AR-727H

Users Guide

Version: 4.2

May 13, 2004

Function Menu
1.Add/Delete
1.Add - Card ID 2.Add - RF-learn 3.Suspend - Addr 4.Suspend ID # 5.Delete - Addr 6.Delete ID# 7.Recover - Addr 8.Recover ID # 9.Antipass Group

2.User Setting

1.Password 2.Access Mode 3.Extend Options 4.Single Floor 5.Multi Floors

3.Parameters(1)

1.Node ID 2.Auto Open Zone 3.Door Relay Tm 4.Door Close Tm 5.Alarm Relay Tm 6.Alarm Delay Tm 7.Arming Delay Tm 8.Arming PWD 9.Arming Pulse

4.Parameters(2)

1.Auto Relock 2.Egress(R.T.E.) 3.Attendance 4.Master Node 5.Force Open 6.Close & Stop 7.Anti-passback 8.Duress Code 9.Factory Reset 1.Language 2.Master Code 3.Master Range 4.Terminal Port 5.AR721R32 Port 6.Open TimeZone 7.Informations 8.Clock Setting 9.Control Mode 10.View Events

5.Tools

6.Quit 7.Quit & Arming

Table of Contents Page 1. 2. 3. Main Feature --------------------------------- 4 Control Mode --------------------------------- 5 Notice --------------------------------- 7 How to know card ID of user address?---------------------- 7 LCD display show card ID except user address (ex. 00005) when the user flash card? ---------------------- 8 How to know how many users in the system now?------- 8 How to start/suspend (auto open zone)?-------------------- 8 How to disarming? --------------------------------- 9 How to restore master code to the factory default?------ 9 How to reset all parameter to the factory default?-------- 9 How to set the time on AR-727H? ------------------------- 10 How to check the historical records?------------------------- 11 Front Panel & Functions --------------------------------- 12 Mode 4 / 8 / 9 --------------------------------- 14 5.1 Card Editing --------------------------------- 14 5.2 Access Mode --------------------------------- 15 5.3 Duress function --------------------------------- 18 5.4 Force on/off code --------------------------------- 19 Mode 6 --------------------------------- 21 6.1 Card editing --------------------------------- 21 6.2 Access mode --------------------------------- 21 Quick Guide --------------------------------- 22 Function description --------------------------------- 23 Special designed --------------------------------- 25 9.1 Connecting one AR-727H with 2 AR-661U for Anti-pass-back --------------------------------- 25 9.2 How AR-727 connects with a weigand reader (AR-721K, AR-721U, AR-661U) and to apply to anti-pass back --------------------------------- 26 9.3 How to set multi AR-727H connects with a net controller and to apply to anti-pass-back-------------- 26

4. 5.

7 8 9

10

11 12

13 14 15 16 17

9.4 How to setting the weigand reader (AR-721U, AR-721K, AR-661U) and AR-727H at the same net controller to apply to the anti-pass-back -------------------------------- 26 9.5 How to set that user arrive single floor or multi-floor28 9.6 How to set AR-401RO16 parameter------------------- 29 Installation -------------------------------- 31 10.1 Step -------------------------------- 31 10.2 Installation Notice -------------------------------- 32 Wiring -------------------------------- 34 Installation diagram -------------------------------- 36 12.1 Magnetic lock -------------------------------- 36 12.2 Electric bolt lock -------------------------------- 37 12.3 Electric strike -------------------------------- 38 12.4 Magnetic door contacts and alarm system ---------- 39 12.5 Wiegand reader -------------------------------- 40 12.6 Networking installation -------------------------------- 42 12.6.1 two set of AR-716EV2 parallel installation-- 42 12.6.2 AR-716EV2, AR-829E and AR-727H parallel installation-------------------------------- 43 12.7 Lift controller AR-401RO16 installation--------------- 44 12.8 AR-727H & AR-801CM & PC installation------------ 45 Troubleshooting -------------------------------- 46 Return of Products -------------------------------- 47 Warranty -------------------------------- 47 Transponder Record Table -------------------------------- 48 Specification -------------------------------- 49

1. Main Features
With waterproof, could be installed outside. Special feature for stand-alone use: Keep last 20 transactions Editable 2 time zone for door release purpose Controller needless anti-pass back:: AR-727H supports anti-pass back with its external reader. Master Cards range assignable. Clear and big LCD panel with 4 line messages. (128 * 64 graphic) One RS-485 Port supported for networking. Built-in one Door sensor and Arming on/off input. Support with keypad locks immd & all cards entrance allowance before cards editing finished. Support remote operation to relays on networking controller AR-716E / AR-727E via Force on/off code. Support with Auto-relock automatically and keypad locked if continuous wrong code inputted. Control mode, card capacity and card type assignable by user directly. Built-in a proximity reader, a external wiegand reader port and IC card reader (optional). Auto-discriminating between stand-alone & networking system, AR-727H could connect with controller AR-716E, AR-727E to have multi-door anti-pass back. Alarm function available. (Tamper, Force entrance, door open too long) Universal serial port supported for LED display, printer, lift controller, etc

