Вы находитесь на странице: 1из 38

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA

Instruction Manual DeviceNet

Drives Solutions
www.danfoss.com/drives

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s

Contents Introduction to Danfoss VLT series and DeviceNet


...................... Product Overview ................................................................................................... Product and Environment ....................................................................................... Overall Function ..................................................................................................... Network ................................................................................................................. User Profile ............................................................................................................. Data Communication Interface ............................................................................... Initialization of VLT frequency converter Interface .................................................... Network Variable Handling ..................................................................................... Error Handling ........................................................................................................ Overall Function ..................................................................................................... 2 2 2 2 2 2 2 2 3 3 3 5 5 5 5 5 6 6 7 7 7 7 8 9 10 11 11 11 12 12 12 13 13 13 15 17 18 19 20 20 20 26 27

Technical Data

.................................................................................................. Identity Object ........................................................................................................ Message Router ..................................................................................................... General Information ................................................................................................ Network Power Supply ........................................................................................... Cable Lengths ........................................................................................................ Cable Specifications ............................................................................................... Cable Cross Section ............................................................................................... Connection of the Cable Screen ............................................................................. Earth Connection ................................................................................................... DeviceNet Connection ............................................................................................ User Interface ......................................................................................................... Understanding Module Configuration Switches ...................................................... EMC Precautions ................................................................................................... Setting the DeviceNet Node Address ..................................................................... Switch Settings for DeviceNet Node Addressing .................................................... Setting the Baud Rate ............................................................................................ VLT Response Time ............................................................................................... General Purpose Discrete I/O ................................................................................. I/O Assembly Instances ..........................................................................................

Fieldbus Profile

................................................................................................ Fieldbus Profile ....................................................................................................... Control Word .......................................................................................................... Status Word ........................................................................................................... Control Word under VLT standard .......................................................................... Status Word under VLT standard ............................................................................ Control Word and Status Word under Instance 20/70 ............................................ .................................................................................................... Quick Setup ........................................................................................................... Special Attention .................................................................................................... Warning and Alarm Messages ................................................................................ Factory Settings .....................................................................................................

Programming

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Product Overview s Product and Environment The DeviceNet Option Card is an interface between the DeviceNet serial communication bus and the VLT frequency converter from Danfoss. The option card will function as an integrated part of the drive. DeviceNet is a distributed control network. The DeviceNet protocol is embedded in the controller option card and is a communication protocol conforming to the Open DeviceNet Vendor Association (ODVA) standard. The option card allows DeviceNet compatible controllers, sensors, and network management tools to control, monitor, and supervise the VLT frequency converter. The option is designed to the DeviceNet System Protocol for Vendors as a slave device. s Network The VLT frequency converter will function as a slave on the DeviceNet network. All addressing and linking to nodes is done at installation time by a network manager tool. The network installer and the network management master have a significant influence on how the node functions on the network. A DeviceNet network can support up to 64 nodes.

s User Profile The end-user is a network manager programmer or a controller who see the DeviceNet control card as a transparent bridge to the VLT frequency converter. Control and supervision of the VLT frequency converter will still be possible through the standard parameter set.

s Data Communication Interface s Overall Function No direct data communication interface (e.g. via a A DeviceNet compatible device has the ability to serial port) other than the DeviceNet interface and the perform the following operations with the VLT frequency VLT frequency converter interface is considered. converter over the DeviceNet network: 1. Control speed references and send drive control commands. 2. Monitor the status of the drive, access alarm and warning messages, and monitor drive and motor information. 3. Upload and download drive settings, configure drives, and also perform the operations defined in 1 and 2. Therefore, the level of control and flexibility of the VLT frequency converter over the network depends on the capabilities built into the controlling device. The application program has the following functions: 1. Support interger parameters through the dual ported RAM. 2. Manipulate the dual ported RAM parameters to interface with the CAN. 3. Monitor network activity "watchdog" function to determine Master Slave communication continuity.

s Initialization of VLT frequency converter Interface The VLT frequency converter interface is initialized in three phases. The first two phases are initiated and controlled by the VLT which will write commands to the option card through the dual port RAM.

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


Phase 1: Is the initialization of the communication system. During this phase the option card must respond correctly to the VLT frequency converter initialization command or else the VLT will not function and display a "No Option Init" message. Phase 2: Is the interface watchdog function performed by the option card as the first operational action. After completion of this phase, data can be passed between the VLT frequency converter and the option card through the command channel in the dual port RAM. Phase 3: The VLT frequency converter will write to the Initialization Channel of the dual port RAM which will set the displacement values of the various channels (Control Channel, Status Channel, Command Channel 1, Command Channel 2, Command Channel 3, Warning Channel, and Spontan Channel), and the DeviceNet option card software will read these displacements and return a response to the VLT frequency converter notifying that the initialization was successful or an error was obtained in the process. 1. The node has been disconnected from the network 2. A network management tool has the Option Card go Off-line 3. A hardware fault on the DeviceNet Option Card PCB prevents reliable operation By withholding the watchdog message, the VLT frequency converter can detect a "Bus Time-out" and enter secure, pre-defined state. For recoverable errors such as [1] and [2] the option card shall re-send the watchdog message when the fault or condition has disappeared such as after re-connection of the node to the network. For unrecoverable errors such as [3] the application program shall permit logging of network errors without resetting or restarting the microprocessor. This will send information to a network management tool that will allow appropriate actions to be taken. The only way to recover from a serious error is to re-initialize the VLT frequency converter DeviceNet option card by cycling power. In case of serious VLT frequency converter fault, the DeviceNet processor shall hold the CAN chip reset, thereby disabling any communication to the node until the VLT frequency converter has been re-initialized.

During operation (after initialization) the dual port RAM interface is supervised by a watch-dog in the VLT frequency converter. The VLT frequency converter will be kept "alive" by cyclic writing to a channel in the dual port RAM by the watch-dog handler of the option card. s Overall Function DeviceNet is a low-level network that standardizes communications between industrial devices (sensors, limit switches) and high level devices (controllers). s Network Variable Handling The communication network can be peer to peer or The parameter access network variable is a structure master/slave. DeviceNet uses CAN technology for containing parameter number, data, value, and a Media Access Control and Physical Signaling and it function code containing a read or write command. supports up to 64 nodes. DeviceNet also defines The application program shall receive the data, device profiles for devices belonging to specific classes. validate the data, convert the data to the format of For other devices, a custom class must be defined in the VLT frequency converter, process the read or order to make it DeviceNet compatible. This further write of the parameter, then send the information enhances the interchangeability and interoperability of back in an output network variable of the same the network. Each node on the network has its own structure. This output variable would contain the unique media access control identifier (MAC ID) to parameter number, error code information in the event distinguish it on the network. The MAC ID is stored of an exception, and parameter value. in the header of the message which is split into four different message groups. However, DeviceNet only makes use of three message groups keeping the fourth s Error Handling one for future use. If two nodes attempt to get control The option card will stop sending a watchdog signal of the network bus simultaneously, the CAN protocol to the VLT frequency converter when:

MG.50.H4.22 - VLT is a registered Danfoss trademark

Introduction to Danfoss VLT series and DeviceNet

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


resolves the issue by arbitration. A dominant bit (0) will win arbitration over a recessive bit (1). For the VLT frequency converter, the option card will be slave node on the DeviceNet network. The option card will be a message server that will request and set parameters in the VLT via a dual ported RAM interface. The option card has an embedded CAN controller that will screen all network messages with a Mask and Match register. This feature allows the option card to filter out any unwanted messages from the network. The option card will receive group 2 and group 3 messages. Group 2 messages allows the option card to use the predefined Master/Slave connection set which identifies a use for all group 2 message identifiers. The ability to receive Group 3 messages allows the option card to also be an Unconnected Explicit Message Manager (UCMM) with the UCMM request and response message identifier. Explicit message connections are unconditionally point-to-point. Point-to-point connections exist between two devices only.

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Technical Data s Identity Object This object is used to provide identification and general information about the device. This object is required by all DeviceNet products. This object requires no class attributes. Its instance attributes are the following: s Network Power Supply The DeviceNet option is an optically isolated node, where transceiver power is provided by the network. External network power supply requirements are: - 11 - 25 VDC - 70 mA draw per VLT 5000 DeviceNet node

Vendor Device Type Product Code Revision - Major, Minor Status Serial Number Product Name

97 2 Depends of the Drive Depends of option

VLT 5000

s Message Router The Message Router object provides a messaging connection point through which a Client may address a service to any object class or instance residing in the physical device. This object requires no class attributes. Its instance attributes are the following: 1. Object List - Number of Classes

s General Information Parameter 502 = "BUS". Otherwise terminals 12 and 27 of the control card must be connected, before motor start. In parameters 502-508 it is possible to define how to gate the control commands from the DeviceNet with the equivalent control commands of the digital inputs.

