Вы находитесь на странице: 1из 32

Page 1

Associate isolation (www.freebz.net) foreground

C 8364:2008

Previous Next

Page

Preface 1 Scope 2 Normative references 3 Terms and definitions 4 Types and ratings 5 Legal 5.1 Standard Conditions 5.2 Special conditions 6 Performance 6.1 Temperature rise 6.2 Insulation resistance 6.3 Power Frequency withstand voltage 6.4 Rated short time withstand current 6.5 Strength level 6.6 vertical intensity 6.7 Impact Strength 6.8 degree of protection against water for outdoor bus duct 6.9 Fire Resistance of bus duct fire 6.10 Heat-cycle performance of the instrument and disconnect plug 6.11 for the branch opening and closing apparatus with an operating mechanism connecting the handle or cover 6.12ignition performance of the thermal performance and insulation resistance 7 Structure 7.1 Structure of the bus duct

One One One One Five Six Six Six Six Six Seven Seven Seven Eight Eight Eight Eight Eight Eight Nine Nine Nine Nine

7.2 Structure of the connection equipment for the branch 11 8 material 8.1 Conductor
11 11

8.2 insulator 8.3 out of boxes and equipment for branch duct connections 9 Test methods 9.1 General requirements 9.2 Structural testing 9.3 Temperature rise test 9.4 Insulation resistance test 9.5 Power Frequency withstand voltage test 9.6 Rated short time withstand current test
(1)

11 12 13 13 13 13 14 14 15

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Fenxiang Page 2 (www.freebz.net) foreground

Page C 8364:2008

9.7 Strength level test 9.8 vertical strength test 9.9 Impact test 9.10 degree of protection for water tests for outdoor bus duct 9.11 The bus duct fire test fire 9.12 and the heat cycle test plug-in removable appliances

17 17 17 19 19 20

9.13 Test equipment connections for the branch opening and closing operation mechanism with the handle or cover 21 9.14 Performance Test performance and resistance to ignition of the thermal insulation 21 9.15 Inspection and testing electrical wiring work 21 10 inspection 10.1 format checks 10.2 Delivery Inspection 11 more products called 12 view
21 21 22 22 22

(2)

Associate isolation (www.freebz.net) immediately below or note books Associate isolation (www.freebz.net) Page 3 foreground

C 8364:2008

Introduction

This standard is based on the provisions of Article 12 Paragraph 1 of Article 14 shall apply to the Industrial Standardization Law, Institute of Electrical Society (IEIEJ) and the Japanese Standards Association (JSA) from the Japan Industrial Standard and equipment should be revised and a draft industry standard In the complaints, after deliberation of the Japanese Industrial Standards Committee, Japanese Industrial Standards is amended by the M inister of Industry. This, eight thousand three hundred and sixty-four JIS C : 1,995 has been revised and replaced with the standard. This standard is subject to copyright which is protected by copyright law. Some of this standard, patents, patent applications filed after publication, on application for registration of a utility model or utility model patent application after publication Be warned that there could be conflict. Japanese Industrial Standards Committee and the M inister of Economy, such patents Right, after publication of patent applications filed, according to an application for utility model registration confirmation after publication of the application or utility model right , responsibility Have.

(3)

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Fenxiang Page 4 (www.freebz.net) foreground

Page C 8364:2008

White

Paper

(4)

Associate isolation (www.freebz.net) immediately below or note books Associate isolation (www.freebz.net) Page 5 foreground

Japanese Industrial Standards

JIS C 8364

: 2008

Bus duct
Busways
Preface This standard was established in 1962, has come to today after six subsequent amendments. The last revision in 1995. Is made, the relevant laws and fire laws and technical standards for electrical equipment for subsequent advances in technology such measures consistent with the revised Together with the amendment to the current products to address the situation.

One Scope of application This standard is less than 1 000 V alternating current (less than 1 000 Hz frequency) and its Affiliated below 1 500 V dc bus duct or Prescribed for the product family. Except trolley bus duct. Furthermore, in this context and accessories, Endokuroza, refers to equipment and feed-box for branch connections.

Two Normative reference The standards listed below, are incorporated by this standard, forming part of the provisions of this standard. These Normative references, the latest edition (including any amendments.) Applies. JIS A 1304 test method portion of the building structure fire JIS C 0920 grade electrical equipment protected by the outer (IP Code) JIS C 1302 Insulation Testers JIS C 1602 Thermocouple JIS C 2110 Test M ethod for Dielectric Strength of Solid Electrical Insulation M aterials JIS C 3005 Test M ethod Rubber and plastic insulated wire JIS C 60695-2-10 fire test - electrical and electronics - glow-wire test apparatus and general test methods JIS C 60695-2-11 fire test - electrical and electronics - glow-wire flammability test method for end products JIS K 7113 plastics tensile test method JIS Z 8703 standard conditions of test site JIS Z 8721 how these colors - three attributes displayed by

ThreeTerms and definitions The main terms and definitions used in this standard are as follows. 3.1 Bus duct Supported by an insulator or a conductor bare, naked and covered with an insulated conductor or an assembly into the duct. 3.2 Duct

Associate isolation (www.freebz.net) immediately below or note books

Isolation isolation Associate www.bzfxw.com Page 6 (www.freebz.net) Fenxiang foreground T wo C 8364:2008

