VIVADENS MCR

WALL-HUNG GAS CONDENSING BOILERS


MCR 24 : from 6,3 to 25,3 kW, for heating only MCR 24/28 BIC : from 6,3 to 25,1 kW, for heating and domestic hot water preparation by integrated calorifier MCR MI : from 6,3 to 35,9 kW, for heating and instant domestic hot water production for chimney or forced flue connection

MCR 24 MCR MI

MCR 24/28 BIC

MCR 24 + BMR 80

MCR 24 + SR 130

MCR 24 : for heating only

MCR BIC, +BMR/SR or MI Heating and domestic hot water by independent calorifier or micro-accumulated

All of these boilers are factory fitted with a control panel which can be complemented by a control system offering 2 comfort levels: Either by room thermostat Or by remote control according to the outside temperature with the possibility of controlling a circuit with mixing valve in addition to a direct circuit Various air/flue gas connection configurations are possible: we offer solutions for connection by horizontal or vertical forced flue, to a chimney, in bi-flow.

Condensing

All natural gases Propane

N didentification CE : 0063BQ3009

CONDITIONS OF USE Boiler: Max. operating temperature: 90 C Max. operating pressure: 3 bars Safety thermostat: 110 C Power supply: 230 V/50 Hz Protection index: IPX4D BMR 80 and SR 130 DHW calorifier: Max. operating pressure primary and secondary circuits: 10 bars Max. operating temperature primary and secondary circuits: 95 C HOMOLOGATION B23P - C13x - C33x - C53 - C43x - C63x - C83x* GAS CATEGORY II2ESi3P, Classe NOx : 5
*to be adapted according to the country for wich the boilers are intended

PRESENTATION
MCR 24, MCR 24/28 BIC and MCRMI boilers are delivered fully assembled and factory tested. They come ready to operate on natural gases; operation on propane is possible by simple adjustment or by conversion kit (available as optional equipment). MCR 24 boilers are factory fitted with a heating/DHW reversal valve for connection to an independent hot water calorifier: 2 types of optional DHW calorifiers are available: - 80-litre BMR 80 calorifier to be juxtaposed to the right or left of the boiler: version MCR 24 + BMR 80; - 130-litre SR 130 calorifier to be placed on the floor under the boiler: version MCR 24 + SR 130. The MCR 24/28 BIC version is particularly compact (900 x 600 x 450 mm) and efficient: DHW production, with *** performance in accordance with EN 13203, is handled by a 40-litre storage calorifier integrated into the boiler, combined with an external plate exchanger with a large exchange surface, a DHW pump and a heating/DHW reversal valve. MCR .. MI boilers are mixed boilers and produce large quantities of domestic hot water (*** classification in accordance with the standard EN 13203) thanks to an oversized plate exchanger and very reactive electronics.

STRONG POINTS
- Particularly compact, light boilers - Perfect adaptation of boiler output to actual needs thanks to the stainless steel gas burner with complete premixing, modulating from 25 to 100% output, fitted with a silencer on the air intake. - Stainless steel exchanger with double external envelope in composite material. - Electronic ignition and ionisation flame check. - Delivered with a mounting frame with prefitted water and gas valves (including the disconnector), 8-litre expansion vessel (no vessel on MCR 34/39 MI), automatic air vent. The MCR 24/28 BIC is also fitted with the 7-bar DHW safety valve and a flow collector. - Simple, functional control panel with optional control system offering 2 comfort levels: By room thermostat According to the outside temperature, with the possibility of also controlling a direct circuit, a circuit with mixing valve by connecting a remote control with specific communication interface and the outside sensor. - For the various air/flue gas connection options, see page 11.

