DATE
GENERALLY REVISED AND REISSUED REVISED WITH MOTOR CONTROL SCHEME REISSUED WITH REVISED MOTOR CONTROL SCHEME
DETAILS OF REVISION
DOCUMENT NO
EECS-50-100-003
GEN-004-R1
Page 2 of 28
REV NO
04
01 02 03
00
REV
04
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
CLAUSE
4.0 1.0 3.0 INTRODUCTION CODES AND STANDARDS INSTRUMENT IDENTIFICATION INSTRUMENT TAG NUMBERING 2.0
ANNEXURE -1: MOTOR CONTROL SCHEMES ANNEXURE -2: MOV CONTROL SCHEMES
INDEX
DESCRIPTION
DOCUMENT NO
EECS-50-100-003
GEN-004-R1
Page 3 of 28
PAGE
4
REV
04
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
1.0
1.1
1.1.1 1.1.2
INTRODUCTION
GENERAL
This technical description is issued to cover the minimum technical requirements for Instrument Symbols. The Instrument Symbols shall be strictly in accordance with this document / codes and standards referred to in the attached documents.
1.1.3
Any conflict generated within this document shall be referred to the client in writing for approval.
1.2
DEFINITIONS
For this technical description the following definitions are applicable:
Contractor / Buyer: The party which carries out engineering and/or procurement and/or construction.
Seller: Any manufacturer, supplier or seller who is appointed by the Contractor/Buyer and is responsible for the supply of materials or equipment or services.
Wherever the word shall has been used, its meaning is to be understood as mandatory.
2.0
DOCUMENT NO
REV
EECS-50-100-003
Page 4 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
3.0
3.1
INSTRUMENT IDENTIFICATION
For administrative purposes all instrument components and functions shall be identified by means of a unique tag number. A tag number is a combination of letters and numbers used to uniquely identify instrument components and instrument functions. A combination of electrically interconnected instrument components and functions performing a basic operation is called an instrument loop and shall be identified by means of a unique loop number. A loop number is the unique identification of a combination of instrument components and/or instrument functions performing a dedicated instrument safeguarding, control and/or monitoring function.
3.2
Traditionally, all components/functions shall be shown in individual balloons: TE-0101 TT-0101 Temperature element (e.g. RTD) Temperature transmitter
Components in the instrument index are similar to those above with format mentioned in paragraph 3.3.
DOCUMENT NO
REV
EECS-50-100-003
Page 5 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
3.3
Components/functions in the instrument index as per PCD/typical loop are in principle identical to the traditional listing as follows. TAG NUMBER: PAATMFFF-SLLLXX
P AA T M FFF S LLL XX
= = = = = = = =
Phase number for Expansion project (1= Phase 1 Expansion, 2 = Phase 2 Expansion) Train or Area. Type (first letter). Modifier. Function. First digit of Section number. (Always 0.) Sequence number. (From 001..999) Tag number suffix. (A, B, C,etc.)
e.g:-
110PDT -0103 110PDC -0103 110PDV -0103A 110PDV -0103B 110HS -0174AB
Note: The prefix 110 (Unit No.) shall not appear in the instrument "balloon", but shall be mentioned in a note on the P&ID, identifying the Train or Area number relating to the instrumentation on the P&ID. For Unit Numbers please refer Table in 7.1 Annexure-I: Unit Numbers of the Project Engineering Procedure For Document Numbering PPPO-0000-000-MGT-000001.
3.4
DOCUMENT NO
REV
EECS-50-100-003
Page 6 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
3.5
IDENTIFICATION LETTERS
IDENTIFICATION LETTERS FIRST LETTER Measured or initiating variable A B C D E Analysis Burner, combustion User's choice Density Voltage Differential Sensor (primary element) Ratio, fraction, factor High Indicate, Glass, Viewing Device Control station, panel, cabinet Lamp / Light Low Control Close Modifier SUCCEEDING LETTER Readout or passive function Alarm Output function Modifier
Active
User's choice
F G H I J K L M N O P Q R S T U V
Flow rate
Hand Current (electric) Power Scan Time, time schedule Time rate of change Level Motor / Drive User's choice User's choice Pressure, vacuum Quantity Radiation Speed, frequency Temperature Multivariable / Safety(ESD) Vibration, mechanical analysis Integrate, totalize Reactive Safety
User's choice
Record (hardwired) Switch Multifunction Transmit Multifunction Valve,damper, louver, final control element Well
W X Y Z
User's choice
Position
DOCUMENT NO
REV
EECS-50-100-003
Page 7 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
3.6
SEQUENCE NUMBER
For each measured or initiating variable the loop number sequence will restart. Example: Loop 110P-0103 and loop 110L-0103 may coexist.