2. Control Mode
AR-727H Card user Capacity Access Mode Anti-pass Back Control Mode in Networking Note Lift control WG32 32 stop 600 card users WG 16 WG32 32 stop 600 card user x WG32 Mode 4 Mode 8 Mode 9 MODE 4 Stand-alone 1000 Card only Card & PIN
User nbr. & PIN

MODE 6 Stand-alone 63200

MODE 8 Stand-alone 1000 Card only

MODE 9 Stand-alone 1000 Card only Card & PIN


User nbr. & PIN

Networking Depend on Controller Depend on Multi-door

Card only

Card & PIN PIN only

Single door

Single door

anti-pass back (16 doors) Mode 4 Or Mode 8 WG32 32 stop 600 card users

Now, 727H CPU version 3.7 was added a new control mode- Mode 9. Version 4.2 mode 9 directly connect to PC through AR-801CM converter for only Time and Attendance function.

Special feature for stand-alone use: (Version 3.7 UP) Under Mode 9, keep 480 transactions Not support Anti-pass-back and lift control. 1000 user cards capacity. Can connect to PC through AR-801CM for only Time and Attendance function. (Version 4.2 UP) Under Mode 9, keep 480 transactions 1000 user cards capacity. Not support Anti-pass-back, lift control, Time zone and Door group.

Please note transaction record just show normal access Message, without the message from invalid card and Push button. How to set Mode 4 ,Mode 6 , Mode 8 and Mode 9: 2 3 4 5 Step1: * + 1 enter the FUNCTION MENU 1:M4 2:M6 3:M8 6 + #

Step2: Tool / control mode (commandG 59) 4:M9, input Mode value. tags format1:EM 2:SOYAL, input card value.

Note: Changing control mode from Mode 6 to Mode 4 or from Mode 4 to Mode 6, it is necessary to delete all card user data first.

Depend on controller: For example, controller AR-716EV2 has 15,000 card users capacity. Lift control: For 600 card users, everyone could be assigned for single floor or multi-floor access.

3. Notice
Keep AR-727H away from the followings: Keep away from magnets or any magnetized items. Do not apply strong shock to 727H After flash master card and press F1 F2 F3 F4 or within 2 seconds can enter the FUNCTION MENU. Master Cards range assignable. Default value: user address 00000 00004. Each card has 10 digits code, including Site code (5 digits) and Card code (5 digits). Neither the Site Code nor the Card Code numbers can be 0. After card editing finished, Site Code and Card Code is not important anymore. System will require a USER ADDRESS instead. User can request to exit through the controlled door without using transponder (and without causing an alarm condition), by pressing an exit button. This will operate the door relay for the programmed door relay release time & stop alarm. How to know card ID of user address? (For example: which card ID do we want to know user address 00003) 2 3 4 5 6 + # Step1: * + 1 enter the FUNCTION MENU Step2: Add/Delete (command 1) Step3: Add / Card ID (command 1) Step4: Enter user address 00003, then you will see card ID. #

LCD display show card ID except user address (ex. 00005) when the user flash card? How to do? Step1: * + 1 2 3 4 5 6 + # enter the FUNCTION MENU Step2: Parameters (1) (command 3) Step3: Node ID (command 1) Step4: Set Node ID Step5: Then, the system will ask if show card ID? 1. No 2. WG 3. ABA 4. HEX Cur.: 1 Step6: If select 2. WG, for example as follows: User address 00005 for card ID 00020:25000 When user flash card, LCD display will show both user address 00005 and card ID 00020:25000. Note that CPU version must be at least 4.1 or up. How to know how many users in the system now? (Not including suspend card) Step1: * + 1 2 3 4 5 6 + # enter the FUNCTION MENU Step2: Tools (command 5) Step3: Informations (command 7) AR-727H Ver 3.4 in the system) How to start/suspend (auto open zone)? Step1: main manual Step2: tools (command 5) Step3: setting Open Time Zone (command 6) Step4: come back to main manual Step5: Parameters (1) (command 3) Step6: start Auto open zone function (command 2) Step7: Yes / No Note: The electronic lock would be locked until first one flash 8 Users: 00010 (There are already 10 users

card on the reader when the system enter auto open time zone. And electronic lock will be locked that sensor feels door closed when system exit auto open time zone. How to disarming? (1) User can be disarming by normal access mode once violating anti-pass-back resulting in alarm. (2) User can be disarming by valid card when alarm happen. 2 3 4 5 6 + # (3) * + 1 enter the FUNCTION MENU Step1: main manual Step2: Parameters (2) (command 4) Step3: Close Door Stop Alarm (command 6), then enter 1: YES. How to restore master code to the factory default (123456)? If the master code is forgotten it can be restored to the factory default (123456). Remove the AR-727H from the mounting plate, disconnect power, remove AR-727H CPU, install AR-727H-CLE CPU, and restore power about 10 seconds. Then disconnect power, remove AR-727H-LCE CPU, install AR-727H CPU, and restore power.