MG.50.H4.22 - VLT is a registered Danfoss trademark

Technical Data

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Cable Lengths

Baud Rate

Max. total cable length [m] Maximum

Drop Length Cumulative 156 meters (512 ft.) 78 meters (256 ft.) 39 meters (128 ft.)

125k baud 250k baud 500k baud

500 meters (1640 ft.) 250 meters (820 ft.) 100 meters (328 ft.)

6 meters (20 ft.) for one drop

s Cable Specifications

Physical Characteristics Two shielded pairs Overall braid shield Drain wire Outside diameter Jacket insulation * Jacket marking * Electrical Characteristics DRC (braid + tape + drain) Applicable Environmental Characteristics Agency Certifications (U.S. and Canada) Bend radius - installation / fixed Operating ambient temperature Storage temperature Pull tension
* Other types of jacket insulation are allowable provided that internal construction and electrical charactersitics adhere to this specification.

Specification Common axis with drain wire in center 65% coverage 36 AWG Cu braid. (individually tinned) # 18 (19 x 30 AWG) Copper (individually tinned) 0.475 0.015 inches (round), roundness - radius delta to be within 15% of 0.5 O.D.* 0.040 inches minimum Vendor Name & Part # 1 Pr 18 and 1 Pr 15 AWG shielded, additional markings are acceptable Specification 1.75 Ohms/1000 ft. (nom. @ 20C) Specification NEC (UL) type, CL2/CL3 (min.) 20 x diameter / 7 x diameter -20 to + 60C @ 8 amps; de-rate current linearly to zero @ 80C -40 to + 85C 190 Ibs max

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Cable Cross Section in a DeviceNet network it can be necessary to use additional potential equalizing cables, connecting the individual stations to the same earth potential.

s DeviceNet Connection It is essential that the bus line be terminated properly. A mismatch of impedance may result in reflections on the line that will corrupt data transmission. The DeviceNet Option Card is provided with a pluggable screw connector. By using a pluggable screw connector as a splice between two trunk lines, removal of devices will not sever the network. Strain relief, if required, must be provided by the developer. In current installations of this type of connector, the strain relief is attached to the product. NOTE Wires should not be installed while the network is active. This will prevent problems such as shorting the network supply or disrupting communications.

s Connection of the Cable Screen The screen of the DeviceNet cable must always be connected to ground at both ends, that means the screen must be connected to ground in all stations connected to the DeviceNet network. It is very important to have a low impedance ground connection of the screen, also at high frequencies. This can be obtained by connecting the surface of the screen to ground, for example by means of a cable clamp or a conductive cable gland. VLT frequency converter Series are provided with different clamps and brackets to enable a proper ground connection of the DeviceNet cable screen. The screen connection is shown in the drawing.

s Earth Connection It is important that all stations connected to the DeviceNet network are connected to the same earth potential. The earth connection must have a low HF (high frequency) impedance. This can be achieved by connecting a large surface area of the cabinet to ground, for example by mounting the VLT frequency converter on a conductive rear plate. Especially when having long distances between the stations

MG.50.H4.22 - VLT is a registered Danfoss trademark

Technical Data

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s User Interface The DeviceNet option card contains two bi-color (green/red) LEDs for each connector hookup port, to indicate the state of the device and network, respectively. For the device status LED: 1. when the LED is off, the device is off 2. when the LED is green, the device is operational 3. When the LED is flashing green, the device is in standby 4. when the LED is flashing red, the device detects a minor fault 5. when the LED is red, the device detects an unrecoverable fault 6. when the LED is flashing red/green, the device is self testing For the network status LED: 1. when the LED is off, the network is non-powered/not online 2. when the LED is flashing green, the network is online but not connected 3. when the LED is green, the network is online and connected 4. when the LED is flashing red, the network has a connection time-out 5. when the LED is red, the network has a critical link failure. No further direct user interface is considered No further direct user interface is considered.

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Understanding Module Configuration Switches The DeviceNet Communication modules DIP switch settings determine: DeviceNet node address DeviceNet baud rate When you make changes to the switch settings, use a pointed instrument such as a ball point pen. DO NOT use a pencil because damage may occur Unpredictable operation may occur if you fail to check connections and DIP switch settings for compatibility with your application. Unpredictable operation may result in death, personal injury, and equipment damage. Hazard of injury or equipment damage may occur due to unintended or incorrect machine motion. When a system is configured for the first time, the motor must be disconnected from the machine or process during initial system testing. NOTE When setting the Communication Modules addressing Dip Switches, you must ensure that each serial device on the network has a unique address. Also, all devices connected to the network must be set at the same baud rate.

MG.50.H4.22 - VLT is a registered Danfoss trademark

Technical Data

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s EMC Precautions EMC precautions The following EMC precautions are recommended to obtain interference free operation of the DeviceNet network. Additional information on EMC can be found in the VLT 5000 Series Instruction Manual. NOTE Relevant national and local regulations, for example regarding protective earth connection, must be observed The DeviceNet communication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable to the other. Normally a distance of 8 inches (200 mm) is sufficient, but it is generally recommended to keep the greatest possible distance between the cables, especially where cables are running in parallel over long distances. If the DeviceNet cable has to cross a motor and brake resistor cable they must cross each other at an angle of 90.

10

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Setting the DeviceNet Node Address Dip switches 6 through 1 set the modules node address using binary addressing.

s Switch Settings for DeviceNet Node Addressing Follow these steps to set the DeviceNet node address: 1. Refer to the table below for the switch settings of a specific address.

2. Using your finger or a pointed object, slide switches 1 through 6 to the appropriate ON/OFF positions.

DeviceNet Address 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47

48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

s Setting the Baud Rate Dip switches 7 and 8 set the baud rate at which the Communication Module communicates on the network. The factory default setting is 125K BPS.

Switch Settings for DeviceNet Module Baud Rate:

Baud Rate 125 250 500 125 kBPS kBPS kBPS kBPS

Switch Setting 7 0 1 0 1

Switch Setting 8 0 0 1 1

MG.50.H4.22 - VLT is a registered Danfoss trademark

11

Technical Data

Switch Settings 1 6 000000 100000 010000 110000 001000 101000 011000 111000 000100 100100 010100 110100 001100 101100 011100 111100

DeviceNet Address

Switch Settings 1 6 000010 100010 010010 110010 001010 101010 011010 111010 000110 100110 010110 110110 001110 101110 011110 111110

DeviceNet Address

Switch Settings 1 6 000001 100001 010001 110001 001001 101001 011001 111001 000101 100101 010101 110101 001101 101101 011101 111101

DeviceNet Address

Switch Settings 1 6 000011 100011 010011 110011 001011 101011 011011 111011 000111 100111 010111 110111 001111 101111 011111 111111

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s VLT Response Time The update time via the DeviceNet connection can be divided into two parts: 1. The communication time, which is the time it takes to transmit data from the master to the slave (VLT with DeviceNet option). 2. The internal update time, which is the time it takes to transmit data between the VLT 5000 control card and the DeviceNet option card. in use. More data or lower transmission speed will increase the communication time. The internal update time (tint) depends on the type of data in question as there are different channels for the data transfer where time critical data e.g. control word has highest priority. The internal update time for the different types of data are stated below.

Data Control word/Main reference (part of PPO) Status word/Actual output frequency (part of PPO) Parameter read via PCD-part of PPO Parameter write via PCD-part of PPO Parameter read/write via explicite message

Update time, tint 2 msec 2 msec 2 msec 83 msec 22 msec

Communication time (tcom) depends on the actual transmission speed (baudrate) and the type of master

s General Purpose Discrete I/O The General Purpose Discrete I/O device I/O assemblies consist of: five predefined input assemblies with single status bits one productspecific input assembly with a single status bit

five predefine input assemblies with multiple status bits one productspecific input assembly with multiple status bits five predefined output assemblies one productspecific output assembly

s I/O Assembly Instances The I/O Assembly Instance definitions in this section define the format of the "data" attribute (attribute 3) for I/O Assembly Instances. I/O Assemblies support a hierarchy of motor control devices. The device hierarchy includes motor starters, soft starters, AC and DC drives, and servo drives. Assembly Instances are numbered within the hierarchy so that each device type is assigned a range of Assembly Instance

numbers, with higher functionality devices supporting higher instance numbers. Devices in the hierarchy can choose to support instance numbers that are lower than theirs in the hierarchy. For example an AC drive may choose to support some I/O Assemblies in the starter profile to make it easier to interchange starters and drives within the system.

