902,Kamadgiri Apartments,Kaushambi,GHAZIABAD PIN 201010 (UP) INDIA Phone Office 0120-2894158,Mobile 9810116114, 9818363143 Fax 0120-2585220 RECOGNISED COMPETENT PERSON UNDER SMPV(U) RULES 1981 BY CCE NAGPUR CERTIFICATE OF SAFETY FOR STORAGE OF COMPRESSED GAS UNDER RULE 33 OF SMPV (U) RULES 1981 CERTIFICATE NO.: AR/ R33/11012/08 DATE: 29-04-2011

I, Shri S.S.Kamthan hereby certify that the compressed gas installation of Ranbaxy Laboratories Ltd., Village Toansa,P.O. Rail Majra,Distt. Nawanshahr-144533,State Punjab has been constructed in accordance with the specification and plans approved by the Chief Controller of Explosives and the conditions of the licence form III and that in my opinion the installation and foundations of the above ground pressure vessels are of such a nature and all vessels have been so installed and secured as to ensure safety. The particulars of the installation and examinations carried out are noted below: 1 VESSELS AND FITTINGS :As described in the annexure enclosed

2 FIRE PROTECTION (i) WATER No. & Location of hydrant points :NOT APPLICABLE AS IT IS A CRYOGENIC STORAGE Pressure in hydrant line : Whether hose and watert throwing : arrangement provided Particulars there of Sprinkler System provided: Particulars of water Capacity of static fire : water Storage or equivalent arrangement Observations on the adequacy of the arrangement FIRE EXTINGUISHERS Make :REPUTED MAKE Type :DCP TYPE Capacity :2NOS., 9 KG CPACITY + 4NOS. SAND BUCKETS 3 DECANTING PUMP NOT APPLICABLE Make Specification : Electrical Motor Make : HP/RPM : Flameproof construction : Protection : 4 ELECTRICAL FITINGS (Nature,Specification,Location : Lamps : Contd2

A.R.ASSOCIATES
902,Kamadgiri Apartments,Kaushambi,GHAZIABAD PIN 201010 (UP) INDIA Phone: Office 0120-2894158,Mobile 9810116114, 9818363143 Fax 0120-2585220 CERTIFICATE NO.: AR/ R33/11012/08 DATE: 29-04-2011

Switches : Switch Gear : Junction Boxes : Wiring : 5 PIPELINES Location and length :AS PER APPROVED DRAWING,20 METRES (As per approved drwgs) Make :REPUTED MAKE Specifications : 1 NB, SS 304,SCH.40 PIPE LINE Pipe tested at 20.00 Kg/cm2 by A.R.ASSOCIATES personnel on 29-04-2011 Fittings in the pipeline: . Type and make : Suitability of the fittings : 6 VAPOURISERS Type (Electrical or direct Fired) : NIL Make : Capacity : Defects if any : 7 HOSE PIPE FOR DECANTATION Make :NA Material and Construction : Test Pressure : 8 PAINTING & EXTRNL CORROSION:PAINTED WITH WHITE ENAMEL PAINT,GOOD ON VESSEL PARTICULARS :EXTERNAL CONDITION,NO CORROSION 9 FOUNDATION Nature :RCC Material :CONCRETE Packing between tank and foundation: 10 DRAWINGS : DRAWING NO. APPROVAL NO.&DATE (a) Fabrication,Flow Scheme,Foundation detail & General Assembly Drawing V0018DC/1-001-AL REV.0, V0018DC/1-003-AL REV.0, V0018DC/1-023 REV.0 V0018DC/1-002-LB REV.0

PV(M)390/XXXVIII DTD 03-11-2009 PV(M)390/XXXVIII DTD 03-11-2009 PV(M)390/XXXIV DTD 12-01-2009 PV(M)390/XL DTD 19-05-2010 Contd----3

A.R.ASSOCIATES
902,Kamadgiri Apartments,Kaushambi,GHAZIABAD PIN 201010 (UP) INDIA Phone: Office 0120-2894158,Mobile 9810116114, 9818363143 Fax 0120-2585220 CERTIFICATE NO.: AR/ R33/11012/08 (b)Layout drawing RLL/LAYOUT/11/01 S/HO/PB/03/108(S12699) & AS BUILT DRAWING BEING SUBMITTED 11 EARTHING 12 REMARKS IF ANY : DONE : INSTALLATION IS SAFE DATE: 29-04-2011

PLACE: GHAZIABAD DATE: 29-04-2011

Signature Name and designation: S.S.KAMTHAN Qualification & Ref. Of CCEs Recognition PV(R) 210

A.R.ASSOCIATES
902,Kamadgiri Apartments,Kaushambi,GHAZIABAD PIN 201010 (UP) INDIA Phone: Office 0120-2894158,Mobile 9810116114, 9818363143 Fax 0120-2585220 CERTIFICATE NO.: AR/ R33/11012/08 DATE: 29-04-2011