Box body coated with an insulator into a conductor or a bare conductor. 3.3 Bare conductor bus duct Supported by an insulated conductor bus duct naked. 3.4 Insulated conductor bus duct Coated with an insulating bus duct bare conductors. 3.5 Bus duct fire Bus duct having a fire resistance. 3.6 Feeder bus duct Have a branching bus duct. 3.7 Plug-In Bus Duct Provided a plug socket, plug-in bus duct can be branched by instruments. 3.8 Straight Linear bus duct. 3.9 Tapped bus duct And intermediate in the termination bolt fixtures, equipment, bus duct taps to connect with a wire and so on. 3.10 Elbow Bent at any angle in bus duct. 3.11 Offset Bus duct with a step. 3.12 T Three directions can be connected to the bus duct. 3.13 Cross Bus duct can be connected to the four directions.

3.14 Reducer Bus duct can be connected together with different rated current bus duct.

3.15 Duct Expansion Bus

Associate isolation (www.freebz.net) immediately below or note books Associate isolation (www.freebz.net) Page 7 foreground

T hree C 8364:2008

And / or heat shrinkable bus duct having a structure to absorb the amount of change or thermal expansion. 3.16 Bus duct transposition Replaced in the position of the bus duct in a duct cross-conductor. And averaging the impedance of each phase, the phase sequence Intended to be changed. 3.17 Endokuroza Closed end of the bus duct components. 3.18 Feed-box Connect power to the bus duct components. 3.19 Connection equipment for the branch Generic plug-in appliances and equipment bolted. 3.20 Instrument plug-in Insert the plug into the plug socket bus duct, bus duct unit to connect to a conductor such as by clips Equipment. 3.21 Plug-In Breaker Equipment with built-in circuit breaker plug. 3.22 Plug-In Switch Plug-in switch with built-in appliances. 3.23 Plug-In Box Has no internal switching mechanism, with the only instrument plug-in terminals for wire connection and fuse holders or equipment. 3.24 Bolt Supplies By tightening the bolts to the tap of a tapped bus duct to connect equipment. 3.25

Bolt-on breaker Bolt with an internal circuit breaker equipment.

3.26 Bolt-on switch Bolt with an internal switch equipment. 3.27 Bolt-on box

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Fenxiang Page 8 (www.freebz.net) foreground

Four C 8364:2008

Has no internal switching mechanism, with only the terminal equipment for connecting bolt or wire fuse and holder tool. 3.28 Handle operating mechanism Plug-breaker, plug-in switch, lid open and close the bolt on bolt-on breakers and switches Without opening and closing mechanism, the operation performed by the handle. 3.29 Cover operating mechanism You can open and close the lid of the bolt-on plug-in switch and the switch by opening and closing operation of the switch line Selling Organization. 3.30 Clearance The shortest space of two isolated bare live parts. 3.31 Creepage distance Shortest distance along the surface of the insulating material between two conductive parts. 3.32 Rated short time withstand current Under the terms of the regulation circuit, the prescribed time, short-time current limit is also not allowed to live in the bus duct abnormalities.

Associate isolation (www.freebz.net) immediately below or note books Associate isolation (www.freebz.net) Page 9 foreground

Five C 8364:2008

Four Types and ratings Type of bus duct and ratings tables, one with. Table 1 - Types and Ratings
T ype Name Bus duct Feeder bus duct Straight Elbow Offset T Cross Reducer Expansion Bus Duct T apped bus duct T ransposition bus Sudakuto Plug-In Bus Duct Indoor Insulated conductor of ventilation Form Bare conductor Form a non-ventilated Outdoor Fireproof Indoor Indoor Form Pole Rating Current Number A 60 100 200 300 400 600 800 1 000 1 200 1 500 1 600 2 000 2 500 3 000 3 500 Rating Voltage V 300 300 600 750 1 000 1 500
a) a) a)

Rated short Withstand current A 5 000 7 500 10 000 14 000 18 000 22 000 25 000 30 000 35 000 42 000 50 000 60 000 65 000 75 000 85 000

Insulated conductor of ventilationT wo Form T hree Bare conductor Form a non-ventilated Insulated conductor of ventilationFour Form Bare conductor Form a non-ventilated Insulated conductor a non-ventilated Form Bare conductor

4 000 4 500 5 000 5 500 Accessories Endokuroza Feed-box 6 000 300 300 600 750 1 000 1 500 Plug T ool Bolt T ool
b) b) a) a) a)

90 000 100 000 125 000 150 000 200 000 -

Plug-in Bolt Breaker Plug-in Bolt Switch Plug-in Box Bolt Box

Handle operation Internal switching operations

T wo T hree Four

Instruments inBreaker

Handle operation Cover Operations Internal switching operations

Cartridge fuse Plug fuse

T wo T hree Four

On instruments Switch

Fused

Cartridge fuse Plug fuse

T wo T hree Four

Fuse

Note

a) b)

Shows the DC voltage. Rated voltage and rated current of equipment and instruments plug-bolt, rated current and rated current, such as a built-in circuit breaker And pressure.