How to reset all parameter to the factory default? Step1: * + 1 2 3 4 5 enter the FUNCTION MENU Step2: Parameters(2) (command 4) Step3: Factory Reset (command 9) 6 + #

Then, LCD display will show Initial System message to reset all parameter to factory default. Note that CPU version must be at least 3.8 or up.

How to set the time on AR-727H? Step1: * + 1 2 3 4 5 6 + #

enter the FUNCTION MENU Step2: Tools (command 5) Step3: Clock Setting (command 8) Step4: Input Date&Time YyMmDdHhMmSs

10

How to check the historical records? (1) Press * + 1 2 3 4 enter the FUNCTION MENU. (2) (3)

Tools (Command 5) -> View Events (Command 0) Then, you will see the following message from LED screen:

Date

Time

Work Status : A: Duty On


A 01/16 15:45:25 001

B: Duty Off
FRI 00001

Serial Number

C: Overtime on D: Overtime off E: Break out F: Break RTN G: Go H: Return Week User Address

11

4. Front Panel & Functions

Arming (Green) Alarm (Red) Transmission: Receive (Green) Send (Red)

Input Indicator Reading (Green) OK (Green) Error (Red)

Keypad Press 1 time Duty on Duty off Overtime on Overtime off Attendance Press 2 times Break out Break RTN Go Return

F1 F2 F3 F4 Other:

Up Down Correct Esc Enter Press

+ Master Code (default : 123456, changeable) + -

to enter Function Menu Before card editing finished, the master could enter Function Menu and press Press + + F4 for all cards entrance allowance. to lock / unlock keypad immd.

12

Functions: 1. System will automatically exit from FUNCTION MENU, if no key or card entry is made within 30 seconds. 2. In FUNCTION MENU, LED [OK] will flash continuously and quickly. 3. In card access mode, flashing qualified card on the unit LED [OK] and LED [Reading] will light up, a beep sound and LCD panel message shown [OK], 4. Flashing unqualified card on the unit LED [ERROR] and LED [Reading] light up, two beeps sound and LCD panel message shown [Invalid Card!]. 5. 6. 7. Green LED [ARMING] light up in Arming On. Red LED [ALARM] lights up if any abnormal condition arisen. Continuous wrong PIN Code or Master Code will make keypad locked for 30 seconds, LED [Error] light up and LCD panel shown [keypad Locked]. 8. Once Alarm arisen, user must push exit button or flashing qualified card to release and return to standby state. 9. Transmission: Receive [Green] lights up when it receives message from PC or its external reader. Send [Red] lights up when AR-727H sends data to PC

13

5. Mode 4 / 8 / 9
Pre-explanation Arming PWD (4 digits)
Default value:1234 Could be setup via Function Menu (Function no. 38)

PIN Code (4 digits)


Could be setup via Function Menu (Function no. 21) Or, via 701 Client \ Setting \ User card

Duress Code (4 sets, 4 digits) Networking System:


Default value:1111 ; 2222 ; 3333 ; 4444 Changeable via 701 Server\ Setting \ 701 Configuration \ Duress Code

Stand-alone System:
Default value:4321 Changeable via Function Menu (Function no. 48)

Force on/off Code (4 sets, 4 digits) Networking System:


Default value:1111 ; 1111 ; 1111 ; 1111 Changeable via 701 Server\ Setting \ 701 Configuration \ Duress Code

5.1 Card Editing


After entering Function Mode, user uses following order to edit cards. Function Add Add Card ID RF learn Addr ID# Addr ID# Nbr. 11 12 15 16 17 18

Delete Delete Recover Recover

14

How to edit ten pcs sequential cards? ( Default access mode is Card only) Step1: * + 1 2 3 4 5 6 + #

enter the FUNCTION MENU Step2: Add/Delete (command 1) Step3: Add RF learn (command 2) Step4: Then, LCD display will show as follow: Please follow LCD display indicator to edit card Step5: InputStartAddr (0-00999) Enter 1, start from user no. 1 Step6: Tag Uints (pcs) Must be Sequence (1-00999) Enter 10 Step7: Close Tag Into RF Area Present the lowest card code of card to the unit.