3.7
3.8
All Field Gauges shall use the function letter I, e.g. Pressure Gauge 110PI-0102, see example S-04 and 110LI-0102, see example S-02, until unless it is specified.
3.9
PRESSURE POINTS
Process pressure points shall not be provided with an instrument loop or tag number.
3.10
3.11
MASS-FLOW LOOP
Where a mass-flow computation is done by the measurement of flow with pressure and temperature compensation, each individual part of the overall loop (flow, pressure and temperature) shall have a unique Number e.g. 110F-0232, 110P-0232 and 110T-0232, with the control valve being tagged as part of the flow Loop (110FV-0232). See example L-15. Loop Number shall be same for all such components if possible.
3.12
RELIEF VALVES
Where there are two (2) or more relief valves installed (e.g. vessel pressure relief) for the same service, then the tag numbers shall have an alphanumeric suffix, e.g. 110PSV-0107A and 110PSV-0107B. Installed spare valves shall have "S" suffix.
3.13
SELF-REGULATING VALVES
Self-regulating valves shall have a tag number format using e.g.110PCV-0112. See example S-08.
3.14
3.14.1
CONTROL VALVES
Where a valve is used in a "control only" loop, the valve will have the same identifier and loop sequence number as the main function component. See examples L-03, L-04, L-06.
3.14.2
Electropneumatic positioners are fitted to control valves, these will not be assigned a tag number but
DOCUMENT NO
REV
EECS-50-100-003
Page 8 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
will be considered to be part of the valve. 3.14.3 When a control valve is part of a cascade loop, the valve tag number shall have the same tag number type as the secondary control loop. See example L-05.
3.15
3.16
3.16.1
SOLENOID VALVES
The tag number for a solenoid valve connected to an on/off valve shall have the same type letter and loop sequence number as the valve, e.g. valve 110XV-0103, solenoid valve 110XY-0103. See examples L-10.
3.16.2
The tag number for solenoid valve connected to a control valve (in normal operation, but which is also included in a safeguarding loop), shall have the number that of the valve e.g. valve 110LV-0140, solenoid valve110LY-0140. See examples L-06.
3.17
3.17.1
ID/IS BLOCKS
Where a ID/IS block is associated with solenoid valve connected to a control valve, the ID/IS block shall have a unique tag number and not that of the valve and solenoid valve, e.g. valve 110LV-0140, ID/IS block 110I-0210, solenoid valve 110LY-0140. See example L-06.
3.17.2
Trip signals to motors / MOVs are outputs from the ESD (i.e. ID/IS -blocks) and shall be tagged as per ANNEXURE - 1: MOTOR CONTROL SCHEMES & ANNEXURE - 2: MOV CONTROL SCHEMES. Please refer the same for all signals of Motor and MOV.
3.18
ESD DCS
= =
3.19
KB BLOCKS
The KB blocks should be used for time sequence control only (see examples L-11). Input and output signals shall be tagged in analogy with input and output signals from ID/IS blocks.
DOCUMENT NO REV
GEN-004-R1
EECS-50-100-003
Page 9 of 28
04
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
3.20
DOCUMENT NO
REV
EECS-50-100-003
Page 10 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.0
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
COMMENTS
4.1.2
LEVEL
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
COMMENTS
DOCUMENT NO
REV
EECS-50-100-003
Page 11 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.1.2.2
CALIBRATED INSTRUMENT
Example S-03
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
COMMENTS
4.1.3
4.1.3.1
PRESSURE
LOCAL PRESSURE INDICATING INSTRUMENT
Example S-04
TAG NUMBER
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION
PCD NO.
