Вы находитесь на странице: 1из 3

E06

PREVENTATIVE MAINTENANCE TECHNICAL DATA SCHEDULES

High Voltage Switchgear ELECTRICAL

ACTIVITY Last Amendment Date: 18-Jan-2008 1 Carry out diagnostic testing techniques, where practical, to indicate the condition of equipment as per AS2467 Where practical, trip and re-close circuit breaker, to verify that it is capable of satisfactory operation as per AS2467. *Tripping should be initiated by electrical operation of the trip coil Check switch room especially for;-general cleanliness. -heating. -ventilation. and other relevant items detailed in 6.5.1, 6.5.2 & section 3,AS 2467. Clean switchgear as detailed in AS2467 Inspect and carry out other operation as detailed in AS2467 Inspect equipment enclosure heaters and anti-condensation finishes as detailed in AS2467 Examine and clean arc control devices as detailed in AS2467 Inspect or examine mechanisms as detailed in AS2467 Inspect and clean auxiliary switches, indicating devices and interlocks as detailed in AS2467 Inspect and clean isolating contracts and renew or recondition where necessary as detailed in AS2467 Maintain overload devices and protective devices as detailed in AS2467 Maintain instrument and protective devices as detailed in section 13, AS2467 Inspect control relays & contactors as detailed in clause 6.5.1.12, AS2467 Verify connections as detailed in clause 6.5.2.12, AS2467 Maintain secondary wiring & fuses as detailed in clause 6.5.2.13, AS 2467. A

TYPE OF SERVICE B C D Y E

4 5 6

Y Y Y

7 8 9

Y Y Y

10

11 12 13 14 15

Y Y Y Y Y
Page 1 of 3

ACTIVITY Last Amendment Date: 18-Jan-2008 16 17 Verify the operation of any heaters as per clause 6.5.2.15, AS2467 Inspect, verify and maintain isolators and earthing switches as per clause 6.5.2.16, AS2467 Verify operation of any shutter mechanism and lubricate operating mechanism and associated linkage as detailed in clause 6.5.2.18, AS2467 Inspect, examine and clean switchgear spouts as per clause 6.5.2.18, AS2467 Maintain busbars and busbar chambers as per clause 6.5.2.19, AS2467 Check weather shields as per clause 6.5.2.20, AS2467 Carry out final verification operations as detailed in AS2467 Maintain auxiliary items as per section 12, AS2467 Carry out operation involving high voltage fuse connections and associated linkage as detailed in AS2467 Where applicable, carry out operations involving testing and sampling of insulating oils, replacement of oil and operations involving tanks and tank lining and tank lifting mechanisms as detailed in clauses 7.3.1.8, 7.3.1.9 and 7.3.1.10, AS2467 Carry out all maintenance operations recommended for the particular type of switchgear as summarised in the applicable table in AS2467 Carry out maintenance tasks to the manufacturer's operations and maintenance instructions which shall be read in conjunction with AS2467 Maintain records as required by AS2467 Record all results in log book A

TYPE OF SERVICE B C D Y Y E

18

19 20 21 22 23 24

Y Y Y Y Y Y

25

26

27

28 29

Y Y

SPECIAL COMMENTS AND TECHNICAL DATA **SPECIALIST LICENSED CONTRACTOR REQUIRED FOR THIS WORK. *WHERE SHUT DOWN OF SUPPLY IS REQUIRED FOR INSPECTION AND TESTING PURPOSES ,LIASE AND CO-OPERATE WITH THE CLIENT IN ARRANGING DATES AND TIMES TO REDUCE TO A MINIMUM ANY INTERFERENCE TO THE CLIENT'S OPERATIONS. *ESTABLISH SAFE WORKING CONDITIONS FOR ANY WORK OR TESTING. *D SERVICE ANNUAL BUT MAY VARY DEPENDING ON THE NUMBER OF OPERATIONS PERFORMED ON FIXED TIME INTERVAL.

Page 2 of 3

Page 3 of 3

Вам также может понравиться