ANNEXURE TO SAFETY CERTIFICATE UNDER RULE 33 OF STATIC & MOBILE PRESSURE VESSELS (UNFIRED)RULES 1981 A VESSEL PARTICULARS : Identification No. :1011021002/3,MODEL-2118 DC Fabricators Name :INOX INDIA Particulars of :TUV SUD INDUSTRIE SERVICE Inspection certificate :0036 DATED 12-08-2010 Design Code : AD 2000 MARKBLATT & PED 97/23/EC Design Pressure(Kg/sq.cm.(g) :18.369 KG/CM2 Design Temperature(deg.Cent.) : (-)196 & 40 DEG.CENT. Working Pressure : 17.336 KG/CM2 Working Temperature(deg.Cent) : (-)196 & (+) 40 DEG.CENT. Working Capacity :19377 LIT. GROSS, 18409 LIT. NET Name of the gas to be stored :LIQUID NITROGEN Initial Hydraulic test done on 08-07-2010 (date) at 26.27 Kg/cm2 pressure by TUV Note 1(*)Subsequent pneumatic test after installation of the vessel at site on 29-04-2011 at 18.10 Kg/cm2 pressure by A.R. Associates (Competent Person) Remarks on the test :SATISFACTORY Foundation Type :RCC Remarks about foundation :SATISFACTORY Behaviour during hydraulic test :SATISFACTORY Whether the vessel is insulated :YES If so nature of Insulation :PERLITE FILLED VACUUM INSULATED B FITTINGS 1 SAFETY VALVES NO1 NO2 Identification No & : 848140 848247 Manufacturing Date : --------- 2010 ---------Make : ------------------HEROSE VALVES----- --------Set Pressure : ------------- 17.00 KG/CM2----------Tested by A.R.ASSOCIATES on 29-04-2011 (Competent Person) at 17.00 Kg/cm2 Note-2(**) Particulars of original test by (inspecting agency at manufacturers premises) on (date) TEST CARRIED OUT BY manufacturer ON 21-06-2010 Discharge Flow rate : ----------674 NM3/HR. -------Size : -----------1/2X1---------Are size & flow rateadequate for : ----------- YES -----------the vessel (if no reasons may be given) Contd..2

A.R.ASSOCIATES
902,Kamadgiri Apartments,Kaushambi,GHAZIABAD PIN 201010 (UP) INDIA Phone: Office 0120-2894158,Mobile 9810116114, 9818363143 Fax 0120-2585220 CERTIFICATE NO.: AR/ R33/11012/08 Height of the vent from vessel & ground level Whether provided with shut off valves 2 DATE: 29-04-2011

:AT THE SIDE OF THE VESSEL,1200 MM ABOVE GROUND LEVEL :YES

LEVEL GAUGE (a) Slip tube gauge/Magnetic : level Gauge: (b) Maximum level gauge :DP TYPE,6DIAL SIZE Make,location,no.& :WIKA MAKE,0-12500 MM WC Manufacturing date (c)Rotogauge : Make,Location,manufacturing date PRESSURE GAUGE Make,range,date of :WIKA MAKE ,4DIAL ,0-25 KG/CM2 Caliberation,whether Excess flow valve provided if yes, : particulars make,size,identification no. EMERGENCY SHUT OFF ARRANGEMENT: Excess Flow Valve Location Make :NA & Manufacturing Date Size & Closing : Flow rate : Date of last test : Whether size and closing Flow rate : Adequate (If NO reasons may be given) Any other type of Emergency Shut: off Arrangement Particulars thereof DISCHARGE VALVE Location Make Size : SIDE OF THE VESSEL : LONG STEM CRYOGENIC VALVE : 1.5 Contd----- 3

A.R.ASSOCIATES
902,Kamadgiri Apartments,Kaushambi,GHAZIABAD PIN 201010 (UP) INDIA Phone: Office 0120-2894158,Mobile 9810116114, 9818363143 Fax 0120-2585220 CERTIFICATE NO.: AR/ R33/11012/08 6 DRAINAGE PIPE Size : 1/2 Mode of closure :MANUAL NOTE-3(***)Whether extended Beyond shadow of vessel If NO give reasons 7 MANHOLE Location Size :NIL :NA DATE: 29-04-2011

SEAL

SIGNATURE Reference of CCEs recognition PV( R ) - 210 As competent person

NOTES * 1) Hydraulic test to be carried out after installation at site at test pressure(if not tested at test pressure within preceeding 2 or 5 years) or at design pressure(if already tested at test pressure during preceeding 2 or 5 years).For cryogenic vessels for Industrial Gases,test pressure should be design pressure(minimum0 ** 2) SRVs must be inspected and cerified by 3rd Party Inspector at manufacturer;s premises,particulars thereof should be furnished. *** 3) Darail pipe for flammable gases must be extended beyond the shadow of the vessel and provided with two shutoff valves