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 10 Fenxiang foreground (www.freebz.net)

Six C 8364:2008

Five Use conditions 5.1 5.1.1 Standard Terms and Conditions General requirements

Terms and Conditions and Standard 5.1.2 and 5.1.3 refers to the conditions applicable to either. 5.1.2 Terms of Use for indoor bus duct

a) the ambient temperature is ambient temperature, and -5 ~ +40 , and the average ambient temperature was measured over 24 hours, And below 35 . b) relative humidity Humidity: 85% at 40 and the highest temperature. However, for example, at temperatures as low as 20 The humidity may be 90%. c) above sea level elevation of the place of use, and less than 2 000 m.

d) dust of the air surrounding the state of air pollution, smoke, corrosive or flammable gases, steam and stain with salt, To be negligible. 5.1.3 Terms of Use for outdoor bus duct

a) the ambient temperature is ambient temperature, and -25 ~ +40 , and the average ambient temperature was measured over 24 hours, And below 35 . b) relative humidity Humidity does not affect the extent and even cause condensation inside the bus duct. c) Elevation above sea level where used, and less 2 000 m.

d) dust of the air surrounding the state of air pollution, smoke, corrosive or flammable gases, steam and stain with salt, To be negligible. e) snow, rain and snow sunlight, to be negligible. Rain, temperature and sunlight are subjected. 5.2 Special Conditions And the special conditions applicable to any of the following cases, when used in this state, the parties agreed on settlement M ust. a) ambient temperature, humidity, altitude condensation and 5.1 exceed the provisions. b) In exceptional speed or condensation inside the bus duct, temperature and / or humidity changes happen. c) Dust, smoke, corrosive or radioactive particles, if there is significant contamination of the atmosphere with steam or salt.

d) Exposure to strong magnetic fields or strong electric field. e) f) Extreme temperature, for example, exposure to radiation from the furnace. If the snow is particularly high.

g) -location there is a risk of fire or explosion. h) exposure to severe vibration and shock. i) I built the machine, by being recessed in the wall, breaking capacity is affected or where the current capacity Installing the.

S ix Performance 6.1 Temperature rise The bus duct temperature rise is 9.3 when tested by either temperature rise well beyond the following limits for They do not. In this case, the reference ambient temperature shall be 40 . a) limit the surface temperature of the surface temperature of the bus duct bus duct ceiling, the table 2 and shown in the.

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 11 (www.freebz.net) foreground

Seven C 8364:2008

Table 2 - bus duct ceiling surface temperature


Unit K Part Duct that can be accessed T hat can be accessed while driving touch

Surface Metal Synthetic resin 30 40

Surface of the duct does not need to be 55 55

b) materials used to limit the internal temperature inside the bus duct bus duct, temperature limits for parts and equipment Degree, according to the following conditions specified by the manufacturer. 1) The temperature of the ceiling insulation is in contact with the conductor insulator, shall not exceed the maximum allowable temperature of the insulator Not. 2) conductor - The temperature must not cause deterioration of mechanical strength to the conductive material . - The temperature must not adversely affect the equipment connected to the conductor . - Surface temperatures adversely affect the properties of the material and plug contacts should be. 3) The ceiling temperature of the conductor connecting the conductor connection, the table 3 and values shown. Table 3 - Limits of the junction temperature rise
Unit K Where members Bare copper or bare copper alloy Such as bolting According to the connection T in-plated Or silver-plated Nickel plating Bare copper or bare copper alloy Contact area T in-plated Or silver-plated Nickel plating Screw or bolt it to the Pins Bare copper T emperature rise 50 65 75 35 55 65 50 65

What is connected to the outer Silver-plated, nickel plating conductor Come or tin-plated

4) The temperature rise of conductors insulated conductor that connects to the external terminal 2) by a temperature rise of the connecting part 3) by. Simply However, the maximum allowable temperature of the insulating material used for outer insulated conductor terminal 2) or 3) is less than the isolation of the To apply the permissive temperature. 6.2 Insulation resistance Insulation resistance is 9.4 must be at least 5 M when tested by. 6.3 Power frequency withstand voltage Power frequency withstand voltage is 9.5 when tested by the need to endure it. 6.4 Rated short time withstand current Rated short time withstand current is 9.6 when tested by the following shall be compatible. a) cracks in the insulating material and harmful damage, deformation and damage from harmful and practical parts that make up the bus duct You should not occur.

Associate isolation (www.freebz.net) immediately below or note books Isolation www.bzfxw.com Associate isolation

(www.freebz.net) Fenxiang foreground Page 12 Eight C 8364:2008

b) Ingress Protection (IP Code), there is less variation in the reduce clearances and creepage distances are specified and they do not. c) There deformation prevents the insertion of the plug-in unit should not be.

d) 6.2 and 6.3 must retain the performance shown. 6.5 Horizontal intensity Straight horizontal intensity is 9.7 when tested by the following shall be compatible. a) if there is any damage to the joints and parts should. b) degree of protection, there is less variation in the reduce clearances and creepage distances are specified and they do not. c) 6.6 After the test the horizontal intensity, 6.3 must retain the performance shown. Vertical intensity Vertical strength of a facility in the vertical bus duct, 9.8 when tested by, shall comply with the following. a) cause damage or permanent deformation or practice harmful to the supporting parts of the conductor, the conductor must have moved. b) 6.2 and 6.3 must retain the performance shown. 6.7 6.7.1 Impact Strength Impact strength of the bus duct