5.2 Access Mode Users can select one of the following access modes 5.2.1 Card Only
Access the door by flashing card Open door & turn Arming on / off: Flash card, then press Arming PWD + F1 Not open door & turn arming on / off: Press + Arming PWD, then flash card

5.2.2

Card and PIN


Flash card, then press PIN Code -

Open door & turn Arming on / off: Flash card, press PIN code & - , then Arming PWD + F1 Not open door & turn arming on / off: Not available

15

How to set access mode of user is card and PIN? Step1: * + 1 2 3 4 5 6 + #

enter the FUNCTION MENU Step2: User Setting (command 2) Step3: Access Mode (command 2) Step4: Enter user number, Then, LCD display will show as follow: 1:Card 2:or PIN 3:& PIN 4:Pause Data: 1 Please select number 3: & PIN Step5: Return to main menu to set the password of user Step6: User Setting (command 2) Step7: Password (command 1) Step8: Enter user number Then, LCD display will show as follow: Input 4 Digit No. Range:0001~9999 Data:

5.2.3 User address and PIN (Mode 4) Press keypad: User address (5 digit), then PIN code & Open door & turn Arming on / off: User address, press PIN code & , then Arming PWD + F1

Not open door & turn arming on / off: Not available How to set access mode of user is card or PIN? Step1: * + 1 2 3 4 5 6 + #

enter the FUNCTION MENU Step2: User Setting (command 2) Step3: Access Mode (command 2) Step4: Enter user number, Then, LCD display will show as follow: 1:Card 2:or PIN 3:& PIN 4:Pause Data: 1

16

Please select number 2:or PIN Step5: Return to main menu to set the password of user Step6: User Setting (command 2) Step7: Password (command 1) Step8: Enter user number Then, LCD display will show as follow: Input 4 Digit No. Range:0001~9999 Data:

5.2.4 PIN only (Mode 8)


Same as Card Only Or, press keypad Door access: PIN code (4 digit) Open door & turn Arming on / off: PIN code & , then Arming PWD + F1 Not open door & turn arming on / off: Not available How to set access mode of user is PIN only? Step1: * + 1 2 3 4 5 6 + #

enter the FUNCTION MENU Step2: User Setting (command 2) Step3: Access Mode (command 2) Step4: Enter user number, Then, LCD display will show as follow: 1:Card 2:or PIN 3:& PIN 4:Pause Data: 1 Please select number 2:or PIN Step5: Return to main menu to set the password of user Step6: User Setting (command 2) Step7: Password (command 1) Step8: Enter user number, Then, LCD display will show as follow: Input 4 Digit No. Range:0001~9999 Data:

17

5.2.5 Change PIN code AR-727H connects with PC, running 701 client and set PIN code variable.
By user: Flash card, then press PIN code (4 digit) twice + By 701 client \ setting \ user card )

Not connecting with PC


Entering Function menu \ User setting \ Password

5.3 Duress function


This function could help users to send a message to the computer asking for help. Only available in networking state, running 701 Server and setting 4 sets of Duress code on PC. (Anyone of these 4 sets is workable.) This function is not available for CARD ONLY access mode and mode 8 directly 4-digit PIN. Access Mode Card Only Card and PIN Users addr. and PIN (Mode 4) PIN Only (Mode 8) Command Format Not available Flash card, then press Duress code & Press user address, then Duress code & Duress code

18

5.4 Force on/off Code (4 sets, 4 digits) Only workable in networking system, running 701 Server and setting 4 sets of Force code on PC. (Anyone of these 4 sets is workable.) User could press related code to turn on / off its connected equipment, diagram as below.
PC board of Controller AR-716EV2 / AR-727E
K1 K2 K3 K4 COM

RELAY K1

RELAY K2

RELAY RELAY COM K4 K3 DI.4 DI.3 JP3 D12 DI.2 JP4 D11 DI.1 D10 V12 D9 CN5

Relay K1 K2 K3 K4

Code 16 17 18 19

After access OK, press following order to turn on / off its connected equipment.
Access mode Card only Card + user code User no. + user code (Mode 4) User code only (Mode 8) ON/Off ON Off ON Off ON Off ON Off Flashing card Flashing card Flashing card Flashing card User no. User no. User code User code Force code Force code User code User code Order Code Code Force code Force code Code Code -

User code User code Force code Force code

Force code Force code Code Code -

Code Code

19

This function is good for force control television, air conditioning, audio, etc. by Relay-1, 2, 3, 4 on the multi-door networking controller. To avoid the conflict of the use of each controller relay, it is user responsibility to define each controller relay for one purpose use only.

20

6. Mode 6
6.1 Card Editing
Under Mode 6, the system built in card code from 00001 to 63200 itself, so user can only suspend or recover cards, not allowed to add or delete. The card which its card code is over than 63200 cant be used under Mode 6. After entering Function Mode, user uses following order to edit cards. Function Suspend Delete Addr Addr Nbr. 13 15

Recover Addr 17 How to start / stop using cards? Example: Start using cards, which card ID from 12345: 00001 to 12345: 00100, totally 100 cards in sequence. Step1: Entering Function Mode Step2: Recover -> Addr. (Order no. 17) Step3: Input Start Addr. -> 00001 Step4: Input End Addr.-> 00100 Succeed!

