Вы находитесь на странице: 1из 57

SPRINKLER DIVISION

WATERFLOW SWITCHES PRESSURE SWITCHES SUPERVISORY DEVICES EXPLOSION-PROOF DEVICES

VSR-F
VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St.Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL, ULC and CSFM Listed, FM and LPC Approved, NYMEA Accepted Service Pressure: Up to 450 PSI Minimum Flow Rate for Alarm: 10 GPM Maximum Surge: 18 FPS Contact Ratings: Two sets of SPDT (Form C) 15.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2" conduit Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4/IP54 Rated Enclosure - use with appropriate conduit fitting Temperature Range: 40F/120F, 4.5C/49C Non-corrosive sleeve factory installed in saddle Caution: This device is not intended for applications in explosive environments Sizes Available: Pipe schedules 10 thru 40, sizes 2" thru 8" BS 1387 pipe 50mm thru 200mm Service Use: Automatic Sprinkler One or two family dwelling Residential occupancy up to four stories National Fire Alarm Code NFPA-13 NFPA-13D NFPA-13R NFPA-72

U.S. PAT. NO. 3921989 CANADIAN PAT. NO. 1009680 OTHERS PATENTS PENDING POTTER ELECTRIC, Rd., 1990
GENERAL INFORMATION The Model VSR-F is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2" thru 8". LPC approved sizes are 2" thru 8" (50mm thru 200mm). The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 gallons per minute or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, diecast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instructions of this switch.
PRINTED IN USA

Optional: Cover Tamper Switch Kit, Stock No. 0090018

INSTALLATION: See Fig.2 These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a fitting which changes the direction of the waterflow or within 24" of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices require a hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm 2mm). All other sizes require a hole with a diameter of 2" 1/8" (50mm 2mm). Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an eventual 50 ft-lbs. of torque (see Fig. 2). The vane must not rub the inside of the pipe or bind in any way. Specifications subject to change without notice.
PAGE 1 OF 2

MKT. #8800001 - REV L MFG. #5400761 - 11/95

VSR-F
VANE TYPE WATERFLOW SWITCH WITH RETARD FIG. 1
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

FIG. 2

CAUTION:

TO INSTALL, DRILL A HOLE AS INDICATED: PIPE SIZE 2" to 2 1/2" (50mm to 65mm) 3" to 8" (80mm to 200mm) HOLE SIZE 1 1/4" +1/8" -1/16" (33mm 2mm) 2" 1/8" (50mm 2mm)

An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

FIG. 3

TYPICAL ELECTRICAL CONNECTIONS

Note: For supervised circuits see Switch Terminal Connections drawing and caution note (Fig. 1).

NOTES: 1. The Model VSR-F has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. 2. A condition of LPC Approval of this product is that the electrical entry must be sealed to exclude moisture. TESTING The frequency of inspection and testing for the model VSR-F and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspectors test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-F is not recommended or advisable. A minimum flow of 10 gpm is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions.

PRINTED IN USA

MKT. #8800001 - REV L MFG. #5400761 - 11/95

PAGE 2 OF 2

VSR-SF
FOR SMALL PIPE Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com

VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD


Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833

Stock No. 1113000 U.S. PAT. NO. 3921989, CANADIAN PAT. NO. 1009680 OTHER PATENTS PENDING.
The Model VSR-SF is a vane type waterflow switch for use on wet sprinkler systems that use 1", 1 1/4", 1 1/2" or 2" pipe size. The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 gallons per minute or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. INSTALLATION: These devices may be mounted in horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a valve, drain or fitting which changes the direction of the waterflow. The unit has a 1" NPT bushing for threading into a non-corrosive TEE. See Fig. 2 for proper TEE size, type and installation. Screw the device into the TEE fitting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of
PRINTED IN USA

UL, ULC, CSFM LISTED and NYMEA ACCEPTED Service Pressure: Up to 250 PSI Minimum Flow Rate for Alarm: 10 GPM Maximum Surge: 18 FPS Enclosure: Die-cast, red enamel finish Cover held in place with tamper resistant screws Contact Ratings: Two sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC Conduit Entrances: Two knockouts provided for 1/2" conduit. Usage: Listed plastic, copper and schedule 40 iron pipe. Fits pipe sizes - 1", 1 1/4", 1 1/2" and 2" Note: 10 paddles are furnished with each unit, one for each pipe size of threaded and sweat TEE, one for 1" CPVC and one for 1 1/2" polybutylene. (CTS-Copper tubing size) Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4/IP55 rated enclosure - use with appropriate conduit fitting. Temperature range: 40 F to 120 F (4.5 C to 49 C) Caution: This device is not intended for applications in explosive environments. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, order Stock No. 0090018 waterflow. The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand. The device can also be used in copper or plastic pipe installations with the proper adapters so that the specified TEE fitting may be installed on the pipe run. INSPECTION AND TESTING: Check the operation of the unit by opening the inspectors test valve at the end of the sprinkler line or the drain and test connection, if an inspectors test valve is not provided. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-SF is not recommended or advisable The frequency of the inspection and testing and its associated protective monitoring system should be in accordance with the applicable NFPA Codes and Standards and/or authority having jurisdiction (manufacturer recommends quarterly or more frequently).
PAGE 1 OF 2

MKT. #8800003 - REV N MFG. #5400802 - 7/97

VSR-SF
FOR SMALL PIPE FIG. 1
Retard Adjustment: To change time, turn knob (either direction) for desired time delay. Use the minimum amount of retard necessary to prevent false alarms. A B setting is usually adequate for this. Factory set at B.

VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD

FIG. 2

Important: There are 10 paddles furnished with each unit. One for each size of threaded, sweat or plastic TEE as described in Fig. 2. These paddles have raised lettering that shows the pipe size and type of TEE that they are to be used with. The proper paddle must be used. The paddle must be properly attached (see drawing) and the screw that holds the paddle must be securely tightened.

Screw the device into the TEE fitting as shown. Care must be taken to properly orient the device for the direction of the waterflow. On sweat TEE's no threaded bushings, inserts or adapters are permitted unless they comply with the dimensions listed in the chart below. Important - The depth to the inside bottom of the TEE should
CAUTION: TO PREVENT LEAKAGE APPLY TEFLON TAPE SEALANT TO MALE THREADS ONLY. DO NOT USE ANY OTHER TYPE OF LUBRICANT OR SEALANT. APPROX. RETARD SETTINGS (IN SEC.) 0 0 A 10-25 B 20-40 C 35-55 D 50-70 E 60-90

APPROXIMATE DEPTH REQUIREMENT


TEE SIZE 1" x 1" x 1" 1 1/4" x 1 1/4" x 1" 1 1/2" x 1 1/2" x 1" 2" x 2" x1" THREADED 2 1/16" 2 7/16" 2 11/16" 3 3/16" SWEAT 1 3/4" 2 7/16" 2 1/4" 2 3/4" CTS, POLYBUTYLENE N/A N/A 2 1/2" N/A CPVC 2 7/16" N/A N/A N/A

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

FIG. 3

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

FIG. 4

TYPICAL ELECTRICAL CONNECTIONS

NOTE: FOR SUPERVISED CIRCUITS SEE SWITCH TERMINAL CONNECTIONS DRAWING AND CAUTION NOTE (FIG. 3).

NOTE: The Model VSR-SF has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other is used to operate a local audible or visual annunciator. TESTING: The frequency of inspection and testing for the model VSR-SF and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
PRINTED IN USA MKT. #8800003 - REV N MFG. #5400802 - 7/97 PAGE 2 OF 2

VANE TYPE WATERFLOW ALARM SWITCH - SMALL PIPE


Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL, ULC, CSFM and NYBSA Listed Service Pressure: Up to 250 PSI Minumum Flow Rate for Alarm: 10 GPM Maximum Surge: 18 FPS Enclosure: Die-cast, red enamel finish Cover held in place with tamper resistant screws Contacts: One set of SPDT (Form C), standard Second set optional, see below: 15 Amps at 125/250VAC 0.5 Amps at 125VDC 0.25 Amps at 250VDC 2.5 Amps at 30 VDC resistive Conduit Entrance: One opening for 1/2" conduit Usage: Listed plastic, copper and schedule 40 iron pipe For pipe sizes - 1", 1-1/4", 1-1/2", and 2" Note: 10 paddles are furnished with each unit, one for each pipe size of threaded and sweat TEE's, one for 1" CPVC, and one for 1-1/2" polybutylene. (CTS-Copper Tubing Size). Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4/IP55 rated enclosure - use with appropriate conduit fitting. Temperature range: 40F to 120F (4.5C to 49C) Caution: This device is not intended for applications in explosive environments. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional : Extra Contacts Switch Kit, Stock No. 0090013 Cover Tamper Switch Kit, Stock No. 5420220 installation. Screw the device into the TEE fitting as shown in Fig. 2. Care must be taken to properly orient the device for the direction of waterflow. The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand. TESTING: Check the operation of the unit by opening the inspectors test valve at the end of the sprinkler line, or the drain and test connection if a test valve is not provided. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSSP is not recommended or advisable.

VS-SP

STOCK NO. 1111100 U.S. Patent No. 3921989, Canadian Patent No. 1009680 Other Patents Pending

The Model VS-SP is a vane type waterflow switch for use on wet sprinkler systems. These devices may be used as sectional flow indicators on large sprinkler systems and on smaller sprinkler systems such as mobile homes and residential dwellings. INSTALLATION: These devices may be mounted in horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a valve, drain or fitting which changes the direction of the water flow. The unit has a 1" NPT bushing for threading into a noncorrosive TEE. See Fig. 2 for proper TEE size, type and
PRINTED IN USA

MKT. #8800004 - REV K MFG. #5400769 - 7/97

PAGE 1 OF 2

VANE TYPE WATERFLOW ALARM SWITCH - SMALL PIPE FIG. 1 FIG. 2

VS-SP

Important: There are 10 paddles furnished with each unit. One for each size of threaded, sweat or plastic TEE as described in Fig. 2. These paddles have raised lettering that shows the pipe size and type of TEE that they are to be used with. The proper paddle must be used. The paddle must be properly attached (see drawing) and the screw that holds the paddle must be securely tightened.

Screw the device into the TEE fitting as shown. Care must be taken to properly orient the device for the direction of the waterflow. On sweat TEE's no threaded bushings, inserts or adapters are permitted unless they comply with the dimensions listed in the chart below. Important - The depth to the inside bottom of the TEE should have the following dimensions: APPROXIMATE DEPTH REQUIREMENT
TEE SIZE 1" x 1" x 1" 1 1/4" x 1 1/4" x 1" 1 1/2" x 1 1/2" x 1" 2" x 2" x1" THREADED 2 1/16" 2 7/16" 2 11/16" 3 3/16" SWEAT 1 3/4" 2 7/16" 2 1/4" 2 3/4" CTS, POLYBUTYLENE N/A N/A 2 1/2" N/A CPVC 2 7/16" N/A N/A N/A

SWITCH INFORMATION

TYPICAL CONTROL PANEL CONNECTIONS

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal

NOTE: The Model VS-SP has one SPDT switch. An optional second switch is available if required. For example, one switch would connect to an annunciator panel, and the optional switch could be used to operate a local bell. Order Switch Kit No. 0090013.

TESTING
The frequency of inspection and testing for the Model VS-SP and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).

PRINTED IN USA

MKT. #8800004 - REV K MFG. #5400769 - 7/97

PAGE 2 OF 2

VSR-CF
VANE TYPE WATERFLOW SWITCH WITH RETARD FOR COPPER OR PLASTIC PIPE Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL, CSFM and NYBSA LISTED Service Pressure : Up to 175 PSI Minimum Flow Rate for Alarm: 10 GPM Maximum Surge: 18 FPS Contact Ratings: Two sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.0 Amps at 30 VDC resistive Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4/IP55 rated enclosure - use with appropriate conduit fitting Temperature range: 40 F to 120 F (4.5 C to 49 C) Non-corrosive sleeve factory installed in saddle Conduit Entrances: Two knockouts provided for 1/2" conduit Caution: This device is not intended for applications in explosive environments. Sizes Available: 2", 2 1/2", 3" and 4" for type K, L and M copper pipe 2", 2 1/2" and 3" for listed CPVC pipe, SDR 13.5 (Standard Dimensional Ratio) Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090018 INSTALLATION: See Fig. 2. These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a fitting which changes the direction of the water flow or within 24" of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" and 2 1/2" devices require a hole with a diameter of 1 1/4" 1/16". All other sizes require a hole with a diameter of 2" +1/16", -1/8". Clean the inside of the pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vanes so that the arrow on the saddle points in the direction of the water flow. Install the saddle strap and tighten nuts alternately to an eventual 100 in-lbs. of torque, see Fig. 2. The vane must not rub the inside of the pipe or bind in any way.