Impact strength of the linear bus duct is 9.9 when tested by the damage or cracks on the practical parts of the harmful Without which, and the 6.2 and 6.3 shall hold the performance shown. 6.7.2 Impact strength of the outer case of the synthetic resin equipment for branch connections

Equipment for the branch connecting the outer case of synthetic resin, 9.9 when tested by the cracking and damage from harmful practical You should not occur. 6.8 Degree of protection against water for outdoor bus duct Degree of protection against water for outdoor bus duct, the following a) and b) must comply with. a) JIS C 0920 number 3 bus duct with the performance of the property referred to in the second degree of protection, a 9.10) by the line test When was no puddles can cause harmful in the duct, and 6.2 and 6.3 are shown in maintaining the performance Shall be. b) JIS C 0920 4-digit bus duct with the performance characteristics referred to in the second degree of protection, 9.10 b) the line test When was no puddles can cause harmful in the duct, and 6.2 and 6.3 are shown in maintaining the performance Shall be. 6.9 Fire Resistance of bus duct fire Refractory bus duct is 9.11 when tested by the table 4 shall comply with the performance.

Table 4 - fireproof
Measurement period Before heating During heating Heat just before the end T est 1 500 V AC voltage, with 1 minute withstand voltage test Insulation resistance test using a 500 V insulation tester Bear 50 M or higher Performance

600 V AC voltage applied to the test in the heat for 30 minutes Cause a short circuit Insulation resistance test using a 500 V insulation tester More than 0.1 M Bear

After completion of the heating 500 V AC voltage, with 1 minute withstand voltage test 1

6.10 Heat-cycle performance of the instrument and disconnect plug Heat-cycle performance of the instrument and disconnect plug-in 9.12 by detachable test, temperature rise due to rated current

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 13 (www.freebz.net) foreground

Nine C 8364:2008

Heat cycle test and when tested, the temperature rise at the end of 84 cycles, heat conduction, the following: a) And b) have at least 5 K higher than the value of should. a) the rated current through removable after the test, the temperature rise when the temperature is constant on each conductor of the branch. b) temperature rise caused by current flow measured at the end after 42 cycles. 6.11 for the branch opening and closing apparatus with an operating mechanism connecting the handle or cover Equipment for the branch connecting with the handle or cover operating mechanism is 9.13 when tested by parts of the equipment and paid Have caused a defect. 6.12ignition performance of the thermal performance and insulation resistance Parts made of insulating material used in bus duct, the temperature has been reached by the current overload of live parts or accident, Do not fire when the fire or flames shall not spread. Its performance is 9.14 tests performed by When the addition or not cause burning or glowing of the specimen, or the next a) and b) must comply with. a) a flame or glowing of the specimen, disappear within 30 seconds after removal of the glow-wire. b) does not ignite the wrapping tissue placed in the position of 200 mm below the specimen.

S even Structure 7.1 Structure of the bus duct Structure of the bus duct is 8.1 conductor 8.2 or coated with an insulating support, this 8.3 not containing duct, Shall comply with the following. a) steel duct is subjected to an appropriate rust preventive. b) the mutual connection of the conductors, in contact with the plug-in appliances and equipment connections and bolt is plated, M ust complete the electrical contact structure. However, less than 100 A rated current, and the material of the conductor In the case of copper or copper alloy may omit the plating of the conductor connection. c) Duct connecting portion can be securely connected to the mechanical and electrical, and you can check the inside of an opening or M ust be fitted with a bar. However, because of special shapes, if unavoidable structural clause 6 to If you meet the prescribed performance, may RiKenaku cover for inspection. d) degree of protection of the bus duct is, JIS C 0 920 numbers must be at least two characteristics defined in the first. e) Degree of protection against water for outdoor bus duct, JIS C 0.92 thousand numbers must be at least three characteristics defined in the second Not. In refractory bus duct, the duct that you need to block the flue is fitted with a fireproof shield Should be. g) Plug-in bus duct or branch of bus duct taps tapped into the plug socket, attach the cover Only must.

f)

h) The equipment for connecting a branch duct and attaching the ground wire, and be fitted with a ground terminal of sufficient capacity for They do not. i) j) Rated current value of the neutral conductor is greater than or equal to the rated current of the other conductors. Clearance and creepage distances are in Table 5 must be greater than or equal. However, the width of the groove on the surface of the boil sure insulator Depth, 1.5 mm less than the height of the ribs, or grooves or ribs should be there.

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 14 Fenxiang foreground (www.freebz.net)

T en C 8364:2008

Table 5 - M inimum creepage distance and minimum space


Rated voltage V Space 300 300 a) 600 Very different between them and the bare charge Between bare live parts and the non-metal parts 750 a) 1 000 1 200 1 500 Note
b) c) a) a)

Insulation distance mm Creeping


b) T en

Region

5.5

Eight

20 c)

14 14

32 40

a)

Shows the DC voltage. For indoor bus duct may be as 5.5 mm. For indoor bus duct may be a 10 mm.

k) how to determine the clearance and creepage distances, figure 1 shows.