THEY OFFER HIGH LEVELS OF PERFORMANCE:


- Efficiency at 40/30C up to 109 % - Efficiency class CE - NOx < 70 mg/kWh - NOx classification: 5 in accordance with PR EN 15420 - Noise level in compliance with NRA (see page 5)

MODELS AVAILABLE
Boiler Model Useful output heating mode DHW mode at 50/30 C (kW) at 80/60 C (kW)

MCR_Q0001

For heating only

MCR 24

6,3-25,3

MCR_Q0026

For heating and domestic hot water preparation by integrated 40-litre calorifier

MCR 24/28 BIC

6,3-25,1

6,3-27,4

MCR_Q0001

For heating and instant domestic hot water production

MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

6,3-25,3 6,6-31,6 6,8-35,9

6,3-27,4 6,3-34,3 6,3-38,2

TECHNICAL SPECIFICATIONS
DESCRIPTION
MCR MI

Mounting frame with prefitted plumbing fixtures Automatic air vent

Air/flue gas connection 60/100 mm with measuring point

Expansion vessel (8 litres initial pressure 1 bar (no vessel on MCR 34/39 MI)

Heating body and burner

Ionisation and ignition electrodes

Gas valve unit 2-speed circulator pump 3-bar safety valve Plate exchanger for instant DHW (MCRMI)

Heating body and burner

MCR_Q0011

Control panel see p. 6

MCR 24/28 BIC

Automatic air vent

Air/flue gas connection with measuring point

Heating body and burner

Expansion vessel (8 litres) Stainless steel exchanger with low inertia and considerable resistance to corrosion with double exterior envelope in composite material used for thermal and phonic insulation

2-speed heating circulator pump

40-litre DHW storage calorifier protected by a magnesium anode Calorifier drainage 7-bar DHW safety valve
MCR_Q0030

Stainless steel burner with total premix modulating from 25 to 100% of the output, with low NOx and CO emissions, with silencer on the air intake

DHW pump 3-bar heating safety valve Plate exchanger with large exchange surface Mounting frame with prefitted water and gas valves (flow collector provided)

Control panel (see p. 6)

MCR_Q0005

TECHNICAL SPECIFICATIONS
MAIN DIMENSIONS (IN MM AND INCHES)
MCR 24 MCR MI MCR 24/28 BIC

600
400 379 328,5 160 71,5 25 9 300 132,5

446 128

160

21 51

456

51 21 900 584

972

741 670 584

106

117

4 3

6 73,3 5 79,8

2 6 73,3 10 4 11 79,8

2 10 4 11 6
50 65 65 68 66

26,5

2 10 6 11 4

MCR 24 + BMR 80 (package EE 53) and Connection kit (package HG 29)

MCR 24 + SR 130 (package EE 22) and Connection kit (package HG 30)


400 379 328,5 160 71,5 25
9

444 300 132,5

400 379 328,5 160 71,5 25

300 132,5

209

176,5 741 584 670

741 584 670

880 680

32

106 422 73,3

73,3

106

2
17 194 260 427

6
MCR_F0002

446

2000
10 11

10 11 10 11

48

110

153 305 932 590

Heating outlet interior 18 mm MCR 24: Primary calorifier outlet interior 16 mm (1) MCR .. MI: Domestic hot water outlet interior 16 mm Gas inlet interior 18 mm MCR 24: Primary calorifier return interior 16 mm (1) MCR .. MI: Domestic cold water inlet interior 16 mm (1) Heating return interior 18 mm Evacuation of combustion products and air inlet pipe 60/100 mm Domestic hot water outlet - MCR 24/28 BIC: 16 mm - MCR 24 + BMR/SR: R 3/4 Domestic cold water inlet - MCR 24/28 BIC : 16 mm - MCR 24 + BMR/SR: R 3/4 (1) if a DHW calorifier is connected R: threading

570
MCR_F0004

* or exterior 15/22 mm, dimensions to be adapted according to the country for which the boilers are intended

MCR_F0013A

MCR_F0001

26,5 4 23

TECHNICAL SPECIFICATIONS
SPECIFICATIONS TABLE
Boiler Boiler type: condensing Burner: modulating with complete premixing Energy used: natural gas or propane Combustion evacuation: chimney or sealed Min. flow temperature: 15 C Min. return temperature: none Ref. CE certificate: 0063BQ3009

