The arresters (Varistors, Metal Oxide Varistors MOV) are connected in parallel to the capacitor bank They protect the capacitors from overvoltage by diverting the capacitor current They have non linear voltage / current characteristic Several units are connected in parallel to accommodate the required energy accumulation capability They can have porcelain or polymer housings
Arresters Bank-PORCELAIN
Arresters Bank-POLYMER
capacitor impedance rated line current overload current magnitude and duration swing currents during network disturbances
Types
of simulation:
fault clearing in parallel line fault clearing in other lines voltage versus time stresses v(t) maximum continuous operating voltage (MCOV) minimum number of discs in series connection
Check:
Results:
Voltage Time Characteristics (preheated to 60C due to nominal energy discharge) 1,3 1,25 1,2 Rated Voltage / pu 1,15 1,1 1,05 1 0,95 0,9 0,85 0,8 0,1 1 10 time / sec 100 1000
Input
External and internal fault cases (type, sequence, number and duration) By-pass device operation sequence By-pass switch closing cycles Fault clearing cycles Re-closing cycles
Establish and coordinate an appropriate control & protection strategy Simulate external fault cases and calculate MOV energy Establish appropriate MOV energy rating including redundancy Simulate internal fault cases and calculate MOV energy Check MOV voltage protective level
Are normally four columns arresters Use the SIOV-E78 SR123 Metal Oxide (MO) block Rated energy withstand capability of one block is 36 kJ Maximum current per column 1600 A
3EQ3
Are normally three columns arresters Use the SIOV-E99 SR 113 Metal Oxide (MO) block Rated energy withstand capability of one bock is 64 kJ Maximum current per column 2100 A The three digit figure in the middle of the type identification denote the rated voltage: 3EQ3 127-5CZ7 has a rated voltage of 127 kV
10
operation counters exist on the arresters leakage current measurement exist, or is possible operation may result in temporary by-pass of the bank
Arrester Failure If
one or more of the parallel arresters fail, the protection settings have to be adjusted via the human machine interface
11
annual maintenance the units shall be checked for pollution and cleaned if required vent opening shall be checked if they are still intact
The
Electrical
and mechanical connections shall be checked for correct torque units shall be removed form platform
Damaged Do
12
currents
If
the number of units on one platform falls below the minimum number, all units have to be exchanged at the same time mixing arresters of different phases consult the manufacturer consult the manufacturer on failure of arresters of arrester to higher energy accumulation is not
Before
Always
Upgrading
possible
13