Parameter 904 PP03 PP01 PP02 PP04

Decimal 20 100 101 102 CTW CTW CTW 915.1

WRITE SPEED RPM REF REF 915.2

Decimal 70 150 151 152 STW STW STW 916.1

READ AC REF MAV MAV 916.2

915.1 915.3

915.2 915.4

916.1 916.3

916.2 916.4

12

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Fieldbus Profile s Control Word Control Word as per Profidrive standard (parameter 512 = Fieldbus Profile). The control word is used for transmitting commands from a master (e.g. a PC) to a slave (VLT frequency converter). Bit 02. OFF3/ON3: Quick-stop, which uses the ramp time set in parameter 212. Bit 02 = "0" leads to a quick stop and leads to output relay 01 or 04 being activated, when the output frequency is 0 Hz, provided Relay 123 has been selected in parameter 323 or 326. Bit 02 = "1" means that the adjustable frequency drive is able to start, provided the other conditions for starting are fulfilled. Bit 03, Coasting/enable: Coasting stop. Bit 03 = "0" leads to a stop. Bit 03 = "1" means that the adjustable frequency drive is able to stop, provided the other conditions for starting are fulfilled. Note: in parameter 502 the choice is made as to how bit 03 is to be combined (gated) with the corresponding function in the digital inputs. Bit 04, Quick-stop/ramp: Quick-stop which uses the ramp time in parameter 212. Bit 04 = "0" leads to a quick- stop. Bit 04 = "1" means that the adjustable frequency drive is able to start, provided the other conditions for starting are fulfilled. Note: In parameter 503 the choice is made as to how dit o4 is to be combined (gated) with the corresponding function on the digital inputs. Bit 05, Freeze output frequency/ramp enable: Bit 05 = "0" means that the given output frequency is maintained even if the reference is changed. Bit 05 = "1" means that the adjustable frequency drive is again able to regulate, and the given reference is followed. Bit 06, Ramp stop/start: An ordinary ramp stop that uses the ramp time in parameters 207/208 or 209/210; in addition, output relay 01 or 04 will be activated when the output frequency is ) Hz, provided Relay 123 has been selected in parameter 323 or 326. Bit 06 = "0" leads to a stop. Bit 06 = 1" means the adjustable frequency drive is able to start, provided the other conditions for starting are fulfilled. In parameter 505 the choice is made as to how bit 06 is to be combined (gated) with the corresponding function on the digital inputs. Bit 07, No function/reset: Reset of trip. Bit 07 = "0" means that there is no reset. Bit 07 = "1" means that a trip is reset.

Bit 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

Reversing

Bit 00, OFF1/ON1: An ordinary ramp stop which uses the ramp time in parameters 207/208 or 209/210. Bit 00 = "0" leads to a stop and leads to output relay 01 or 04 being activated, the output frequency is 0 Hz, provided Relay 123 has been selected in parameter 323 or 326. Bit 00 = "1" means that the adjustable frequency drive will be able to start if the other conditions for starting have been fulfilled. Bit 01, OFF2/ON2: Coasting stop. Bit 01 = "0" leads to a coasting stop and leads to output relay 01 or 04 being activated, when the output frequency is 0 Hz, provided Relay 123 has been selected in parameter 323 or 326. Bit 01 = "1" means that the adjustable frequency drive is able to start provided the other conditions for starting are fulfilled.

MG.50.H4.22 - VLT is a registered Danfoss trademark

13

Fieldbus Profile

Bit = 0 OFF 1 OFF 2 OFF 3 Motor coasting Quick stop Freeze output frequency Ramp stop No function Jog 1 OFF Jog 2 OFF Data not valid No function No function Choice of Setup (lsb) Choice of Setup (msb) No function

Bit =1 ON 1 ON 2 ON 3 Enable Ramp Ramp enable Start Reset ON ON Valid Slow down Catch

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


Bit 08, Jog 1 OFF/ON: Activation of pre-programmed speed in parameter 509 (Bus Jog 1). JOG 1 is only possible when Bit 04 = "0" and bit 00-03 = "1". Bit 09, Jog 2 OFF/ON: Activation of pre-programmed speed in parameter 510 (Bus Jog 2). JOG 2 is only possible when Bit 04 = "0" and bits 00-03 = "1". If both JOG 1 and JOG 2 are activated (bits 08 and 09 = "1"), JOG 1 has the higher priority, which means that the speed programmed in parameter 509 will be used. Bit 10, Data not valid/valid: Used for telling VLT 5000 whether the control word is to be used or ignored. Bit 10 = "0" means that the control word is ignored. Bit 10 = "1" means that the control word is used. This function is relevant because the control word is always contained in the telegram, regardless of the type of telegram used, i.e. it is possible to disconnect the control word if it is not to be used in connection with updating or reading of parameters. Bit 11, No function/slow down: Used for reducing the speed reference by the value in parameter 219. Bit 11 = "0" means that there is no change of the reference. Bit 11 = "1" means that the reference is reduced. Bit 12, No function/catch-up: Used for increasing the speed reference by the value of parameter 219. Bit 12 = "0" means that the reference is increased. If both slow down and catch-up are activated (bits 11 and 12 = "1"), slow down has the higher priority, i.e. the speed reference is reduced. Bits 13/14, Choice of Setup: Bits 13 and 14 are used for choosing among the four menu Setups in accordance with: NOTE Parameter 507 is used for choosing how bits 13/14 are to be combined (gated) with the corresponding function on the digital inputs. Bit 15, No function/reversing: Reversing of the direction of rotation of the motor. Bit 15 = "0" leads to no reversing, bit 15 = "1" leads to reversing. Note that as a point of departure reversing has been selected as Digital in parameter 506. Bit 15 only leads to reversing if bus, logical or or logical and has been selected (logical and, however, only together with terminal 19). NOTE Unless otherwise mentioned, the control word bit is combined (gated) with the corresponding function on the digital inputs as a logical "or" function.

Setup 1 2 3 4

Bit 14 0 0 1 1

Bit 13 0 1 0 1

This function is only possible if Multi-Setups have been selected in parameter 004.

14

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Status Word Status Word (according to Profidrive standard (parameter 512 = Fieldbus Profile). The status word is used for informing the master (e.g. a PC) of the condition of a slave (VLT frequency converter). Bit 03, No fault/trip: Bit 03 = "0" means that VLT 5000 Series is not in a fault condition. Bit 03 = "1" means that VLT 5000 Series has tripped and needs a reset signal in order to run. Bit 04, ON2/OFF2: Bit 04 ="0" means that control word bit 01 ="1". Bit 04 ="1" means that control word bit 01 ="0". Bit 05, ON3/OFF3: Bit 05 ="0" means that control word bit 02 ="1". Bit 05 -"1" means that control word bit 02 ="0".

Bit 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

Bit 00, Control not ready/ready: Bit 00 = "0" means that bit 00, 01 or 02 of the control word is "0" (OFF1, OFF2 or OFF3), or that the adjustable frequency drive has tripped. Bit 00 = "1" means that the adjustable frequency drive is ready, but that there is not necessarily any supply to the power component (in case of external 24 V supply to the controls). Bit 01, VLT not ready/ready: Same meaning as bit 00; however, there is also a supply to the mains component, and the adjustable frequency drive is ready to run when it receives the necessary start signals. Bit 02, Coasting/enable: Bit 02 = "0" means that the control word bit 00, 02 or 03 is "0" (OFF1, OFF2, OFF3 or Coasting), or the VLT 5000 Series unit has tripped. Bit 02 = "1" means that the control word bits 00, 01, 02 or 03 are "1" and that VLT 5000 Series has not tripped.

Bit 09, Local control/Bus control: Bit 09 = "0" means that VLT 5000 Series has been stopped by means of the stop key on the control panel, or that Local operation has been selected in parameter 002. Bit 09 = "1" means that it is possible to control the adjustable frequency drive via the serial port. Bit 10, Out of operating range/Freq. limit OK: Bit 10 = "0" means that the output frequency is out of the range set in parameter 225 (Warning: Low frequency) and parameter 226 (Warning: High frequency). Bit 10 = "1" means that the output frequency lies within the mentioned range. Bit 11, Does not run/runs: Bit 11 = "0" means that the motor is not running. Bit 11 = "1" means that VLT 5000 Series has a start signal of that the output frequency is greater than 0 Hz.