Model Useful output at 50/30 C Pn (heating mode) Nominal output at 80/60 C (DHW mode) Efciency in % of 100 % Pn at ave. temp. 70 C low calorific power 100 % Pn at return temp. 30 C at load % Pn and 30 % Pn at return temp. 30 C water temp. C Nominal water output at Pn, t = 20 K Loss when not in use at t = 30 K Auxiliary electrical power at Pn (without circul.) Circulator pump output Useful output at 80/60 C - min/max Manometric height avail. heating circuit Water capacity - gas H/L Gas flow at Pn (15C, 1013 mbar) - propane Average flue gas temperature at 80/60 C Min/max mass flue gas output Pressure available at the boiler outlet Total weighted min./max. noise output in accordance with NF EN ISO 3741 Net weight kW kW % % % m3/h W W W kW mbar l m3/h kg/h C kg/h Pa dB (A) kg

MCR 24 6,3-25,3 98,3 104,4 108,7 1,03 30 25 90 5,5-23,6 > 200 1,7 2,5/3 1,9 78 10/47 50 43,1-49,3 29

MCR 24/28 BIC 6,3-25,1 27,4 98,3 104,4 108,7 0,93 nc. 25 90 5,5-23,1 > 200 1,8 2,5/3 1,9 78 10/48 100 nc. 61

MCR 24 + BMR 80 MCR 24 + SR 130 6,3-25,3 98,3 104,4 108,7 1,03 30 25 90 5,5-23,6 > 200 1,7 2,5/3 1,9 78 10/47 50 43,1-49,3 97/105

MCR 24/28 MI 6,3-25,3 27,4 98,3 104,4 108,7 1,03 30 25 90 5,5-23,6 > 200 1,8 2,5/3 1,9 78 10/47 100 43,1-49,3 30,5

MCR 30/35 MI 6,6-31,6 34,3 98,2 104,4 109,7 1,29 29 25 125 5,7-29,5 > 200 2,0 3,2/3,7 2,3 74 10/59 100 45,0-47,9 32

MCR 34/39 MI 6,8-35,9 38,2 98,0 104,4 110,5 1,47 28 45 135 5,9-33,3 > 200 2,2 3,6/4,2 2,6 71,5 10/62 140 44,1-49,5 31,5

Specifications domestic hot water


Model MCR 24/28 BIC MCR 24 + BMR 80 MCR 24 + SR 130 MCR 24/28 MI Exchanged power kW 27,4 22,6 22,6 27,4 l/10 min 180 165 200 Flow over 10 min at t = 30 K Flow over 10 min at t = 35 K l/h 670 555 555 Spec. output at t = 30 K (1) l/min 18,0 16,5 20,0 14,0 Min. pressure for a flow of 11 l/min bar 0,4 DHW losses through the outer casing at t = 45 K W 73 Aux. elec. output in DHW mode W 175 115 115 115 kWh/24hl.K. 0,27 Cooling constant
Domestic performance at room temp. 20 C, cold water temp. 10 C, primary hot water temp. 85 C (1) in accordance with EN 13203-1 for MCR 24 + BMR/SR and MCR 24/28 BIC in accordance with EN 625 for MCR MI

MCR 30/35 MI 34,3 17,0 0,4 150 -

MCR 34/39 MI 38,2 19,0 0,4 180 -

CONTROL PANEL
CONTROL PANEL ON MCR BOILERS
MCR boilers are fitted with a very simple control panel. This allows the continuous adaptation of heating and DHW output to needs. It incorporates functions for antifreeze protection
Large LCD display

and cleaning the circulator pump every 25 hours and a troubleshooting assistance system with alarm code display.

On/Off switch Menu key Sweep key


MCR_Q0004

Manometer

Space or reset key Heating temp. adjustment key or key

Maintenance key or validation key DHW temp. adjustment key or + key

CONTROL PANEL OPTIONS


Package AD 140
8801Q003

Programmable wire-controlled room thermostat - Package AD 137 Programmable wireless room thermostat - Package AD 200 Non-programmable room thermostat - Package AD 140 The programmable thermostats handle the regulation and weekly programming of heating by activating the burner in accordance with the various operating modes: Automatic depending on programming, Permanent at a set temperature or Holidays. The wireless version is delivered with a receiver box to be affixed to the wall close to the boiler. The non-programmable thermostat is used to regulate the room temperature according to the instruction given by activation of the burner.

