Water-Cooled

Screw Chiller
A i r Co n d i t i o n i n g S y s t e m

R134a
100 to 350RT
New Dream, New Start
To become a leader in the competitive global market, LG has been divided into
three groups, electronics and chemicals for LG, energy and machineries distribu-
tion for GS, Industrial electric · electronic materials for LS based on their business
specialties.

LS' main companies, such as LS Mtron, LS cable, LS industrial systems, LS-


Nikko copper, Gaon cable, E1 and Kukdong City gas, are ranked as No.1 in their
respective industry. However, LS won't just sit back, satisfied with being the best
in Korea. We will pave the way for becoming the world's best in Industrial electric ·
electronics and material industry with the new CI, LS.

Your best partner LS Cable is making a


fresh start as LS Mtron
LS Mtron is No.1 machinery maker in Korea and its business fields are components
& materials and machinery. Also, LS Mtron is creating new businesses particularly in
component and materials industry. LS Mtron makes its best to accomplish the vision,
'Your No.1 Creative Partner' and be one of the world leaders with high technology
and best level of service.

Research &
Development

Tractor Components &


Materials Business

Injection Molding
System
Air-Conditioning
System
MAIN CHARACTERISTICS

The high-performance screw chiller is designed Advanced control algorithm is adopted to control
AIR CONDITIONING SYSTEM
depending on 30 years research & development chiller in advance and hence avoid frequent
experience of LS Air-Conditioning System. stoppage protection of chiller.

High-performance compressor manufactured by We have set complete safety protection function


specialized manufacturer is adopted to ensure in order to make chiller safely and reliably run.
that the chiller is economical and durable with
low vibration and low noise. The linkage control and remote monitoring
function of peripheral equipments ensure that
The primary and secondary selection function the chiller can run safely and the operation and
the double-head chiller compressor evenly used monitoring are convenient.
and hence the service life of entire machine is
prolonged. The selection of excellent raw materials and
fittings is the key to guaranteeing chiller quality.
Highly integrated motherboard is adopted and
hence the function is strong and reliable. The product is divided into flooded screw chiller
SFWW and dry screw chiller SWW.

Model description

S F W W X X X S A S 3 Y S
Application :
S-air-condition,
L-low temperature

Starting mode : S-direct start, Y-Y-,


I-conversion start
Power : 2-220V 50Hz, 3-380V 50Hz
4-440V 50Hz, 5-220V 60Hz
6-380V 60Hz, 7-440V 60Hz
Unit type : E- conversion, N- external oil distributor
S-Iinner oil distributor, M-downward film type

Refrigerant : A-R134a

Compressor No. : S-1set, D-2sets, T-3sets, F-4sets

capacity : (RT)

Evaporator : W-water cooled tube and shell type, P-plate exchanger

Condenser : W-water cooled tube and shell type, P-plate exchanger

evaporation mode : F-flooded

Semi-closed screw chiller

Model explanation
SFWW-320DAS-3YS
This is a flooded double screw chiller which is Water-cooled ,with R134a as refrigerant and made in
LS Air-conditioning system (Shandong) Co., Ltd. It’s nominal capacity is 320USRT

4
SPECIFICATION

R134a (50Hz)
MODEL UNITS SFWW- SFWW- SFWW- SFWW- SFWW- SFWW- SFWW-
100SAS 110SAS 120SAS 140SAS 160SAS 180SAS 230SAN
USRT 94.1 112.1 120.7 137.4 160.3 172.6 226.0
Capacity Kw 331.1 394.3 424.4 483.4 563.8 607.1 795.0
104kcal/h 28.5 33.9 36.5 41.6 48.5 52.2 68.4
Power input kw 67.6 79.1 85.0 97.5 109.9 118.3 154.9
Power - 3PH-380V-50HZ
Rated Current A 113.7 133.0 142.8 163.8 184.8 198.9 260.5
Comp. Starting current A 265.3 310.3 333.2 382.3 431.2 464.1 607.8
Number SET 1
Starting mode - Y-∆
T-Inlet /outlet °C 32-37
Cooling Flow m3/h 69 81 88 100 116 125 163
water Pressure kgf/cm2 0.58 0.57 0.59 0.60 0.58 0.61 0.63
Diameter DN 100 100 100 125 125 125 150
T-Inlet/outlet °C 12-7
Chilled Flow m3/h 57 68 73 83 97 104 137
water Pressure kgf/cm2 0.48 0.44 0.45 0.46 0.44 0.46 0.48
Diameter DN 100 100 100 125 125 125 150
L mm 4300 4300 4300 4326 4326 4326 4351
Dim. W mm 1521 1521 1521 1571 1571 1571 1627
H mm 1636 1749 1749 1815 1815 1815 1964
Transporting ton 2.4 2.8 3.0 3.5 3.5 3.6 4.1
Weight
Running ton 2.6 3.2 3.4 3.9 3.9 3.9 4.7
Weight kg 125 150 150 180 180 180 280
Ref.
Type - R134a
Frozen Volume L 18 23 23 28 28 28 95
oil Trademark - CP-solest-220

