Submittal Data: SEZ-KD12NA

12,000 BTU/H Horizontal-ducted Indoor Unit for MXZ Multi-Zone Heat-pump SYSTEMs

Job Name:

Location:

Purchaser:

Engineer:

Submitted to:

For

System Designation:

Schedule No.:

GENERAL Features
Ceiling-concealed ducted indoor unit for residential applications
Ultra thin body: 7-7/8" high
Built-in drain mechanism for condensate removal; lifts to 21-11/16"
Air filter is included with indoor unit
Quiet operation as low as 23 dBA
PAR-21MAA wired remote controller is included
Indoor unit powered from outdoor unit using A-Control
Automatic fan speed control
Auto restart following a power outage
Limited warranty: one year on parts and defects
OPTIONAL AccessorieS
M-NET Control Adapter (MAC-399IF)
External Heat Adapter (PAC-YU25HT)
CN24 Relay Kit (CN24RELAY-KIT-CM)
Three-pole Disconnect Switch (TAZ-MS303)
Cooling*
Rated Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12,000 Btu/h
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 W
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.57 A
Heating*
Rated Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13,600 Btu/h
Total Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 W
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.46 A
* Rating Conditions (Cooling) - Indoor: 80F (27C) DB / 67F (19C) WB.
Outdoor: 95F (35C) DB / 75F (24C) WB.
(Heating) - Indoor: 70F (21C) DB / 60F (16C) WB. Outdoor: 47F (8C) DB /
43F (6C) WB.
(For data on specific indoor units [all ducted, all non-ducted, and both ducted
and non-ducted] combinations, see the MXZ Technical and Service Manual.)

Electrical Requirements
Power Supply . . . . . . . . . . . . . . . . . . . 208 / 230V, 1-Phase, 60 Hz
MCA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A
Voltage
Indoor - Outdoor S1-S2 . . . . . . . . . . . . . . . . . . . . . . . AC 208 / 230V
Indoor - Outdoor S2-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC 24V
MXZ Multi-Zone Heat-pump Outdoor Units
MXZ Multi-Zone SYstems Can Include:
All Horizontal-ducted Indoor Units:
SEZ-KD09, 12, 15, 18NA
Select Wall-mounted Indoor Units:
MSZ-A09, 12, 15, 17, 24NA
and
MSZ-FD09, 12NA
A combination of both Horizontal-ducted
and Wall-mounted Indoor Units
Refer to the separate submittal forms for the
MSZ-A and MSZ-FD Indoor Units and MXZ
Outdoor Units.
Outdoor Unit: MXZ-3A30NA

Reference

Date:

Approval

Construction

Indoor Unit: SEZ-KD12NA

Remote Controller: PAR-21MAA

Fan
Type x Quantity . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sirocco Fan x 2
Motor . . . . . . . . . . . . . . . . . . . . . . Direct-driven DC Brushless Motor
Motor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 W
Airflow (Lo - Med - Hi) . . . . . . . . . . . . . . . . . . . 247 - 317 - 388 CFM
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . Polypropylene Honeycomb
External Static Pressure . . . . . . . . . . . 0.02 - 0.06 - 0.14 - 0.20"WG
Sound Pressure Level (Lo - Med - Hi) . . . . . . . . . 23 - 28 - 33 dB(A)
DIMENSIONS
W
D
H

UNIT INCHES / MM
39 / 990
27-9/16 / 700
7-7/8 / 200

Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 lbs. / 21 kg
Field Drainpipe Size O.D. . . . . . . . . . . . . . . . . . . . . . 1-1/4" / 32 mm
Wall-mounted Remote Controller . . . . . . . . . . . . . . . . . PAR-21MAA
(See Data Submittal Sheet)
Refrigerant Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R410A
Refrigerant Pipe Size O.D.
Gas Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/8" / 9.52 mm
Liquid Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/4" / 6.35 mm
Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Flared
MXZ Compatible Indoor UNits and Remote Controllers

Wall-mounted Indoor Unit: MSZ-A09, 12, 15, 17, 24NA

Wireless Remote Controller Packaged with MSZ-A and MSZ-FD


(Optional Wired Remote Controller
PAR-21MAA)
Wall-mounted Indoor Unit: MSZ-FD-NA

Horizontal-ducted Indoor Unit: SEZ-KD-NA

Remote Controller
PAR-21MAA Packaged with SEZ

SEZ-KD12NA Indoor Fan Performance and Corrected Air Flow Charts


SEZ-KD12NA

SEZ-KD12NA

(External static pressure 0.02[in.WG](5Pa)) 208/230V 60Hz

(External static pressure 0.06[in.WG](15Pa)) 208/230V 60Hz


50
[0.20]

External static pressure [in.WG](Pa)

External static pressure [in.WG](Pa)

40
[0.16]

30
[0.12]

Limit

20
[0.08]

High

10
[0.04]

Middle

40
[0.16]
Limit

30
[0.12]
High

20
[0.08]
Middle
Rated point

10
[0.04]
Rated point

Low

Low

0
6
[212]

7
[247]

8
9
10
[282]
[318]
[353]
3
Airflow rate(m /min)[CFM]

11
[388]

SEZ-KD12NA

6
[212]

70
[0.28]

70
[0.28]

60
[0.24]

Limit

50
[0.20]
40
[0.16]
Rated point

30
[0.12]

