
Considerations and Impulse Impedance of
Ground Grids", IEEE Transaction on Power
Distance from the center of grid (m) "Diagonal Apparatus and Systems, Vol. Pas-100, pp. 2053-
Profile".
2059, March 1981.
[3] F. Menter and L. Gercev, "EMTP-Based Model of
Grounding System Analysis" IEEE Transactions
Fig.7. Effect of the vertical rod radius on the earth on Power Delivery, Vol. 9, pp. 1838-1849, Oct.
surface potential at the same fault current. (16 meshes) 1994.
[4] I. Colominas, F. Navarrina, M. Casteleiro, "A
V. EFFECT OF GRID DEPTH Boundary Element Numerical Approach for
The results explained that the grid depth plays an Earthing Grid Computation", Computer
important role in decreasing the grid resistance and the Methods in Applied Mechanics &
earth surface potential, this fact appears in figure 8. Engineering, vol. 174, pp 73-90, 1990.
[5] I. Colominas, F. Navarrina, M. Casteleiro, "A
Depth 0.5 m
=
Numerical Formulation for Grounding Analysis
450 Depth 0.8 m
= in Stratified Soils", IEEE Transactions on Power
Depth 1 m
=
Delivery, vol. 17, pp 587-595, April 2002.
50- [6] F. Navarrina, I. Colominas, " Why Do Computer
Methods for Grounding Analysis Produce
300 Anomalous Results?," IEEE Transaction on
o ~~~~250- power delivery, vol. 18, No. 4, pp 1192-1201,
o
200 October 2003.
[7] IEEE Std.80, "IEEE Guide for safety in AC
150- substation grounding", New York, 2000.
100
50 IX. BIOGRAPHIES
Sherif Ghoneim (PhD student): Received B.Sc. and
-20 -10 0 10 20 M.Sc. degrees from the Faculty of Engineering at
Distancefrom the center of grid (m) Shoubra, Zagazig University, Egypt, in 1994 and
"diagonal profile". 2000, respectively. Starting from 1996 he was a
teaching staff at the Faculty of Industrial Education,
Suez Canal University, Egypt. Since end of 2005 he is
Fig. 8. Effect of grid depth on the earth surface a guest researcher at the Institute of Energietransport-
potential at the same fault current. (16 meshes) und Speicherung (ETS) of the University of Duisburg-
Essen, under the supervision of Prof. Dr.-Ing. Holger
VI. CONCLUSIONS Hirsch. His research focuses in the areas of earth
This paper aims to explain the role of the vertical surface potential calculation and improving designs of
ground rods that add to the grounding grid in reducing grounding grids.
the value of grid resistance, step and touch voltages to
a value that is safe for public and human. Additional Holger Hirsch (Prof. Dr.-Ing.): After his PhD from
vertical ground rods gives nearest results to that the University of Dortmund, Germany, he had worked
results when add the horizontal rods to the same grid, as head of EMC Test NRW GmbH, Dortmund,
then the addition of vertical rods to the grounding grid Germany. He became full Professor at the same
gives a good performance and decrease the cost of university in 1998 where he taught theoretical and
design. The grid resistance and ground potential rise practical EMC subjects until 2003. Since beginning
decrease with the increase of the burial depth and 2003 he is the head of the Institute of
number of meshes of the grounding grids. Energietransport- und Speicherung (ETS) of the
University of Duisburg-Essen, Germany, where he is
505

engaged in the teaching, testing and measurement


techniques of EMC and HV systems and equipment.
He is a member of different workgroups of CISPR,
IEC, ETSI and DKE.
Ahdab Elmorshedy (Member IEEE): received the
B.Sc., M.Sc. and Ph.D. in 1971, 1974, and 1978
respectively, in Electrical Engineering, from Cairo
University, Egypt. Since 1971, she joined the faculty
of Electrical Engineering at Cairo University, Egypt as
a Teaching staff. During the academic years of 1979
to 1981, she was a research scientist in the Department
of Electrical Engineering, College of Engineering at
Ohio State University, Columbus, Ohio, U.S.A. Since
1988 she was a Professor at the Department of
Electrical Engineering, Cairo University. Her research
activities include grounding, protection and safety of
power systems, over-voltage transients, and pollution
of insulators.
Rabah Amer: received the B.Sc., M.Sc. and Ph.D. in
1975, 1979, and 1983 respectively, in Electrical
Engineering, from Cairo University, Egypt. Since
1975, he joined the faculty of Electrical Engineering at
Cairo University, Egypt as a Teaching staff. Since
1994 he was a Professor at the Department of
Electrical Engineering, Cairo University. His research
activities include grounding, gas discharge, electric
and magnetic field calculations, prediction of
polluted insulators flashover using laser methods,
lightning protection of petroleum companies, and
overhead transmission line design and commissioning.
Also, he is a consultant for petroleum, industrial and
electrical companies.

Вам также может понравиться