Calculation of weight of solid material from known dia.

Enter the value of d in mm Weight in running meter

40 mm 9.86 kg/mtr

For flat Enter B in cm H in cm in kg/cm2 4 0.6 0.79 1.88 Kg/mtr

Weight in running mtr

Sl no

Switchyard equipment 1 Generator Transformer 2 Station Service Transformer 3 Circuit Breaker 4 Isolator without Earthing switches 5 Isolator with Earthing switches 6 Current Transformer 7 Voltage transformer 8 CVT 9 LA 10 Post Insulator(PI) 11 Lightning Mast 12 TA 13 TB 14 Beams Considering all beams)

Nos 2 1 8 7 16 24 6 12 21 23 8 15 7 1

Earthing material

material required in mtr/ item 30 30 144 27 35 12 12 12 20 12 50 34 22 700 Add 10% for cutting & welding Add 10% Extra

GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm) GS flat (size 65 x 8 mm)

15 Marshalling box for CT 16 Marshalling box for CB 17 MarH Box for Iso.with Earth switch

24 8 7

GS flat (size 50 x 6 mm) GS flat (size 50 x 6 mm)

10 45 6

18 MarH Box for Iso.without Earth switch 19 Marshalling box for CVT 20 Marshalling box for VT 21 MarH box for Transformer 22 Bay Marshalling Box

16 12 6 3 8 Add 10% for cutting & welding Add 10% Extra

12 10 10 10 10

Total (mtr) 60 30 1152 189 560 288 72 144 420 276 400 510 154 700 4955

Total weight ( Kg) 244.92 122.46 4702.46 771.5 2285.92 1175.62 293.9 587.81 1714.44 1126.63 1632.8 2081.82 628.63 2857.4 20226.31 202.26 202.26 20630.84 20MT 565.2 847.8 98.91

say 240 360 42

192 120 60 30 80

Say

452.16 282.6 141.3 70.65 188.4 2647.02 26.47 26.47 2699.96 3 MT