MODEL UNITS SFWW- SFWW- SFWW- SFWW- SFWW- SFWW- SFWW- SFWW-
270SAN 310SAN 190DAS 230DAS 250DAS 280DAS 320DAS 350DAS
USRT 264.8 308.0 188.3 224.2 246.2 274.9 320.6 345.2
Capacity kw 931.5 1083.2 662.2 788.7 865.8 966.7 1127.5 1214.2
104kcal/h 80.1 93.1 56.9 67.8 74.4 83.1 96.9 104.4
Power input kw 179.3 207.4 135.2 158.2 170.0 194.9 219.8 236.6
Power - 3PH-380V-50HZ
Rated Current A 301.5 348.7 113.7*2 133.0*2 142.8*2 163.8*2 184.8*2 198.9*2
Comp. Starting current A 703.5 813.6 265.3*2 310.3*2 333.2*2 382.2*2 431.2*2 464.1*2
Number SET 1 2
Starting mode - Y-∆
T-Inlet /outlet °C 32-37
Cooling Flow m3/h 191 222 137 163 178 200 232 249
water Pressure kgf/cm2 0.62 0.61 0.61 0.62 0.57 0.58 0.55 0.56
Diameter DN 150 200 150 150 150 150 200 200
T-Inlet/outlet °C 12-7
Chilled Flow m3/h 160 186 114 136 149 166 194 209
water Pressure kgf/cm2 0.47 0.47 0.42 0.44 0.43 0.47 0.45 0.46
Diameter DN 150 200 150 150 150 150 200 200
L mm 4393 4393 4430 4430 4393 4393 4522 4522
Dim. W mm 1846 1846 1681 1681 1785 1785 1891 1891
H mm 2105 2105 1845 1845 1941 1941 1990 1990
Transporting ton 4.3 4.5 4.1 4.6 5.2 5.4 6.1 6.3
Weight
Running ton 4.9 5.1 4.4 4.9 5.6 5.8 6.5 6.7
Weight kg 280 280 210 210 245 245 290 290
Ref.
Type - R134a
Frozen Volume L 114 114 36 46 46 56 56 56
oil Trademark - CP-solest-220

1. 1RT = 3024kcal/h = 3.517kw, 1mH2o = 9.8kpa


2. Fouling factor of water in condenser and evaporator is 0.086m2 k / kw
3. Maximum pressure of chilled water and cooling water system 10kgf/cm2
4. Specifications subject to change without prior notice

L S W A T E R - C O O L E D S C R E W C H I L L E R 5
SPECIFICATION

R134a (60Hz)
MODEL UNITS SFWW-110SAS SFWW-130SAS SFWW-145SAS SFWW-165SAS SFWW-190SAS SFWW-200SAS
USRT 110.9 132.1 145.1 167.0 188.9 203.4
CAPACITY kw 390.1 464.7 510.2 587.25 664.3 715.5
104kcal/h 33.5 40.0 43.9 50.5 57.1 61.5
POWER INPUT kw 80.1 93.7 100.7 115.5 130.3 140.2
Power - 3PH-380V-60Hz
Rated Current A 134.7 157.6 169.2 194.1 219.0 235.6
COMP. Starting current A 314.3 367.7 394.8 452.9 511.0 549.7
Number SET 1
Starting mode - Y-D
T-Inlet /outlet °C 32-37
COOLING Flow m3/h 81 96 105 121 137 147
WATER Pressure kgf/cm2 0.80 0.84 0.90 0.79 0.82 0.91
Diameter DN 100 125 125 125 125 125
T-Inlet/outlet °C 12-7
CHILLED Flow m3/h 67 80 88 101 114 123
WATER Pressure kgf/cm2 0.60 0.60 0.61 0.61 0.63 0.63
Diameter DN 100 125 125 125 125 125
L mm 4290 4290 4290 4290 4290 4320
DIM. W mm 1200 1200 1200 1300 1300 1400
H mm 1800 1850 1850 1900 1900 1900
Transporting ton 2.8 3.0 3.5 3.5 3.6 3.8
WEIGHT
Running ton 3.2 3.4 3.9 3.9 3.9 4.2
REF. Trademark - R134a
FROZEN Volume L 18 23 23 28 28 28
OIL Trademark - CP-solest-220