6.2 Access Mode


Under Mode 6, with different Arming PWD and Duress Code, users have different access mode as below.
Arming PWD Arming PWD Duress Code Duress Code Mode 6 Access Mode = Card only Card and =

Duress Code Duress Code only

Arming PWD not workable

21

7. Quick Guide (Function Menu)


Under Function Menu, you could just press the indicative nbr. to get into concerning set-up screen directly.
Function Add Add Card ID RF learn Addr ID # Nbr. 11 12 13 14 15 16 17 18 19 21 22 23 24 25 Language (English) Master Code Master Range Terminal Port AR721R32 Node Node ID Auto Open Zone Door Relay Tm Door Close Tm Alarm Relay Tm 31 32 33 34 35 Open Time Zone Information Clock Setting Control Mode View Events 511 52 53 54 55 56 57 58 59 50 Auto Relock Egress (R.T.E.) Attendance Master Node Force Open.. Password Access Mode Extend Options Single Floor Multi Floors Close & Stop Anti-pass back Duress Code 41 42 43 44 45 46 47 48 Function Alarm Relay Tm Arming Delay Tm Arming PWD Arming Pulse Nbr. 36 37 38 39

Suspend Suspend Delete Delete Recover Recover

Addr ID # Addr ID #

Antipass Group

22

8. Function description
24 Single Floor To setup user for single floor access (This function is only workable under the situation that AR-727H combined with AR-401RO16 and Control Mode is not Mode 6.) 25 Multi Floors To setup user for multi floors access (This function is only workable under the situation that AR-727H combined with AR-401RO16 and Control Mode is not Mode 6.) For example: User 0001 access to floor 17,
22, 31, 32 (Supposed no basement) 1. 2. 3. 4. 5. Entering Function Menu Press 25 Enter user address: 00001 Select range: 2 (for 17 32) 1: 01 16 0 -> stop 2: 17 32 1 -> Yes

1000010000000011 31 Node ID To setup Node ID (default: 001), range from 001 to 254 33 Door Relay Tm To setup how long the time will be that door close after a card flashing. Range: 0 ~ 600 (sec.) To set value 0 will make door keep opening, after 2
nd

card flashing, then

door close. (Default value: 7 sec.) 23

34

Door Close Tm

Extended time for door opening time. (Default value: 15 sec.)

35

Alarm Relay Tm

When abnormal condition arisen, how long the alarm will take place. Range: 0 ~ 600 (sec.) To set value 0 will make alarm relay keep on until disarming, then alarm relay off. (Default value: 7 sec.)

36

Alarm Delay Tm

The time between setting Alarm on and its real starting working time. (Default value: 1 sec.)

37

Arming Delay Tm

The time between setting Arming on and its real starting working time. Range: 0 ~ 600 (sec.) (Default value: 1 sec.)

39

Arming Pulse

Range: 0 ~ 2500 (sec.) TTT = 000: Latch (Toggle) (Default value: 1 sec.)

56

Open Time Zone

Set door open / close automatically.


Details: 1. 2. 3. Enter Function Menu Setup opening time first, Function no. 56 Auto Open Zone, Function no. 32 1: Yes 2: No

24

9. Special Design
9.1 AR-727H connected with 2 pcs of AR-661U long-range reader (Set one AR-661U being Exit reader and the other one being Entry reader) to apply to Anti-pass back. CPU version must be at least 3.2 or up. In stand-alone system, without connecting to any controller, AR-727H could integrate with 2 pcs of AR-661U to apply to anti-pass back. No special setting up necessary for AR-727H. Set one AR-661U with wiegand 34 bit format output and the other one with 38 bit. (Please refer to manual of AR-661U to have details.) Set card to have anti-pass back checking. (Order no. 19) This special design is especially suitable for car parking control. The special design is only workable with AR-661U, not available with AR-721U, AR-721K. (wiegand reader) Soyal Product AR-829E (CPU version at least 5.6) B AR-721H4 (CPU version at least 3.1V) also have this special design. The original function that AR-727H connecting with one wiegand reader (AR-661U, AR-721U, AR-721K) to apply to Anti-pass back is still available.

25

9.2

How AR-727 connects with a weigand reader (AR-721K, AR-721U, AR-661U) and to apply to anti-pass back? (1) (2) Main manu Input command:47A enable antipass1:YES in or out 1:in 2:NOA input1F 2: outA input default value(1 or 2 ).

attentionG if AR-727H would be in door and then the weigan reader would be out door. 9.3 How to set multi AR-727H connects with a net controller and to apply to anti-pass back? Both card and reader have to apply to anti-pass back. 1.card setting: step1:701 Client step2:user card edit step3:mark anti-pass back. . 2. reader setting (AR-727H): step1:main manu step2:command 47 step3: enable antipass1:YES in or out 1:in 9.4 2:NOA input1F 2: outA input default value(1 or 2 ).

How to setting the weigand reader (AR-721U, AR-721K, AR-661U) and AR-727H at the same net controller to apply to the anti-pass back? Both card and reader have to apply to anti-pass back Card setting: step1:701 Client step2:user card edit step3:mark anti-pass back.

