Fault Level Calculation

Fault Level Calculation of consumer end point from kallaynpur 33/11 KV S/S to resedinetial Building of STDL Tipti,Plot #80,Road#06, Monsurabad R/A, Adabor,Dhaka-1207

33 KV

N/C

20/28MVA 13.67% Imp.

20/28 MVA 13.67% Imp.

11 KV

N/C

U/G Cable 11KV O/H Line 185 mm2 XLPE(A) Conductor DOG

50mm2 Xlpe(Cu)

Load point

Assuming 33 KV BUS FAULT LEVEL = 1000 MVA Using % REACTANCE METHOD

% of Source impedance at 10 MVA Base Substation Transformer % impedance at 10 MVA Base Percentage (%) Impedance of U/G Cable Percentage (%) Impedance of DOC Conductor Total Circuit % REACTANCES AT PCC IS FAULT LEVEL AT THE POINT OF COMMON COUPLING FAULT LEVEL KILO-AMPS Recommended Minimum size of HT Cable = = =

= = = =
 

       

   

   

=
 


  

  



Calculation for PFI Plant

kVA
1

kVA
2

kVAR

kW

kW

A) Consider Power factor (cos 1) = 0.70 1 = cos (0.70) tan 1 = tan (cos 0.70) = 1.0202 B) Required Power factor (cos 2) = 0.95 2 = cos (0.95) tan 2 = tan (cos 0.95) = 0.328 Capacitor Bank (Capacity of PFI Plant) required to enhance PF from 0.70 to 0.95 kVAR = kW (tan 1- tan 2) = 120 (1.202-0.328) = 120 X 0.6922 = 83.064 90 KVAR The 90 kVAR PFI plant (Auto) is capable for maintaining power fator from 0.70 to 0.95 lagging.