PIPE SECTION SHOWN FOR ILLUSTRATION PURPOSES ONLY U.S. Patent No. 3921989, Canadian Patent No. 1009680 Other Patents Pending, Potter Electric, Rd., 1990

GENERAL INFORMATION The Model VSR-CF is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed for use on type K, L and M copper pipe, sizes 2" thru 4" and listed CPVC pipe, SDR 13.5 (standard dimensional ratio), sizes 2" thru 3". The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole, double throw, snap action switches and an adjustable pneumatic retard. The switches are actuated when a flow of 10 gallons per minute or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instructions of this switch.
PRINTED IN USA

MKT #8800002 - REV M MFG. #5400771 - 2/97

PAGE 1 OF 2

VSR-CF
VANE TYPE WATERFLOW SWITCH WITH RETARD FOR COPPER OR PLASTIC PIPE

FIG. 1
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

FIG. 2

CAUTION:

An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

FIG. 3

TYPICAL ELECTRICAL CONNECTIONS

Note: For supervised circuits see Switch Terminal Connections drawing and caution note (Fig. 1).

NOTE: The Model VSR-CF has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. TESTING The frequency of inspection and testing for the model VSR-CF and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspectors test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes.

If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-CF is not recommended or advisable. A minimum flow of 10 gpm is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions.
PAGE 2 OF 2

PRINTED IN USA

MKT #8800002 - REV M MFG. #5400771 - 2/97

VSR-F 10"
VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936
UL Listed Service Pressure: Up to 300 PSI Minimum Flow Rate for Alarm: 10 GPM Maximum Surge: 18 FPS Contact Ratings: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC 2.00 Amps at 30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2" conduit Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4 Rated Enclosure - use with appropriate conduit fitting Temperature Range: 40F/120F, 4.5C/49C Pipe Schedules: 10 thru 40 Caution: This device is not intended for applications in explosive environments. Service Use: Automatic Sprinkler One or two family dwelling Residential occupancies up to four stories National Fire Alarm Code NFPA-13 NFPA-13D NFPA-13R NFPA-72

Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833

U.S. PAT. NO. 3921989 CANADIAN PAT. NO. 1009680 OTHER PATENTS PENDING POTTER ELECTRIC, Rd., 1990
GENERAL INFORMATION The Model VSR-F 10" is a vane type waterflow switch for use on wet sprinkler systems The unit contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 gallons per minute or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE The unit is enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See Bulletin No. 5400775 for installation instructions of this switch.

Optional: Cover tamper switch kit, Order Stock No. 0090018

INSTALLATION (See Fig. 2) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a fitting which changes the direction of the waterflow or within 24" of a valve or drain. Drain the system and drill a hole with a diameter of 2" 1/8" in the pipe using a circular saw in a slow speed drill. Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an eventual 50 ftlbs. of torque (see Fig. 2). The vane must not rub the inside of the pipe or bind in any way.
PAGE 1 OF 2

PRINTED IN USA

MKT. #8800007 - REV B MFG. #5401023 - 12/95

VSR-F 10"
VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FIG. 1
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

FIG. 2

CAUTION:

An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

FIG. 3

TYPICAL ELECTRICAL CONNECTIONS

Note: For supervised circuits see Switch Terminal Connections drawing and caution note (Fig. 1).

NOTE: The Model VSR-F 10" has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. TESTING The frequency of inspection and testing for the model VSR-F 10" and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspectors test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-F 10" is not recommended or advisable. A minimum flow of 10 gpm is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the Fire Protection System that this system must be tested in accordance with the Testing Instructions.
PRINTED IN USA MKT. #8800007 - REV B MFG. #5401023 - 12/95 PAGE 2 OF 2

VSR-FE-2
VANE TYPE WATERFLOW SWITCH WITH ELECTRONIC RETARD
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL LISTED and FM APPROVED Service Pressure: Up to 450 PSI Minimum Flow for Alarm: 10 GPM Maximum Surge: 18 FPS Power Requirements: STANDBY: 10 mA at 120VAC or 1.5 mA at 24VAC/DC ALARM: 40 mA at 120VAC or 35 mA at 24VAC/DC Contact Ratings: DPDT (Form C) 2 Amps at 30VDC or 125VAC resistive Conduit Entrances: Two knockouts provided for 1/2" conduit Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4 Rated Enclosure - use with appropriate conduit fitting Temperature range: 40F / 120F, 4.5C/49C Non-corrosive sleeve factory installed in saddle. Caution: This device is not intended for applications in explosive environments. Sizes Available: Schedules 10 thru 40, sizes 2" thru 8" Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stk. No. 0090018 INSTALLATION: See Fig. 1. These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a fitting which changes the direction of the waterflow or within 24" of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" and 2 1/2" devices require a hole with a diameter of 1 1/4" +1/8" -1/16". All other sizes require a hole with a diameter of 2" 1/8". Clean the inside of the pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an eventual 50 ft.lbs. of torque (see Fig. 1). The vane must not rub the inside of the pipe or bind in any way.
PAGE 1 OF 2

U.S. PAT. NO. 3921989, CANADIAN PAT. NO. 1009680 OTHER PATENTS PENDING, POTTER ELECTRIC, Rd., 1990

GENERAL INFORMATION: The Model VSR-FE-2 is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 thru 40, sizes 2" thru 8". The unit may also be used as a sectional waterflow detector on large systems. The unit contains an output relay and an adjustable electronic retard. The relay is actuated when a flow of 10 gallons per minute or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, diecast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instructions of this switch.
PRINTED IN USA

MKT. #8800006 - REV I MFG. #5400985 - 12/95

VSR-FE-2
VANE TYPE WATERFLOW SWITCH WITH ELECTRONIC RETARD
RETARD ADJUSTMENT

FIG. 1

The retard time is selected by turning the appropriate switches to the off position. Example: For 45 seconds turn switches 1, 2 and 3 to the off position. Approximate time is as follows: Switch Off 1 thru 8 On 1 1&2 1, 2, & 3 1, 2, 3, & 4 1, 2, 3, 4, & 5 1, 2, 3, 4, 5, & 6 7 8 Time in Sec. 0 15 30 45 60 75 90 not used not used

TO INSTALL, DRILL A HOLE AS INDICATED: PIPE SIZE 2" TO 2 1/2" 3" TO 8" HOLE SIZE 1 1/4" +1/8" -1/16" 2" 1/8"

FIG. 2

TYPICAL ELECTRICAL CONNECTIONS

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL CAUTION: When supervised circuits are used the following must be observed: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. See drawing at right.

TESTING: The operation of the waterflow switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspectors test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes.
PRINTED IN USA

If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-FE-2 is not recommended or advisable. A flow of 10 GPM is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the preceding section.
PAGE 2 OF 2

MKT. #8800006-REV I MFG. #5400985 - 12/95

VSG
LOW FLOW RATE VANE TYPE WATERFLOW SWITCH WITH ELECTRONIC RETARD
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg. LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL LISTED Germanisher Lloyd Approved No. 97 778-95HH Service Pressure: Up to 450 PSI Flow Required for Alarm: 3.0 GPM Maximum Surge: 18 FPS Power Requirements: STANDBY: 10ma at 120V AC or 1.5ma at 24V AC/DC ALARM: 40ma at 120V AC or 35ma at 24V AC/DC Contact Ratings: DPDT (Form C) 2 Amps at 0-30VDC or 0-125VAC resistive Conduit Entrances: 2 knockouts provided for 1/2" conduit Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4 Rated Enclosure - use with appropriate conduit fitting. Temperature Range: 40F/120F, 4.5C/49C Non-corrosive sleeve factory installed in saddle. Caution: This device is not intended for applications in explosive environments. Nominal OD and Wall Thickness: 2" (60.3mm OD), 3.9mm to 4.5mm wall 2 1/2" (73.0mm OD), 4.8mm to 5.2mm wall 2 1/2" (76.1mm OD), 4.3mm to 4.7mm wall 3" (88.9mm OD), 5.0mm to 5.6mm wall 4" (114.3mm OD), 5.4mm to 6.4mm wall Service use: Water mist systems where low flow for alarm is required. Optional: Cover Tamper Switch Kit, Stock No. 0090018 INSTALLATION: See Fig. 1. These devices may be mounted on a horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a fitting which changes the direction of the waterflow or within 24" of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" and 2 1/2" devices require a hole with a of 1 1/4" +1/8" -1/16". The 3" and 4" devices require a hole with a diameter of 2" 1/8". Clean the inside of the pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an eventual 50 ftlbs. of torque. See Fig. 1. The vane must not rub the inside of the pipe or bind in any way.

U.S. PAT. NO. 3921989, CANADIAN PAT. NO. 1009680 OTHER PATENTS PENDING, POTTER ELECTRIC, Rd., 1990

GENERAL INFORMATION: The Model VSG is a flexible vane type of waterflow switch for use in wet pipe water mist systems where a low flow for alarm is required. It is designed for installation in sections of 2 to 4 inch stainless steel or brass pipe with wall thickness in accordance with the above specifications (see Nominal OD and Wall Thickness). The unit may also be used as a sectional waterflow detector on large systems. The unit contains an output relay and an adjustable electronic retard. The relay is actuated when a flow of 3 gallons per minute or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A field installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instructions of this switch.
PRINTED IN USA

MKT. #8800008 - REV D MFG. #5400999 - 1/98

PAGE 1 OF 2

VSG
LOW FLOW RATE VANE TYPE WATERFLOW SWITCH WITH ELECTRONIC RETARD
RETARD ADJUSTMENT The retard time is selected by turning the appropriate switches to the off position. Example: For 45 seconds turn switches 1, 2 and 3 to the off position. Approximate time is as follows: Switch Off 1 thru 8 On 1 1&2 1, 2, & 3 1, 2, 3, & 4 1, 2, 3, 4, & 5 1, 2, 3, 4, 5, & 6 7 8 Time in Sec. 0 15 30 45 60 75 90 not used not used FIG. 1

TO INSTALL, DRILL A HOLE AS INDICATED: PIPE SIZE 2" TO 2 1/2" 3" TO 4" HOLE SIZE 1 1/4" +1/8" -1/16" 2" 1/8"

DIRECTION OF WATERFLOW

FIG. 2

TYPICAL ELECTRICAL CONNECTIONS

FIG. 3

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

CAUTION: When supervised circuits are used the following must be observed: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. TESTING: The operation of the waterflow switch and the associated alarms is to be tested upon completion of the installation and periodically thereafter in accordance with the applicable NFPA standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). A minimum flow of 3 GPM is required to activate this device.
PRINTED IN USA MKT. #8800008 - REV D MFG. #5400999 - 1/98 PAGE 2 OF 2

MODEL PS10A
PRESSURE SWITCH
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL and CFSM LISTED, FM and LPC APPROVED,NYMEA ACCEPTED Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H Enclosure: Cover - Die-cast with textured red powdercoat finish Base - Plated Steel Pressure Connection: 1/2" NPT Male Factory Adjustment: Operates on Pressure increase at 6 1 PSI Operates on Pressure decrease at 5 1 PSI Maximum Differential: 1 PSI Maximum System Pressure: 250 PSI Switch Contacts: SPDT (Form C) 15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC One set in PS10-1A, Two sets in PS10-2A Environmental Specifications: Indoor or outdoor use NEMA 4/IP55 Rated Enclosure Temperature range: -40F to 140F (-40C to 60C) (Not for use in hazardous locations) Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential Occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Tamper: Cover incorporates tamper resistant fasteners that require a special key for removal. One key is supplied with each device. For optional cover tamper switch kit, order Stock No. 0090134.