Figure 1 - Determination of the clearance and creepage

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 15 (www.freebz.net) foreground

11 C 8364:2008

l) To distinguish the ground or phase, if you need to identify the conductor, the display clearly and legibly marked in a manner easily File. m) coating paint color when the duct is usually, JIS Z 8 721 to 5Y 7 / 1 to be prescribed. 7.2 Connection equipment for the branch structure Structure of the connection equipment for the branch, then you must comply. a) plug-in appliances such as clips, to ensure that contact with the conductor of the bus duct, or the conductor temperature rise The instrument is removable, it must change its retention. b) temperature limits of the contact clip instrument plug-in tables 3 through. c) When attached to the bus duct appliances for branch connections, shall maintain a specified degree of protection.

d) shall be structured for easy mounting and replacement of the fuse wire not. e) Paint colors when painting the outer case of the connection equipment for the branch, usually, JIS Z 8 721 to 5Y 7 / 1 to be prescribed.

Eight M aterial 8.1 Conductor The conductor cross sections can be energized by having a current rating of copper, copper alloy, aluminum or aluminum alloy Used. However, the bus duct is fire resistant, copper or copper alloy shall be used. See the material used for the conductor For example consider table 6 shows. Table 6 - Example of materials used for the conductor

T ype Copper Copper alloy Aluminum or Aluminum alloy

Standard JIS H 3140 under the provisions JIS H 3100 under the provisions JIS H 4000 and JIS H 4100 Positive Shall be defined

8.2

Insulator

a) an insulator covering the conductor of the bus duct insulated conductor the insulation out of acceptable temperature limits, the normal use in tub To withstand the rated short time withstand current and thermal conduction file. Limits of the permissible temperature of the insulation manufacturing Specified by the. Example of an insulator covering the conductor, table 7 shows. Insulator, the same type in different In those with acceptable temperature limits.

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 16 Fenxiang foreground (www.freebz.net)

12 C 8364:2008

Table 7 - Example of an insulator covering the conductor


T ype of insulator T here is a heat-resistant vinyl T here is a heat-resistant cross-linked polyethylene Silicon rubber Polyester Polypropylene Polycarbonate Epoxy Fluorine Resin Mica Cross-linked polyethylene Butyl rubber T ensile Strength MPa Over 9.8 Over 9.8 Over 3.9 Over 147.0 Over 29.4 Over 54.9 Over 17.6 Over 9.8 Over 29.4 Over 9.8 Over 3.9 Growth % Over 120 More than 350 More than 200 60 More than 250 60 More than 250 More than 350 300 + Breakdown strength kV / mm More than 30 40 More than 20 60 More than 30 Over 14 At least 12 At least 16 8 or more 40 More than 25

EP rubber Chloroprene Polyethylene Styrene-butadiene rubber Vinyl

Over 3.9 Over 5.9 Over 9.8 Over 4.9 Over 9.8

300 + More than 250 More than 350 300 + More than 100

More than 25 More than 20 More than 20 More than 30 More than 30

T est method for tensile strength and elongation, thre e thousand and five JIS C by. However, polyester, polypropylene Applications, polycarbonate and epoxy, JIS K 7 113 by. How to test the strength of the dielectric breakdown, JIS C 2 110 by.

b) The thickness of the insulation covering the conductor of the bus duct insulated conductors shall be not less than 0.5 mm. However, the following If you meet any of the conditions of isolation may be more than 0.38 mm thickness as that. 1) Flammability, electrical resistance, dimensional stability, tensile strength, elongation, weather resistance, tear resistance, permeability, abrasion and consider If it is determined to be applicable and considered. 2) covered with metal foil coated with an insulating material around the conductor (foil) in between, the AC power frequency of 50 Hz or 60 Hz 5 000 V for one minute when you add pressure, if it endured. c) Insulator supporting the conductor of the bus duct bare conductors, fire retardant insulation material in heat resistance and moisture resistance, good mechanical Shall be used having the strength. Outer case of the apparatus for connecting a branch duct and

8.3

a) the thickness of the material and equipment used on the box for connecting a branch duct and the force applied to the normal conditions of use in To bear. b) material used for the duct to withstand mechanical stress and rated short time withstand current horizontal forces due to the strength test without example Should be. c) Ducts used in the refractory material of the bus duct, must withstand a fire resistance test.

d) synthetic resin can be used for branch connections on the box of the instrument. Equipment used out of the box and for branch duct connections Example of the material, table 8 shows. Table 8 - Example of materials used for the outer case of the apparatus for connecting a branch duct and
T ype Steel Aluminum or Aluminum alloy JIS G 3131 to the provisions H 4,000 JIS -A1200P A1100P prescribed or H14-H14 Four thousand one hundred JIS H -A1200S A1100S prescribed or H112-H112 Standard

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 17 (www.freebz.net) foreground

13 C 8364:2008

Table 8 Example of the thickness of the duct when using a reference example of the materials shown in table 9 shows. Table 9 - Example of the thickness of the duct
In mm T he maximum width of the duct cross section Steel A aluminum or

150 Less than 300 over 150 500 or less than 300 700 less than 500 More than 700

1.0 (1.6) 1.4 (1.6) 1.6 (1.6) 2.0 (2.0)

Aluminum alloy 1.6 2.0 2.5 3.0 4.0

T he number in parentheses is applied to the bus duct fire.