COMMENTS
110PI-0102
FIELD
DOCUMENT NO
REV
EECS-50-100-003
Page 12 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.1.3.2 4.1.3.2.1
TAG NUMBER
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION
PCD NO.
COMMENTS
110PSV-0106
FIELD
4.1.3.2.2
TAG NUMBER
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION
PCD NO.
COMMENTS
110PSV-0108
FIELD
DOCUMENT NO
REV
EECS-50-100-003
Page 13 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.1.3.2.3
RUPTURE DISC
Example S-07
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
COMMENTS
4.1.3.2.4
PRESSURE REGULATOR
Example S-08
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
COMMENTS
DOCUMENT NO
REV
EECS-50-100-003
Page 14 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.1.4 4.1.4.1
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
COMMENTS
110 TI-0102
FIELD
4.1.4.2
TEMPERATURE POINT
Example S-10
COMPONENT/FUNCTION THERMOWELL
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
DOCUMENT NO
REV
EECS-50-100-003
Page 15 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2
4.2.1
LOOP INSTRUMENTS
INDICATION WITH HIGH ALARM (SOFTWARE) IN DCS
Example L-01
TAG NUMBER COMPONENT/FUNCTION PRESSURE TX DCS INDICATOR HIGH ALARM H SOFTWARE FUNCTION / ALARM I/O TYPE SIGNAL FROM FIELD SIGNAL TO DCS LOCATION PCD NO. COMMENTS
AI SW
4.2.2
TAG NUMBER
COMPONENT/FUNCTION PRESSURE TX
SIGNAL TO DCS
LOCATION
PCD NO.
COMMENTS
110PT-0204
FIELD
110PI-0204
SW
DCS
110PI-0204A 110PAH-0204
FIELD DCS
Note: 1. In case of conventional type, Local Indicator shall be wired with transmitter loop. 2. In case of FF type, Local Indicator shall be FF compliant to be configured on same segment.
DOCUMENT NO
REV
EECS-50-100-003
Page 16 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.3
CONTROL LOOP
Example L-03
TAG NUMBER
COMPONENT/FUNCTION FLOW ELEMENT ORIFICE D/P TX FLOW FLOW IND CONTROLLER HIGH ALARM LOW ALARM GLOBE CONTROL VALVE
I/O TYPE
SIGNAL FROM
SIGNAL LOCATION TO
PCD NO.
COMMENTS
FIELD AI H,L SW FIELD DCS FIELD DCS DCS DCS AO DCS FIELD FIELD
4.2.4
DOCUMENT NO
REV
EECS-50-100-003
Page 17 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
TAG NUMBER 110PT-0160 110PIC-0160 110PAH-0160 110PAL-0160 110PV-0160A 110PV-0160B 110PY-0160A 110PY-0160B
COMPONENT/-FUNCTION PRESSURE TX PRESSURE IND CONTROLLER HIGH ALARM LOW ALARM GLOBE CONTROL VALVE GLOBE CONTROL VALVE FUNCTION BLOCK FUNCTION BLOCK
I/O TYPE AI
SIGNAL TO DCS
PCD NO.
COMMENTS
H,L H L
SW
SPLIT RANGE
AO AO SW SW
DCS DCS
FIELD FIELD
4.2.5
SOFTWARE TAG NUMBER COMPONENT/-FUNCTION FUNCTION / ALARM 110FT-0231 110FIC-0231 110FAH-0231 110FV-0231 110LT-0210 110LIC-0210 110LAL-0210 VORTEX FLOW METER FLOW IND CONTROLLER HIGH ALARM GLOBE CONTROL VALVE D/P TX LEVEL LEVEL IND CONTROLLER LOW ALARM L H
I/O TYPE AI SW
SIGNAL TO DCS
PCD NO.