26

Hardware setting: weigand reader (AR-721U, AR-721K): Set controller WG port as in or out if WG port is port 1 then would be in door and port 2 would be out door.

AR-716Ei PCB

Port 1 (Channel 17)

Port 2 (Channel 18)

Software setting: 701 Server. Step1: 701E Parameter Step2: door number Step3:mark [Door Number 17]or [Door Number 18] AR-727H setting: (1) main manu (2) command 47 enable anti-pass back 1:YES in or out 1:in would be our door. 2:NOA input1F 2: outA input default value(1 or 2)

Attention: if weigand reader would be in door then AR-727H

27

9.5 How to set that user arrive single floor or multi-floor? Either way to set user arrive single floor or multi-floor function. 1. Set by keypad for standalone installation (AR-727H+AR-829L485+AR-401RO16) Set user arrive single floor Step1: * + 1 2 3 4 5 enter the FUNCTION MENU Step2: User Setting (command 2) Step3: Single Floor (command 4) Set user arrive multi-floor + 1 2 3 4 5 enter the FUNCTION MENU Step2: User Setting (command 2) Step3: Single Floor (command 5) Step1: * explanation. 2. Set by software for networking installation (PC+AR-801CM+AR-716EV2+AR-727H+AR-829L485+ AR-401RO16) 6 + # 6 + #

Step4: Enter user address and set to access which one floor.

Step4: Please refer to function description to get detailed

28

Go to 701 Client \ User card edit \ User Access Floor Edit Select User. Select controller and reader node that manages that elevator. Select the card user can access which floor. Click Write to Controller. 9.6 How to set AR-401RO16 parameter? (ex. Card Release Tm) 2 3 4 5 6 Step1: * + 1 enter the FUNCTION MENU Step2: Tools (command 5) Step3: AR-721R32 Node (command 5) Tm (Default value: 7 sec.) Note: 1. AR-401RO16 has no push button input function, but you still enter push button input second in order to complete this

Step4: Input NodeID, Card Release Tm and P.B Release

29

command. Otherwise, this command will be failed. 2. They are one-way transmission is between AR-727H and AR-401RO16, so you will find that you change Card Release Tm from 7 sec. to 10 sec. But the parameter will be stay default value 7 sec. Dont worry about this matter. Actually, it is already changeable.

30

10. Installation
10.1 Steps: 1. 2. Use the screwdriver to screw the mounting plate on the wall. Pull cable ends through the access hole in the mounting plate. Connect plug 7 pins to socket CN1 Connect plug 4 pins to socket CN2 Connect plug 8 pins to socket CN3 Connect plug 3 pins to socket CN5 3. Attach AR-727H to the mounting plate and install screw (supplied) into the hole at the bottom with the Allen wrench (supplied). 4. Apply power. Green LED [POWER] will light up, a beep sound and LCD panel message will show up.

31

10.2 Installation Notice: 1. The distance between AR-727H and its auxiliary reader should be more than 50 cm and less than 12 meter. (Suggested value) AR-727H could be fixed inside the secure area as an exit and its auxiliary reader outside as an entrance reader, but not directly behind AR-727H. 2. The reading range of AR-727H will be up to15 cm. However, when AR-727H or its auxiliary reader is mounted directly on a metal surface, the reading distance decreases slightly. To reduce this effect, we suggest inserting a wood or plastic between the mounting surface and the unit. 3. 4. Exit Switch input must be a dry contact, without voltage present. AR-727H does not supply power to operate electric strike or magnetic locks, a separated power supply are required. Refer to strike or magnetic lock manufactures instructions, if common power supply is used for both AR-727H and electronic door lock; make sure to install the diode, which is provided with AR-727H. 5. Power supply should be at least 9 VDC to max. 24 VDC and at least 3W. DC power should be clean and filtered with no more than 0.3 VAC ripple (Peak to Peak). Do not run AC power in the same cable with DC power to AR-727H. While it is always preferable to use a separate power supply for AR-727H and strike.

32

6.

Run the following cables to the AR-727H location. Conduit is recommended to reduce the effects of EMI/RFI and for physical protection of the wires.

Cable Types and Distances Wire Application


From Power Supply From Locking Device and power supply or gate operator From external alarm systems Door Monitor Switch (for shunting) From Exit Button From Optional Auxiliary Reader 2-cond, 18-22 AWG 2-cond unshielded 22 AWG, plus a separate 4-cond, shielded 22-24 AWG cable 100 m 50 cm - 12 m 2-cond, 18-22 AWG 100 m

Cable Type
2-cond, 18-22 AWG 2-cond. See Mfrs Specifications

Description
n/a n/a

33

11. Wiring
Table 1 - Connector CN3 Color Coding Wire Application Door Relay Door/Alarm Relay Door Sensor Exit Switch Alarm Relay Power Wire 1 2 3 4 5 6 7 8 Color Blue White Purple White White Orange Purple Gray Thick Red Thick Black Description (N.O.)DC24V1Amp (N.C.)DC24V1Amp (COM)DC24V1Amp Negative Trigger Input Negative Trigger Input N.O. / N.C. Optional DC Power 12V DC Power 0V