Package AD 200

8666Q120A

Package AD 201
8666Q119A

Package AD 221
MCR_Q0022

Easymatic communicating wire-controlled remote control - Package FM 50 Easyradio communicating wireless remote control - Package AD 201 To function, these remote controls must be complemented with a boiler/remote control interface PCB: Easymatic/Easyradio interface for connecting 1 direct circuit - Package AD 221 Easymatic/Easyradio interface for connecting 1 direct circuit + 1 mixer valve circuit - Package AD 222 These remote controls handle the regulation and weekly programming of heating by activating the burner and the circulator pump on the direct circuit or the valve circuit (if one exists) according to several operating modes: Automatic according to programming, Permanent comfort, Reduced permanent, Holidays or Summer. Likewise, they handle the regulation and programming of domestic hot water.

Package AD 222

MCR_Q0023

(1) For controlling a valve circuit, the connection of an outside sensor is required, see below.

Outside sensor - Package AD 225 The outside sensor can be used alone or in combination with room thermostats or communicating remote controls for heating regulation dependent on the outside temperature. Domestic hot water sensor - Package AD 226 The domestic hot water sensor is used to apply priority regulation to DHW production by an independent calorifier. It is necessary, particularly

MCR_Q0021

It is essential if using an installation with a mixing valve circuit.

MCR_Q0018

if connecting a BMR 80 or SR 130 calorifier, presented as optional equipment for these boilers.

BOILERS OPTIONS
Height adjustment frame - MCR 24 et MCR MI - Package HG 19 - MCR 24/28 BIC - Package HG 75 This frame replaces the mounting frame delivered pipes behind the boiler (upwards). The plumbing as standard with MCR boilers in order to make fixtures are taken from the original frame and it possible to pass the water and gas connection fitted to the height adjustment frame.
MCR_Q0015 MCX_F0005

Connecting pipe kit 16/18 or 15/22 mm for height adjustment frame* - Package HG 20 or HG 32 This kit comprises the 5 water and gas connecting top rear section of the boiler through the height pipes to be connected to the plumbing fixtures on adjustment frame (option above). the MCR mounting frames to be passed behind the

MCR 24 and MCR MI


MCR_Q0020

Pipe cover - MCR 24 and MCR MI - Package HG 21 - MCR 24/28 BIC - Package HG 76 Provides a neat finish underneath the boiler.

MCR 24/28 BIC


MCR_Q0029

Mounting frame with disconnector for MCR 24 - Package HG 27 Mounting frame with disconnector for MCR .. MI - Package HG 33 These mounting frames are delivered as standard with the boilers concerned. However, they can be delivered in a separate package to be prefitted
MCR_Q0006

and thus enable the fitter to make all the hydraulic connections in advance and install the boiler only at the last minute.

DHW expansion vessel for MCR 24/28 BIC - Package HG 77 This prevents water losses due to expansion during Capacity: 2 litres reheating of the domestic hot water calorifier.
8531Q050

Package HC 33
8531Q027

Condensates neutralisation calorifier - Package HC 33 Wall bracket for neutralisation calorifier - Package HC 34 Granule refill for neutralisation - Package HC 35 The materials used for the condensates flow pipes must be appropriate; otherwise the condensates must be neutralised. A regular check of the neutralisation system and particularly the effectiveness of the granules by measuring the pH is necessary. If need be, the granules should be replaced.

Package HC 34
8531Q028A MCX_F0010

Flow collector - Package HG 28* Used to collect the run-off from the condensates flow siphon, the safety valve and the disconnector.
*options : to be adapted according to the country for wich the boilers are intended

BOILER OPTIONS
BMR 80 HG 29

SR 130 HG 30
8666Q043 8666Q043

BMR 80 domestic hot water calorifier - Package EE 53 BMR 80-MCR 24 connection kit - Package HG 29 SR 130 domestic hot water calorifier - Package EE 22 SR 130 - MCR 24 connection kit - Package HG 30 BMR 80 and SR 130 domestic hot water The boiler/water calorifier connection kits available calorifiers are high performance calorifiers. They include rigid and/or flexible connection pipes are protected inside by food quality standard between the boiler and the calorifier. high quartz content vitrified enamel and by a magnesium anode. The specifications of these calorifiers combined with MCR boilers are given on pages 2 and 3.