COMMENTS
AO AI SW
DCS FIELD
FIELD DCS
DOCUMENT NO
REV
EECS-50-100-003
Page 18 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.6
TAG NUMBER 110HS-0140 110LT-0140 110LIC-0140 110LAH-0140 110LAL-0140 110LV-0140 110LT-0180 110LI-0180 110LALL-0180 110LY-0140 110LZSO-0140 110LZSC-0140 110LZAO-0140 110LZAC-0140
COMPONENT/FUNCTION HAND SWITCH D/P TX LEVEL LEVEL IND CONTROLLER HIGH ALARM LOW ALARM GLOBE CONTROL VALVE D/P TX LEVEL DCS INDICATOR LOW LOW ALARM SOLENOID VALVE LIMIT SWITCH OPEN LIMIT SWITCH CLOSE STATUS OPEN STATUS CLOSE
SOFTWFUNC/ALM
I/O TYPE SI AI
PCD NO.
COMMENTS RESET
H,L
AO AI LL SI SI DO DI DI SI SI
DOCUMENT NO
REV
EECS-50-100-003
Page 19 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.7 4.2.8
4.2.9
TAG NUMBER
COMPONENT/FUNCTION PRESSURE TX DCS INDICATOR SOLENOID VALVE LIMIT SWITCH CLOSE LIMIT SWITCH OPEN STATUS OPEN STATUS CLOSE GLOBE ON-OFF VALVE
I/O TYPE AI SI DO DI DI SI SI
SIGNAL LOCATIO TO N ESD DCS FIELD ESD ESD DCS DCS FIELD DCS FIELD FIELD FIELD DCS DCS FIELD
PCD NO.
COMMENTS
DOCUMENT NO
REV
EECS-50-100-003
Page 20 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.10
TAG NUMBER 110XY-0103 110XV-0103 110XZSC-0103 110XZSO-0103 110XZAO-0103 110XZAC-0103 110HS-0103A 110HS-0103
SOFTWARE COMPONENT/-FUNCTION FUNCTION / ALARM SOLENOID VALVE GLOBE ON-OFF VALVE LIMIT SWITCH CLOSE LIMIT SWITCH OPEN STATUS OPEN STATUS CLOSE HAND SWITCH HAND SWITCH
I/O TYPE DO
PCD NO.
COMMENTS
DI DI
FIELD FIELD
DCS DCS
DOCUMENT NO
REV
EECS-50-100-003
Page 21 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.11
KB BLOCK
Example L-11
TAG NUMBER
COMPONENT/-FUNCTION
SIGNAL TO DCS
PCD NO.
COMMENTS
110PDT-0570 110PDI-0570 110PDAHH-0570 110PDALL-0570 110PDAH-0570 110PDAL-0570 110HS-0310 110KA-0310A 110KA-0310B 110XY-0310A 110XY-0310B 110XZSC-0310A 110XZSO-0310A 110XZAC-0310B 110XZSO-0310B 110XV-0310A 110XV-0310B
DIFF. PRESSURE TX DIFF. PRESS INDICATOR DCS D/P ALARM HIGH HIGH D/P ALARM LOW LOW DIFF PRESS ALARM HIGH DIFF PRESS ALARM LOW HAND SWITCH STATUS INDICATOR ALARM INDICATOR SOLENOID VALVE SOLENOID VALVE LIMIT SWITCH CLOSE LIMIT SWITCH OPEN STATUS CLOSE STATUS OPEN GLOBE ON-OFF VALVE GLOBE ON-OFF VALVE
DCS DCS FIELD FIELD FIELD FIELD DCS DCS FIELD FIELD
DOCUMENT NO
REV
EECS-50-100-003
Page 22 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.12 4.2.13
4.2.14
TAG NUMBER 110PT-0212A 110PT-0212B 110PT-0212C 110PI-0212A 110PI-0212B 110PI-0212C 110PAH-0212A 110PAH-0212B 110PAH-0212C 110PAHH-0212
COMPONENT/FUNCTION PRESSURE TX PRESSURE TX PRESSURE TX DCS INDICATOR DCS INDICATOR DCS INDICATOR HIGH ALARM HIGH ALARM HIGH ALARM HIGH HIGH ALARM
I/O TYPE AI AI AI SI SI SI
IGNAL TO LOCATION PCD NO. ESD ESD ESD DCS DCS DCS FIELD FIELD FIELD DCS DCS DCS DCS DCS DCS
COMMENTS
SI
ESD
DCS
DCS
DOCUMENT NO
REV
EECS-50-100-003
Page 23 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.15
TAG NUMBER COMPONENT/-FUNCTION 110FE-0232 110FT-0232 110FIC-0232 110FAL-0232 110FAH-0232 110FV-0232 110TE-0232 110TT-0232 110TI-0232 110TAH-0232 110PT-0232 110PI-0232 110PAL-0232 FLOW ELEMENT ORIFICE D/P TX FLOW FLOW IND CONTROLLER LOW ALARM HIGH ALARM GLOBE CONTROL VALVE RTD TEMP. TRANSMITTER DCS INDICATOR HIGH ALARM PRESSURE TX DCS INDICATOR LOW ALARM
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION FIELD
PCD NO.