PS10-1A Single Switch - Stk. No. 1340101 PS10-2A Double Switch - Stk. No. 1340102 INSTALLATION AND TEST PROCEDURES The Potter PS10A Series Pressure Actuated Switches are designed for the detection of a waterflow condition in automatic fire sprinkler systems of particular designs such as wet systems with alarm check valves or dry pipe systems. They may also be used to provide a low pressure supervisory signal. They may be adjusted to operate on pressure between 4 and 20 PSI. MOUNTING: Device should be mounted in upright position (threaded connection down). Requires NEMA type 4 conduit hub for outdoor installations. TESTING: The operation of the pressure alarm switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). WET SYSTEM: METHOD 1: When using PS10A and control unit with retard - connect PS10A into alarm port piping on the input side of retard chamber and electrically connect PS10A to control unit that provides a retard to compensate for surges. Insure that no unsupervised shut-off valves are present between the alarm check valve and PS10A. METHOD 2: When using the PS10A for local bell application or with a control that does not provide a retard feature - the PS10A must be installed on the alarm outlet side of the retard chamber of the sprinkler system. PRINTED IN USA

TESTING: Accomplished by opening the inspector's end-of-line test valve. Allow time to compensate for system or control retard. CAUTION: Method 2 is not applicable for remote station service use, if there is an unsupervised shut-off valve between the alarm check valve and the PS10A. WET SYSTEM WITH EXCESS PRESSURE: Connect PS10A into alarm port piping extending from alarm check valve. Retard provisions are not required. Insure that no unsupervised shut-off valves are present between the alarm check valve and the PS10A. TESTING: Accomplished by opening the water by-pass test valve or the inspector's end-of-line test valve. When using end-of-line test, allow time for excess pressure to bleed off. DRY SYSTEM: Connect PS10A into alarm port piping that extends from the intermediate chamber of the alarm check valve. Install on the outlet side of the in-line check valve of the alarm port piping. Insure that no unsupervised shut-off valves are present between the alarm check valve and the PS10A. TESTING: Accomplished by opening the water by-pass test valve. CAUTION: The above tests may also activate any other circuit closer or water motor gongs that are present on the system.

MKT. #8810001 - REV N MFG. #5400923 - 12/97

PAGE 1 OF 2

MODEL PS10A
PRESSURE SWITCH
DIMENSIONS
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

TYPICAL SPRINKLER APPLICATIONS

CAUTION:

Closing of any shutoff valves between the alarm check valve and the PS10A will render the PS10A inoperative. To comply with NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model BVS.

TYPICAL ELECTRICAL CONNECTIONS

PRESSURE SWITCH TERMINATION

ORDERING INFORMATION Model Description PS10-1A Pressure switch with one set SPDT contacts PS10-2A Pressure switch with two sets SPDT contacts Hex Key Cover Tamper Switch Kit BVS 1/2" Ball Valve with tamper switch ENGINEER/ARCHITECT SPECIFICATIONS

Stock No. 1340101 1340102 5250062 0090134 1010150

Pressure type waterflow switches shall be a Model PS10A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed on the sprinkler systems as shown on the drawings and/or specified herein. Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the alarm check valve of a wet sprinkler system or into the intermediate chamber of a dry pipe system and shall be actuated by any flow of water to or in excess of the discharge from one sprinkler head. Switches shall have a maximum service pressure rating of 250 PSI and shall be factory adjusted to operate on pressure increase at 6 1 PSI. There shall be one (1) or two (2) SPDT contacts rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC. The switch housing shall be weather proof and oil resistant. The cover shall incorporate tamper resistant screws. The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted.
PRINTED IN USA MKT. #8810001 - REV N MFG. #5400923 - 12/97 PAGE 2 OF 2

MODEL PS40A
HIGH/LOW PRESSURE SWITCHES
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com
MODEL PS40A PRESSURE SWITCH FOR MONITORING HIGH AND/OR LOW PRESSURE VARIATIONS

Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL and CSFM LISTED, FM and LPC APPROVED, NYMEA ACCEPTED Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H Enclosure: Cover - Die-cast with textured red powdercoat finish Base - Plated Steel

Pressure Connection: 1/2" NPT Male Factory Adjustment: PS40-1A: Operates on decrease at 30 PSI PS40-2A: Operates on increase at 50 PSI, and on decrease at 30 PSI Pressure Range: 10 - 175 PSI Maximum Differential: Approx. 2 lbs. at 20 PSI 5 lbs. at 175 PSI Maximum System Pressure: 250 PSI Switch Contacts: SPDT (Form C) 15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC One set in PS40-1A, Two sets in PS40-2A Environmental Specifications: Indoor or outdoor use NEMA 4/IP55 Rated Enclosure Temperature range: -40F to 140F (-40C to 60C) (Not for use in hazardous locations) Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Tamper: Cover incorporates tamper resistant fasteners that require a special key for removal. One key is supplied with each device. For optional cover tamper switch kit, order Stock No. 0090134. Dry System: Connect PS40A in air supply line on the system side of any shutoff or check valve. Provision for testing the unit can be accomplished with the installation of a Potter Bleeder Valve (Model BVL) in the line to the PS40A. Testing: The operation of the pressure supervisory switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). CAUTION: Testing the PS40A may activate other system connected devices.
PAGE 1 OF 2

PS40-1A Single Switch - Stk. No.1340401 PS40-2A Double Switch - Stk. No.1340402 The Potter PS40A Series are pressure actuated switches designed primarily to detect a 10 PSI increase and/or decrease from normal system pressure in automatic fire sprinkler systems. Typical applications are air pressure supervision in dry pipe systems and pressure supervision of pressure tanks, air supply or water supply. INSTALLATION AND TEST PROCEDURES Mounting: Device should be mounted in upright position (threaded connection down). Requires NEMA type 4 conduit hub for outdoor installations.
PRINTED IN USA

MKT. #8810002 - REV M MFG. #5400924 - 12/97

MODEL PS40A
HIGH/LOW PRESSURE SWITCHES
DIMENSIONS NOTE: TO PREVENT LEAKAGE, APPLY TEFLON TAPE SEALANT TO MALE THREADS ONLY. WARNING: USE OF PIPE JOINT CEMENT MAY RESULT IN OBSTRUCTION OF APERTURE AND LOSS OF SIGNAL. FIELD ADJUSTMENTS: The operating point of the switch (or switches on the PS40-2A) can be adjusted to any point between 10 and 175 PSI by turning the adjustment knob(s) clockwise to raise the actuation point, and counter-clockwise to lower the actuation point. In the case of the PS40-2A, the two switches operate completely independently of one another, and each switch may be adjusted to actuate at any point the system requires. Final adjustment should be made with a pressure gauge.

Typical Sprinkler Application - Dry System

Pressure Switch Terminations

Typical Electrical Connections

NOTE: Switches are shown in standby condition with normal pressure applied. Switch #1 (high) changes with pressure increase. Switch #2 (low) changes with pressure decrease.

Ordering Information Model Description


PS40-1A PS40-2A BVL Pressure switch with one set SPDT contacts Pressure switch with two sets SPDT contacts Bleeder Valve Hex Key Cover Tamper Switch 1/2" Ball Valve with tamper switch

Switch Terminal Connections Clamping Plate Terminal


Stk. No.
1340401 1340402 1000018 5250062 0090134 1010150 CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

BVS

Engineer/Architect Specifications
Air pressure supervisory switch shall be a Model PS40A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed on the sprinkler systems as shown on the drawings and/or as specified herein. Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the air supply line on the system side of any shut-off valve. A Model BVL bleeder valve as supplied by Potter Electric Signal Co. of St. Louis, Mo. or equivalent shall be connected in line with the PS40A to provide a means of testing the operation of the supervisory switch. (See DWG. #924-1) The switch unit shall contain SPDT (Form C) switch(es). One switch shall operate at a pressure decrease of 10 PSI from normal. If two switches are provided, the second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC. The units shall have a maximum pressure rating of 250 PSI and shall be adjustable from 10 to 175 PSI. The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws. The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted. PRINTED IN USA MKT. #8810002 - REV M MFG. #5400924 - 12/97 PAGE 2 OF 2

MODEL PS100-2A
PRESSURE TYPE FLOW SWITCHES
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com
PRESSURE SWITCH FOR MONITORING WET SYSTEMS WITH EXCESS PRESSURE

Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL and CSFM LISTED, FM and LPC APPROVED, NYMEA ACCEPTED Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H Enclosure: Cover - Die-cast with textured red powdercoat finish Base - Plated Steel Pressure Connection: 1/2" NPT Male Factory Adjustment: Operates on decrease at 90 PSI Pressure Range: 10 - 175 PSI Maximum Differential: Approx. 2 lbs. at 20 PSI 5 lbs. at 175 PSI Maximum System Pressure: 250 PSI Switch Contacts: Two sets of SPDT (Form C) 15.0 Amps at 125/250VAC 2.5 Amps at 30VDC

Environmental Specifications: Indoor or Outdoor Use NEMA 4/IP55 Rated Enclosure Temperature range: -40F to 140F (-40C to 60C) (Not for use in hazardous locations) Service Use: Automatic Sprinkler One or two family dwelling Residential occupancy up to four stories National Fire Alarm Code NFPA-13 NFPA-13D NFPA-13R NFPA-72

PS100-2A Double Switch - Stock No. 1341002

Tamper: Cover incorporates tamper resistant fasteners that require a special key for removal. One key is supplied with each device. For optional cover tamper switch kit, order Stock No. 0090134.

The Potter PS100-2A is a pressure actuated switch designed primarily to detect a 10 PSI decrease from normal system pressure in automatic fire sprinkler systems. TYPICAL APPLICATION: Alarm device on systems with excess pressure INSTALLATION AND TEST PROCEDURES: Device should be mounted in upright position (threaded connection down). Requires NEMA type 4 conduit hub for outdoor installations. WET SYSTEM: (With excess pressure) Connect PS100-2A in the constant pressure line on the system side of any shut-off or check valve.
PRINTED IN USA

Provision for testing the unit can be accomplished with the installation of a Potter Bleeder Valve (Model BVL) in the line to the PS100-2A. Testing: The operation of the pressure supervisory switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). CAUTION: Testing the PS100-2A may activate other system connected devices.

MKT. #8810003 - REV L MFG. #5400925 - 12/97

PAGE 1 OF 2

MODEL PS100-2A
PRESSURE TYPE FLOW SWITCHES
DIMENSIONS
NOTE: TO PREVENT LEAKAGE, APPLY TEFLON TAPE SEALANT TO MALE THREADS ONLY. WARNING: USE OF PIPE JOINT CEMENT MAY RESULT IN OBSTRUCTION OF APERTURE AND LOSS OF SIGNAL. FIELD ADJUSTMENTS: The operating point of the switch (or switches on the PS100-2A) can be adjusted to any point between 10 and 175 PSI by turning the adjustment knob(s) clockwise to raise the actuation point, and counter-clockwise to lower the actuation point. In the case of the PS100-2A, the two switches operate completely independently of one another, and each switch may be adjusted to actuate at any point the system requires. Final adjustment should be made with a pressure gauge.