Table 8 for the branch connecting hardware when using a synthetic resin material and the reference example shown in the Example of the thickness of the outer case of the table 10 Shown. Table 10 - Example of the thickness of the outer case of the appliance for branch connections
T he maximum surface area of one side of Steel the outer box cm
Two

Aluminum or Aluminum alloy mm

Plastics mm 2.0

mm 0.8 1.0 1.2 1.6

Below 500 Less than 1 000 500 Less than 1 000 2 000 More than 2 000

2.0 -

Nine Test method 9.1 General requirements The test, JIS Z 8 703 at room temperature as defined in (20 15 ) and humidity [relative humidity (65 20)%] of ventilation, the temperature Where it made no significant impact on the results of other tests should be. 9.2 Structural test Clause 7 and Clause 8 for verifying the requirements prescribed. 9.3 Temperature rise test Temperature rise test is carried out by the next. a) the form of bus duct temperature rise test, connect two or more of the same rated straight, more than 6 m length Placed horizontally to a height of 300 mm above the floor to close the ends, and then rated current through the exposure to wind The same figure two conductor bus duct and duct of the conductors and ducts and connections shown in the temperature, the temperature of the parts M easured using a thermocouple fixed and when. However, if the bus duct is insulated conductors, bus duct Conductor temperature measurement is made. Note: When a constant temperature and refers to the state falls below 1 K temperature change per hour.

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 18 Fenxiang foreground (www.freebz.net)

14 C 8364:2008 In mm

Figure 2 - Temperature measurement point

b) when the temperature rise test instruments and plug-ins combined with temperature rise test instrument plug-in bus duct Is attached to the bus duct plug-in to use state equipment, the rated current to the bus duct, the plug-in The instrument was built through the current rating of the equipment, the temperature of the conductor branches of each thermocouple to be constant when the temperature of the parts M easured using a pair. However, if the circuit breaker built-in equipment, if the circuit breaker during the test, the barrier Test, such as by connecting the power supply and load side without a breaker. c) M easurement of ambient temperature in the ambient temperature test, at a distance of about 1 m from one side of the duct along the length of the almost In the center, and center position and the height of the bus duct.

d) To reduce the test time may be over-current through the early stages. 9.4 Insulation resistance test Insulation resistance test, JIS C 1,302 for a 500 V DC insulation resistance meter as defined in, and between live parts and non-charge for each pole M easure the insulation resistance between the metal parts. 9.5 Power Frequency withstand voltage test

Commercial frequency withstand voltage test, the non-carrying metal parts and between live parts and between each pole and with frequency of 50 Hz or 60 Hz, Table 11 in the form of testing AC voltage shown in 1 minute in 1 second is applied to the delivery test.

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 19 (www.freebz.net) foreground

15 C 8364:2008

Table 11 - test voltage bus duct


V Unit Rated voltage U i (T he line). 300 600 750 1 000 1 500 Note
a) a) a)

T est voltage AC rms 2 000 2 500 3 000 3 500 3 500

T o apply only to DC.

Control circuits and auxiliary circuits, such as equipment for the branch connection, if it is not directly connected to the electrical bus duct and the Table 12 shows a test by test voltage. However, the table 12 is inappropriate electronic components tested in the test voltage If you have any, may be tested to exclude them.

Table 12 - test voltage control circuits and auxiliary circuits, such as appliances for branch connections
V Unit Rated voltage U i (T he line). T han 12 More than 12 to 60 More than 60 T est voltage AC rms 250 500 T wo i+1 000 U However, with a minimum of 1 500.

9.6

Rated short time withstand current test Connect two or more feeder bus duct at least 2 m, after a short end, mark a 50 Hz or 60 Hz AC voltage

Be added. Rated short time withstand current conduction, the second or 0.1 seconds with either one of the following test conditions, And the effective value of AC component Specify the time and power, perform the test. a) a power-on time 1 seconds of rated short time withstand current is the rms value of AC component (rms), and the maximum peak value that is Table 13 shows the effective value of n times or less.

Table 13 - Coefficient n of the standard value


Rated short time withstand current rms Power factor n

kA :5 More than 5 to 10 20 over 10 More than 20 to 50 More than 50 0.7 0.5 0.3 0.25 0.2 1.5 1.7 T wo 2.1 2.2

b) a power-on time 0.1 seconds of rated short time withstand current draws the maximum envelope of the AC component, from a short circuit occurred 1 / full amplitude after 1 / 2 cycle (2 ) And Two as of the effective value of the AC component, power factor, the table 14 to indicate to.

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 20 Fenxiang foreground (www.freebz.net)

16 C 8364:2008

Table 14 - Rated short time withstand current power factor


Rated short time withstand current A 5 000, 10 000 18 000, 25 000, 35 000, 50 000, 65 000, 85 000, 7 500 14 000 22 000 30 000, 42 000 60 000, 75 000, 90 000, 0.2 Lagging power factor 0.4 0.3 0.25

100 000 125 000 150 000 200 000

c)

Plug-in bus duct, one while wearing the appliance plug, perform the test.

