30, 60, 100, 150, 300 A

Three phase

State-of-the-Art active filter, that dynamically


cleans up Harmonics and improves Power
Factor, for all types of electrical installations.
It has dynamic control feature and has no
resonance effect, no reactive power
circulation, no passive components.

Core Competence in Power Electronics


Reduction in kVA demand

INTRODUCTION FEATURES
The huge gap between demand and supply has put extra ordinary w Synchronous Rotating Reference Frame principle
stress on Electrical Supply systems. They are stretched beyond its
limits, which gave rise to several Power Quality related issues.
w 32 bit, DSP control
Hence, it has become important to pay highest attention towards w Internal CAN Communication
efficient and effective use of power. All the possible leakages, from w Employs high speed IGBTs in power circuit
source to the distribution point, are to be avoided by taking integrated
solution approach. w Closed loop active filter with source current sensing

Earlier the poor power factor was considered to be the only w High attenuation up to 96% of individual harmonics
parameter responsible for making electrical system inefficient. More w Programmable selective harmonic elimination
emphasis was given on the solutions, like use of PF correction
w PF compensation, leading as well as lagging
capacitors etc. to improve the power factor. SEB’s apply penalty on
the users, if they fail to maintain PF. However, this does not address w Load balancing
the real problem of high percentage of harmonics getting injected into w PF can be programmed from 0.7 to unity
the supply line, and deteriorating power quality. It actually pollutes the
w Selection between PF and harmonic compensation
whole power supply system.
The increased level of current harmonics is the result of phenomenal w Remote monitoring and diagnosis
growth of Industrial and IT establishment in recent past. The power w Self current limiting, under overloading condition
consumption pattern has totally changed, due to the nature of electric
w Automatic current limit modification with respect to
power consuming equipment employed by these establishments.
ambient temperature
The Industrial and Commercial applications are increasingly make
use of large number of PCs, Servers, UPSs, AC / DC drives, w Helps compliance to IEEE 519
Rectifiers, Chargers, SMPS, CFL lamps, etc. These equipments w IEC / EN 62040 - 2 category C3
draw current which is non-sinusoidal in nature, which categories
w User friendly PC interface
them as non-linear loads. These non-linear loads, puts extensive
stress on Electrical distribution system, by generating harmonic w CE marking
currents. w Alarm log with date and time stamp for fault diagnosis
The high level of harmonics, lowers the power factor, affects the
power usage and reduces component life. They also affect
performance of DG sets, transformers, cables and switch gears and
causes great drain on the power supply.
The harmonic pollution can be effectively controlled by making use of
+
Swan Active Harmonic filter
+
Swan is solid state, State-of-the-Art designed filter, which measures
level of current harmonic in supply line and eliminates it by generating
the counter harmonics. The control and reduction of harmonics
improves the power quality in multi-folds, making the electrical
distribution system highest efficient. The power savings to the tune of
10 to 40% is possible, depending on the applications.
+
Swan developed by DB , is useful for end users as well as to the
power supply companies. For the user, it helps in optimizing use of
available power, increases productivity, decrease utility charges and
+
improves equipment reliability. In fact Swan has many more
unparalleled features ; it is the single answer on power quality issues
for all types of applications.

Perfect solution for Datacenter, IT, Industrial & Medical applications


OPERATING PRINCIPLE +
Swan uses latest technology to eliminate harmonics injected
into the mains supply by non-linear loads, as well supplies
Fundamental only idistortion
Supply inductive power demanded by the load so as to correct input
Load power factor to near unity.
icompensation Current harmonic elimination is achieved by sensing load
current and extracting harmonic current signal. This, and the
Swan
reactive current signal, together are used to generate a
reference for the controlled current source connected at the
PCC (Point of Common Connection) of source and load. This
results in mains supplying only real power for the load and
reactive & harmonics being sourced from the Swan+. This is
carried out dynamically, so that any change in the load pattern
Waveforms

or its nature is immediately responded without any manual


intervention.
In the following example first Figure shows the recorded input
Clean
Load
current + Swan
current
Feeder
current
current waveform of a Six pulse thyristorised rectifier.
Bottom figures show considerable improvement in the
Harmonics

waveform due to Swan+, connected in shunt.


One is with only harmonic correction and the other is with
power factor & harmonic correction.

Without Active Filter


THDi = 27.4 % PF = 0.87

Only Harmonic Correction


THDi = 4.0 % PF = 0.92

PF + Harmonic Correction
THDi = 3.9 % PF = 1.00
Better utilization of distribution
Transformer & Generator

SPECIFICATIONS

Model SWAN+ 30 SWAN+ 60 SWAN+ 100 SWAN+ 150 SWAN+ 300


Input Voltage range 400 V, 3 Ph+N (+10 %, – 15 %)
Input Frequency range 50 Hz (± 10 %) (60 Hz Optional)
Capacity 30 A 60 A 100 A 150 A 300 A
Harmonics Filtering Non-zero sequence 2nd to 50th Harmonic compensation
(Any 20 Harmonics individually selectable) Attenuation ratio up to 96 %

