Академический Документы
Профессиональный Документы
Культура Документы
Using the Belotti BTS POWERSAFE solution your AC Connected units, such as rectifiers, Inverter and air condition units, will continue operating even during extreme mains voltage variation without need for the back-up generator to switch-on and, furthermore, thanks to the Galvanic Isolation provided by the Isolation transformer all the site will be totally protected from any Mains problem as well as protected from surges and spikes by our three poles Surge Protection. Working hours of back-up generators will dramatically decrease. Our Solution for Telecom is the result of the experience we gained in years of operation all over Africa working in partnership with the most important Telecom companies allowing our product to meet their stringent requirements in spite of the environmental difficulties. The solution briefly is the integration of three of our products: A) Belotti Voltage Stabiliser (AVR) B) Belotti Ultra-Isolation transformer C) Belotti Surge Protection (TVSS)
A Large voltage variations can be harmful to many ACunits, causing temporary or definite shut down and By-passing the Loads to the Back-Up Generator. Wit the Belotti Stabiliser it is not just possible to protect your connected units, but you will maintain full operation! B Ultra-Isolation Transformer D/Y (Dyn11) guarantee the Best electrical Protection and noise filtering for your BTS. Belotti transformer design gives: Galvanic Isolation and screen Pri/Sec Increased Voltage Phase Equilibration Generation of new, clean Neutral at Secondary avoiding all problems caused by the mains neutral. Clean neutral is essential for the correct operation of Single-phase loads. C Belotti Surge Protection Module SLP class C connected at the Mains entrance with its high discharge Power (40kA 8/20 s) and low residual Voltage is completing the protection of the installation. Higher Discharge Modules or combined (B+C) Modules are available for special locations. Components can be supplied also separately. We can customize our BTS POWERSAFE to meet your needs and requirement. Designed and Manufactured in Italy
MAINS FEATURES:
Wide voltage regulation range : 160-290V(Phase-N) 10 to 200kVA, three-phase 400/230V or 208/120V 50/60Hz 3 to 200kVA single phase and three/mono Indoor IP21construction (Rack 19 space save) or Outdoor IP54 construction (Fibreglass). - Emergency By-pass - Customized project
SURGE PROTECTION
The Belotti BTS Powersafe is supplied in three different configurations in order to satisfy the different Telecom requirements. The Standard Input window is +/-25% The Standard Output stability is +/-1% THREE-PHASE (BTS POWERSAFE 3/3) Indoor or Outdoor SINGLE-PHASE (BTS POWERSAFE 1/1) Indoor or Outdoor THREE-MONO (BTS POWERSAFE 3/1) Indoor or Outdoor Input Three-phase/ Output single-phase Common features: Isolation Transformer Surge protection class C Voltage Monitory Relay Fast Response Customized Input window
R
TB
SINGLE-PHASE MODEL
U
S T A B IL IS E D OUTPUT
IN P U T
ISO
AT M CC
TB AT CC M ISO
BOOSTER TRANSFORMER VARIABLE AUTOTRANSFORMER SOLID STATE CONTROL CIRCUIT SERVOMOTOR INSULATION TRANSFORMER
THREE-MONO MODEL
is the latest version implemented to satisfy the needs of some of our client affected by phase missing problem during operation. It can guarantee supply (single-phase) to the BTS even when one or two phases are missing thanks to the Belotti patented Voltage PHASE SELECTOR.
B) ULTRA ISOTRANSFORMER
Belotti Ultra-Isolation Transformers guarantee the best Mains Input protection and noise filtering at BTS Powersafe Input. FEATURES: Galvanic Isolation Primary / Secondary Isolating Screen Dyn11 Design giving Phase Equilibration and Creation of a New Neutral Noise Filtration
SLP-275V/3 SPD type 2-surge arrester Replaceable varistor module, visual fault signalling
TECHNICAL DATA Nominal Voltage Maximum operating Voltage Nominal Discharge current (8/20 s)/pole Maximum Discharge current (8/20 s)/pole Voltage Protection Level Response Time Maximum overcurrent protection Degree of Protection Range of Operating Temperatures Mounting on Fault Indication Meets the requirements of Standard Un Uc in lmax Up ta SLP-275 V/3 230V AC 275V AC/350V DC 20 kA 40 kA 0,9 kV 1,2 kV 25 ns 35 kA 160 A gL/gG IP 20 -40C +80C DIN rail 35 mm Red Indication Field EN 61643-11 +A11
Stabilisers AVR for Telecom BST powersafe BST powersafe PWM BTS powersafe EB
Variable autotransformers
El Core transformers