d) RM S value of AC component in the three-phase test circuit, and the average of the effective value of the AC component of each phase. e) For three-phase three-wire bus duct is tested in three-phase circuit, three-phase four-wire bus duct for three-phase circuit In addition to testing, to test the single-phase circuits between adjacent conductors and the neutral conductor. Rated short time withstand current is the amount of electrical substation equipment, etc. are determined by the receiving system. The single transformer Rated short time withstand current examples of the standard when the feed table 15 shows. Table 15 - Example of the rated short time withstand current
Current rating of the bus duct A 60 100 200 300 400 600 800 22 000 0.25 Rated short time withstand currentLagging power factor A 5 000 7 500 14 000 18 000 0.3 0.4

1 000 1 200 1 500 1 600 2 000 2 500 3 000 3 500 4 000 4 500 5 000 5 500 6 000 90 000 60 000 0.2 42 000

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 21 (www.freebz.net) foreground

17 C 8364:2008

9.7

Horizontal strength test Horizontal strength test, Figure 3 is connected with two straight 3 m in length, that in 150 at 3 m wide and the center of the connections between

mm, placed on a fulcrum length of two dimensional channel steel exceeds the width of the bus duct in addition, of the bus duct connection Place the same materials used in the fulcrum on for five minutes put a weight equivalent to 4 m the mass of the bus duct minutes File. As for the more than 600 A rated current, put the weight corresponding to the mass of 60 kg more.
In mm

Figure 3 - Horizontal strength test 9.8 Vertical strength test The vertical strength test, using the condition one attached to a vertical bus duct shall be facility, the conductor of bus duct At the same time to hanging for 2 minutes each conductor corresponding to the mass of the body weight of 5-Phase 1 (Figure 4 reference).

Figure 4 - vertical strength test 9.9 Impact test Impact test, for the outer case of the connecting hardware for straight and branched synthetic resin, made by the next. a) test, the figure 5 performed using the apparatus shown in the test apparatus according thereto. Test equipment, when not compressed thickness At 40 1 mm difference, 450 kg / m density
Three

~ 550 kg / m

Three

Sponge placed on the rug of ethylene-propylene rubber

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 22 Fenxiang foreground (www.freebz.net)

18 C 8364:2008

Sure.

In mm

Figure 5 - Impact Test Equipment

b) hammer to fall to the next position, place the specimen, the vertical nature once the hammer from a height of each of the provisions Is dropped. Hammer mass and the height of the table 16 shows. 1) The impact force is applied to the top and sides of the bus straight duct (Figure 6 references.)

Figure 6 - Impact surface

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 23 (www.freebz.net) foreground

19 C 8364:2008

2) seems to be the weakest point of the outer case made of synthetic resin equipment for branch connections (excluding the knockout.) two places where Selected, the impact force. Table 16 - Impact test values
Classification Mass of the hammer kg Drop height mm

Bus duct

6.8

300 1 100 1

2.0 Equipment for the branch connecting the outer case of the synthetic resin

9.10 degree of protection for water tests for outdoor bus duct Degree of protection for water tests for outdoor bus duct, connecting two or more of the outdoor bus duct, 300 mm from the floor Placed horizontally on a height above, carried by the following. a) Protection Class II property number 3 bus duct having a second characteristic properties of the number 3 bus duct with a performance degree of protection Examination of the degree of protection against water, JIS C 0,920 in 14.2.3 [3 digit second characteristic degree of protection (to protect against water spray Ru) performed by the method prescribed in. b) The second characteristic numerals protection class 4 four-digit bus duct characteristics with the characteristics of the degree of protection with the performance of the bus duct Examination of the degree of protection against water, JIS C 0,920 in 14.2.4 [4 digit second characteristic degree of protection (protection against water splashes To protect) performed by the method prescribed in. 9.11 The bus duct fire test fire The bus duct fire test fire is carried out by the next. a) heating furnace heating furnace, and then use one to meet. 1) The structure in Figure 7 or it must be structured according to the structure shown. 2) The effective length of the furnace must be at least 2 m. 3) The furnace is heated by the state if not insert the specimen at least 30 minutes to maintain the temperature of 840 84 M ust be able.

In mm

Figure 7 - Example of specimen placed

b) placement of the specimen 1) The test bus duct is about 500 mm of length on each side leaving the furnace wall from the exterior, the junction in its center Not have to shield at both ends of the insulation materials. 2) The horizontal support of the bus duct test interval, the more than 1 m, placed at the center between the supporting connections.

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 24 Fenxiang foreground (www.freebz.net)

20 C 8364:2008

3) The temperature in the furnace, JIS C 1,602 with the performance of the thermocouple wire diameter of 0.75 or higher grade in the K-wire types of symbols defined in Use automatic recorder using a figure eight to measure the temperature at the position shown.
In mm

Figure 8 - Temperature measurement location c) Heating test, the specimen is inserted into the furnace, carried by the following. 1) before heating, after addition of 1 500 V for 1 minute or 60 Hz alternating voltage of 50 Hz, non-metal charge gap and charge for each unit M easure the insulation resistance between the parts. 2) Then, JIS A 1 304 according to the prescribed standard curve and heated for 30 minutes. 3) during heating, adding an AC voltage of 600 V 50 Hz or 60 Hz and continuously test bus duct. 4) before the end of the heating to stop the 600 V alternating voltage is applied, the insulation between live parts and metal parts and between each pole and the nonTo measure resistance. 5) After completion of heating, 1 500 V 50 Hz or 60 Hz AC voltage between the frequency of non-metal parts and between live parts of each pole Add 1 minute. 9.12 and the heat cycle test plug-in removable appliances The test is carried out by the following. a) Before performing the test temperature rise at rated current plug-load equipment, Table 17 and Figure 9 or removing. Table 17 - Number of fixtures removable plug-in
Rated current I A T o 63 T han 63 200 More than 200
n