MG.50.H4.22 - VLT is a registered Danfoss trademark

15

Fieldbus Profile

Bit = 0 Control not ready VLT not ready Motor coasting NO fault ON 2 ON 3 Start enable No warning Speed - reference Local control Out of operating range Not running VLT OK Voltage OK Torque OK Timer OK

Bit =1 Ready Ready Enable Trip OFF 2 OFF 3 Start disable Warning Speed = ref. Bus control Freq. limit OK Running Stalls, auto-start Above limit Above limit Above limit

Bit 06, Start enable/start disable: Bit 06 is always "0" if Danfoss has been selected in parameter 512. If Profidrive has been selected in parameter 512, bit 06 will be "1" after reset of a trip, after activation of OFF2 or OFF3 and after connection of mains voltage. Start disable is reset, setting control word bit 00 to "0" and bits 01, 02 and 10 to "1". Bit 07, No warning/warning: Bit 07 = "0" means that there is no unusual situation. Bit 07 = "1" means that an abnormal condition has arisen for the VLT 5000 Series. All warnings described in the VLT 5000 instruction manual will set bit 07 to "1". Bit 08, Speed ref/speed. = ref.: Bit 08 = "0" means that the actual motor speed is different from the speed reference set. This can be the case while the speed is ramped up/down during start/stop. Bit 08 = "1" means that the present motor speed equals the speed reference set.

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


Bit 12, VLT OK/stalling, autostart: Bit 12 = "0" means that there is no temporary overtemperature on the inverter. Bit 12 = 1" means that the inverter has stopped because of overtemperature, but that the unit has not tripped and will continue, once the overtemperature stops. Bit 13, Voltage OK/above limit: Bit 13 = "0" means that the voltage limits of VLT 5000 Series have not been exceeded. Bit 13 = "1" means that the DC voltage of the VLT 5000 Series intermediate circuit is too low or too high. Bit 14, Torque OK/above limit: Bit 14 = "0" means that the motor current is lower than the torque limit selected in parameter 221. Bit 14 = "1" means that the torque limit in parameter 221 has been exceeded. Bit 15, Timers OK/above limit: Bit 15 = "0" means that the timers for the motor thermal protection and VLT thermal protection, respectively, have not exceeded 100%. Bit 15 = "1" means that one of the timers has exceeded 100%.

16

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


Control Word under VLT standard (parameter 512 = FC Profile). The control word is used for sending commands from a master (e.g. a PC) to a slave (VLT frequency converter). Bit 02, DC Brake: Bit 02 = "0" leads to DC braking and stop. Braking current and duration are set in parameters 125 and 126. Bit 02 = "1" leads to ramping. Bit 08, Activation of Jog speed in parameter 213: Bit 08 = "0": Jog speed not activated. Bit 08 = "1" means that the motor is running at Jog speed. Bit 09, Choice of ramp 1/2: Bit 09 = "0" means that ramp 1 is active (parameters 207/208). Bit 09 = "1" means that ramp 2 (parameters 209/210) is active. Bit 11, Relay 01: Bit 11 = "0": Relay 01 not activated. Bit 11 = 1: Relay 01 activated, provided Control word bit has been chosen in parameter 323. Bit 12, Relay 04: Bit 12 = "0": Relay 04 has not been activated. Bit 12 = "1": Relay 04 has been activated, provided Control word bit has been chosen in parameter 326. See the description of other bits under control word for Profidrive standard. NOTE Unless otherwise mentioned, the control word bit is combined (gated) with the corresponding function on the digital inputs as a logical "or" function.

Bit 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

Bit 00/01: Bits 00 and 01 are used for choosing among the four pre-programmed references (parameters 215-218) in accordance with the following table:

Preset ref. 1 2 3 4

Parameter 215 216 217 218

Bit 01 0 0 1 1

Bit 00 0 1 0 1

NOTE Parameter 508 is where to choose the way bits 1/12 are to be combined (gated) with the corresponding function on the digital inputs.

MG.50.H4.22 - VLT is a registered Danfoss trademark

17

Fieldbus Profile

Bit = 0 Preset reference choice Isb Preset reference choice msb DC brake Coasting Quick stop Hold Ramp stop No function No function Ramp 1 Data not valid No function No function Choice of Setup (lsb) Choice of Setup (msb) No function

Bit =1 ON 1 ON 2 Ramp Enable Ramp Ramp enable Start Reset Jog Ramp 2 Valid Relay 01 activated Relay 04 activated

Reversing

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


Status Word under VLT standard (parameter 512 = FC Profile). The status word is used for informing the master (e.g. a PC) about the condition of the slave (VLT frequency converter).

Bus reference value:

Bit 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

Bit = 0 Control not ready VLT not ready Coasting NO fault Reserved Reserved Reserved No warning Speed - reference Local control Out of range Not running VLT OK Voltage OK Torque OK Timer OK

Bit =1 Ready Ready Enable Trip

The frequency reference value is transmitted to the adjustable frequency drive in the form of a 16-bit word. The value is transmitted as a whole number (0-32767). 16384 (4000 Hex) corresponds to 100%. (Negative figures are formatted by means of 2s complement.) The bus reference has the following format: Parameter 203 = "0"

"refMIN - ref MAX" 0-16384 (4000 Hex) ~ 0-100% ~ ref MIN - refMAX Warning Speed = ref. Bus control Frequency OK Running Stalling, auto-start Above limit Above limit Above limit
Parameter 203 = "1"

- refMIN - + ref - 16384 (...Hex) - + 16384 (4000 Hex) ~ - 1000 - + 100% ~ - refMAX - + refMAX

MAX

Actual output frequency

Bit 00, Control not ready/ready: Bit 00 = "0" means that the adjustable frequency drive has tripped. Bit 00 = "1" means that the adjustable frequency drive controls are ready, but the power component is not necessarily receiving any power supply (in case of external 24 V supply to controls). Bit 02, Coasting/enable: Bit 02 = "0" means that the control word bit 03 is "0" (Coasting) or that VLT 5000 Series has tripped. Bit 02 = "1" means that control word bit 03 is "1" and that VLT 5000 Series has not tripped. See the description of other bits under status word for the Profidrive standard. The value of the actual output frequency of the adjustable frequency drive is transmitted in the form of a 16-bit word. The value is transmitted as a whole number (0-32767). 16384 (4000 Hex) corresponds to 100%. (Negative figures are formed by means of 2s complement).

18

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Control Word and Status Word under Instance 20/70 Set parameter 904 PPO type 1(900) to choose
Instance 20 Byte 0 0 Bit 7 Bit 6 Bit 5

Instance 20/70. The control word in Instance 20 is defined as following:


Bit 4 Bit 3 Bit 2 Fault Reset Bit 1 Bit 0 Run Fwd

1 2 3 Speed reference (low byte) Speed reference (high byte)

Bit 0, Run Fwd: Bit 0 = "0" means that the VLT frequency converter has a stop command. Bit 0 = "1" leads to a start command and the VLT frequency converter will start to run the motor.

Bit 2, Fault Reset Bit 0 = "0" means that there is no reset of a trip. Bit 0 = "1" means that a trip is reset. The Speed reference in Instance 20 is defined as a word. See description by Bus reference Value. The status word in Instance 70 is defined as following:

Instance 70

Byte 0 0

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2 Running

Bit 1

Bit 0 Fault

1 2 3 Speed actual value (low byte) Speed actual value (high byte)

Bit 0,Fault: Bit 0 = "0" means that there is no fault on the VLT frequency converter. Bit 0 = "1" means that there is a fault on the VLT frequency converter.

The Speed Actual value in Instance 70 is defined as a word. See description by Actual Output frequency

MG.50.H4.22 - VLT is a registered Danfoss trademark

19

Fieldbus Profile

Bit 2, Running Bit 0 = "0" means that there is no active start command. Bit 0 = "1" means that there is an active start command.

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Quick Setup For how to program the ordinary VLT parameters refer to the VLT 5000 Series Instruction Manual. Communication is established by setting the following parameters: Parameter 904: Select the PPO type to be applied. Parameter 918: Readout of the actual address of the DeviceNet option via dip switch. Parameter 801: Readout the transmission speed in bit/sec. The default setting is 125 kbaud, which means the VLT automatically detects the transmission speed of the connected bus. If you set a fixed value it must be the same as that selected in the master. Function: This parameter displays the actual Baud rate of the devicenet option.

803 Time after bus error (BUS TIME OUT) Value: 1 - 99 sec 1 sec

804 Response after bus error (TIME OUT FUNCT.) Value: Off (OFF) Freeze output frequency (FREEZE OUTPUT) Stop with auto restart (STOP) Output frequency = JOG frequency (JOGGING) Output frequency = Max. freq. (MAX SPEED) Stop with trip (STOP AND TRIP) Control without DeviceNet ( NO DEVICENET CONTROL) Select set up 4 (SELECT SETUP 4) [0] [1] [ 2] [3] [4] [ 5] [6] [ 7]

s Special Attention Special attention must be given to the following parameters described in the VLT 5000 Series Instruction Manual: 002: If operation site = Local, then control via DeviceNet is not possible. 502-508: Selection of how to gate DeviceNet control commands with control commands on the digital inputs of the control card. 512: Selects DeviceNet profile. 515-538: Data read out parameters that can be used to read various actual data from the VLT, as for example actual status on the analog and digital inputs of the control card thus using these as inputs to the master.