MODEL UNITS SFWW-220DAS SFWW-260DAS SFWW-290DAS SFWW-330DAS SFWW-380DAS SFWW-410DAS


USRT 221.8 264.3 290.1 333.9 377.8 406.9
Capacity Kw 780.2 929.4 1020.4 1174.5 1328.6 1431.0
104kcal/h 67.1 79.9 87.7 101.0 114.2 123.0
Power input kw 80.1*2 93.7*2 100.7*2 115.5*2 130.3*2 140.2*2
Power - 3PH-380V-60Hz
Rated Current A 134.7*2 157.6*2 169.2*2 194.1*2 219.0*2 235.6*2
Comp. Starting current A 314.3*2 367.7*2 394.8*2 452.9*2 511.0*2 549.7*2
Number SET 2
Starting mode - Y-D
T-Inlet /outlet °C 32-37
Cooling Flow m3/h 162 192 210 242 273 294
water Pressure kgf/cm2 0.84 0.85 0.89 0.86 0.89 0.91
Diameter DN 150 150 150 200 200 200
T-Inlet/outlet °C 12-7
Chilled Flow m3/h 134 160 175 202 228 246
water Pressure kgf/cm2 0.63 0.65 0.65 0.66 0.66 0.67
Diameter DN 150 150 150 200 200 200
L mm 4320 4320 4470 4470 4650 4650
Dim. W mm 1400 1400 1580 1580 1700 1700
H mm 1950 1950 2010 2010 2040 2040
Transporting ton 4.6 5.2 5.4 6.1 6.5 6.5
Weight
Running ton 4.9 5.6 5.8 6.5 6.9 6.9
Ref. Trademark - R134a
Frozen Volume L 36 46 46 56 56 56
oil Trademark - CP-solest-220

1. 1RT = 3024kcal/h = 3.517kw, 1mH2o = 9.8kpa


2. Fouling factor of water in condenser and evaporator is 0.086m2 k / kw
3. Maximum pressure of chilled water and cooling water system 10kgf/cm2
4. Specifications subject to change without prior notice

6
INSTALLATION AND DIMENSION

Chiller room requirements


The design and location of central air conditioner room is a comprehensive work, which must be closely coordinated
with architecture, structure, water supply and drainage, building electricity and other professional work.

1. The air conditioner room should be located as near 7. When the central air conditioner room is located in the
as possible to the cooling load center. For High-rise basement, it Space between equipments in machinery
buildings with basement available for use, it should be room should be equipped with mechanical ventilating
located in the basement; for super high-rise building, equipment and the least air displacement of such
it may be located at middle floor (technical equipment equipment should not less than 36.5G2/3(m3/H), where: G
floor) in accordance with system division; for air is the total cooling capacity of chiller. In order to reduce
conditioning modification or addition works, it may also be air displacement under non-emergency conditions, it is
reconstructed outside air conditioning building or located recommended to use multi-speed blower. The inlet and
at the roof or other place of air conditioning building, conduit of exhausting blower should be near to chiller
while it must be guaranteed that the building structures with proper protection.
have enough bearing capability.
8. The central air conditioner room inside should be
2. The equipments in the air conditioner room should be equipped with water discharging facilities and toilets
arranged closely to save covered building area. The and if available, with telephone. Also, emergency lighting
equipment arrangement and pipe connection should should be taken into consideration.
accord with technological flow requirement and be easy
to install, maintain and repair. 9. The inflammable and explosive materials are not allowed
to be stored in the air conditioner room except refrigerant
3. When the tube shell and the heat exchanger of chiller existing in the chiller.
are arranged, the possibility to clean and replace tube
nest should be considered. Generally, a space with length
equal to chiller length will be left on one end of chiller. If
there is no enough space, one end of chiller in the length
direction may be directly faced to window with proper
height for lighting or to gate with proper height.
Space between equipments in machinery room
ITEMS SPACE (M)
4. The air-conditioner room should be made of Grade II
Width of main channel and operation channel >1.5
refractory materials or incombustible materials with good
Distance between jut of chiller and switch-house >1.5
sound insulation property. The room should have two Distance between jet of chiller >1.0
exits as far as possible from each other, of which at least Distance between chiller and wall >0.8
one should directly face to outside. Also, the direction of Width of subordination channel >0.8
opening should be towards the outdoor. Distance between side jut of the chiller >1.5
Distance between sides of absorption chill and wall >1.2
5. please refer to Air conditioner Room Guaranteed Space
for room height.