Removable times 25 T en Five

Figure 9 - removable plug-in appliances

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 25 (www.freebz.net) foreground

21 C 8364:2008

b) rated current through the appliance plug and then, when the value of the constant temperature of the bifurcation using a thermocouple conductor M easured. After measuring the temperature, the current is interrupted, the specimen back to room temperature. c) Then, the next heat cycle test. The power is first measured the temperature rise to 2 hours after the start of energization of differences in temperature rise, the next Of 1) or 2) conduct tests. 1) that the temperature rise b) compared with the measured temperature rise in, if less than 5 K, 2 h rated current through The electricity, the current interruption for 2 hours. 2) that the temperature rise b) compared to the temperature rise was measured at 5 K greater than the rated current for 3 hours Energized, the current interruption for 3 hours to do. M easuring the temperature at the end of the cycle when power after 84 and after 42 cycles. 9.13 Test equipment connections for the branch opening and closing operation mechanism with the handle or cover For equipment for the branch connecting with the handle or cover operating mechanism, inJinai current line of action open to 1 000 times Window. The "open" and "closed" once have counted as actions, and its speed is about 10 times per minute. 9.14 Performance Test ignition resistance of the insulator and thermal performance Resistance and ignition performance test of the thermal performance of insulationbus duct is used for, JIS C 60695-2-10 and JIS C 60695-2-11 , according to the test. According to the usages of the insulation, the table 18 to 30 seconds pushing the temperatures shown in the glow-wire, observe the following: Record. a) Since I started pushing the edges, tissue wrapping is fired instantaneous position of 200 mm was placed beneath the specimen or Between time. b) Since I started pushing the edges, while pushing or after, the time until the flame is gone the moment c) The maximum height of any flame. However, at the start of combustion because it can generate a high flame, after the start of combustion of about Second is not considered. d) M ost of the material that is burning, you pass the test specimen to be removed and attached to the glow-wire . This will be specified in the test report. e) recording the burning of tissue placed in packaging of 200 mm below the specimen position. Table 18 - glow-wire temperature
Usages of the insulator Covering the conductor or insulator T o fix the conductor insulator Other external parts made of insulating material T emperature 960 15 650 15

9.15 Inspection and testing electrical wiring work

a) mechanical interlocking mechanism and external operations, such as equipment for the branch connection device to check the operation. b) Inspection and electrical wiring of an integrated circuit devices such as auxiliary equipment for the branch connection and to check the operation.

10 Inspection 10.1 format checks Inspection form, remove the specimen from a representative of each product, perform the following inspection items. a) ~ D) is the same test

Associate isolation (www.freebz.net) immediately below or note books Isolation isolation Associate www.bzfxw.com Page 26 Fenxiang foreground (www.freebz.net)

22 C 8364:2008

For test items, made by order. For other tests may be performed in different products. a) Structure b) temperature rise c) Insulation resistance d) Power Frequency withstand voltage e) Rated short time withstand current f) horizontal intensity g) Vertical intensity h) Impact strength i) j) Degree of protection against water for outdoor bus duct Fire Resistance of bus duct fire

k) and heat cycle performance plug-in removable appliances l) Switching equipment for connecting the branch with a knob or cover operating mechanism

m) and resistance to ignition performance of the thermal performance of insulation 10.2 Delivery Inspection Acceptance inspection is performed the following test items for each product. The order of these tests are optional. a) inspect the wiring and electrical behavior b) c) Insulation resistance Power frequency withstand voltage

11

I called the product

I called the product name, the material of the conductors and ducts, format, number of poles, rated voltage, rated current and rated short time withstand Currents. Feeder bus duct eg, aluminum, steel, indoor, insulated conductor, form a non-ventilated pole, 4, 600 V, 1 500 A, 60 000 A

12

View Conspicuous place of the product in a manner easily disappear, showing the name plate must be fitted with the following items.

a) bus duct, at least, to appear in the arterial system of the bus duct in one place. 1) The number and name of the product standards 2) The abbreviations of the duct or conductor and material 3) Format 4) The number of poles 5) Rated Voltage 6) Rated current 7) Rated short time withstand current 8) manufacturer's name 9) Date of manufacture 10) serial number

Associate isolation (www.freebz.net) immediately below or note books Associate isolation Page 27 (www.freebz.net) foreground

23 C 8364:2008

b) feed-box connectivity for branch and fixtures 1) The name of the device product name or number, and internal standards 2) The number of poles 3) Rated voltage (if applicable) 4) Rated current (if applicable) 5) Rated short time withstand current (if applicable) 6) The manufacturer's name 7) Date of manufacture 8) serial number

References JIS G 3131 hot rolled mild steel plate and steel JIS H 3100 Copper and copper alloy sheet and conditions JIS H 3140 Copper busbars JIS H 4000 Aluminium and aluminum alloy sheet and conditions JIS H 4100 extruded shapes in aluminum and aluminum alloys

Associate isolation (www.freebz.net) immediately below or note books

Вам также может понравиться