Table 2 - Connector CN1 Color Coding Wire Application Networking Wire 1 2 3 Wiegand Color Thick Green Thick Blue Thin Blue Description RS-485(B-) RS-485(A+) Wiegand DAT:1 Input ABA Clock Input 4 Thin Green Wiegand DAT:0 Input ABA Data Input Buzzer 5 Pink Buzzer Output 5V/100mA, Low 6 LED Brown LED Green Output 5V/20mA, Max 7 Yellow LED Red Output 5V/20mA, Max

34

Table 3 - Connector CN5 Color Coding Wire Application Wire 1 Tamper Switch 2 3 Color Red Orange Yellow Description N.C. COM N.O.

Table 4 - Connector CN2 Color Coding Function Card Present Wire Color 1 2 3 Brown Yellow White Red White Description ON
OFF

Latch type

Serial Port Arming LED Arming Setting Switch

Serial output (Transistor open collector) (4800,N,8,1) Arming output (Active low)

Orange Card present output active low White (Transit output)


COM

White
Door Relay K1 NC NO

Purple White Blue White

Alarm Relay

K2

JP1

Gray

35

12. Installation diagram


12.1 Magnetic lock

The installation of 727H and magnetic lock


Power Supply 12VDC 2A
M. CO
ND

-G

. NO

2V +1

DC

Push Button DOOR EXIT

Red( +12VDC )

Black( - GND )

Purple

CN1 CN3

CN5

CN3

CN2

Purple White( N.C. )

White( COM. )

AR-727H

Lock( -GND )

-GND

Power Supply 12VDC 2A

Magnetic Lock
+12VDC Lock(+12VDC )

36

12.2 Electric bolt lock

The installation of 727H and electric bolt lock


Power Supply 12VDC 2A
M.

CO

-G

ND + V 12

DC

. NO

Black( - GND )

Push Button DOOR EXIT

Red( +12VDC )

Purple

CN1 CN3

CN5
Blue White( NO. )

CN3

CN2

White( COM. )

AR-727H

-G

ND

Power Supply 12VDC 2A

Lock( -GND ) +12VDC Lock(+12VDC )

Electric Bolt Lock

37

12.3 Electric strike

The installation of 727H and electric strike

CO

M.

-G

ND 12 + C VD

. NO

Black( - GND )

Push Button DOOR EXIT

Red( +12VDC )

Power Supply 12VDC 2A

Purple

CN1 CN3

CN5 CN2
Blue White( NO. )

White( COM. )

CN3

AR-727H
Lock( -GND ) -GND

Power Supply 12VDC 2A

+12VDC

Lock(+12VDC )

Electric Strike

38

12.4 Magnetic door contacts and alarm system

The installation of 727H, magnetic door contacts and alarm system


Power Supply 12VDC 2A

Alarm System

DC 2V +1 D GN -

Red( +12VDC )

Black( - GND )

N.C. N.O. COM. ALM. +12VDC

Red( +12VDC )

Black( - GND )

CN1 CN3

Gray( ALM. )

Orange( Door Sensor )

CN5

CN3

CN2

Magnetic Door Contacts( COM. )

+12VDC

- GND

AR-727H

Power Supply 12VDC 2A

Magnetic Door Contacts ( NC. )

Magnetic door contacts

39

The installation of 727H and auxiliary readers


Power Supply 12VDC 2A

12.5 Wiegand reader

721U
Black

1
Red

Red(+12VDC)
Blue

Green

Brown Purple

Yellow

40
1
Black Red

Black(-GND)
Yellow Brown Yellow Brown

CN3

727H

721K
CN1 CN2

Pink Green Blue

Pink Green Blue

CN1

661U

The installation of 727H and auxiliary readers 737U


Power Supply 12VDC 2A

Black

1
Red

41
Green
Blue

Red(+12VDC)
Brown Purple
Yellow

Black(-GND)
Yellow Brown Pink Green Blue

CN3

AR-727H
CN1

AR-737U

AR-727H and AR-716E/727E neworking installation


connect to PC

CN1

Red Green Blue

Black

Vin Vin BV+ BVGND

~~ ~~

CN2

727i CH2 CN3


CN1 CN3

AR-716E or
CH1 HOST JP1
CN5

Blue
CN1 CN3 CN5 CN2

Blue

12.6 Networking installation

Green

Green

JP2

AR-727E

CN2

CN1

Node: 009 To Node: 016

CN1

Red

12.6.1 two set of AR-716EV2 parallel installation

42
AR-727H
Blue
CN1 CN3 CN5 CN2

AR-727H

Black
CN1

Vin Vin BV+ BVGND

Power Supply 15VDC 2A

~~ ~~
Blue

CN2

Green

Green

727i CH2 CN3


CN1 CN3

AR-716E
CH1 HOST
CN5 CN2

or
JP1 JP2

AR-727E
Node: 001 To Node: 008
CN1

CN1

AR-727H

AR-727H

Next Controller

Note:1.The connecting disance between the 801cm and your pc can not be more than 2m.