Function: The time out counter is triggered at the first reception of a valid control word i.e. bit 10 = ok. 1. CTW is not updated within the specified time 2. Parameter 805 = "bit 10 = 0 time out" and bit 10 = "0" The VLT remains in the timeout state until one of the following four conditions occurs: 1. Valid control word (Bit 10 = ok) is received and reset (Bus, terminals or local control panel) is activated (reset is only necessary when the time out function Stop w/trip is selected) control via DeviceNet is resumed with the actual control word 2. Parameter 002 = Local Local control via local control panel is enabled. Normal control via 3. Parameter 928 = Disabled terminals and RS485 is enabled. 4. Parameter 804 = Off control via DeviceNet is resumed, with the control word used last being taken. NOTE The time out counter is reset and needs to be triggered by a valid control word before a new timeout can be activated

801 Baud rate selection (BAUD RATE SELECT) Value: 125 kBaud (125 KBAUD) 250 kBaud (250 KBAUD) 500 kBaud (500 KBAUD) [20] [21] [22]

= factory setting. () = display text [] = value for use in communication via serial communication port 20
MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


Description of choice: Save output frequency: Save (freeze) the output frequency until communication resumes. Stop with auto restart: Stop with automatic restart on resumption of communication. Output frequency = Fixed speed frequency: Motor runs with fixed speed frequency until resumption of communication. Output frequency = max. frequency: Motor runs with the maximum frequency until resumption of communication. Stop with trip: Motor has stopped, a reset is necessary for a restart, see explanation above. Control without DeviceNet: Control via DeviceNet is inactive; control is possible via the terminals and/or the RS 485 standard interface until communication resumes. Selection parameter setup 4: Parameter setup 4 is selected in parameter 004; the settings of parameter setup 4 are used. Parameter 004 is not reset to the original value upon resumption of communication. Without function: Bit 10 is ignored, i.e. the control word and speed reference value are always valid.

805 Function control word bit 10 (BIT 10 FUNCTION) Value: Without function (NO FUNCTION) Bit 10 = 1 CTW active CTW ACTIVE) (BIT 10 = 1 CTW active Bit 10 = 0 CTW ACTIVE) (BIT 10 = 0 Bit 10 = 0 Timeout (BIT 10 = 0 [ 0] [1] [2] [3]

Description of choice:

= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.H4.22 - VLT is a registered Danfoss trademark

CTW active: If bit 10 = 0, the control Bit 10 = 1 word and speed reference value are ignored. CTW active: If bit 10 = 1, the control Bit 10 = 0 word and speed reference value are ignored. If all bits of the control word are 0, the VLT will switch to coasting in response hereto. Bit 10 = 0 Timeout: If bit 10 = 0, the timeout function selected in parameter 804 is activated.

21

Programming

Function: This is sometimes necessary since some masters set all bits to 0 in different error situations. In these cases it makes sense to change the function of bit 10 so that the command to stop (coasting) goes to the VLT if all bits are 0.

TIMEOUT )

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


904 PPO selection (PPO TYPE SELECT) Value: PPO type 1 (PPO PPO type 2 (PPO PPO type 3 (PPO PPO type 4 (PPO TYPE TYPE TYPE TYPE 1) 2) 3) 4) [900 [901 [902 [903 ] ] ] ] Note that subindex 3 - 8 are having no function.

916 PCD read configuration (PCD CONFIG READ) Value: Sub index 1 (PCD 1) Sub index 2 (PCD 2) [Parameter number] [Parameter number]

Function: The choice of PPO type has to match the input and output data of the master. Description of choice: 900 = PPO type 1 (100/150): This PPO type has a 16 bit control word and a 16 bit reference to controlling the VLT. The status word and the actual speed value will also be returned as 16 bit value. See Fieldbus profile. 901 = PPO type 2 (101/151): The same structure as in PPO type 1, but with 2 additional free selectable process data. 902 = PPO type 3 (20/70): This profile fulfill the Instance 20/70 profile. See Control word under Instance 20/70. 903 = PPO type 4 (102/152): 4 free selectable process data that can be chosen in parameter 915/916 PCD configuration.

Function: Different parameters can be assigned to PCD 1-2 if instance 101/151 is selected in parameter 904 PPO Selection. The values in PCD 1-2 will be read from the selected parameters in the form of data values. Description of choice: The sequence of subindices corresponds to the sequence of the PCD in the PPO, i.e.subindex 1 = PCD 1, subindex 2 = PCD 2 etc. Each subindex may contain the number of any VLT parameter. Note that subindex 3 - 8 are having no function.

918 User address (STATION ADDRESS) Value: 0 - 63 63

915 PCD write configuration (PCD CONFIG WRITE) Value: Sub index 1 (PCD 1) Sub index 2 (PCD 2) [Parameter number] [Parameter number]

Function: Readout of actual address of the devicenet option.

927 PCV operating authority (PARAMETER EDIT) Value: Without DeviceNet (DISABLE) With DeviceNet (ENABLE) [ 0] [1 ]

Function: Different parameters can be assigned to PCD 1-2 if instance 101/151 is selected in parameter 904 PPO Selection. The values in PCD 1-2 will be written to the selected parameters in the form of data values. Description of choice: The sequence of the subindixes corresponds to the sequence of the PCD in the PPO, i.e. subindex 1 = PCD 1, subindex 2 = PCD 2 etc. Each subindex may contain the number of any VLT parameter.

Function: The parameter channel PCV may be blocked so that the modification of parameters through this channel is not possible. Access through the standard RS 485 interface is still possible. NOTE When parameters 927 and 928 are deactivated, the "Warning 34" in the display of the VLT will also be suppressed.

= factory setting. () = display text [] = value for use in communication via serial communication port 22
MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


Description of choice: Without DeviceNet: Parameter processing through the DeviceNet is not active. With DeviceNet: Parameter processing through the DeviceNet is active

Bit 0 1 2 3 4 5 6 7
[ 0] [1 ]

LSB

In the following cases, bit is = "1" Connection to the master is not OK FDL (field bus data security layer) is not OK Command to erase data received Current value not updated FIFO overflow of the spontaneous messages DeviceNet ASIC does not transmit Initialization of the DeviceNet option is not OK Not used Not used Not used Not used Not used Not used Not used Not used

928 Control authority (PROCESS CONTROL) Value: Without DeviceNet (DISABLE) With DeviceNet (ENABLE)

Function: The process control (adjustment of control word and speed reference value and of the following variable PCD) can be blocked. Control through the control card terminals is still possible via the terminals, depending on how the parameters 502-508 have been set. Access through the standard RS 485 is also still possible. NOTE When parameters 927 and 928 are deactivated, the "Warning 34" in the display of the VLT will also be suppressed. Description of choice: Without DeviceNet: Process control through the DeviceNet is not active. With DeviceNet: Process control through the DeviceNet is active NOTE The motor may start without advance warning when parameter 928 is being changed and start commands are present.

8 9 10 11 12 13 14 15

MSB

967 Control Word (CONTROL WORD) Value: 16 bit binary code Function: Parameter 967 is dedicated to sending a control word to the VLT frequency converter when using explicit message. This parameter is not available via LCP.

953 Warning messages (WARNING PARAM.) Value: Read only (16 bit binary code) No control panel access Function: A bit is assigned to every warning (see the following list)

= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.H4.22 - VLT is a registered Danfoss trademark

23

Programming

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


968 Status Word (STATUS WORD) Value: Read only (16 bit binary code) Function: Parameter 968 is dedicated to read the status word from the VLT frequency converter when using explicit message. This parameter is not available via LCP. value returns to Not active after all parameter values have been saved. Save edit setup: All parameter setups of the setup being processed are saved in EEPROM. The value returns to Not active after all parameter values have been saved. Save all setups: All parameter setups in all setups are saved in EEPROM. The value returns to Not active after all parameter values have been saved. Store Always: Each parameter write request will automatically be stored in EEPROM. NOTE Please note that continous writing via explicit message may damage the EEPROM. [0] [ 1] [ 2] [ 3] [ 4] [ 5]

970 Parameter setup selection (EDIT SETUP SELECT) Value: Factory setting () Parameter setup 1 (SETUP 1) Parameter setup 2 (SETUP 2) Parameter setup 3 (SETUP 3) Parameter setup 4 (SETUP 4) Active set up (ACTIVE SETUP) Function: Like parameter 005 (described in the product manual for the VLT 2800 series).