Typical Sprinkler Applications Wet System with Excess Pressure

Pressure Switch Terminations

Typical Electrical Connections - Decreasing Pressure

Ordering Information Model Description PS100-2A Pressure switch BVL Bleeder Valve Hex Key Cover Tamper Switch BVS 1/2" Ball Valve with tamper switch
Engineer/Architect Specifications

Switch Terminal Connections Clamping Plate Terminal Stock No. 1341002 1000018 5250062 0090134 1010150
CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

Pressure type waterflow switch shall be a Model PS100-2A as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed on the sprinkler systems as shown on the drawings and/or as specified herein. Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the excess pressure supply line on the system side of any shut-off valve. A Model BVL Bleeder Valve as supplied by Potter Electric Signal Co. of St. Louis, MO or equivalent shall be connected in line with the PS100A to provide a means of testing the operation of the pressure type switch. The switch unit shall contain two SPDT (Form C) switches. Both switches shall operate when the pressure decreases to 90 PSI. The switch contacts shall be rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC. The unit shall have a maximum pressure rating of 250 PSI and shall be adjustable from 10 to 175 PSI. The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws. The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted. PRINTED IN USA MKT. #8810003 - REV L MFG. #5400925 - 12/97 PAGE 2 OF 2

MODEL PS120A
HIGH/LOW PRESSURE SWITCHES
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com
PRESSURE SWITCH FOR MONITORING HIGH AND/OR LOW PRESSURE VARIATIONS

Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL and CSFM LISTED, FM and LPC APPROVED, NYMEA ACCEPTED Dimensions: 4 3/4"W x 2 1/4"D x 4 3/8"H Enclosure: Cover - Die-cast with textured red powdercoat finish Base - Plated Steel Pressure Connection: 1/2" NPT Male Factory Adjustment: PS120-1A: Operates on decrease at 110 PSI PS120-2A: Operates on increase at 130 PSI, and on decrease at 110 PSI Pressure Range: 10 - 175 PSI Maximum Differential: Approx. 2 lbs. at 20 PSI 5 lbs. at 175 PSI Maximum System Pressure: 250 PSI Switch Contacts: SPDT (Form C) 15.0 Amps at 125/250VAC, 2.5 Amps at 30VDC One set in PS120-1A, Two sets in PS120-2A Environmental Specifications: Indoor or outdoor use NEMA 4/IP55 Rated Enclosure Temperature Range: -40F to 140F (-40C to 60C) (Not for use in hazardous locations) Service Use: Automatic Sprinkler One or two family dwelling Residential occupancy up to four stories National Fire Alarm Code NFPA-13 NFPA-13D NFPA-13R NFPA-72

PS120-1A Single Switch - Stock No. 1341201 PS120-2A Double Switch - Stock No. 1341202

Tamper: Cover incorporates tamper resistant fasteners that require a special key for removal. One key is supplied with each device. For optional cover tamper switch kit, order Stock No. 0090134. excess pressure line on the system side of any shut-off or check valve. Provision for testing the unit can be accomplished with the installation of a Potter Bleeder Valve (Model BVL) in the line to the PS120A. Testing: The operation of the pressure supervisory switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). CAUTION: Testing the PS120A may activate other system connected devices.
PAGE 1 OF 2

The Potter PS120A Series are pressure actuated switches designed primarily to detect a 10 PSI increase and/or decrease from normal system pressure in automatic fire sprinkler systems. Typical applications are pressure supervision in systems with excess pressure. INSTALLATION AND TEST PROCEDURES Mounting: Device should be mounted in upright position (threaded connection down). Requires NEMA type 4 conduit hub for outdoor installations. Wet System (with excess pressure): Connect PS120A in the
PRINTED IN USA

MKT. #8810004 - REV N MFG. #5400926 - 12/97

MODEL PS120A
HIGH/LOW PRESSURE SWITCHES
DIMENSIONS
NOTE: TO PREVENT LEAKAGE, APPLY TEFLON TAPE SEALANT TO MALE THREADS ONLY. WARNING: USE OF PIPE JOINT CEMENT MAY RESULT IN OBSTRUCTION OF APERTURE AND LOSS OF SIGNAL. FIELD ADJUSTMENTS: The operating point of the switch (or switches on the PS120-2A) can be adjusted to any point between 10 and 175 PSI by turning the adjustment knob(s) clockwise to raise the actuation point, and counter-clockwise to lower the actuation point. In the case of the PS120-2A, the two switches operate completely independently of one another, and each switch may be adjusted to actuate at any point the system requires. Final adjustment should be made with a pressure gauge.

Typical Sprinkler Application

Pressure Switch Terminations

Typical Electrical Connections

NOTE: Switches are shown in standby condition with normal pressure applied. Switch #1 (high) changes with pressure increase. Switch #2 (low) changes with pressure decrease.

Ordering Information
Model Description Stock No.
1341201 1341202 1000018 5250062 0090134 1010150 PS120-1A Pressure switch with one set SPDT contacts PS120-2A Pressure switch with two sets SPDT contacts BVL Bleeder Valve Hex Key Cover Tamper Switch BVS 1/2" Ball Valve with tamper switch

Switch Terminal Connections Clamping Plate Terminal


CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

Engineer/Architect Specifications
Pressure supervisory switch shall be a Model PS120A as manufactured by Potter Electric Signal Co. of St. Louis, MO and shall be installed on the sprinkler systems as shown on the drawings and/or as specified herein. Switches shall be provided with a 1/2" NPT male pressure connection and shall be connected into the excess pressure supply line on the system side of any shut off valve. A Model BVL Bleeder Valve as supplied by Potter Electric Signal Co. of St. Louis, MO or equivalent shall be connected in line with the PS120A to provide a means of testing the operation of the supervisory switch. The switch unit shall contain SPDT (Form C) switch(es). One switch shall operate at a pressure decrease of 10 PSI from normal. If two switches are provided, the second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0 Amps at 125/ 250VAC and 2.5 Amps at 30VDC. The unit shall have a maximum pressure rating of 250 PSI and shall be adjustable from 10 to 175 PSI. The switch housing shall be weatherproof and oil resistant. The cover shall incorporate tamper resistant screws. The unit shall be UL and CSFM Listed, FM and LPC Approved, and NYMEA Accepted. PRINTED IN USA MKT. #8810004 - REV N MFG. #5400926 - 12/97 PAGE 2 OF 2

WFSR-F
WATERFLOW ALARM SWITCH WITH RETARD
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL and CSFM LISTED, FM APPROVED and NYMEA ACCEPTED Dimensions: 5 9/16"H x 3 1/2"W x 5 7/8"D (14.1cm H x 8.9cm W x 14.9cm D) Weight: 1.5 lbs. (3.3 kg.) Enclosure: Cover - Die-cast with textured red powdercoat finish Base - Die-cast aluminum Pressure Connection: 1/2" Male NPT Pressure Adjustments: Factory adjusted to operate between 4 and 8 PSI on rising pressure Maximum system pressure: 175 PSI Contact Ratings: Two Sets of SPDT (Form C) 15.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2" conduit Environmental Specifications: 40F to 120F (4.5C to 49C) NEMA 4 Enclosure Caution: This device is not intended for applications in explosive environments. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Tamper: Cover incorporates tamper resistant fasteners that require a special key for removal. One key is supplied with each device. For optional cover tamper switch kit, order Stock No. 0090018.

STOCK NO. 1010080


WATERFLOW ALARM SWITCH WITH RETARD FOR SUPERVISION OF WET ALARM CHECK VALVE: The Model WFSR-F is a pressure operated switch with an adjustable, instantly recycling pneumatic retard to prevent false alarms due to water pressure variation. The WFSR-F is connected into the alarm port of a wet sprinkler system alarm check valve (see " WARNING", page 2). INSTALLATION: A male 1/2" NPT pipe fitting is provided for connection to the alarm port of the alarm check valve. No additional mounting or support is required. Allow 5 inches to the front of the unit for removal of the cover. TESTING: Operation of the unit is checked by opening the by-pass test valve or inspector's test valve. The frequency of the inspection and testing for the Model WFSR-F and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or authority having jurisdiction (manufacturer recommends quarterly or more frequently).

FIG. 1

WFSR-F

FIG. 2

TYPICAL ELECTRICAL CONNECTIONS

PRINTED IN USA

MKT. #8810009 - REV G MFG. #5400987 - 5/97

PAGE 1 OF 2

WFSR-F
WATERFLOW ALARM SWITCH WITH RETARD FIG. 3
Retard Adjustment: To change time turn knob (either direction) for desired time delay. Use the minimum amount of retard necessary to prevent false alarms, a B setting is usually adequate for this. Factory set at B.

FIG. 4
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

APPROX. RETARD SETTINGS (IN SEC.) 0 0 A 10-25 B 20-40 C 35-55 D 50-70 E 60-90

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

FIG. 5

TYPICAL WET SYSTEM

WARNING Use teflon tape sealant only. Apply only to male threads of connectors. Use of pipe cement voids warranty as this material may obstruct pressure aperture resulting in loss of alarm signal. Device must be installed before any shut off valve on alarm port line unless it is supervised by a supervisory switch such as POTTER Model BVS. The system should be tested on a quarterly basis or more frequently to insure proper operation.

PRINTED IN USA

MKT. #8810009 - REV G MFG. #5400987 - 5/97

PAGE 2 OF 2

BVL
LEVER TYPE BLEEDER VALVE
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833

Valve Body: Bronze Handle: Zinc plated steel Maximum Pressure: 175 PSI Connections: 1/2" NPT Exhaust Orifice: .125"

STOCK NO. 1000018

GENERAL INFORMATION The Model BVL, lever type bleeder valve, is for use as a test valve for pressure operated devices on wet pipe sprinkler systems that have excess pressure, or dry pipe sprinkler systems. The BVL should be installed in-line with the pressure device. It provides a convenient means for removal or testing the pressure actuated device without affecting the pressure in the system. Closing the valve (moving the valve handle perpendicular to the 1/2" pipeline) shuts off the water or air from the supply and opens a small orifice (pin-hole) to exhaust the pressure between the valve and the pressure device. This should provide a low presPRINTED IN USA

sure actuation of the pressure device, testing its operation. INSTALLATION The BVL should be installed in-line to the alarm or supervisory device with the PD (Potter Device) stamp, or with the arrow pointing toward the alarm or supervisory device that is to be tested. Caution: The BVL should be installed so the exhaust orifice is pointed in a safe direction.

MKT. #8900067 - REV D MFG. #5400799 - 12/95

PAGE 1 OF 1

PCVS-1, -2
CONTROL VALVE SUPERVISORY SWITCH
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL and CSFM LISTED, FM APPROVED, NYMEA ACCEPTED Dimensions: 4.75"L x 2.25"W x 7.2"H (stem extended) 12.1cm L x 5.7cm W x 18.3cm H Weight: 1.35 lb. / .61 kg Enclosure: Cover - Die-cast Finish - Red Spatter Enamel Base - Die Cast Zinc All parts have corrosion resistant finishes Cover Tamper: Tamper Resistant Screws, Optional cover tamper kit available Mounting: 1/2" NPT Contact Rating: PCVS-1: One set of SPDT (Form C) PCVS-2: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC 2.50 Amps at 30VDC resistive Environmental Limitations: -40F / +140F (-40C to 60C) NEMA 4 and NEMA 6P Enclosure (IP67) Indoor or Outdoor Use (Not for use in hazardous locations.) See Bulletin No. 5400694 PIVS-U-EX for hazardous locations. Conduit Entrances: Two knockouts for 1/2" conduit provided Service Use: Automatic Sprinkler One or two family dwelling Residential occupancy up to four stories National Fire Alarm Code NFPA-13 NFPA-13D NFPA-13R NFPA-72

PCVS-1 STOCK NO. 1010107 PCVS-2 STOCK NO. 1010207 The Model PCVS is a weather proof and tamper resistant switch for monitoring the open position of fire sprinkler control valves of the post indicator, butterfly and other types. Depending on the model, one or two SPDT (Form C) contacts are provided which will operate when the valve position is altered from an open state. The unit mounts in a 1/2" NPT tapped hole in the post indicator or butterfly valve housing. The device is engaged by the indicating assembly of the post indicator or the operating mechanism of the butterfly valve, actuating switch(es) when the valve is fully open. The unit should be installed where it is accessible for service. The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furPRINTED IN USA

nished with each device and should be left with the building owner or responsible party. Replacement or additional cover screws and hex keys are available. See ordering information on page 6. OPTIONAL COVER TAMPER SWITCH: A field installable cover tamper switch is available as an option which may be used to indicate removal of the cover. See ordering information on page 6. TESTING: The PCVS and its associated protective monitoring system should be tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).