High

Middle

20
[0.08]

External static pressure [in.WG](Pa)

80
[0.32]

11
[388]

12
[424]

Limit

60
[0.24]
50
[0.20]

Rated point

High

40
[0.16]
Middle

30
[0.12]
20
[0.08]

Low

Low

10
[0.04]

0
6
[212]

8
9
10
[282]
[318]
[353]
3
Airflow rate(m /min)[CFM]

(External static pressure 0.20[in.WG](50Pa)) 208/230V 60Hz

80
[0.32]

10
[0.04]

7
[247]

SEZ-KD12NA

(External static pressure 0.14[in.WG](35Pa)) 208/230V 60Hz

External static pressure [in.WG](Pa)

12
[424]

0
7
[247]

8
9
10
[282]
[318]
[353]
3
Airflow rate(m /min)[CFM]

11
[388]

12
[424]

6
[212]

7
[247]

8
9
10
[282]
[318]
[353]
Airflow rate(m3/min)[CFM]

11
[388]

12
[424]

Dimensions: SEZ-KD12NA

159(6-9/32)

Suspension bolt hole


4-14X30(9/16X1-3/16) Slot

Control box

116
(4-19/32)

70
(2-25/32)
270(10-21/32)

2X2-2.9(1/8)

Refrigerant piping
flare connection (gas)

100(3-15/16)XJ=K
100(3-15/16)
12(1/2)

88(3-15/32)
20(13/16)

Knockout hole 27(1-3/32)


(Remote controller transmission line)

Terminal block (Indoor/outdoor connecting line)

Refrigerant piping
flare connection (liquid)

Air filter

Knockout hole 27(1-3/32)


(Indoor/outdoor connecting line)

102(4-1/32)
170(6-23/32)
200(7-7/8)

23(29/32)

25(1)
100
(3-15/16)

150(Duct)
(5-29/32)

700(27-9/16)
677(26-21/32)

23(29/32)
10(13/32)

23(29/32)

57(2-1/4)

90
(3-9/16)

25(1)

20(13/16)
30(1-3/16)

10(13/32)
625(Suspension bolt pitch)
(24-5/8)

49
(1-15/16)

Air
inlet

57(2-1/4)

Air
outlet

Drain pipe(O.D.32(1-1/4))

37(1-15/32)
100(3-15/16)
157.5 (6-7/32)
37(1-15/32)

L-2.9(1/8)

N
B (Suspension bolt pitch)
C
M

D (Duct)
100(3-15/16)X(E-1)=F
100(3-15/16)

2XE-2.9(1/8)

20(13/16)
12(1/2)

88(3-15/32)

15(19/32)

Unit : mm(in.)

Drain pipe(O.D.32(1-1/4))
(Emergency draining)

345(13-19/32)

Terminal block (Remote controller transmission line)


Drain pipe(O.D.32(1-1/4))
(Spontaneous draining)

)
7
77 9/32
-1 Access
(30

50
(1
G -31/3

Less than 550


(21-21/32)

Note2

/32

31

(150

door

2)

(1-

31

/32 50 ~
~ 5 150
-29
/32
)

(17 450
-23
/32
)

0
0
45 2)
/3 n 30 6)
-23 tha 13/1
7
(1 ore 11(
M

More than 10
(13/32)
More than 20
(13/16)

Less than 300


(11-13/16)

1755(6-29/327/32)
(Actual length)

Ceiling surface Access door

Make the access door at the appointed position properly


for service maintenance.

Drain hose (I.D.32(1-1/4))


<accessory>

Required space for service and maintenance

mm(in.)
Model
SEZ-KD09NA
SEZ-KD12NA

700

752

798

660

900

952

998

860

(27-9/16) (29-5/8) (31-7/16)

(26)

SEZ-KD15NA

(35-7/16) (37-1/2) (39-5/16) (33-7/8)

SEZ-KD18NA

1100 1152 1198 1060

(43-5/16) (45-3/8) (47-3/16) (41-3/4)

600

800

660

800 1000

860

9
11

(23-5/8) (31-1/2)

(26)

(31-1/2) (39-3/8) (33-7/8)

1000 1200 1060

(39-3/8) (47-1/4) (41-3/4)

500

16

839

790

700

1039 990
20 (40-29/32)
(39)

7
9

(19-11/16)
(27-9/16)

900

(35-7/16)

(33-1/16) (31-1/8)

1239 1190

24 (48-25/32) (46-7/8)

Gas pipe

Liquid pipe

9.52(3/8)
6.35(1/4)
12.7(1/2)

Note1.Use M10 screw for the suspension bolt (field supply).


2.Keep the service space for the maintenance at the bottom.
3.This chart indicates for SEZ-KD15NA model,which has 3 fans.
SEZ-KD09,12NA models have 2 fans.
SEZ-KD18NA models have 4 fans.
4.In case an inlet duct is used,remove the air filter(supply with
the unit), then install the filter(field supply) at suction side.

C SD - SEZ-KD12NA - 200903 MITSUBISHI ELECTRIC / HVAC 2009

3400 Lawrenceville Suwanee Rd


Suwanee, GA 30024
Tele: 678-376-2900 Fax: 800-889-9904
Toll Free: 800-433-4822 (#3)
www.mehvac.com
Specifications are subject to change without notice.