COMMENTS
AI H,L SW
FIELD
DCS
AO
DCS
FIELD
FIELD FIELD
AI H SW
FIELD
DCS
AI SW
FIELD
DCS
DOCUMENT NO
REV
EECS-50-100-003
Page 24 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.16
LEVEL CONTROL
Example L-16
TAG NUMBER
COMPONENT/FUNCTION D/P TX LEVEL LEVEL IND CONTROLLER LOW ALARM HIGH ALARM GLOBE CONTROL VALVE
I/O TYPE AI
SIGNAL TO DCS
PCD NO.
COMMENTS
H,L
SW
AO
DCS
FIELD
FIELD
DOCUMENT NO
REV
EECS-50-100-003
Page 25 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.17
RATIO CONTROL
Example L-17
TAG NUMBER
COMPONENT/FUNCTION FLOW ELEMENT ORIFICE D/P TX FLOW DCS INDICATOR LOW ALARM HIGH ALARM FLOW ELEMENT ORIFICE D/P TX FLOW DCS INDICATOR LOW ALARM HIGH ALARM RATIO IND CONTROLLER GLOBE CONTROL VALVE
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATION
PCD NO.
COMMENTS
110FE-0102 110FT-0102 110FI-0102 110FAL-0102 110FAH-0102 110FE-0103 110FT-0103 110FI-0103 110FAL-0103 110FAH-0103 110FFIC-0104
FIELD AI H,L SW FIELD DCS FIELD DCS DCS DCS FIELD AI H,L SW FIELD DCS FIELD DCS DCS DCS RATIO SW DCS RATIO CONTROL
110FV-0104
AO
DCS
FIELD
FIELD
DOCUMENT NO
REV
EECS-50-100-003
Page 26 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.18
Example L-18
COMPONENT/-FUNCTION FLOW ELEMENT ORIFICE D/P TX FLOW FLOW IND CONTROLLER HIGH ALARM GLOBE CONTROL VALVE
I/O TYPE
SIGNAL FROM
SIGNAL TO
LOCATI ON FIELD
PCD NO.
COMMENTS
AI H SW
FIELD
DCS
AO
DCS
FIELD
FIELD
FLOW ELEMENT ORIFICE D/P TX FLOW FLOW IND CONTROLLER HIGH ALARM GLOBE CONTROL VALVE D/P TX LEVEL LEVEL IND CONTROLLER SELECTOR SWITCH AO AI SW DCS FIELD FIELD DCS H AI SW FIELD DCS
DOCUMENT NO
REV
EECS-50-100-003
Page 27 of 28
04
GEN-004-R1
The drawing, design and details given on this format are the property of ESSAR ENGINEERING CENTRE. They are merely loaned on the borrower's express agreement that they will not be reproduced, copied, exhibited or used, except in the limited way permitted by a written consent given by the lender to the borrower for the intended use.