MKT. #8820001 - REV K MFG. #5400980 - 2/97

PAGE 1 OF 6

PCVS-1, -2
CONTROL VALVE SUPERVISORY SWITCH
FIG. 1 DIMENSIONS FIG. 2 PARTS

TYPICAL INSTALLATIONS ON POST INDICATOR VALVE HOUSINGS (SEE FIGS. 3 THRU 6)


Refer to Fig. 2 for the location of parts described in the following instructions. NOTE: If the sprinkler system is in service the owner or authorized representative should be notified, before any work is done on the system, that the valve controlling the water supply to the system may be closed for periods of time during the installation and testing of this device, resulting in all or portions of the system being inoperative during these periods. If the system is not in service and valve is closed, be sure that opening the valve will not allow any unwanted water flow due to openings in the system, such as heads off, broken or incomplete piping, etc. 1. Position the valve to fully open (OPEN should appear in the window of the housing). Partially close the valve while observing the direction that the target assembly moves. Reopen the valve. If the valve housing is predrilled with a 1/2" NPT for installation of a monitoring switch, remove the 1/2" plug and fully open the valve. Make sure that OPEN appears in the window of the housing. GO TO STEP NO. 6. 2. 3. Remove the head and target assembly (consultation with valve manufacturer is recommended). If the target assembly moved up as the valve was closed, measure the distance from the bottom of the head to the lower part of the target assembly that will contact the trip rod of the PCVS (see Fig. 3). This is usually a plate or bar on the target assembly, on a side adjacent to the OPEN/ SHUT plates. Subtract 1/8" from the measurement. If the target moved down as the valve was closed, measure the distance from the bottom of the head to the upper portion of the target assembly that will contact the trip rod of the PCVS (see Fig. 4). Add 1/8" to this measurement. 4. Mark the housing at the proper location. Using a 23/32" drill bit, drill and then tap a 1/2" NPT in the housing on the side that coincides with the portion of the target assembly that will engage the trip rod of the PCVS. (Continued on page 3.)

FIG. 3

FIG. 4

PRINTED IN USA

MKT. #8820001 - REV K MFG. #5400980 - 2/97

PAGE 2 OF 6

PCVS-1, -2
CONTROL VALVE SUPERVISORY SWITCH
POST INDICATOR VALVE INSTALLATIONS (CONT.)
5. 6. 7. 8. Replace the head and target assembly. Loosen the socket head screw that holds the nipple in the PCVS and remove the nipple. Screw the locknut that is provided onto the nipple. Screw the nipple into the 1/2" NPT hole in the valve housing - hand tighten. Tighten the locknut against the valve housing to secure the nipple firmly in place. Insert a scale or probe thru the nipple to measure the distance from the open end of the nipple to the target assembly. Subtract 1/2" from this measurement. NOTE: In some cases, it may be necessary to attach an angle bracket to the target assembly to engage the PCVS trip rod. 10. Using the special tool provided, loosen the two cover screws and remove the cover from the PCVS. 11. Loosen the locking screw that holds the trip rod in place and adjust the rod length, from the end of the collar to the end of the rod, using the dimension determined in Step 9. Tighten the locking screw to hold the rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 7). Reinstall trip rod and repeat Step 11 procedure. 12. Partially close the valve (3 to 4 revolutions of the handle/ hand wheel). 13. Slide the PCVS unit as far as possible onto the nipple, FIG. 5 WINDOW INSTALLATION Note A - See Fig. 5 Subject to the approval of the authority having jurisdiction the alternate method of installation shown in Fig. 5 may be used. In this method, one of the glass windows of the housing is replaced with a 1/4" thick metal plate that is cut to fit in place of the glass and drilled and tapped to receive the 1/2" NPT pipe nipple. In some cases it may be necessary to attach an angle bracket to the target assembly to engage the PCVS trip rod. Note B - See Fig. 6 If the target is stationary and a hood arrangement is used, such as is shown in Fig. 6, the hood must be drilled with a 23/32" drill and tapped with a 1/2" NPT. The center line of this hole should be 1/8" below the portion of target assembly that strikes the PCVS trip rod. The 11 3/8" dimension shown is for a Clow Valve. Flexible conduit must be used for this type of installation.
PRINTED IN USA MKT. #8820001 - REV K MFG. #5400980 - 2/97 PAGE 3 OF 6

observing which direction the rod will move when the valve is closed. Orient the device to actuate the switches when the valve is open. Tighten the socket head screw in the collar. 14. Carefully open the valve to the fully open position. As the target moves to the open position it should engage the trip rod and actuate the switch(es). There should be a minimum overtravel of 1/2 revolution of the handle/hand wheel after the switch(es) actuate (a continuity meter connected to each set of contacts is one method that could be used to determine this). 15. Slowly close the valve. The switch must operate during the first two revolutions of the handle/hand wheel or during 1/5 of the travel distance of the valve control apparatus from its normal condition. NOTE: Small adjustments of the target position may be necessary (consultation with valve manufacturer is recommended). 16. Complete the required electrical wiring, connections and tests. The valve should be operated through the entire cycle of fully closed and fully open to determine the integrity of the PCVS installation and the signaling system. Check that all electrical and mechanical connections are secure. 17. When the installation and testing are complete, return valve to its proper position. 18. Alternative installation for other post indicator valve housing shown in Fig. 5 and 6.

9.

FIG. 6 CLOW VALVE INSTALLATION

PCVS-1, -2
CONTROL VALVE SUPERVISORY SWITCH
TYPICAL INSTALLATION ON A BUTTERFLY VALVE (SEE FIGS. 8 AND 9)
B1. Remove the 1/2" NPT plug from the gear operator case. Refer to Fig. 2 for location of parts described in the following instructions: B2. Loosen the set screw that holds the nipple in the PCVS and remove the nipple. B3. Screw the locknut that is provided onto the nipple. B4. Screw the nipple into the 1/2" NPT hole in the gear operator - hand tighten. Tighten the locknut against the case, to secure the nipple firmly in place. B5. Partially close the valve (3 or 4 revolutions of the hand wheel or crank). B6. Using the special tool provided, loosen the two cover screws and remove the cover from the PCVS. B7. Loosen the locking screw that holds the trip rod in place. Estimate trip rod length required and extend slightly past that point. Slide the PCVS unit as far as possible onto the nipple, observing which direction the rod will move when the valve is closed. Orient the device to actuate switches when valve is open. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 7). Reinstall trip rod and repeat Step B7 procedure. B8. Remove device from nipple and withdraw trip rod 1/32" (this dimension is important). Tighten the locking screw B9. to hold the rod in place. Re-install the device on the nipple. Tighten the screw in the collar against the nipple. NOTE: In some cases it may be necessary to remove the gear box cover to ensure correct operation (consultation with the valve manufacturer is recommended). Carefully open the valve to its full open position, as the boss on the gear hub moves to the open position it must engage the PCVS trip rod and actuate the switch(es). There should be a minimum overtravel or revolution of the crank or hand wheel after the switch(es) actuate (a continuity meter connected to each set of contacts is one method that could be used to determine this). NOTE: Slight adjustment of gear stops may be necessary to prevent overtravel of the trip rod (consultation with valve manufacture is recommended). B10. Carefully close the valve. The switch(es) must operate during the first two revolutions of the crank or hand wheel or during 1/5 of the travel distance of the valve control apparatus from its normal condition. B11. Complete the required electrical wiring, connections and tests. The valve should be operated through the entire cycle of fully closed and fully open to determine the integrity of the PCVS installation and signaling system. Check that all electrical and mechanical connections are secure. B12. When the installation and testing are complete, return valve to its proper position.

FIG. 7

BREAKING EXCESSIVE ROD LENGTH

PRINTED IN USA

MKT. #8820001 - REV K MFG. #5400980 - 2/97

PAGE 4 OF 6

PCVS-1, -2
CONTROL VALVE SUPERVISORY SWITCH
ITT GRINNELL/KENNEDY INDICATING BUTTERFLY VALVE

DRESSER INDICATING BUTTERFLY VALVE FIG. 9

FIG. 8

OTHER SELECTED INSTALLATIONS


NOTE: THE APPLICATIONS IN FIGURES 10, 11 AND 12 ARE SUBJECT TO THE APPROVAL OF THE AUTHORITY HAVING JURISDICTION

PBK - PRATT IBV BUTTERFLY VALVE KIT FIG. 10

PVK (STOCK NO. 1000060) - PRATT PIVA POST FIG. 11 INDICATOR VALVE KIT

MODEL PBK-L Stock No. 0090132 (14" and Up)

MODEL PBK-S Stock No. 0090133 (Up to 12") Pratt Valve Kit as used to mount a PCVS on a Pratt Model PIVA Valve. Kit contains: Instructions, template, screw and nut.
MKT. #8820001 - REV K MFG. #5400980 - 2/97 PAGE 5 OF 6

Pratt Butterfly Valve Kit as used to mount a PCVS on a Pratt Model IBV Valve. Kits contains: Bracket, nuts and instructions
PRINTED IN USA

PCVS-1, -2
CONTROL VALVE SUPERVISORY SWITCH
TYPICAL PRESSURE REDUCER TYPE VALVE INSTALLATION
This figure shows the Model PCVS mounted on the valve yoke, with a bracket supplied by the valve manufacturer, to supervise a pressure reducer type valve.

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL FIG. 13

FIG. 12

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

FIG. 14

TYPICAL ELECTRICAL CONNECTIONS (Switches Shown in Valve Open Position)

Please Note: This device should be wired in accordance with the applicable parts of the National Electrical Code, all state and local codes, applicable NFPA Standards and the requirements of the authority having jurisdiction.

TYPICAL SWITCH ACTION

TYPICAL ELECTRICAL CONNECTIONS

Contacts shown in normal (valve open) condition.

ORDERING INFORMATION
MODEL PCVS-1 PCVS-2 --PBK-S PBK-L PVK -DESCRIPTION Potter Control Valve Switch (single switch) Potter Control Valve Switch (double switch) Cover Screw Hex Key for Cover Screws and Installation Adjustments Pratt Butterfly Valve Kit (Up to 12") Pratt Butterfly Valve Kit (14" and Up) Pratt Valve Kit Optional Cover Tamper Switch Kit STOCK NO. 1010107 1010207 5490293 5250062 0090133 0090132 1000060 0090131

For pressure reducer type valve installation kits (if required) contact valve manufacturer.
PRINTED IN USA MKT. #8820001 - REV K MFG. #5400980 - 2/97 PAGE 6 OF 6

OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833 UL and CSFM LISTED, FM APPROVED and NYMEA ACCEPTED Dimensions: 6.19"L X 2.25"W X 5.88"H 15.7cm L X 5.7cm W X 14.6cm H Weight: 2 lbs (.9 kg) Enclosure: Cover - Die-Cast Finish - Red Spatter Enamel Base - Die Cast Zinc All parts have corrosion resistant finishes Cover Tamper: Tamper resistant screws, Optional cover tamper kit available. Contact Ratings: OSYSU-1: One set of SPDT (Form C) OSYSU-2: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC 2.50 Amps at 30VDC resistive Environmental Limitations: -40F to 140F (-40C to 60C) NEMA 4 and NEMA 6P Enclosure (IP67) Indoor or outdoor use (Not for use in hazardous locations.See Bulletin No. 5400705 OSYS-U-EX for hazardous locations). Conduit Entrances: 2 knockouts for 1/2" conduit provided Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72

OSYSU-1 Stock No. 1010106 OSYSU-2 Stock No. 1010206

GENERAL INFORMATION The OSYSU is used to monitor the open position of an OS & Y (outside screw and yoke) type gate valve. This device is available in two models; the OSYSU-1, containing one set of SPDT (Form C) contacts and the OSYSU2, containing two sets of SPDT (Form C) contacts. These switches mount conveniently to most OS & Y valves ranging in size from 2" to 12". They will mount on some valves as small as 1/2". The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replacement or
PRINTED IN USA

additional cover screws and hex keys are available. See ordering information on page 4. OPTIONAL COVER TAMPER SWITCH A field installable cover tamper switch is available as an option which may be used to indicate removal of the cover. See ordering information on page 4. TESTING The OSYSU and its associated protective monitoring system should be inspected and tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
PAGE 1 OF 4

MKT. #8820004 - REV J MFG. #5400979 - 2/97

OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH

FIG. 1

SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" SIZES

THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME VALVES AS SMALL AS 1/2". J-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE.