Power Loss in filter < 1000 W < 2200 W < 3600 W < 5100 W < 7200 W
Enclosure Protection IP 40 (IP 41 optional)
Approx Weight 120 kg 180 kg 285 kg 285 kg 600 kg
Colour RAL 7035
Installation Floor / Wall mounted Floor mounting
Cable entry from Bottom, Front Side (top entry optional)
Acoustic Noise Level < 65 dBA @ 1.0 meter (Ref. ISO 3746)
Operating Temperature 0 to 40 O C
Relative Humidity Upto 95 % (Non-condensing)
Interface (Optional) Remote monitoring through MODBUS, SNMP, HTTP Web Browser,
Ethernet based monitoring through E-DAPCMON, LIFENET
Standards Meets IEEE 519 for compensated harmonics
IEC / EN 62040-2 Category C3, EN 50178
Potential free contacts Filter Trip and Filter ON
Dimensions in mm 585 x 310 x 700 800 x 600 x 1000 800 x 600 x 1600 800 x 600 x 1600 1200 x 900 x 1600
+ 100 + 150 + 150 + 150 + 150
(W x D x H) + Plinth
Current Transformer 500 A : 5 A 1000 A : 5 A 3000 A : 5 A , 3000 A : 5 A 5000 A : 5 A
15 VA, Class 1 15 VA, Class 1 15 VA, Class 1 15 VA, Class 1 15 VA, Class 1
with short link with short link with short link with short link with short link

+
Note : Consider SWAN N model (available up to 150 A) for Zero Sequence triplen harmonic compensation. Please contact Technical Support Group.

OLED based graphics display showing


i Harmonic spectrum up to 64th harmonics of Line Current
i True measurement of Line Voltage, Current, kVA, kW , Power Factor
i Waveform display - Showing real time visual of Line Current & Voltage
i Harmonics & PF configuration

Remote Monitoring & Diagnosis


Load Current i All front display parameters including waveforms can be monitored through PC
i Supports MODBUS protocol for integration with MODBUS compliant software
i Life.NET compatibility* i.e. parameters can be monitored remotely through
telephone line
i Potential free contacts for monitoring the status of the filter
i Inbuilt Ethernet based TCP/IP, HTTP, SNMP Support *

* Optional

Harmonic Spectrum
Increases efficiency, capacitor life, PF, uptime...

SWAN+ : Sizing Calculation

An easy to use software has been designed by DB Power


for calculating the rating of the Active Harmonic filter, Swan+.
For sizing the AHF following data should be available ;
- Present load current
- Measured value of THDi
- Power consumed
- Input PF measured
- Phase to phase voltage
After inputting the above data, define how much PF compensation is
required in percentage or the actual value for the installation and then click the 'calculate' button. The software
calculates required current rating of Swan+ and the effective power factor of the installation, after the Swan+ is
connected.

Connectivity Diagram

Active Harmonic Filter

Life Adaptor
Card MODEM
Telephone Line
Serial
RS 232
Cable
Link
Telephone Exchange
Communication
Interface Card
(Inbuilt in AHF)
RS 232 MODBUS
Main monitoring Life Station
Ethernet Link

Ethernet Link

PC for
LIFENET
Settings
BMS Software

E-DAPCMON

SNMP MIB Browser Web Browser

Swan has innate quality of separating milk from water.


This special quality of separating two mixed identities,
which otherwise is not easy, has inspired us to name
this State-of-the-art Active Filter as Swan.

Swan+, an active filter, cleans up electrical power and sets


free load (& the user) from the harmonic pollution !
Freedom from Harmonic pollution

Application area

At the input side of Rectifier, AC Drive, UPS


Harmonic & PF compensation
Mains source w To reduce harmonics and improve power factor of
UPS, Rectifiers, AC & DC drives etc.
w To improve PF of motor loads
6 Pulse (i.e. inductive loads)
12 Pulse
Rectifier,
uncontrolled w Can be used at the output of UPS, to reduce
or controlled harmonic effects on UPS and increase available
capacity. UPS will supply only fundamental and
active power.
w Can be used as Hybrid filter
PF Compensation i.e. it can be used along with passive filter and
capacitor filter, resulting in reduction of
cost and rating of active filter.
Mains source
Unity PF Lagging PF Motor w A single unit can be used
Load
at the input of multiple UPSs
e.g. 60 A filter is sufficient
for 160 kVA DB Synergyi UPS
and the same can be used for 4 nos of 40 kVA.

At the source input

Load
2
Mains source

Load
4

Load Load
1 3

Load 1 to 4
are non linear loads
atulrk@gmail.com

120/37, Ramtekdi Industrial Area, Hadapsar, Pune 411 013 (India)


T +91 20 30469200 F 3046 9214 E sales@dbups.com SÜD

ISO 9001 : 2000


MK-IND-CAT-Swan -R3-1010

Western Region • Mumbai • Nagpur • Aurangabad • Goa • Kolhapur • Nashik • Indore • Bhopal • Vadodara • Ahmedabad • Surat • Silvasa • Jamnagar
Southern Region • Hyderabad • Vizag • Vijayawada • Chennai • Madurai • Coimbatore • Bengaluru • Mangalore • Cochin • Trichy
+

Eastern Region • Kolkata • Patna • Bhubaneshwar • Jamshedpur • Raipur • Raigarh • Guwahati • Siliguri
Northern Region • New Delhi • Mohali • Gurgaon • Noida • Lucknow • Jaipur
Overseas Partners • Italy • France • UK • Sri Lanka • Nepal • Bangladesh • Saudi Arabia

R&D being continuous process, the specifications are subject to change without prior notice.
www.dbups.com