4.2.21
Refer Annexure -1 for Motor Control Schemes Refer Annexure -1 for Motor Control Schemes
4.2.19
4.2.20
DOCUMENT NO
EECS-50-100-003
GEN-004-R1
Page 28 of 28
REV
04
P & ID SYMBOL
DESCRIPTION
TYPICAL - 5 : SIGNALS AND COMMANDS FOR THE MOTORS WITH MANUAL START & DCS INTERLOCK STOP
ADDED
Note 10 To be connected to process parameter
ML*
ML*R
0123
0123
Note-10
Tag Number ML* -0123 ML*R -0123 MS*S -0123 MS*T -0123
I/O Type SI / DI SI SI DO
MS* 0123
Note-2
0001
*M-0123
MS*
MS*
0123
0123
Note 11
Notes 1. LOCAL : All motors shall have START & STOP and LOCAL-REMOTE selection facility in the field on LCS. 2. DCS : RUN and REMOTE status is used as monitoring signals hence shall be via serial link. STOP command based on interlock from DCS shall be via hardwired. START command by operator from DCS shall be connected via serial link as shown. 3. Interlock : STOP command shall be generated by "OR-ing" between process interlock and manual STOP by DCS operator. 4. If any additional signal(s) are required to be configured in DCS or ESD, the same shall be indicated as per the legends sheet. 5. * = Equipment Code Letter as per Legend sheet Table-1. (ML*R - Remote status feedback to DCS.) 6. Start - Stop and Local-Remote selector switches of LCS shall not be indicated in P&ID. 7. If REMOTE is selected, the motor shall START based on DCS interlock. If LOCAL is selected, the motor can START from field (LCS). In LOCAL mode, START interlock(DCS) shall remain bypassed. 8. STOP from field(LCS) and DCS(if indicated) shall always be available irrespective of Local-Remote selection. 9. LOCAL-REMOTE selection from field is required where START from Remote(DCS/ESD) is considered. 10. If RUN status signal is used for interlock in DCS or ESD, the connection shall be indicated as HARDWIRED. 11. If STOP by operator from DCS is also required, then the same shall be indicated as shown.
Note-2
TYPICAL - 6 : SIGNALS AND COMMANDS FOR THE MOTORS WITH DCS INTERLOCK - AUTO START & STOP
ADDED
Note 10
ML*
ML*R
0123
0123
Note-10
Tag Number ML* -0123 ML*R -0123 MS*S -0123 MS*T -0123 To be connected to process parameter
I/O Type SI / DI SI D0 DO
MS* 0123
0001
*M-0123
Notes 1. LOCAL : All motors shall have START & STOP and LOCAL-REMOTE selection facility in the field on LCS. 2. DCS : RUN and REMOTE status is used as monitoring signals hence shall be via serial link. START & STOP commands are generated based on process interlock, hence shall be via hardwired. 3. Interlock : START & STOP from DCS shall be based on process interlock 4. If any additional signal(s) are required to be configured in DCS or ESD, the same shall be indicated as per the legends sheet. 5. * = Equipment Code Letter as per Legend sheet Table-1. (ML*R - Remote status feedback to DCS.) 6. Start - Stop and Local-Remote selector switches of LCS shall not be indicated in P&ID. 7. If REMOTE is selected, the motor shall START/STOP based on DCS interlock. If LOCAL is selected, the motor shall be operated from field (LCS). In LOCAL mode, DCS START interlock shall remain bypassed. 8. STOP from LCS(field) and DCS(interlock) shall always be available irrespective of Local-Remote selection. 9. LOCAL-REMOTE selection from field is required where START from Remote(DCS/ESD) is considered. 10. If RUN status signal is used for interlock in DCS or ESD, the connection shall be indicated as HARDWIRED.