SMALL VALVE INSTALLATION 1. Remove and discard "C" washer and roller from the trip rod. 2. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the nonthreaded portion of the valve stem. 3. Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 procedure. 4. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. On valves with limited clearance use J-hooks supplied instead of the carriage bolts and clamp bar to mount the OSYSU. 5. Mark the valve stem at the center of the trip rod. 6. Remove the OSYSU. File a 1/8" deep groove centered on the mark on the valve stem utilizing a 3/16" diameter straight file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. 7. Mount the OSYSU with the trip rod centered in groove. 8. Final adjustment is made by loosening 2 screws (see Fig. 1) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate when the trip rod moves out of the groove. 9. Tighten the adjustment screws and all mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION.

PRINTED IN USA

MKT. #8820004 - REV J MFG. #5400979 - 2/97

PAGE 2 OF 4

OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH

FIG. 2

LARGE VALVE INSTALLATION - 3" THRU 12" SIZES

LARGE VALVE INSTALLATION 1. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the nonthreaded portion of the valve stem. 2. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. 3. Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 procedure. 4. Mark the valve stem at the center of the trip rod. 5. Remove the OSYSU. File a 1/8" deep groove centered on the mark of the valve stem utilizing a 3/8" diameter straight file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. 6. Mount the OSYSU loosely with the trip rod centered in groove. 7. Final adjustment is made by loosening 2 screws (see Fig. 2) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. 8. Tighten the adjustment screws and mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION.

PRINTED IN USA

MKT. #8820004 - REV J MFG. #5400979 - 2/97

PAGE 3 OF 4

OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH FIG. 3 DIMENSIONS FIG. 4 PARTS

BREAKING EXCESSIVE ROD LENGTH

FIG. 5

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

TYPICAL ELECTRICAL CONNECTIONS

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

Contacts shown in normal (valve open) condition.

TYPICAL SWITCH ACTION

ORDERING INFORMATION
MODEL OSYSU-1 OSYSU-2 ---DESCRIPTION Outside Screw & Yoke-Supervisory Switch (Single switch) Outside Screw & Yoke-Supervisory Switch (Double switch) Cover Screw Hex Key for Cover Screws and Installation Adjustments Optional Cover Tamper Switch Kit STOCK NO. 1010106 1010206 5490293 5250062 0090131

For pressure reducer type valve installation kits (if required) contact valve manufacturer.

PRINTED IN USA

MKT. #8820004 - REV J MFG. #5400979 - 2/97

PAGE 4 OF 4

BVS-1/2"
BALL VALVE WITH SUPERVISORY SWITCH
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com UL Listed Dimensions: 4.8"L x 2.6"W x 5.5"H 12.0cm L x 6.6cm W x 14.0cm H Weight: 2.25lbs (1.0kg) Enclosure: Die-cast zinc, red enamel finish (All parts plated to resist corrosion) Conduit Entrance: One opening for non-threaded 1/2" conduit provided Contact Ratings:Two sets of SPDT (Form C) 15.0 Amps at 125/250VAC 2.50 Amps at 30VDC resistive Environmental Specifications: Indoor or outdoor use Temperature range: 40F/140F (4.5C/60C) NEMA 4 rated enclosure Not for use in hazardous locations Maximum Pressure: 175 PSI BVS-1/2" Stock No. 1010150 Pipe Connection: 1/2" Female NPT Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-13R National Fire Alarm Code NFPA-72 Cover Tamper: Tamper resistant screws standard. For optional cover tamper switch kit, order Stock No. 0090140 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833

GENERAL INFORMATION The BVS utilizes a 1/2" ball valve in conjunction with a switch assembly. The switch assembly is enclosed in a tamper resistant NEMA 4 enclosure. The switch assembly monitors the fully open position of the valve. Two sets of SPDT contacts are provided which will operate when the valve position is altered from an open state. The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replacement or additional cover screws and hex keys are available.

PRINTED IN USA

MKT. #8820014 - REV C MFG. #5401021 - 6/97

PAGE 1 OF 2

BVS-1/2"
BALL VALVE WITH SUPERVISORY SWITCH
INSTALLATION
The BVS-1/2" is intended to be installed in the 1/2" alarm trim line of a wet or dry fire sprinkler system. (It serves as an electrically supervised shut-off valve to allow for maintenance or service on alarm attachments, without closing the sprinkler supply valve.) For retrofit installations, it is necessary to remove the existing shut-off valve and replace it with the BVS-1/2".

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

TYPICAL SPRINKLER APPLICATIONS

TYPICAL ELECTRICAL CONNECTIONS

TESTING
The BVS-1/2" and its associated protective monitoring system should be inspected and tested in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
PRINTED IN USA MKT. #8820014 - REV C MFG. #5401021 - 6/97 PAGE 2 OF 2

PTS-B
PLUG TYPE SUPERVISORY SWITCH
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL AND ULC LISTED AND FM APPROVED Dimensions: 5.25"L x 2.63"W x 2"D 13.3cm L x 6.7cm W x 5.1cm D with Bracket 8" L (20.3cm) Weight: 2 lbs. (.91 kg.) Enclosure: Cast Aluminum Finish: Red Wrinkle Enamel Tamper: Activated by Cover Removal

Stk. No. 1010095 U.S. Patent No. 4234879


GENERAL The Model PTS-B is designed to supervise sprinkler system control valves. This unit is particularly useful for unusual conditions, such as non-rising stem valves. Turning the valve wheel will pull the plug out of the receptacle. The plug cannot be reinserted after operation until the cover is removed with special key provided. Cover tamper is provided. CONTACTS: SPST normally closed when plug is in receptacle. Contacts rated 250 mA 28 VDC/VAC. The PTS-B is NOT available with normally open contacts.

Electrical Ratings: 250 mA at 28VDC/AC Cable: 2-wire, 18 Ga. Waterproof - Approx. 8' long

INSTALLATION The receptacle housing is mounted near the valve. With the valve in the full OPEN position, the approximate 8' of waterproof wire provided, can be cut to the desired length and looped through the valve wheel and terminated in the plug. This forms a normally closed single circuit loop when the plug is inserted into the receptacle. The cover tamper switch can be series wired into this loop or can be wired into a separate normally closed protection circuit (see wiring diagrams).

WARNING As stipulated by FACTORY MUTUAL and UNDERWRITER'S LABORATORIES


This unit is not intended or designed for ordinary use. It is a special application device to be used for unusual conditions such as non-rising stem gate valves where no other approved or listed method of protection is available or practical. As this unit does not meet NFPA codes and standards, requiring restoration signal when the valve is positioned to normal, special attention should be given by the responsible parties to assure that the proper operation of this device is maintained. This device should only be restored to normal when the valve is in the normal condition.

COVER TAMPER IN SERIES WITH PROTECTIVE CIRCUIT

SEPARATE COVER TAMPER CIRCUIT

PRINTED IN USA

MKT. #8820007 - REV D MFG. #5400701 - 12/95

PAGE 1 OF 1

PMS
MAGNETIC PLUG TYPE SUPERVISORY SWITCH
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833 UL and ULC LISTED and FM APPROVED Dimensions: 9"L x 4"W x 2"D 22.9cm L x 10.2cm W x 5.1cm D

Weight: 3 lbs. (1.35 kg.) Enclosure: Cover - Stainless Steel and Aluminum Base - Die Cast Aluminum Finish - Red Spatter Enamel STK. NO. 1010007 Contact Rating: One set (form C) SPDT contacts 0.1 Amp at 120VDC

The Model PMS magnetic plug switch is designed to supervise sprinkler system control valves. This unit is particularly useful on non-rising stem valves. The unit consists of a glass magnetic reed switch sealed in a stainless steel tube, a condulet fitting for connection of the external circuit to the cable that is connected to the switch, and a condulet fitting that houses the magnet and serves as a receptacle for the stainless steel tube. INSTALLATION: The bracket holding the two condulet fittings is mounted on the wall near the valve, in such a manner that when the cable is fed thru the valve wheel and the tube is inserted into its receptacle, turning the wheel will cause the tube to pull straight out of its receptacle. FIG. 1 CONTACT CONDITIONS OPERATION: When the valve wheel is turned, the encased switch will pull out of its receptacle, and away from the magnet, and the switch contacts will transfer. A key that is provided must be inserted in the keyhole in the receptacle cover and turned before the tube can be re-inserted. FIG. 2 TYPICAL ELECTRICAL CONNECTIONS

WARNING
As stipulated by FACTORY MUTUAL and UNDERWRITERS LABORATORIES
This unit is not intended or designed for ordinary use. It is a special application device to be used for unusual conditions such as non-rising stem gate valves where no other approved method of protection is available or practical. As this unit does not meet NFPA standards, requiring restoration signal when the valve is positioned to normal, special attention should be given by the responsible parties to assure that the proper operation of this device is maintained. This device should only be restored to normal when the valve is in the normal condition. PRINTED IN USA MKT. #8820010 - REV F MFG. #5400614 - 1/96 PAGE 1 OF 1

WLS
TANK WATER LEVEL SWITCH
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com UL Listed Dimensions:Housing - 5.56"H x 3.50"W x 2.56"D 14.1cm H x 8.9cm W x 6.5cm D Weight: 11.0 lb / 4.95 kg Enclosure: Cast aluminum with red enamel finish Applications: Steel or wood tanks (With the optional wood bushing adapter, Stock No. 5180199) Contacts: Two sets SPDT (Form C) One set for high / One set for low Rated - 15.00 Amps at 125/250VAC 0.50 Amp at 125VDC 0.25 Amp at 250VDC Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833

Detection Range: Before 3" Rise /Before 3" Fall Environmental Specifications: Suitable for indoor or outdoor use Temperature range: 40F to 140F (4.5C to 60C) NEMA 4 rated enclosure Maximum Pressure: 175 PSI The Model WLS Water Level Switch is a float operated device for supervising water level in a sprinkler supply gravity or pressure tank. The Model WLS has a bushing with 1 1/2" American Standard Pipe Threads for mounting in steel tanks. A 1 1/ 2" x 2" adapter bushing is available for mounting in existing 2" steel flanges. An optional bushing adapter with a buttress thread is available for mounting in wooden tanks. The unit is capable of detecting the level of water before a 3" rise and/or a 3" fall in the water level in a pressure tank, as required.

STOCK NO. 1010117

FIG. 1

PRINTED IN USA

MKT. #8820016 - REV A MFG. #5401040 - 2/97

PAGE 1 OF 2

WLS
TANK WATER LEVEL SWITCH
INSTALLATION INSTRUCTIONS A buttress thread nut and gasket are available for use with devices on installations where the inside of the tank is accessible and it is not convenient to weld a flange on the tank. The nut and gasket can also be used in a wood tank that is not sound enough to hold a thread (see Fig. 2). For installation in steel gravity tanks, weld a 1 1/2" NPT threaded flange (#6660225) 9" below the required water level to receive the 1 1/2" bushing (see Fig. 3). For wood gravity tanks, bore a 2 3/8" hole in the center of a stave 9" below the required water level and screw the buttress bushing adapter (#5180199) in place, allowing the bushing to cut its own thread, then install the WLS into the adapter (see Fig. 4). NOTE: The high signal is not required for gravity tanks and the WLS can be wired so that either High or Low or both switches may be used (see Fig. 5). For pressure tanks, weld the 1 1/2" NPT threaded flange (#6660225) into the tank at the desired water level and use both high and low signals. To replace an existing Potter WLS in a steel tank with a welded flange a 1 1/2" x 2"NPT bushing adapter (#5020126) is available. Thread the bushing adapter into the 2" welded flange securely then install the WLS into the adapter. CAUTION: Do not lift or hold device by float or float rod as bending may occur.