MCR_Q0010

MCR_Q0016

Propane conversion kit - Package HG 44 (for all boilers except MCR 34/39 MI) Propane burner for MCR 34/39 MI - Package HG 31 To run the MCR 34/39 MI on propane, it is necessary to replace the burner fitted to the boiler with this specific burner. For the other boilers, use the propane conversion kit or change the boiler settings.

INFORMATION REQUIRED FOR INSTALLATION


LOCATION
MCR condensing boilers must be installed in premises protected from frost, which can also be ventilated. The IPX4D protection index enables them to be installed in kitchens and bathrooms, excluding protection volumes 1 and 2, however. In order to ensure adequate accessibility around the boiler, we recommend that you respect the minimum dimensions given opposite. Ventilation This must comply with prevailing regulations.
50 mi n. 40 0

mi

n.

25

50 mi

67 n.

GAS CONNECTION AND ELECTRICAL CONNECTION


Comply with prevailing national or even local instructions and regulations.
0 30 0 10ini m

mi

n.

25

0
MCR_F0005

INFORMATION REQUIRED FOR INSTALLATION


HYDRAULIC CONNECTIONS
Important: The principle of a condensing boiler is to recycle the energy contained in the water vapour in the combustion gases (latent vaporisation heat). Consequently, to achieve an annual operating efficiency in the order of 109%, it is necessary to size the heating surfaces in such a way as to obtain low return temperatures, below the dew point (e.g. underfloor heating, low temperature radiators, etc.) during the entire heating period. MCR boilers must only be used in closed-circuit heating installations, previously cleaned to eliminate residues and deposits caused by commissioning the installation. Furthermore, it is important to protect central heating installations against the risk of corrosion, scaling and microbiological growth: the water treatment products used must comply with regulations.

Manometric height of the heating circulator pump fitted to the MCR MCR 24, MCR 24/28 MI AND MCR 24/28 BIC : (with Grundfos UPR 15-60 type pump) MCR 30/35 MI, MCR 34/39 MI : (with Grundfos UPR 15-70 type pump)

Manometric height in mbar

Manometric height in mbar

T 20 C 18 kW

T 20 C 28 kW

Flow rate in l/h

Flow rate in l/h

Condensates discharge The siphon provided must be connected to the waste water discharge system. The connection must be removable and the flow of condensates visible. The connections and pipes must be in corrosion-resistant material.

An optional condensates neutralisation system is available (package HC 33 see page 7).

STANDARD INSTALLATION DIAGRAMS


The examples presented below cannot cover the full range of installation scenarios which may be encountered. Their purpose is to draw the attention to the basic rules to be followed. A certain number of control and safety devices (some of which are already integrated as standard in MCR boilers) are represented but it is ultimately up to installers, experts, consultant engineers and design departments to take the final decision on the safety and control devices to be used in the boiler room according to its specificities. In all cases, it is necessary to abide by the codes of practice and prevailing regulations. Attention: For the connection of domestic hot water, a sleeve made of steel, cast iron or any other insulating material must be interposed between the hot water outlet and these pipes to prevent any corrosion to the connections, if the distribution pipes are made of copper.