980982 Defined parameters (DEFINED PARAM.) Value: Read only Function: The three parameters contain a list of all parameters defined in the VLT. Each of the three parameters can be read as an array by means of a explicit message. Each parameter contains up to 116 elements (parameter numbers). The number of parameters that are in use (980, 981 and 982) depends on the respective VLT configuration.

971 Save date values (STORE DATA VALUE) Value: Not active (OFF) Save active setup (STORE ACTIVE SETUP) Save edit setup (STORE EDIT SETUP) Save all setups (STORE ALL SETUPS) Store Always (STORE ALWAYS) [0] [1] [ 2] [ 3] [ 4]

When a 0 is issued as a parameter number, the list ends.

990992 Modified parameters (MODIFI. PARAM.) Value: Read only Function: The three parameters contain a list of all parameters that have been changed from the factory setting. Every one of the three parameters can be read as an array with the help of the explicit read service. The subindices begin with 1 and follow the sequence of the parameter numbers. Each parameter contains up to 116 elements (parameter numbers). The number of parameters that are in use (990, 991 and 992)

Function: Parameter values modified through DeviceNet are only saved in RAM, i.e. the modifications are lost in the event of a power failure. This parameter is used to activate a function by means of which all parameter values are saved in EEPROM, preserving them even in the case of a power failure. Description of choice: Not active: The function is not active. Save active setup: All parameter setups of the active setup are saved in EEPROM. The

= factory setting. () = display text [] = value for use in communication via serial communication port 24
MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


depends on how many parameters have been modified in comparison with the factory setting. Pure read parameters (Read only), such as data output parameters, are not logged as modified even if they are changing. When a 0 is issued as a parameter number, the list ends.

= factory setting. () = display text [] = value for use in communication via serial communication port
MG.50.H4.22 - VLT is a registered Danfoss trademark

25

Programming

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Warning and Alarm Messages There is a clear distinction between alarms and warnings. In the case of an alarm, The VLT will enter a fault condition. After the cause for the alarm has been cleared, the master will have to acknowledge the alarm message for the VLT to start operating again. A warning on the other hand may come when a warning condition appears, and disappear when conditions return to normal without interfering with the process.

s Warnings Any warning within the VLT is represented by a single bit within a warning word. A warning word is always an action parameter. Bit status FALSE [0] means no warning, while bit status TRUE [1] means warning. To each bit and each bit status there is a corresponding text string. In addition to the warning word message the master will also be notified through a change of bit 7 in the Status Word.

s Alarms Following an Alarm message the VLT will enter Fault condition. Only after the fault has been alleviated and the master has acknowledged the alarm message by setting bit 3 in the Control Word, can the VLT resume operation. Any warning within the VLT is represented by a single bit within a warning word. A warning word is always an action parameter. Bit status FALSE [0] means no fault, while bit status TRUE [1] means fault. To each bit and each bit status there is a corresponding text string.

= factory setting. () = display text [] = value for use in communication via serial communication port 26
MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Factory Settings
PNU # 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018 019 Parameter description La ng u ag e L o c a l/ re m o t e c o n t rol L o c a l re f e re n c e Ac tiv e s et up P ro g r a m m in g s e tu p Co p y in g o f se tu p s LC P c o py D i s p l a y s c a l i n g o f m o t o r f re q u e n c y Dis p la y l inie 2 D is p la y li ne 1. 1 D is p la y li ne 1. 2 D is p la y li ne 1. 3 L o c a l c o n tro l/ c o n f ig u ra Lo c a l st o p Lo ca l jo g L o c a l re v e r s in g L o c a l re s e t o f t r i p Lo ck fo r dat a c ha ng e O p erat in g s t at e at p o w e r-u p , lo c al c o n t ro l Factory setting English Remote control 000.000 Setup 1 Active setup No copying No copying 1 Frequency [Hz] Reference [%] Motor current [A] Power [kW] LCP digital control/as par.100 Possible Not possible Not possible Possible Not locked Forced stop, use saved ref. Changes 4-Setup during operation Yes No Yes Yes Yes Yes Yes No Yes No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Conversion index 0 0 -3 0 0 0 0 -2 0 0 0 0 0 0 0 0 0 0 0 Data type 5 5 4 5 5 5 5 6 5 5 5 5 5 5 5 5 5 5 5

Changes during operation: "Yes" means that the parameter can be changed, while the VLT frequency converter is in operation. "No" means that the VLT frequency converter must be stopped before a change can be made. 4-Setup: "Yes" means that the parameter can be programmed individually in each of the four setups, i.e. the same parameter can have four different data values. "No" means that the data value will be the same in all four setups. Conversion index: This number refers to a conversion figure to be used when writing or reading by means of a VLT frequency converter.

Conversion index 74 2 1 0 -1 -2 -3 -4

Conversion factor 0.1 100 10 1 0.1 0.01 0.001 0.0001

Data type: Data type shows the type and length of the telegram. Data type Description 3 4 5 6 7 9 Integer 16 Integer 32 Unsigned 8 Unsigned 16 Unsigned 32 Text string

MG.50.H4.22 - VLT is a registered Danfoss trademark

27

Programming

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


PNU # 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 Lo a d co m p e ns a tio n at lo w s p ee d Lo a d co m p e ns a tio n at hig h s p eed S lip co m p e ns a tio n S lip c o m p e n s a t io n t im e c o n st a n t R es o n an ce d am p en ing R es o n an ce d a m p en in g t im e c on s ta nt H ig h s ta rt in g t orq u e S ta rt d e la y S ta rt f u n c ti on Fu n ct io n a t s to p M in . f re q u e n c y f o r a c t iv a ti n g f u n c t io n at s to p 124 125 126 127 128 129 130 131 D C h o ld i n g c u rre n t D C b r a k in g c u r re n t DC b raki ng t im e D C b r a k e c u t -i n f re q u e n c y M o t or t h e r m a l p ro t e c t io n E x t er n al m o t or fan S ta rt f re q u e n c y In it ia l vo lt a g e 50 % 50 % 10.0 sec. Off No protection No 0.0 Hz 0.0 V Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 0 0 -1 -1 0 0 -1 -1 6 6 6 6 5 5 5 6 100 % 100 % 100 % 0.50 s 100 % 5 ms 0.0 sec. 0.0 sec. Coasting in start delay time Coasting 0.0 Hz Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 0 0 0 -2 0 -3 -1 -1 0 0 -1 6 6 3 6 6 6 5 5 5 5 5 Parameter description C on f ig u ra ti on To rq u e c h a ra c t e r i s t i c s M o t or p o w er M o t or v o lt ag e M o t or f re q u e n c y M o t or c u rre n t Rated motor spee d A ut o m at ic m o to r ad a p ta tio n , A M A S ta to r re s is to r S t a t o r re a c t a n c e M o t or m a g ne tiz in g , 0 r p m M in . f re q u e n c y n o r m a l m a g n e t izin g Speed control, open loop High - constant torque Depends on the unit Depends on the unit 50 Hz / 60 Hz Depends on the unit Depends on the unit Adaptation off Depends on the unit Depends on the unit 100 % 1.0 Hz Factory setting Changes 4-Setup Conversion index 0 0 1 0 0 -2 0 0 -4 -2 0 -1 Data type 5 5 6 6 6 7 6 5 7 7 6 6 during operation No Yes No No No No No No No No Yes Yes Yes Yes Yes Yes Yes Yes Yes No Yes Yes Yes Yes

28

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


PNU # 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 To rq u e l i m i t f o r m ot o r m o d e To rq u e l i m i t f o r re g e n e r a t i ve o p erat io n 223 224 225 226 227 228 229 230 231 232 233 234 Wa r n i n g : L o w c u r r e n t W a r n i n g : H i g h c u r re n t Wa r n i n g : L o w f r e q u e n c y W a r n i n g : H i g h f re q u e n c y Wa r n i n g : L o w f e e d b a c k Wa r n i n g : H i g h f e e d b a c k F re q u e n c y b y p a ss , b a n d w id t h F re q u e n c y b yp a s s 1 F re q u e n c y b yp a s s 2 F re q u e n c y b yp a s s 3 F re q u e n c y b yp a s s 4 M o t or p ha se m o n it or 0.0 A IVLT,MAX 0.0 Hz 132.0 Hz -4000.000 4000.000 OFF 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz Enable Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes -1 -1 -1 -1 -3 -3 0 -1 -1 -1 -1 0 6 6 6 6 4 4 6 160 % 160 % Yes Yes Yes Yes -1 -1 6 6 Parameter description O u tp u t f re q u e n c y r a n ge / d ire c t io n O u tp u t f re q u e n c y l ow lim it O u tp u t f re q u e n c y h ig h lim it R e f e re n c e / f e e d b a c k a re a M i n i m u m re f e r e n c e M a x i m u m r e f e re n c e Ram p type R am p -u p ti m e 1 R am p -d o w n tim e 1 R am p -u p ti m e 2 R am p -d o w n tim e 2 Jo g ram p t im e Q u ick s to p r a m p -d ow n tim e J o g f re q u e n c y R e f e re n c e f u n c tio n P re s e t r e f e re n c e 1 P re s e t r e f e re n c e 2 P re s e t r e f e re n c e 3 P re s e t r e f e re n c e 4 C atc h u p / s lo w d o w n va lue Only clockwise, 0-132 Hz 0.0 Hz 66 / 132 Hz Min - max 0.000 50.000 Linear Depends on unit Depends on unit Depends on unit Depends on unit Depends on unit Depends on unit 10.0 Hz Sum 0.00 % 0.00 % 0.00 % 0.00 % 0.00 % Factory setting Changes 4-Setup Conversion index 0 -1 -1 0 -3 -3 0 -2 -2 -2 -2 -2 -2 -1 0 -2 -2 -2 -2 -2 Data type 5 6 6 5 4 4 5 7 7 7 7 7 7 6 5 3 3 3 3 6 during operation No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