FIG. 2

Wood or Steel Tank Installation

FIG. 3 tion

Steel Tank Installa-

FIG. 4

Wood Tank Installation

FIG. 5

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

ORDERING INFORMATION Device WLS Accessories Flange 1 1/2" Buttress Nut Gasket Buttress Adapter 1 1/2" NPT x 2 1/2" Bushing Adapter 1 1/2" NPT x 2" NPT 6660225 6660083 5330025 5180199 5020126 Stock No. 1010117

CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.
PRINTED IN USA MKT. #8820016 - REV A MFG. #5401040 - 2/97

PAGE 2 OF 2

TTS
TANK TEMPERATURE SUPERVISORY SWITCH
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833 UL, CSFM LISTED, FM APPROVED and NYMEA ACCEPTED

TTS-W

TTS-S

2 1/2" DIA x 17 1/2"L

The Model TTS-S is a water tank temperature supervisory switch preset to give a low temperature signal at 40F/ 4.5C and a high temperature signal at 140F/60C (3F/2C). It is UL Listed and FM Approved. A glass mercury thermostat is used for low temperature sensing and a bi-metal thermostat for high temperature sensing. A diode is used in this unit as a testing aid. When the polarity of DC current is reversed at the feed wires to a TTS, the diode in the circuit prevents the flow of current, proving the absense of a short circuit fault in the wiring or the device itself. CONTACTS: .15 Amp at 115 VDC The TTS, tank temperature switch is supplied with a one inch pipe thread for steel tanks (Model TTS-S) or with a buttress thread for wood tanks (Model TTS-W).

A buttress thread nut and gasket are available for use with the TTS-W for installations where the inside of the tank is accessible and it is not convenient to weld a flange on the tank. The nut and gasket can also be used on a wood tank, which is not sound enough to hold a thread (see Fig. 1). Locate the switch at a point 24 inches below the required water level of the tank. For steel tanks, weld in a No. 282-1 pipe flange or drill a tap tank to receive the one inch pipe thread of the bushing (see Fig. 2). For wood tanks, drill a 1 3/16" hole in the center of a stave and thread the bushing into the tank allowing the butress bushing to cut its own thread (see Fig. 3).

PRINTED IN USA

MKT. #8820011 - REV D MFG. #5400674 - 12/95

PAGE 1 OF 2

TTS
TANK TEMPERATURE SUPERVISORY SWITCH

INSTALLATION
FIG. 1 TTS-W (WOOD OR STEEL) FIG. 2 TTS-S (STEEL)

FIG. 3

TTS-W (WOOD)

FIG. 4

TTS-S SIMPLIFIED SCHEMATIC

TTS ORDERING INFORMATION


DEVICE TTS-S (Steel) TTS-W (Wood) ACCESSORIES Flange 1" Buttress Nut Gasket
PRINTED IN USA

STOCK NO. 1010040 1010041

5020010 5020105 5330035


PAGE 2 OF 2

MKT. #8820011 - REV D MFG. #5400674 -12/95

RTS-O / RTS-C
ROOM TEMPERATURE SWITCH
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833

Enclosure: White ABS Dimensions: 2 1/16"W x 3 7/16"L x 1 1/4"H Sensor: Epoxy sealed stainless steel case, bimetallic operating mechanism. Contacts: Silver clad, available normally open or normally closed. Electrical Rating: 1Amp at 24VDC Temperature Setting: 405F, 53C Terminals: Screw Terminals
RTS-O STK. #1010108 RTS-C STK. #1010109

Mounting: Surface

The RTS Series Room Temperature Sensors are precision engineered, designed and manufactured for commercial or residential use. Available at factory preset temperature rating of 40 F. Designed to warn of potential sprinkler pipe freezing or other cold detection applications. Each unit consists of a bi-metal operating mechanism, featuring hermetically sealed precious metal contacts, N.O. or N.C., which automatically reset for repetitive operation, eliminating the need for sensing element replacement. Small compact design, highly resistant to vibration and corrosion. Easily installed using the enclosed hardware or adhesive mounting pad. Screw terminals permit easy installation in single or multiple detector circuits.

FEATURES: Easily installed Completely sealed sensor, moisture and vapor resistant Highly resistant to vibration and corrosion Highly sensitive to temperature changes No sensitivity loss due to aging Repetitive operation without the need to replace sensing elements Small compact design Precision and quality at low cost OPERATION The normally open detector, RTS-O, will close the contact when the temperature drops below 40F. The normally closed detector, RTS-C, will open the contact when the temperature drops below 40F. The detector will automatically reset to the normal state when the temperature rises above 40F.

PRINTED IN USA

MKT. #8820013 - REV C MFG. #5401019 - 12/95

PAGE 1 OF 1

VSR-FEX
EXPLOSION PROOF VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL, CSFM and NYMEA Listed and FM Approved Service Pressure: Up to 450 PSI Minimum Flow Rate for Alarm: 10 GPM Maximum Surge: 18 FPS Contact Ratings: Two sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.5 Amps at 30 VDC Resistive Conduit Entrances: Two conduit entrances provided for 1/2" conduit Environmental Specifications: For use in hazardous locations, Classified as: Class I: Groups C, D, Div. 1 Class II: Groups E, F, G, Div. 1 Class III: Div. 1 Suitable for indoor or outdoor use with factory installed gasket and cast aluminum housing. NEMA 4 Rated Enclosure - use with appropriate conduit fitting Temperature: 40F/120F, 4.5C/49C Non-corrosive sleeve factory installed in saddle. Sizes Available: Pipe schedules 10 thru 40, sizes 2" thru 8" Service Use: Automatic Sprinkler National Fire Alarm Code GENERAL INFORMATION The Model VSR-FEX is a vane type waterflow switch for use on wet sprinkler systems located in hazardous locations as shown above. The unit may also be used as a sectional waterflow detector on large systems. The unit contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic retard. The switches are actuated when a flow of 10 gallons per minute or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE The unit is enclosed in a cast aluminum housing. The cover is held in place with tamper resistant screws which require a special key for removal. INSTALLATION (See Fig.2) These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be installed within 6" of a fitting which changes the direction of the waterflow or within 24" of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" and 2 1/2" devices require a hole with a diameter of 1 1/4" + 1/8" - 1/16". All other sizes require a hole with a diameter of 2" 1/8". Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole, do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Install the saddle strap and tighten nuts alternately to an eventual 50 ftlbs. of torque. See Fig. 2. The vane must not rub the inside of the pipe or bind in any way.
PAGE 1 OF 2

NFPA-13 NFPA-72

PRINTED IN USA

MKT. #8880009 - REV D MFG. #5400805 - 5/96

VSR-FEX
EXPLOSION PROOF VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD FIG. 1
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL

FIG. 2

CAUTION:

An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

CAUTION: When this device is to be installed in an area that is classified as Hazardous, the person responsible for safety in the area should be contacted to determine if the tools and operations required for the installation of the device and associated components are permitted in the area. To reduce the risk of ignition of hazardous atmospheres, disconnect supply circuits before opening enclosure. Keep cover tightly closed when in operation. cover screws must be torqued to a minimum of 20 in. lbs.

FIG. 3

TYPICAL ELECTRICAL CONNECTIONS

Note: for supervised circuits see Switch Terminal Connections drawing and caution note (Fig. 1).

NOTE: The Model VSR-FEX has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator. TESTING: The frequency of testing for the model VSR-FEX and its associated protective monitoring system should be in accordance with applicable NFPA Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspectors test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-FEX is not recommended or advisable. A minimum flow of 10 gpm is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions.
PAGE 2 OF 2

PRINTED IN USA

MKT. #8880009 - REV D MFG. #5400805 - 5/96

MODEL PS10-EX
EXPLOSION PROOF PRESSURE SWITCH
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833
UL and CSFM Listed, FM Approved and NYMEA Accepted Dimensions: 6"Dia. x 7"H Enclosure: Cast aluminum Pressure Connection: 1/2" NPT Male Brass Fitting Factory Adjustment: Both switches operate on Pressure Increase at 6 1 PSI Both switches operate on Pressure Decrease at 5 1 PSI Maximum Differential: 1 PSI Maximum System Pressure: 250 PSI Switch Contacts: Two Sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.5 Amps at 30 VDC Environmental Specifications: For use in hazardous locations classified as: Class I: Groups B, C, D, Div. 1 Class II: Groups E, F, G, Div. 1 Class III: Div. 1 NEMA 4 Rated Enclosure Temperature range: -40F to 140F (-40C to 60C) Service Use: Automatic Sprinkler NFPA-13 National Fire Alarm Code NFPA-72 METHOD 2: When using the PS10-EX for local bell application or with a control that does not provide a retard feature, the PS10-EX must be installed on the alarm outlet side of the retard chamber of the sprinkler system. TESTING: Accomplished by opening the inspector's end-of-line test valve. Allow time to compensate for system or control retard. CAUTION: Method 2 is not applicable for remote station service use. WET SYSTEM WITH EXCESS PRESSURE: Connect the PS10-EX into alarm port piping extending from alarm check valve. Retard provisions are not required. Insure that no shut off valves are present between the alarm check valve and the PS10-EX. TESTING: Accomplished by opening the water by-pass test valve or the inspector's end-of-line test valve. When using endof-line test, allow time for excess pressure to bleed off. DRY SYSTEM: Connect the PS10-EX into alarm port piping that extends from the intermediate chamber of the alarm check valve. Install on the outlet side of the in-line check valve of the alarm port piping. Insure that no shut off valves are present between the alarm check valve and the PS10-EX. TESTING: Accomplished by opening the water by-pass test valve. CAUTION: The above tests may also activate any other circuit closer or water motor gongs that are present on the system.
PAGE 1 OF 3

PS10-EX No.1350102 INSTALLATION AND TEST PROCEDURE: The Potter PS10EX Pressure Actuated Switch is designed for the detection of a waterflow condition in automatic fire sprinkler systems located in hazardous locations classified as shown above, of particular designs such as wet systems with alarm check valves or dry pipe systems. It may also be used to provide a low pressure supervisory signal. It can be adjusted to operate on pressure between 4 and 20 PSI. MOUNTING: Device should be mounted in upright position (threaded connection down). Requires NEMA Type 4 conduit hub for outdoor installations. TESTING: The operation of the pressure alarm switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). WET SYSTEM: METHOD 1: When using PS10EX and control unit with retard, connect the PS10EX into alarm port piping on the input side of retard chamber and electrically connect PS10EX to control unit that provides a retard to compensate for surges. Insure that no shut off valves are present between the alarm check valve and the PS10EX.

PRINTED IN USA

MKT. #8880010 - REV G MFG. #5400982 - 5/97

MODEL PS10-EX
EXPLOSION PROOF PRESSURE SWITCH
ORDERING INFORMATION Model Description PS10-EX Pressure switch with two sets SPDT contacts Hex Key

Stock No. 1350102 5250073

TYPICAL SPRINKLER APPLICATIONS

CAUTION: Closing of any shutoff valves between the alarm check valve and the PS10-EX will render the PS10-EX inoperative. To comply with NFPA-72 any such valve shall be electrically supervised with a supervisory switch such as Potter Model BVS.

TYPICAL ELECTRICAL CONNECTIONS

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL


CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

PRINTED IN USA

MKT. #8880010 - REV G MFG. #5400982 - 5/97

PAGE 2 OF 3

MODEL PS10-EX
EXPLOSION PROOF PRESSURE SWITCH
PRESSURE SWITCH TERMINATION

NOTE: To prevent leakage, apply teflon tape sealant to male threads only. WARNING: Use of pipe joint cement may result in obstruction of aperture and loss of signal.

CAUTION: When this device is to be installed in an area that is classified as HAZARDOUS, the person responsible for safety in the area should be contacted to determine if the tools and operations required for the installation of the device and associated components are permitted in the area. To reduce the risk of ignition of hazardous atmospheres, disconnect supply circuits before opening cover. Keep cover tight while circuits are live. Cover screws must be torqued to 45-50 in. lbs.