MCR_F0009

STANDARD INSTALLATION DIAGRAMS


MCR 24 + BMR 80 with 1 direct circuit + 1 domestic hot water circuit, controlled by a wire-controlled programmable room thermostat + outside sensor MCR .. MI with 1 direct circuit + 1 circuit with mixing valve, controlled by an Easyradio communicating wireless remote control + specific interface and outside sensor

21 AD 201 21 AD 137 AD 222


Thermostat d'ambiance filaire

BUS

Commande distance communicante Easyradio

51
+

51
9 32 9 27
230V 50Hz

8 33
230V 50Hz 230V 50Hz

29 9 1 8
72
4

28

64

65 44 23

64

Horloge externe

10 11b
C C C C

27 30 28 9 29
68 68

1a

2a

2b

1b

9
MCR_F0007

27
MCR_F0006

27

MCR 24/28 BIC with 1 direct underfloor heating circuit, controlled by a wireless room thermostat

MCR 24/28 BIC with 1 radiator circuit, controlled by a programmable wire connection room thermostat + outside sensor
21 AD 137

21

AD 200

11/26 16 46 16

11/26 46 8 75 65 75 44 64
230V 50Hz
BUS

51

230V 50Hz

3 55 9 50

3 55 9

27 29 9

50 27

28
MCR_F0017A

29 9

1 2 3 1a 1b 2a 2b 8 9 10 11 11b 16

Heating outlet Heating return 3-bar heating safety valve Heating outlet direct circuit Heating outlet valve circuit Heating return direct circuit Heating return valve circuit Manual bleed valve Isolation valve 3-way mixing valve Heating pump Heating pump for circuit with mixing valve Expansion vessel

21 23 26 27 28 29 30 32 33 44 46 50

Outside sensor Outlet temperature sensor after mixing valve (delivered with PCB package FM 48) Domestic water load pump Non-return valve Domestic cold water inlet Pressure reducer Sealed safety device calibrated to 7 bars* (Optional) DHW loop pump DHW temperature sensor 65 C limiter thermostat with manual reset for underfloor heating 2-position 3-way directional valve Disconnector

51 55 64 65 68 72 75

Thermostat valve DHW safety valve calibrated and sealed to 7 bars Radiator circuit (gentle heat radiators, for example) Low temperature circuit (underfloor heating, for example) Condensates neutralisation system Hydraulic bypass Domestic water pump

* mandatory, in compliance with safety directives

10

MCR_F0018A

28

AIR/FLUE GAS CONNECTION


For the use of the air/flue gas connection pipes and the rules on installation, see details of the various configurations in the current price catalogue.

Lmax = L1+L2 L1 Lmax

Lmax

C43x

C33x
Lmax

Lmax

L2

12

L2

Lmax

Lmax

C13x

C33x

C43x

1
L1 1m Lmax = L1+L2
max

12
1m Lmax

max

1m

max

C53

B23P

C43x

C33x

C33x

C33x

12

Table of maximum air/flue gas pipe lengths admissible according to boiler type
Type of air/flue gas connection Maximum length of the connecting pipes in m MCR 24/28 MI MCR 24 MCR 24/28 BIC MCR 30/35 MI MCR 34/39 MI C13x 60/100 mm 6 31 18 7 32 23,5 4 22 10 24 6 29 12 25,5

Concentric pipes connected to a horizontal terminal (PPS)

Concentric pipes connected to a vertical terminal C 33x 80/125 mm (PPS) 60/100 mm Pipes 80 mm - concentric in the boiler room, C33x - single in the chimney (combustive air with 80/125 mm counter current) (PPS) 80 mm Pipes - concentric in the boiler room, - flex in the chimney (combustive air with counter current) (PPS) Bi-flow adapter and separate single air/flue gas pipes (combustive air taken from outside) (Alu) In the chimney (rigid or flex) (combustive air taken from the premises) (PPS) C33x 80/125 mm 80 mm C53 60/100 mm sur 2x80 mm B23P 80 mm (rigid) 80 mm (flex)

15,5

19

MCR_F0011B

Configuration C13x : Air/flue gas connection by means of concentric pipes to a horizontal terminal (so-called forced flue) Configuration C33x : Air/flue gas connection by means of concentric pipes to a vertical terminal (roof outlet) or Air/flue gas connection using concentric pipes in the boiler room and single pipes in the chimney (combustive air with counter current in the chimney) or Air/flue gas connection using concentric pipes in the boiler room and single flex pipes in the chimney (combustive air with counter current in the chimney) Configuration C53 : Separate air and flue gas connection using a bi-flow adapter and single pipes (combustive air taken from outside) Configuration B23P : Connection to a chimney (combustive air taken from the boiler room) Configuration C43x : not to be taken into consideration