6. The host air conditioner in the central air conditioner


room should be separated from pump room and control
room and the repairing room and storage room should
be arranged in accordance with practical conditions. If
there are fuel absorption chiller or fuel central water
heater in the air conditioner room, the idlest method is
to obtain fuel from special oil depot through oil pipeline.
If the fuel tank is placed in the room, then the floor
arrangement should strictly follow relative fire codes and
the house should be equipped with necessary fire-fighting
equipments.

L S W A T E R - C O O L E D S C R E W C H I L L E R 7
INSTALLATION AND DIMENSION

Installation and size


Installation requirements
The installation space should be considered when the chiller are installed in order that LS service personnel are convenient
to dismantle and hoist compressors and other parts. The minimum space can be determined in accordance with the table
below. For multiple chiller, the space between two chiller should be not less than 120% that of single chiller. If the room
space is too small, please contact LS for consultation and solution.

During installation, special attention should be paid to :


1. The water pump should be installed on the side of inlet of cooled water/cooling water, if it needs to install on the outlet side, please contact LS.
2. The two sides of water pump should be installed with flexible connection to insulate pipe vibration. For water pump, the speed 2900RPM should be not
chosen to the extent possible in case of resonance.

TYPE MODEL A B C D E
SFWW100SAS~SFWW120SAS 1500 3600 1500 1200 1000
R134a
SFWW140SAS~SFWW310SAN 2000 3600 2000 1200 1000
(50Hz)
SFWW190DAS~SFWW350DAS 2500 2500 2000 1500 1500
SFWW110SAS~SFWW130SAS 1500 3600 1500 1200 1000
R134a
SFWW140SAS~SFWW360SAS 2000 3600 2000 1200 1000
(60Hz)
SFWW220DAS~SFWW410DAS 2500 3600 2000 1500 1500

8
DIMENSION OF FLOODED TYPE SCREW CHILLER

R134a(50Hz) - Single compressor series

MODEL L W H E A B C D
SFWW100SAS 4300 1521 1636 563 683 443 485 695
SFWW110SAS~120SAS 4300 1521 1749 613 650 410 510 700
SFWW140SAS~180SAS 4326 1571 1815 663 658 418 485 695

L S W A T E R - C O O L E D S C R E W C H I L L E R 9
DIMENSION OF FLOODED TYPE SCREW CHILLER

R134a(50Hz) - Dual compressor series

Model L W H E A B C D
SFWW190DAS~SFWW230DAS 4430 1681 1845 718 730 430 550 830
SFWW250DAS~SFWW280DAS 4393 1785 1941 770 840 540 615 875
SFWW320DAS~SFWW350DAS 4522 1891 1990 823 840 490 567 867

10
DIMENSION OF FLOODED TYPE SCREW CHILLER

R134a(50Hz) - Single compressor series

MODEL L W H E A B C D
SFWW230SAN 4351 1627 1964 718 730 430 550 830
SFWW270SAN~SFWW310SAN 4393 1846 2105 798 867 567 540 840

L S W A T E R - C O O L E D S C R E W C H I L L E R 11
DIMENSION OF FLOODED TYPE SCREW CHILLER

R134a(50Hz) - Single compressor series

MODEL L W H E A B C D
SFWW110SAS 4290 1200 1800 613 625 385 668 792
SFWW130SAS~145SAS 4290 1200 1850 663 650 410 703 523
SFWW165SAS~190SAS 4290 1300 1900 663 673 433 728 518
SFWW200SAS 4320 1400 1900 718 700 450 750 530

12
DIMENSION OF FLOODED TYPE SCREW CHILLER

R134a(50Hz) - Dual compressor series

MODEL L W H E A B C D
SFWW220DAS~SFWW260DAS 4320 1400 1950 718 730 430 833 650
SFWW290DAS~330DAS 4470 1580 2010 770 805 455 900 710
SFWW380DAS~410DAS 4650 1700 2040 823 805 455 900 755

L S W A T E R - C O O L E D S C R E W C H I L L E R 13
FOUNDATION

R134a - Flooded screw chiller

Notes:
1. Floor installation is the standard installation mode of chiller. For floor installation, the rubber shock pad along with the chiller should be installed.
2. For floor installation, please refer to building codes for floor requirements and fixation methods of foundation bolt.
3. Spring damper should be installed when the chiller floor is installed, which should be noted in the contract to purchase during purchase of chiller.
4. It should be guaranteed that the horizontal tolerance in the direction of the whole length and width of chiller should be less tan 3mm.
5. After the chiller is leveled, the respective space of each spring damper should be not less than 6mm.

