Академический Документы
Профессиональный Документы
Культура Документы
This handout addresses phase lead compensators and improved damping, specifically.
Phase lead compensators are placed in cascade, in the forward path, and are used to
manipulate the phase margin. Phase lead compensators shift Bode phase plots of
KGH(jw) (open loop transfer function) upward in a desired frequency range. This
increases phase margin, which improves damping, as described below. Fundamentally
a phase lead network is beneficial because often other (electromechanical) components
introduce phase lag, due to inertia and inductance. The phase lead network counters
these plant dynamics. Improvements from compensation are illustrated in Figure 1.
Figure 1. Bode plots (above) before and after compensation (l. to r.) and corresponding
step responses (below). The magnitude curve on the Bode plots is darker and phase curve
lighter. Improved damping of the step response is evident in the lower right, with reduced
overshoot and reduced settling time.
Adjusting phase margin to achieve a given damping ratio is relatively easy because (an
approximate) linear relationship exists: φ pm = 100 o ξ (degrees). See Figure 2.
Figure 2. An approximate, linear relationship exists between damping ratio and phase
margin. This is useful when selecting new phase margins in compensator design. From
“Modern Control Systems” by Dorf.
• Phase Change / Time Delay Perspective: As the phase lag increases around
the open loop, it can potentially reach 180o. Such a phase change, together with
the normal negation of a feedback control system amounts to positive feedback
and an unstable response. Adding a phase lead filter in the forward path
reduces the accumulated phase. Note that even though the open loop phase
change reaches 180o for only one frequency, real signals typically contain (at
least a bit of) energy at all frequencies. Any nonzero amount would begin the
positive feedback process, causing the output to grow without bound.
• Bode Perspective: Given that phase margin is linearly related to damping, the
phase margin is readily adjusted by adding a compensation block to the forward
path. This shifts the phase margin, improving damping.
• Root Locus Perspective: When poles or zeros are added to the forward path
these shift the root locus curves – by changing the number of asymptotes or
asymptote center. Hence adding a compensator can redirect the locus to regions
of the S-plane with greater damping, for example. See Figure 4.
Figure 4. Root locus curves before and after compensation (l. to r.). The compensator adds
a real pole and zero. This shifts the curves away from the jw axis, increasing the amount
of damping that may be achieved. Closed loop pole locations of the more dominant poles
are indicated for gain values of K=30 and K=90.
(a) (b)
(c) (d)
Figure 5. Step response associated with varying gain values: K=30, 50, 70, 90 are shown
in (a,b,c,d) respectively. Rapid settling is obtained despite variations in gain, compared to
the uncompensated system.