18

20

44 33 23

48 37 27

30 19 22,5

32,5 33 24,5

11

DESCRIPTION
VIVADENS MCR

WALL-HUNG GAS CONDENSING BOILER FOR CONNECTION TO A CHIMNEY OR A FORCED FLUE


Brand: De Dietrich Classification: **** In accordance with the european efficiency directive, NOx classification: 5 Model: MCR_____ (MCR 24 for heating only, MCR..MI for heating and production of instant DHW) MCR 24/28 BIC: (for heating and production of instant DHW with 40 litres calorifier) Homologation: B23P-C13x-C33x-C53-C43x-C63x-C83x* Gas category: II2Esi3P* Protection index: IPX4D, Power supply: 230 V/50 Hz Useful output in heating mode at 40/30 C: _____kW Useful output in DHW mode at 80/60 C: _____kW Specific flow in DHW mode (MCR..MI): _____l/min Specific flow in DHW mode (MCR 24/28 BIC): 18 l/min Max. operating temperature: 90 C Max. operating pressure: 3 bar Safety thermostat: 110 C Dimensions: 670 x 400 x 300 mm Weight empty: _____kg

DESCRIPTION
- Complies with the requirements of European Directives - Stainless steel exchanger with low inertia and considerable resistance to corrosion, with double exterior envelope in composite material used for thermal and phonic insulation - Stainless steel burner with total premix modulating from 25 to 100% of output, with low NOx and CO emissions and a silencer on the air intake - Control panel facilitating the ongoing adaptation of heating and DHW output to needs, which can be complemented by various options to regulate heating according to the room or outside temperature - Fully fitted boilers: 2-speed circulating pump, 8-litre expansion vessel (except MCR 34/39 MI), automatic bleed valves, 3-bar safety valve, mounting frame with prefitted water and gas plumbing fixtures, plate exchanger for instant DHW on MCR.. MI or heating/DHW reversal valve on MCR 24, air/flue gas connection in diameters of 60 to 100 mm with measuring outlet - MCR 24/28 BIC: MCR 24 with 40-litre DHW calorifier integrated into the boiler combined with a plate exchanger, a DHW pump, a heating/DHW reversal valve. Boiler/calorifier connecting pipes and DHW sensor provided Options for control panel - Programmable wire-controlled room thermostat - Programmable wireless room thermostat - Non programmable room thermostat - Easymatic/Easyradio interface for connecting 1 direct circuit - Easymatic/Easyradio interface for connecting 1 direct circuit + 1 mixer valve circuit - Outside sensor - Domestic hot water sensor Boiler options - Height adjustment frame for MCR 24 and MCR ..MI - Height adjustment frame for MCR 24/28 BIC - Connecting pipe kit 16/18 mm or 15/22 mm for height adjustment frame - Pipe cover for MCR 24 and MCR..MI - Pipe cover for MCR 24/28 BIC - DHW expansion vessel for MCR 24/28 BIC - Flow collector - Mounting frame with disconnector for MCR 24 - Mounting frame with disconnector for MCR.. MI - Condensates neutralisation calorifier - Wall bracket for neutralisation calorifier - Granule refill for neutralisation - BMR 80 domestic hot water calorifier - BMR 80 MCR 24 connecting kit - SR 130 domestic hot water calorifier - SR 130 MCR 24 connection kit - Propane conversion kit - Propane burner for MCR 34/39 MI

DE DIETRICH THERMIQUE
S.A.S. with corporate capital of 22 487 610 d

57, rue de la Gare - F - 67580 Mertzwiller Tl. 03 88 80 27 00 - Fax 03 88 80 27 99 www.dedietrich-heating.com

07/08 300010772 ind. A 347.555.559 R.C.S Strasbourg Document not binding. You can check its validity on the website http:/www.dedietrichthermique.com - Printed in France OTT-Imprimeurs Wasselonne - 82344