Вы находитесь на странице: 1из 4

T/2000 Multi-Function System for Testing Substation Equipment CT, VT, PT and Transducer Testing

H V Diagnostics, Inc 271 Rope Mill Pkwy, Ste 2 Woodstock, GA 30188 Phone: 678-445-2555 Fax: 678-445-2557 E-mail: sales@hvdiagnostics.com
7/14/2004

Page 1

T2000 DataSheet 2004 Subject to change without. notice

Features:

Multi-function system for testing substation equipment such as: Current, Voltage and Power Transformers and most transducers. Primary Current Injection up 800A Up to 3000 VAC Hi Pot Test Multi-Meter Functions Oscilloscope Functions Generates up to 800A and 3000V Large Graphical Display Optional Thermal Printer Test Results and Settings are Saved in Local Memory (up to 500) RS232 Interface for PC Connection Compact and Lightweight, 58 lbs! Software that is compatible with Windows

The T/2000 is a unique solution for all testing operations during commissioning and maintenance of substations. Testing can be performed on all types and on current and voltage transformers, transducers and other electrical devices! In addition, the T/2000 incorporates a powerful multi-meter and phase angle meter, with oscilloscope functions. T/2000: One of the most powerful testing devices available! The T2000 contains a independent (not tied to mains) voltage / current generator amplifier that can produce 6 output modes: High AC current; Low AC current; Low DC current; Current impulses; High AC voltage; Low AC voltage). All outputs are adjustable and metered on the LCD display. The multi-purpose control knob makes navigating the functions of the unit very simple and quick to operate! The instrument has two independent measuring inputs for voltage and current and calculates phase angle, power (W / Vars), Power Factor, impedance and impedance components R and X.

One unit, multiple testing capabilities ~ less equipment to transport...


Current Transformer (CT) Tests

Ratio, polarity and burden (Current mode). Burden; secondary side Excitation curve and knee point calc. Winding or burden resistance Voltage withstand Polarity by impulse test Ratio, Voltage mode Ratio; polarity Burden, secondary side Ratio, electronic transformers Voltage withstand Secondary over-current protection Ration per TAP Resistance of TAP changer contacts

Voltage Transformer (VT) Tests

Power Transformers (PT) Tests

271 Rope Mill Pkwy, Ste 2 Woodstock, GA 30188 Web:www.hvdiagnostics.com


7/14/2004

HV Diagnostics Inc.
Suppliers of:

Phone: 678-445-2555 Fax: 678-445-2557 Email: sales@hvdiagnostics.com


T2000 DataSheet 2004 Subject to change without. notice

Page 2

Other Metering Performed and Displayed:


Active, Reactive, and Apparent Power Power Factor Impedance (Z) and impedance components (R/X)

Frequency Hz Phase Angle Resistance Current and Waveform Display

Software X.Pro-3000
When the PC is connected, settings can be created and transferred into T/2000 using X.PRO3000. X.PRO-3000 is a user friendly software that allows via a graphical interface, to control the set-up of T/2000 and to download test results. X.PRO-3000 is also a powerful report editor that allows the user create professional Test Reports that be exported in Access format.

Optional Accessories
Accessories for CT Testing Mains Supply Cable, 6 long Grounding cable, 12 long, terminated on one end with a banana plug, and on the other end with an earth connection clamp High voltage connection cables, 12 long, 5kV with earth screen. Terminated on both ends with HV connectors. Clamps for the HV connection Clamps to connect low voltage or low current or measurements Cable for low voltage or low current connection, shielded, 12 long. Terminated on one end with the measurement connector, and on the other with two banana plugs Additional Accessories: Interface cable for RS232 port High Current connection cables, 12 long. Terminated on one end with the high current connector; and on the other with the high current clamp Low current connection cables, 12 long. Terminated on both ends with banana plugs. Voltage outputs (4 cables: 2 red and 2 black)

Measurement inputs (4 cables: 2 red and 2 black) The instrument comes complete with the following: user manual, spare fuses (no.5), T16A. Software: X.PRO-3000 with user manual Optional Accessories Thermal printer Transport case Current Clamp: The current clamp avoids opening the secondary current circuit when performing the primary test of CT burden

Ordering Information:
Two Models of the T2000 are available T2000H..3000VAC, 200mA continuous .6A (1 minute) T2000L...1200VAC, 500mA continuous 1.5A (1 minute)

271 Rope Mill Pkwy, Ste 2 Woodstock, GA 30188 Web:www.hvdiagnostics.com


7/14/2004

HV Diagnostics Inc.
Suppliers of:

Phone: 678-445-2555 Fax: 678-445-2557 Email: sales@hvdiagnostics.com


T2000 DataSheet 2004 Subject to change without. notice

Page 3

271 Rope Mill Pkwy, Ste 2 Woodstock, GA 30188 Web:www.hvdiagnostics.com


7/14/2004

HV Diagnostics Inc.
Suppliers of:

Phone: 678-445-2555 Fax: 678-445-2557 Email: sales@hvdiagnostics.com


T2000 DataSheet 2004 Subject to change without. notice

Page 4

Вам также может понравиться