TYPICAL - 7 : SIGNALS AND COMMANDS FOR THE MOTORS WITH DCS STOP INTERLOCK / MANUAL STOP
ML*
ADDED
Note 9 To be connected to process parameter
0123
Note-9
I/O Type SI / DI DO
MS* 0123
0001
Note-6
*M-0123
Notes 1. LOCAL : All motors shall have START & STOP facility in the field on LCS. 2. DCS : RUN status is used as monitoring signals hence shall be via serial link. STOP command based on interlock from DCS shall be via hardwired. If STOP by operator from DCS is required, then the same shall be indicated as shown. 3. Interlock : STOP command shall be generated by "OR-ing" between process interlock and manual STOP by DCS operator. 4. If any additional signal(s) are required to be configured in DCS, the same shall be indicated as per the legends sheet. 5. * = Equipment Code Letter as per Legend sheet Table-1. 6. Start - Stop switches of LCS shall not be indicated in P&ID. 7. There shall be OR logic in interlock. Motor shall stop either by Process interlock or by operator STOP. 8. LOCAL-REMOTE selection from field is not required, where only STOP from Remote(DCS/ESD) is considered. 9. If RUN status signal is used for interlock in DCS or ESD, the connection shall be indicated as HARDWIRED.
MS*
0123
T Note-2
TYPICAL - 8 : SIGNALS AND COMMANDS FOR THE MOTORS WITH ESD INTERLOCK - AUTO START
ADDED
Note 10
ML*
ML*R
0123
0123
Note-10
Tag Number ML* -0123 ML*R -0123 MS*X -0123 MS*T -0123
I/O Type SI / DI SI D0 DO
MS* 0123
MS*
0123
*M-0123
T Note-2
0001
Notes 1. LOCAL : All motors shall have START & STOP and LOCAL-REMOTE selection facility in the field on LCS. 2. DCS : RUN and REMOTE status is used as monitoring signals hence shall be via serial link. If STOP by operator from DCS is required, the same shall be indicated via serial link as shown. 3. Interlock : START from ESD shall be based on process interlock. 4. If any additional signal(s) are required to be configured in DCS, the same shall be indicated as per the legends sheet. 5. * = Equipment Code Letter as per Legend sheet Table-1. (ML*R - Remote status feedback to DCS.) 6. Start - Stop and Local-Remote selector switches of LCS shall not be indicated in P&ID. 7. If REMOTE is selected, the motor shall START based on DCS interlock. If LOCAL is selected, the motor shall be operated from field (LCS). In LOCAL mode, START interlock shall remain bypassed. 8. STOP from LCS(field) and DCS shall always be available irrespective of Local-Remote selection. 9. LOCAL-REMOTE selection from field is required where START from Remote(DCS/ESD) is considered. 10. If RUN status signal is used for interlock in DCS or ESD, the connection shall be indicated as HARDWIRED. 11. For ESD Interlock, instrument tag no. shall be as follows: For pump, 138-P-0001A, ESD Interlock tag shall be like - 138MSPX-0001A. Where P = Pump, X = ESD Interlock command
Page 2 of 4
P & ID SYMBOL
DESCRIPTION
TYPICAL - 1 : SIGNALS AND COMMANDS FOR MOVs (ON-OFF TYPE) - LOCAL OPERATION
Notes 1. LOCAL : All MOVs shall have OPEN - CLOSE facility on MOV actuator in field 2. DCS : OPEN & CLOSE position indication is configured in DCS 3. Interlock : No interlock 4. If MOV actuator fault alarm is required, the same shall be indicated as per the legend sheet 5. If the MOVs are connected in "Pakscan" system, all Signals & Commands shall be indicated by serial link to/from DCS. However, ESD interlock command shall be indicated hardwired. 6. Integral part of the MOV actuator and shall not be indicated in P&ID
HV 0123
HS 0123
TYPICAL - 2 : SIGNALS AND COMMANDS FOR MOVs (ON-OFF TYPE) - DCS OPERATION
O O HZA 0123 C C Note-5 O C Note-6 HZS 0123 HZS L 0123 R C O L 0123 HZA R HS 0123
Notes 1. LOCAL : OPEN - CLOSE and LOCAL - REMOTE selection on MOV actuator in field 2. DCS : OPEN-CLOSE Command, OPEN-CLOSE position & LOCAL-REMOTE indication in DCS 3. Interlock : No interlock 4. If MOV actuator fault alarm is required, the same shall be indicated as per the legend sheet 5. If the MOVs are connected in "Pakscan" system, all Signals & Commands shall be indicated by serial link to/from DCS. However, ESD interlock command shall be indicated hardwired. 6. Integral part of the MOV actuator and shall not be indicated in P&ID
HV 0123
HS 0123
TYPICAL - 3 : SIGNALS AND COMMANDS FOR MOVs (ON-OFF TYPE) - WITH DCS INTERLOCK
O HS 0123 C
0001
Note-7
Notes 1. LOCAL : OPEN - CLOSE and LOCAL - REMOTE selection on MOV actuator in field 2. DCS : OPEN-CLOSE Command, OPEN-CLOSE position & LOCAL-REMOTE indication in DCS 3. Interlock : DCS interlock on process parameter 4. If MOV actuator fault alarm is required, the same shall be indicated as per the legend sheet 5. If the MOVs are connected in "Pakscan" system, all Signals & Commands shall be indicated by serial link to/from DCS. However, ESD interlock command shall be indicated hardwired. 6. Integral part of the MOV actuator and shall not be indicated in P&ID 7. If AUTO is selected, the Valve shall operate as per process interlock. If MAN is selected, operator can close/open the valve manually. In MAN mode, DCS interlock will remain bypassed.