ENGINEER/ARCHITECT SPECIFICATIONS
Pressure type waterflow switches shall be a Model PS10-EX as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed on the sprinkler systems as shown on the drawings and/or specified herein. Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the alarm check valve of a wet sprinkler system or into the intermediate chamber of a dry pipe system and shall be actuated by any flow of water to or in excess of the discharge from one sprinkler head. Switches shall have a maximum service pressure rating of 250 PSI and shall be factory adjusted to operate on pressure increase at 6 1 PSI. There shall be two (2) SPDT contacts rated at 15.0 Amps at 125/250VAC and 2.5 Amps at 30VDC. The switch housing shall be weather proof and oil resistant with a NEMA 4 rating. The cover shall incorporate tamper resistant screws. The unit shall be listed by Underwriters Laboratories, Inc. and CSFM and approved by Factory Mutual. It shall be rated for use in hazardous locations classified as Class I, Groups B, C, D, Div. 1; Class II, Groups E, F, G, Div. 1; Class III, Div. 1.
PRINTED IN USA MKT. #8880010 - REV G MFG. #5400982 - 5/97 PAGE 3 OF 3

MODEL PS40-EX
EXPLOSION PROOF HIGH/LOW PRESSURE SWITCH
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833 UL and CSFM Listed, FM Approved and NYMEA Accepte d Dimensions: 6"Dia. x 7"H Enclosure: Cast Aluminum Pressure Connection: 1/2" NPT Male Brass Fitting Factory Adjustment: One switch operates on decrease at 30 PSI and one switch operates on increase at 50 PSI. Pressure Range: 10 - 175 PSI Maximum Differential: Approx. 2 lbs. at 20 PSI 5 lbs. at 175 PSI Maximum System Pressure: 250 PSI Switch Contacts: Two sets of SPDT (Form C) 15.0 Amps at 125/250 VAC 2.5 Amps at 30 VDC Environmental Specifications: For use in hazardous locations classified as: Class I: Groups B, C, D, Div. 1 Class II: Groups E, F, G, Div. 1 Class III: Div. 1 NEMA 4 Rated Enclosure Temperature range: -40F to 140F (-40C to 60C) PS40-EX No. 1350402 Service Use: Automatic Sprinkler National Fire Alarm Code NFPA-13 NFPA-72

The Potter PS40-EX is a pressure actuated switch designed primarily to detect a 10 PSI increase and/or decrease from normal system pressure in automatic fire sprinkler systems located in hazardous locations classified as shown above. Typical applications are air pressure supervision in dry pipe systems and pressure supervision of pressure tanks, air supply or water supply. INSTALLATION AND TEST PROCEDURE Mounting: Device should be mounted in upright position (threaded connection down). Requires NEMA Type 4 conduit hub for outdoor installations.
PRINTED IN USA

Dry System: Connect PS40-EX in air supply line on the system side of any shutoff or check valve. Provision for testing the unit can be accomplished with the installation of a Potter Bleeder Valve (Model BVL) in the line to the PS40-EX. Testing: The operation of the pressure supervisory switch should be tested upon completion of installation and periodically thereafter in accordance with the applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). CAUTION: Testing the PS40-EX may activate other system connected devices.
PAGE 1 OF 3

MKT. #8880011 - REV H MFG. #5400983 - 5/97

MODEL PS40-EX
EXPLOSION PROOF HIGH/LOW PRESSURE SWITCH Ordering Information Model Description
PS40-EX BVL Pressure switch with two sets SPDT contacts Bleeder Valve Hex Key

Stock No.
1350402 1000018 5250073

TYPICAL SPRINKLER APPLICATION - DRY SYSTEM

TYPICAL ELECTRICAL CONNECTIONS

SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL


CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal.

PRINTED IN USA

MKT. #8880011 - REV H MFG. #5400983 - 5/97

PAGE 2 OF 3

MODEL PS40-EX
EXPLOSION PROOF HIGH/LOW PRESSURE SWITCH
PRESSURE SWITCH TERMINATION

NOTE: Switches are shown in standby condition with normal pressure applied. Switch #1 (high) changes with pressure increase. Switch #2 (low) changes with pressure decrease.

FIELD ADJUSTMENTS The operating point of the switches on the PS40-EX can be adjusted to any point between 10 and 175 PSI by turning the adjustment knob(s) clockwise to raise the actuation point, and counter-clockwise to lower the actuation point. The two switches operate completely independently of one another, and each switch may be adjusted to actuate at any point the system requires. Final adjustment should be made with a pressure gauge. NOTE: To prevent leakage, apply teflon tape sealant to male threads only. WARNING: Use of pipe joint cement may result in obstruction of aperture and loss of signal.

CAUTION: When this device is to be installed in an area that is classified as HAZARDOUS, the person responsible for safety in the area should be contacted to determine if the tools and operations required for the installation of the device and associated components are permitted in the area. To reduce the risk of ignition of hazardous atmospheres, disconnect supply circuits before opening cover. Keep cover tight while circuits are live. Cover screws must be torqued to 45-50 in. lbs. ENGINEER/ARCHITECT SPECIFICATIONS
Air pressure supervisory switch shall be a Model PS40-EX as manufactured by Potter Electric Signal Co. of St. Louis, Mo. and shall be installed on the sprinkler systems as shown on the drawings and/or as specified herein. Switches shall be provided with a 1/2" NPT male pressure connection to be connected into the air supply line on the system side of any shut-off valve. A Model BVL bleeder valve as supplied by Potter Electric Signal Co. of St. Louis, Mo. or equivalent shall be connected between the air line to provide a means of testing the operation of the supervisory switch. The switch unit shall contain SPDT (Form C) switches. One switch shall operate at a pressure decrease of 10 PSI from normal. The second switch shall operate at a pressure increase of 10 PSI from normal. Switch contacts shall be rated at 15.0 Amps at 125/250 VAC and 2.5 Amps at 30 VDC. The units shall have a maximum pressure rating of 250 PSI and shall be adjusted from 10 to 175 PSI. The switch housing shall be weatherproof and oil resistant with a NEMA 4 rating. The cover shall incorporate tamper resistant screws. The unit shall be listed by Underwriters Laboratories, Inc. and CSFM and approved by Factory Mutual. It shall be rated for use in hazardous locations classified as Class I, Groups B, C, D, Div. 1; Class II, Groups E, F, G, Div. 1; Class III, Div. 1.
PRINTED IN USA MKT. #8880011 - REV H MFG. #5400983 - 5/97 PAGE 3 OF 3

PIVS-U-EX
POST INDICATOR VALVE SWITCH EXPLOSION PROOF
Potter Electric Signal Company 2081 Craig Road P.O. Box 28480 St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833 Enclosure: Explosion Proof Switch Enclosure Environmental Limitations: -40 to 140F (-40C to 60C). For use in hazardous locations. Mounting: 1/2" tapped hole in post indicator housing Contact Rating: 10 AMPS at 125VAC 1/2 AMP at 125VDC Service Uses: Automatic Sprinkler One or two family dwelling Residential occupancy up to four stories National Fire Alarm Code
STOCK NO. 1010092

NFPA-13 NFPA-13D NFPA-13R NFPA-72

The PIVS-U-EX is designed to mount in a 1/2" tapped hole in the post indicator housing. The PIVS-U-EX should be located so that the stem of the switch is held against the stem return spring by the indicator assembly when the valve is open. SWITCH ENCLOSURE: UL listed explosion proof switch enclosure. For hazardous locations. Class I, Group C & D; Class II, Groups E, F, & G. INSTALLATION: See Figures 1, 2, 3, 4, and 5. Operate the valve to determine whether the target moves up or down as the valve is closed. Open the valve fully and see that target indicates OPEN. Remove the head from the indicator post and remove target assembly. Select a location for the switch, so that the stem of the switch will be depressed by some part of the target assembly when valve is fully open. The switch location should be accessible for service. If the target assembly moves up when the valve is closed locate the switch below the target with the long part of the case pointing down. If the target assembly moves down when the valve is closed locate the switch above the target with the long part of the case pointing up.

Drill and tap the post at the location selected to receive the 1/2" NPT nipple on the switch. In some cases it may be necessary to attach an angle bracket to the target assembly to engage the switch stem. Any excess length of the stem should be cut off with a hack saw. Close the valve carefully and see that the switch stem is free to move and that no excess pressure is placed on the stem at the end of its travel. Small adjustments of the target position may be made if necessary. The contacts of the switch should operate when the valve is closed 1 or 2 turns. The switch can be tested with a buzzer or ohmeter. Replace the head on the indicator post. An alternate method of installation is shown in Figure 3. In this method one of the glass windows is replaced with a 1/4" thick steel plate cut to fit in place of the glass and drilled and tapped to receive the 1/2" pipe nipple on the switch. A 1/2" or 3/4" square block of steel is attached to the target assembly, in place of the cast letter plate, to actuate the switch stem. Figure 4 shows the switch mounted on a butterfly valve.

PRINTED IN USA

MKT. #8880005 - REV D MFG. #5400694 - 12/95

PAGE 1 OF 2

PIVS-U-EX
POST INDICATOR VALVE SWITCH EXPLOSION PROOF
FIG. 1 TYPICAL VALVE INSTALLATION FIG. 2 TYPICAL VALVE INSTALLATION FIG. 3 VALVE WINDOW INSTALLATION

FIG. 4

BUTTERFLY VALVE INSTALLATION

FIG. 5

TYPICAL ELECTRICAL CONNECTIONS

PRINTED IN USA

MKT. #8880005 - REV D MFG. #5400694 - 12/95

PAGE 2 OF 2

OSYS-U-EX
O S & Y SWITCH - UNIVERSAL EXPLOSION PROOF
Potter Electric Signal Company 2081 Craig Road St. Louis, MO 63146-4161 (314) 878-4321 (800) 325-3936 www.pottersignal.com Potter Electric Signal & Mfg., LTD. 55 Glen Cameron Road Thornhill, Ontario, Canada L3T 1P2 (905) 882-1833

GATE VALVE SWITCH FOR SUPERVISION OF O S & Y VALVES: The Model OSYS-U-EX is designed to supervise the open condition of an O S & Y type gate valve in hazardous locations.

CONTACTS: One set of SPDT (Form C) Contacts rated 15 Amps,125/250/480VAC; 1/2 Amp, 125VDC; 1/4 Amp, 250VDC SWITCH ENCLOSURE: UL listed explosion proof switch enclosure. For hazardous locations. Class I, Groups C & D; Class II, Groups E, F & G

TYPICAL ELECTRICAL CONNECTIONS

PRINTED IN USA

MKT. #8880006 - REV D MFG. #5400705 - 11/97

PAGE 1 OF 2

OSYS-U-EX
O S & Y SWITCH - UNIVERSAL EXPLOSION PROOF
VALVE SIZES 1/2" THRU 2 1/2" FIG.1 FIG.2 VALVE SIZES 3" THRU 12"

SMALL VALVE INSTALLATION 1. 2. Remove and discard "C" washer and roller from the trip rod. With the valve in the FULL OPEN position, locate the OSYS-U-EX across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the non-threaded portion of the valve stem. Excess trip rod length extending beyond the valve stem must be cut off. Mount the OSYS-U-EX loosely with the carriage bolts and clamp bar supplied. On valves with limited clearance use J-hooks supplied instead of the carriage bolts and clamp bar to mount the OSYS-U-EX. Mark the valve stem at the center of the trip rod. Remove the OSYS-U-EX. File a 3/32" deep groove centered on the mark on the valve stem utilizing a 1/4" diameter straight file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. Mount the OSYS-U-EX with the trip rod centered in groove. Final adjustment is made by loosening 2 screws (see Fig. 1) and sliding the OSYS-U-EX on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate when the trip rod moves out of the groove. Tighten the adjustment screws and all mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position.

LARGE VALVE INSTALLATION 1. With the valve in the FULL OPEN position, locate the OSYS-U-EX across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the non-threaded portion of the valve stem. 2. Mount the OSYS-U-EX loosely with the carriage bolts and clamp bar supplied. 3. If the trip stem extends below the valve yoke, the clamp bar must be discarded and the large J hooks must be used to mount the OSYS-U-EX to the valve.

3. 4.

4. Mark the valve stem at the center of the trip rod. 5. Remove the OSYS-U-EX. File a 1/8" deep groove centered on the mark of the valve stem utilizing a 3/8" diameter straight file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. 6. Mount the OSYS-U-EX loosely with the trip rod centered in groove. 7. Final adjustment is made by loosening 2 screws (see Fig. 2) and sliding the OSYS-U-EX on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. 8. Tighten the adjustment screws and mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION.

5. 6.

7. 8.

9.

NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION.

PRINTED IN USA

MKT. #8880006 - REV D MFG. #5400705 - 11/97

PAGE 2 OF 2

Вам также может понравиться