6 6 6 5

MG.50.H4.22 - VLT is a registered Danfoss trademark

29

Programming

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


PNU # 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 Parameter description Te rm i n a l 1 6, i n p u t Te rm i n a l 1 7, i n p u t Te rm i n a l 1 8 S ta rt , i n p u t Te rm i n a l 1 9, i n p u t Te rm i n a l 2 7, i n p u t Te rm i n a l 2 9, i n p u t Te rm i n a l 3 2, i n p u t Te rm i n a l 3 3, i n p u t Te rm i n a l 5 3, a n a l o g u e i n p u t v o l t a g e Te rm i n a l 5 3 , m i n . s c a l i n g Te rm i n a l 5 3 , m a x . s c a l i n g Te rm i n a l 5 4, a n a l o g u e i n p u t v o l t a g e Te rm i n a l 5 4 , m i n . s c a l i n g Te rm i n a l 5 4 , m a x . s c a l i n g Te rm i n a l 6 0, a n a l o g u e i n p u t c u r re n t Te rm i n a l 6 0 , m i n . s c a l i n g Te rm i n a l 6 0 , m a x . s c a l i n g T im e o ut Fu nc tio n a fte r tim e o u t Te rm i n a l 42 , o u t p u t Te rm i n a l 4 2 , o u tp u t, p u l se s c a l i n g Te rm i n a l 45 , o u t p u t Te rm i n a l 4 5 , o u tp u t, p u l se s c a l i n g R ela y 0 1 , o ut p u t R ela y 0 1 , O N d ela y R ela y 0 1 , O F F d el ay R ela y 0 4 , o ut p u t P u l s e r e f e r e n c e , m a x . f re q u e n c y P u l s e f e e d b a c k , m a x . f re q u e n c y E n c o d e r f e e d b a c k p u l s e / re v. F r e e z e re f e r e n c e / o u t p u t f u n c t i o n Reset Freeze reference Start Reversing Coasting stop, inverse Jog Choice of setup, msb/speed up Choice of setup, lsb/speed down Reference 0.0 V 10.0 V No operation 0.0 V 10.0 V Reference 0.0 mA 20.0 mA 10 sec. Off Factory setting Changes 4-Setup Conversion index 0 0 0 0 0 0 0 0 0 -1 -1 0 -1 -1 0 -4 -4 0 0 0 0 0 0 0 -2 -2 0 0 0 0 0 Data type 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 6 5 6 5 6 6 5 6 6 6 5 during operation Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 0-20 mA Yes Yes 0-20 mA Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No

5000 Hz 0 - fMAX

5000 Hz

Ready - no thermal warning 0.00 sec. 0.00 sec. Ready - remote control 5000 Hz 25000 Hz 1024 No operation

30

0 - IMAX

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


PNU # 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 437 438 439 440 441 442 443 444 445 446 447 448 449 450 Parameter description B r a k e f u n c t i o n / o v e r v o l t a g e c o n t ro l B r a k e re si st o r, o h m B r ak e p o w e r lim i t, k W P ow er m o n ito r in g Brake c he ck R es e t fun ct io n A u t o m a t i c re s t a r t t i m e M a in s F a ilu re Q u ic k d i sc ha r ge Tri p d e l a y t o rq u e Tri p d e l a y - i n v e r t e r S w i t c h i n g f re q u e n c y O u tp u t f re q u e n c y d e p e n d e n t s w i tc h in g f re q u e n c y O v erm o d u lat io n fun ct io n M in im u m fee d b ac k M a xi m um f e e d b a c k P ro c e s s u n i t S p e e d P I D p rop o r t io n a l g a in S p e e d P I D in te g ra tio n tim e S p e e d P I D d i ff e r e n t i a t i o n t i m e S p e e d P I D d i ff . g a i n r a t i o S p e e d PI D l ow -p a ss fil te r U 0 v o lt ag e at 0 H z U 1 v o lta g e F 1 f re q u e n c y U 2 v o lta g e F 2 f re q u e n c y U 3 v o lta g e F 3 f re q u e n c y U 4 v o lta g e F 4 f re q u e n c y U 5 v o lta g e F 5 f re q u e n c y To rq u e p ro p o rt i o n a l g a i n To rq u e i n t e g r a l t i m e P ro c e s s P I D N o r m a l / i n v e r s e c o n t ro l P ro c e s s P I D a n t i w i n d u p P ro c e s s P I D s t a r t f r e q u e n c y P ro c e s s P I D p ro p o r t i o n a l g a i n P ro c e s s P I D i n t e g r a l t i m e P ro c e s s P I D d i f f e re n t i a t i o n t i m e P ro c e s s P I D d i f f . g a i n l i m i t P ro c e s s P I D l o w p a s s f i l t e r t i m e Fl yin g s t ar t S w itc hi ng p at t er n To rq u e c o m p e n s a t i o n G ea r r a tio Fr ic tio n l os s M a ins v ol tag e a t m a in s fa ult Factory setting Off Depends on the unit Depends on the unit On Off Manual reset 5 sec. No function Not possible Off Depends on type of unit Depends on type of unit Not possible On 0.000 1500.000 % 0.015 8 ms 30 ms 5.0 10 ms 20.0 V parameter 103 parameter 104 parameter 103 parameter 104 parameter 103 parameter 104 parameter 103 parameter 104 parameter 103 parameter 104 100% 0.02 sec. Normal On parameter 201 0.01 9999.99 sec. (OFF) 0.00 sec. (OFF) 5.0 0.01 Disable SFAVM 100% 1 0% Depends on unit Changes 4-Setup during operation Yes No Yes No Yes No Yes No Yes No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Conversion index 0 -1 2 0 0 0 0 0 0 0 0 2 0 -1 -3 -3 0 -3 -4 -4 -1 -4 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 -1 0 -3 0 0 -1 -2 -2 -2 -1 -2 0 0 0 -2 -2 0 Data type 5 6 6 5 5 5 5 5 5 5 5 6 5 5 4 4 5 6 7 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 7 5 5 6 6 7 6 6 6 5 5 3 4 6 6