TYPE MODEL A B C D
SFWW100SAS 4250 3824 1371 971
SFWW110SAS ~SFWW120SAS 4250 3824 1471 1071
SFWW140SAS ~SFWW180SAS 4250 3824 1571 1171
R134a SFWW230SAN 4250 3824 1681 1281
(50Hz) SFWW270SAN~310SAN 4250 3824 1891 1491
SFWW190DAS ~SFWW230DAS 4250 3824 1681 1281
SFWW250DAS ~SFWW280DAS 4250 3824 1785 1385
SFWW320DAS ~SFWW350DAS 4250 3824 1891 1491
SFWW110SAS ~SFWW145SAS 4250 3824 1450 1017
SFWW165SAS ~SFWW190SAS 4250 3824 1550 1121
R134a SFWW200SAS 4250 3824 1650 1225
(60Hz) SFWW220DAS ~SFWW260DAS 4250 3824 1650 1225
SFWW290DAS ~SFWW330DAS 4250 3824 1800 1385
SFWW380DAS ~SFWW410DAS 4250 3824 1900 1491

14
PIPELINE AND ACCESSORY FACILITIES

Pipeline and accessory facilities

Construction cautions
1. For parts outside broken line, the customers will independently prepare materials and carry out construction.
2. The water system pressure of evaporator and condenser ofCOM2water chiller should52CO be not more than 10kgf/cm2 and if so,
114
the chiller is special type. 52C

3. All chiller should be equipped with special water pump and cooling water pump to the extent possible.
4. The pipeline of cooled water and cooling water should be equipped
300
301 with 10-mesh filter.
5. In order for convenient management and maintenance of chiller,
302
303 the following devices should be installed besides stop valves
304
which are installed on respective pipeline of inlet/outlet of 305
cooler water and cooling water:
(1) Install thermometer and pressure gauge near the inlet/outlet of cooler water and cooling water
(2) Install exhaust valve on respective pipeline of cooler water
T2
224
and cooling water
6. The start and stop of peripheral equipments must be controlled by control system of water chiller to guarantee interlock protection.
223

T2
7. The power line inducted into starting cabinet of each compressor
220 and connecting wire of peripheral equipments will be supplied by
users and please ask for electric diagram of water chiller from
117
the Company during design and construction
SW1
COM2

Electric wiring
The wire between the starting cabinet and the major motor, the
starting cabinet and control cabinet, the staring cabinet and electric
actuating elements, the control cabinet and such sensors as
COM2
114
52CO pressure, temperature, etc have been connected when the chiller
52C
leave factory; the parts within the broken line in the field wiring
diagram above will be supplied by the users.
300
301
302
303
304
305

Notes :
T2 1. The interlock contact of this part will be supplied by the users and it has no
224
223 voltage (dry contact) and the maximum impedance is 100.
T2
220 2. The contact of this part is used for starting/stopping peripheral equipments,
which is lower than 250VAC 0.1A.
117
SW1
COM2
3. 250VAC 0.1A The contact of this part is used for indicating progressive running
status, which is lower than 250VAC 0.1A.

4. The signal of this part will be supplied by the users.

L S W A T E R - C O O L E D S C R E W C H I L L E R 15
www.lsaircondition.com
Distributed by
Overseas Sales Office in Korea
Air conditioning Overseas Business Dept.
6F Sungji Building, 1505-17, Gwanyang-dong,
Dongan-gu, Anyang-si, Gyeonggi-do, Korea
Tel. 82-31-450-3531~3538
Fax : 82-31-450-3540
Factory in China
266109, Yu-Huangling Industrial Area,Xiazhuang,
Chengyang District, Qingdao, China
Tel. 86-532-8096-5648
Fax. 86-532-8096-5688

Specifications subject to change without prior notice. ACOS-01-3000-0901 / Printed in Korea