XV 0123
HS 0123
Page 1 of 3
P & ID SYMBOL
DESCRIPTION
TYPICAL - 4 : SIGNALS AND COMMANDS FOR MOVs (ON-OFF TYPE) - WITH ESD INTERLOCK
0001
UV 0123 Note-6
Notes 1. LOCAL : OPEN - CLOSE and LOCAL - REMOTE selection on MOV actuator in field 2. DCS : OPEN-CLOSE Command, OPEN-CLOSE position & LOCAL-REMOTE indication in DCS 3. Interlock : ESD Interlock on process parameter 4. If MOV actuator fault alarm is required, the same shall be indicated as per the legend sheet 5. If the MOVs are connected in "Pakscan" system, all Signals & Commands to/from DCS shall be indicated by serial link. However, ESD interlock command shall be Hardwired. Note : ESD command shall be directly connected to actuator via hard wire and shall override all DCS commands. 6. Integral part of the MOV actuator and shall not be indicated in P&ID 7. For ESD O/P, tag no. shall be like : 138UVX-0123 (ESD command for UV-0123 of unit 138) X = ESD Interlock Output
TYPICAL - 5 : SIGNALS AND COMMANDS FOR MOVs (INCHING TYPE) - LOCAL OPERATION
Notes 1. LOCAL : All MOVs shall have OPEN - CLOSE facility on MOV actuator in field 2. DCS : Position feedback indication is configured in DCS(0-100%) 3. Interlock : If interlock is required, the same shall be indicated as per Typical-3 or 4, valve tag name(XV or UV) shall change accordingly. 4. If MOV actuator fault alarm is required, the same shall be indicated as per the legend sheet 5. If the MOVs are connected in "Pakscan" system, all Signals & Commands shall be indicated by serial link to/from DCS. However, ESD interlock command shall be indicated hardwired. 6. Integral part of the MOV actuator and shall not be indicated in P&ID
HV 0123
HS 0123
TYPICAL - 6 : SIGNALS AND COMMANDS FOR MOVs (INCHING TYPE) - DCS OPERATION
R HIC 0123 0123 L Note-5 O C Note-6 HZT 0123 HZS L 0123 R 0123 HZI HZA
Notes 1. LOCAL : OPEN - CLOSE and LOCAL - REMOTE selection on MOV actuator in field 2. DCS : Position Command(0-100%) , Position Feedback & LOCAL-REMOTE indications are configured in DCS 3. Interlock : If interlock is required, the same shall be indicated as per Typical-3 or 4, valve tag name(XV or UV) shall change accordingly. 4. If MOV actuator fault alarm is required, the same shall be indicated as per the legend sheet 5. If the MOVs are connected in "Pakscan" system, all Signals & Commands shall be indicated by serial link to/from DCS. However, ESD interlock command shall be indicated hardwired. 6. Integral part of the MOV actuator and shall not be indicated in P&ID
HV 0123
HS 0123
Page 2 of 3