MG.50.H4.22 - VLT is a registered Danfoss trademark

31

Programming

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


PNU # 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 Te l e g r a m p ro f i l e B u s tim e i nt er v al B u s t im e in ter v al fu nc tio n D a t a re a d - o u t : R e f e r e n c e % D a t a re a d - o u t : R e f e re n c e u n i t D a ta re a d -o u t: F e e d b a c k D a ta re a d -o u t : F re q u e n c y D a ta re a d -o u t: F re q u e n c y x S c a l in g D a ta re a d -o u t: C u rre n t D a ta re a d - o u t: To rq u e D a ta re a d - o u t : P o w e r, k W D a ta re a d - o u t : P o w e r, H P D a t a re a d - o u t : M o t o r v o l t a g e D a t a re a d - o u t : D C l i n k v o l t a g e D a t a re a d - o u t : M o t o r t e m p . D a ta re a d - o u t : V LT te m p . D a ta re a d - o u t : D ig ita l in p u t D a ta re a d - o u t: Te rm i n a l 5 3, a n a l o g u e i n p u t D a ta re a d - o u t: Te rm i n a l 5 4, a n a l o g u e i n p u t D a ta re a d - o u t: Te rm i n a l 6 0, a n a l o g u e i n p u t D a t a re a d - o u t : P u l s e re f e r e n c e D a t a r e a d - o u t : E x t e r n a l r e f e re n c e % D a ta re a d -o u t: S ta tu s w o rd , b in a r y D a ta re a d -o u t: B r a k e p o w e r / 2 m in . D a ta re a d -o u t: B r a k e p o w e r/ s e c . D a t a r e a d - o u t : H e a t s i n k t e m p e r a t u re D a ta re a d -o u t: A la r m w o rd , b in a r y D a ta re a d - o u t : V LT c o n t ro l w o rd , b i n a r y D a t a r e a d - o u t : Wa r n i n g w o r d , 1 D a t a r e a d - o u t : Wa r n i n g w o r d , 2 FC Drive 1 sec. Off No Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No Yes Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No 0 0 0 -1 -3 -3 -1 -2 -2 -1 -1 -2 -1 0 0 0 0 -2 -2 -5 -1 -1 0 2 2 0 0 0 0 0 5 5 5 3 4 4 6 7 7 3 7 7 6 6 5 5 5 3 3 3 7 3 6 6 6 5 7 6 7 7 Parameter description A d d re s s Bau drate C oa s tin g Q u ick - s to p D C -b ra k e S ta rt R e v e rs in g S ele cti on o f s e tu p S ele cti on o f s p ee d B u s j og 1 B u s j og 2 1 9600 Baud Logic or Logic or Logic or Logic or Logic or Logic or Logic or 10.0 Hz 10.0 Hz Factory setting Changes 4-Setup Conversion index 0 0 0 0 0 0 0 0 0 -1 -1 Data type 6 5 5 5 5 5 5 5 5 6 6 during operation Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No No Yes Yes Yes Yes Yes Yes Yes Yes Yes

32

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


PNU # 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 Parameter description O p e r a tin g d a t a : O p e r a tin g h o u rs O p e r a tin g d a ta : H o u rs r u n O p er a tin g d a ta: k W h co u nt er O p e r a ti n g d a ta : N u m b e r o f p ow e r -u p s s O p e r a t i n g d a t a : N u m b e r o f o v e r t e m p e r a t u re s O p er a tin g d a ta: Nu m b e r o f o ve r vo lt ag e s D a ta lo g: D ig it al i np u t D a ta lo g : B u s c om m an d s D a ta lo g : B u s s ta tu s w o rd D a t a l o g : R e f e re n c e D a ta lo g : F ee d b ac k D a t a l o g : M o t o r f re q u e n c y D a ta lo g : M o to r v o lt ag e D a ta lo g : M o to r c u rre n t D a ta lo g : D C lin k v o lt ag e F a u l t l o g : E r ro r c o d e Fa ul t lo g: T im e F a u l t l o g: Va l u e Res e t o f kW h co u nt er R es e t o f h o urs -ru n co u nt er O p er a tin g m o d e N o r m al f un ct io n N a m e p l a t e : V LT ty p e N am e p lat e: P o w er s e ct io n N a m e p l a t e : V LT o rd e r i n g n u m b e r N a m e p l a t e : S o f t w a re v e r s i o n n o . N am e p lat e: LC P id en tifi cat io n n o . N am e p lat e: D a tab as e id en tif icat io n n o. N am e p lat e: P o w er s ec tio n id en tifi cat io n n o . N am e p lat e: A p p li cat io n o p t io n ty p e N a m e p la t e : A p p lic a ti on o p t io n o rd e r in g n o . N am e p lat e: Co m m un ic ati on o p t io n ty p e N a m e p l a t e : C o m m u n i c a t i o n o p t i o n o rd e r i n g n o . No reset No reset Normal function Factory setting Changes 4-Setup Conversion index 74 74 2 0 0 0 0 0 0 -1 -3 -1 -1 -2 0 0 -1 0 0 0 0 0 0 0 0 0 -2 0 0 0 0 0 Data ype 7 7 7 6 6 6 5 6 6 3 4 3 6 3 6 5 7 3 5 5 5 9 9 9 9 9 9 9 9 9 9 during operation No No No No No No No No No No No No No No No No No No Yes Yes No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No No

MG.50.H4.22 - VLT is a registered Danfoss trademark

33

Programming

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


PNU # 700 701 702 703 704 705 706 707 708 709 710 711 Parameter description R ela y 6 , fu nc tio n R ela y 6 , O N d e lay R ela y 6 , O FF d e lay R ela y 7 , fu nc tio n R ela y 7 , O N d e lay R ela y 7 , O FF d e lay R ela y 8 , fu nc tio n R ela y 8 , O N d e lay R ela y 8 , O FF d e lay R ela y 9 , fu nc tio n R ela y 9 , O N d e lay R ela y 9 , O FF d e lay Factory setting Ready signal 0 sec. 0 sec. Motor running 0 sec. 0 sec. Mains ON 0 sec. 0 sec. Fault 0 sec. 0 sec. Changes 4-setup Conversion index 0 -2 -2 0 -2 -2 0 -2 -2 0 -2 -2 Datatype 5 6 6 5 6 6 5 6 6 5 6 6 during operation Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

NOTE This VLT Parameter List is only valid when Relay Option is installed.

34

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


ConverPNU # 700 701 702 703 704 705 706 707 708 Parameter description S y s t e m c o n t ro l P rog r a m n u m b e r P I D , P ro p o r tio n a l f a c to r P I D , D er iv ati ve fa ct o r P I D , I n te gr a l fac to r P I D , In te g ra l b a n d w id th P ID, BA ND W IDTH P I D , Ve l o c i ty F e e d - f o r w a rd P ID, A c cel erat io n F e e d -f o r w a rd 709 710 P I D , Ve l o c i t y f i l t e r U se r p a r a m e t e r 1 0 0 0 0 - 65000 Defined by user 711 U se r p a r a m e t e r 1 1 0
1

Factory setting

Changes

4-Setup

sion index

Data type 0 0 0 0 0 0 0 0 0 6 4 4 4 4 4 4 4 4

during operation 0 1 - 1 30 0 0 1000 1000 0 0 -1 - 127 0 - 65000 0 - 65000 0 - 65000 0 - 1000 0 - 65000 0 - 65000 0 - 65000 Yes Yes Yes Yes Yes Yes Yes Yes Yes

No No No No No No No No No

Yes Yes

No No

0 0

4 4

Defined by user
1

Yes

No

... 778 U se r p a t a m e te r 78 0 Defined by user 779 U se r p a r a m e t e r 7 9 0


1

Yes

No

Defined by user
1

Yes

No

780

A ct iv at ed d e ad t im e c om p en s at io n

OFF

0 - 1

No

No

795

U s e r p a r a m e t e r 9 5 ( re a d o n l y )

Defined by user
1

Read only

No

796

U s e r p a ra m e t e r 9 6 (re a d o n l y )

Defined by user
1

Read only

No

797

U s e r p a ra m e t e r 9 7 (re a d o n l y )

Defined by user
1

Read only

No

798

U s e r p a ra m e t e r 9 8 (re a d o n l y )

Defined by user
1

Read only

No

799

U s e r p a ra m e t e r 9 9 (re a d o n l y )

Defined by user
1

Read only

No

NOTE This VLT Parameter List is only valid when Sync/Pos option is installed.

1) The maximum range is -232 to 2 32 - 1 (-2147483648 to 2147483647) but the actual range is specified when defining a user parameter in the application program using LINKGPAR or LINKAXPAR.

MG.50.H4.22 - VLT is a registered Danfoss trademark

35

Programming

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet


s Factory settings
PNU # 801 803 804 805 904 915 916 927 928 953 967 968 970 971s 980 981 982 990 991 992 M o d if i e d p a ra m e t e r s 0 Parameter description B a u d ra te s e le c t io n T i m e a f t e r b u s e r ro r R e s p o n s e a f t e r b u s e r ro r F u n c t i o n c o n t r o l w o rd b i t B i t 1 0 P P O s ele cti on fo r D P P C D w r ite c o nfig u r at io n P C D re a d c o n f i g u r a t i o n P C V o p e r a t in g a u th o ri ty C o n t ro l a u t h o r i t y Wa r n i n g M e s s a g e s C o n t ro l W o r d S ta tu s W o rd P aram et er s et u p s ele ct io n S av e d at a va lue s D e f in e d p a r a m e te rs Active setup Not active (OFF) With PROFIBUS With PROFIBUS 1 sec. Off Bit 10 = CTW active 900 Factory setting Changes 4-Setup Conversion index -1 -1 -1 -1 0 0 0 0 0 0 0 0 0 0 0 Data type 3 3 3 6 6 6 6 6 6 35 35 35 5 5** 6

during operation

** Automatic reset to (0) S Only in stop mode (VLT must be stopped in order to change data value)

36

MG.50.H4.22 - VLT is a registered Danfoss trademark

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA

Instruction Manual

175R5287

MG50H422

*MG50H422*

REV. 2003-04-28

Вам также может понравиться