AR-727H, AR-829E and 716EV2 networking installation


connect to PC Minimum 2 meter
u

CN1

Vin Vin BV+ BVGND

~~ ~~

CN2

AR-716EV2
727i CH2 CN3
CN1 CN3

or AR-727Ei
CH1 HOST JP1
CN5

Blue Blue
CN1 CN3 CN5 CN2

Green
CN1

Green

JP2

CN2

CN1

Red

12.6.2 AR-716EV2, AR-829E and AR-727H parallel installation

43
AR-727H

Node: 009 Node: 016


Blue Green

AR-727H

Black

Power supply 15VDC 2A


CN1 CN3

Blue

Green

CN5 CN2

CN1

CN2

CN2 CN1

AR-727H
Next Controller

AR-829E

Diagram of AR-727H and AR-401RO16

DC 12V

Power Supply 12VDC 2.4A

+
CN3 CN1

Black Red

Red

+ +

12.7 Lift controller AR-401RO16 installation

44
CN CN

Black

Blue

Yellow

Green

12.8 AR-727H & AR-801CM & PC installation

The installation of 727H, 801CM and PC


connect to PC
Minimum 2 meter
AR-801CM
Power Supply 12VDC 2A

To PC
Green

Power Supply 15VDC 2A


Blue Red Black
Red ( +12VDC ) Black ( - GND )

CO M. NO .

Purple

AR-727H
-G ND

Electric Bolt Lock

Lock ( -GND ) Lock (+12VDC ) +12VDC

White ( COM. )

CN1

Blue White ( NO. )

Green

Blue
CN1 CN3 CN5 CN2

Push Button DOOR EXIT

CN3

Power Supply 12VDC 2A

45

13. Troubleshooting
Questions No appearance Can not connect to PC Answer 1. Check power, if it is 9 24 VDC adaptor? 2. Check if the polarity is correct? 1. Check if Transmission LED light up? (Green / Red) 2. Check 701 Server, if set-up is correct? Please refer to 701 Server manual for details. 3. If connecting to PC via AR-801CM converter, check if the power (Green) light up? 1. Entering Function Menu 2. Press 11 3. Entering user address 1. Entering Function Menu 2. Press 57

How to find out Card ID with a user address? How many Cards exist in system?

46

14. Return of Products


Please contact the distributor who sold the unit. All service and repairs must be done through an authorized distributor.

15. Warranty
SOYAL warrants that the product(s) shall be free from manufacturing defects in materials and workmanship for a period of twelve (12) months from the date of delivery provided that the product was properly installed and used. The foregoing warranty shall not apply to defects resulting from abuse, misuse, accident, unauthorized alteration or repair, neglect, acts of God (such as floods, fire, etc.). SOYAL shall, at its option, either repair or replace product(s) which prove to be defective within the warranty period. SOYAL will replace any product found to be defective within the first three months of purchase provided said product was properly installed and used. Distributor agrees to insure the product or assume the risk of loss or damage in transit to prepay shipping charges and to use the original shipping container or equivalent. Customers shall seek assistance from the distributor who sold you product(s). Repaired or replaced product(s) are warranted for ninety (90) days from the date of repair or replacement, or for the remainder of the original products warranty period, whichever is longer. Note: Dont tear a paster such as S/N: 727H Warranty B-0307-000107 on the PCB board, it is SOYAL warranty.

47

16. Transponder Record Table


Be sure to record the user number, the user name, the card ID number (site code: card code), and the user code and keep this information in a secure place. A black user log form has been included for purpose. Do not write on this form; use it as a photocopy master. User Add. User Name Site code: Card code PIN code

Programmed by: Company Name: Company Address: City: Other Information:

Date:

48

17. Specification
Voltage Current RF Frequency Reading range User Interface Networking External reader port Door Relay 10 24 VDC <3W (250 mA @ 12VDC)

125 KHz 10 18 cm 16 metallic texture keypadsB beepB 128*64 dot LCD panel and 8 LED indicator. RS 485, 9600,N,8,1 Suitable for all WGB ABA readerF 125KB 13.56M (Mifare) or 2.4G reader 2A / 12V N.O. / N.C. / COM

0.1 ~ 600 sec. / Latch type 2A / 12V N.O. / N.C. / Jumper selectable

Alarm Relay DI input

0 ~ 600 sec. Egress button Door sensor Arming switch

Transistor output Arming Tamper switch Serial Port Material

Duress

Card sensor N.C. COM.^

Limit Switch] N.O.

Supported for AR-721R32B LED displayB Relay boardB Printer etc.] 4800,N,8,1^ ABS

Dimensions(mm) 127 (L) * 91 (W) * 46 (H) Net Weight 250 gram

49