Manual Instalacion Robur
Manual Instalacion Robur
GA ACF
absorption chiller
gas powered
Revision: P
Code: D-LBR323
This Installation, use and maintenance manual has been drawn up and printed by Robur Corporation; whole or
partial reproduction of this Installation, use and maintenance manual is prohibited.
The original is filed at Robur Corporation.
Any use of this Installation, use and maintenance manual other than for personal consultation must be previously
authorised by Robur Corporation.
The rights of those who have legitimately filed the registered trademarks contained within this publication are not
affected.
With the aim of continuously improving the quality of its products, Robur Corporation reserves the right to modify
the data and contents of this Installation, use and maintenance manual without prior notice.
INDEX OF CONTENTS
I INTRODUCTION
Installation, use and maintenance manual ▶ End user, for appropriate and safe use of the appliance.
▶ Qualified installer, for correct appliance installation.
This Manual is an integral part of the GA ACF unit and ▶ Planner, for specific information on the appliance.
must be handed to the end user together with the
appliance. I.2 CONTROL DEVICE
In order to be able to work, the GA ACF unit needs a control de-
I.1 RECIPIENTS vice (DDC or external request), which must be connected by the
This Manual is intended for: installer.
III WARNINGS
III.1 GENERAL AND SAFETY WARNINGS issue to the owner/client the appliance's workman-
like conformity declaration, according to national/local
regulations in force and the manufacturer's instructions/
provisions.
Misuse
4
III Warnings
Before performing any operation on gas ducting compo- Distance from combustible or flammable materials
nents, close the gas valve.
Upon completing any procedure, perform the tightness Do not deposit flammable materials (paper, diluents,
test according to regulations in force. paints, etc.) near the appliance.
The appliance contains very hot parts. Switching the appliance off
Do not open the appliance and do not touch internal
components before the appliance has cooled down. Disconnecting the power supply while the appliance
is running may cause permanent damage to internal
Pressure vessels components.
Except in the case of danger, do not disconnect the pow-
The appliance has a sealed circuit classified as pres- er supply to switch off the appliance, but always and ex-
sure vessel, the tightness of which is tested by the clusively act through the provided control device (DDC
manufacturer. or external request).
Do not carry out any intervention on the sealed circuit or
on the appliance's valves. In the event of failure
III.2 CONFORMITY
The manufacturer cannot be held responsible for any
The installation of the appliance must conform to the require- damages to persons, animals or goods due to improper,
ments of the authority having jurisdiction or, in the absence of erroneous or irrational installation of these appliances.
such requirements, to the latest edition of the National Fuel
Gas Code, ANSI Z223.1. If the unit is installed in Canada, the
installation must conform to the Canadian Gas Association In particular, the warranty on the appliance may be ren-
Standard CAN1 B149.1 and .2. dered void by the following conditions:
The appliance’s electrical connections and grounding must be
in accordance with the latest edition of the National Electrical Incorrect installation.
Codes, ANSI/NFPA No. 70 (CSA Standard C22.1 when in- Misuse.
stalled in Canada) and with any local codes. To ensure the elec- Failure to comply with the manufacturer's indications on
trical safety of this appliance, it must be correctly connected to installation, use and maintenance.
an efficient grounding system. The manufacturer is not respon- Alteration or modification of the product or any part
sible for any damages caused by the failure of the grounding thereof.
system. Extreme operational conditions or however outside of
the operational ranges set forth by the manufacturer.
Other applicable provisions and standards Damages caused by external agents such as salts, chlo-
The design, installation, operation and maintenance of the sys- rine, sulphur or other chemical substances contained in
tems shall be carried out in compliance with current applicable the installation water or present in the air of the instal-
regulations, depending on the Country and location, and in lation site.
accordance with the manufacturer's instructions. In particular, Abnormal actions transmitted to the appliance by the
regulations regarding the following shall be complied with: plant or installation (mechanical stresses, pressure, vi-
▶ Gas systems and equipment. brations, thermal expansion, electrical surges...).
▶ Electrical systems and equipment. Accidental damages or due to force majeure.
▶ Heating and cooling systems, heat pumps and chillers.
6
1 Features and technical data
1.2 DIMENSIONS
48-1/2” 33-1/2”
A Position of holes for fixing of anti-vibration joints
Figure 1.2 ACF Service plate with plumbing and gas connections
6-1/2” A Water outlet connection Ø 1 1/4" F
B Water inlet connection Ø 1 1/4" F
E Electrical knockouts Ø 7/8"
B A
12”
7-7/8”
5-7/8”
4-1/4”
7-1/8”
Figure 1.3 ACF-HR Service plate with plumbing and gas connections
11-15/16” G Gas fitting Ø 1/2" F
Chiller - CHILLED WATER
6-11/16” D Outlet water fitting Ø 1 1/4" F
C Water inlet connection Ø 1 1/4" F
4-1/4” Recovery exchanger - HOT WATER
A Water outlet connection Ø 1 1/4" F
3-1/8” B Water inlet connection Ø 1 1/4" F
12-3/16”
9-7/8”
7-7/8”
5-7/8”
7-1/8”
8
1 Features and technical data
1.3 COMPONENTS
10
1 Features and technical data
6
5
12
1 Features and technical data
SCH Electronic board S61 P8 (GND, L, H) CAN BUS connector N.O. Contact Circuit water circulating pump
THMF Water delivery temperature probe input J1 CAN bus Jumper controller terminals
THRF Water return temperature probe input A1, A2 Auxiliary inputs (not used) J10 Circuit water circulating pump controller
TCN Condenser outlet temperature probe input TF Flue gas thermostat input jumper
TA Ambient air temperature probe input TL Generator limit thermostat input FAN (BK, WH, BR) Fan output
TG Generator temperature probe input FL Water flow switch input JTAG S61 board programming connector
TA1 Not used FS5 Board supply input 24 Vac ENC Knob
TA2 Not used P7 (R, W, Y, O) operation request inputs JP10 6-pole flame controller connector
SRT1 Oil pump rotation sensor input IGN.BOX (L, N) flame controller supply input 230 Vac F1 T 2A fuse
SRT2 Not used MAIN board supply input 230 Vac F2 T 10A fuse
JP12 Not used PUMP 230V (L, N) oil hydraulic pump supply F3 T 2A fuse
SPI Not used output F4 T 3.15A fuse
14
1 Features and technical data
Figure 1.9 ACF60-00 (standard, HT, TK, HR) unit internal pressure drop as a function of water flow rate, outlet water temperature 44.6 °F
Pressure drop [feet of head]
12.00
ACF60-00,
HT, TK, HR
10.00
8.00
6.00
4.00
2.00
6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00
LB
Figure 1.10 ACF60-00 LB unit internal pressure drop as a function of water flow rate
Pressure drop [feet of head]
18.00
16.00
ACF60-00 LB
14.00
12.00
10.00
8.00
6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00
Ethylene glycol (40%) + water flow [GPM]
Figure 1.11 ACF60-00 HR heat recovery unit internal pressure drop as a function of water flow rate, return water temperature 68.0 °F
Pressure drop [feet of head]
6.03
5.36
4.69
4.02
3.35
2.68
2.01
1.34
0.67
0.00
2.2 3.3 4.4 5.5 6.6 7.7 8.8 9.9 11.0
9.46
Recovery unit water flow [GPM]
16
1 Features and technical data
Ambient air Chilled water outlet temperature [°F] Ambient air Chilled water outlet temperature [°F]
temperature [°F] 41.0 44.6 50.0 54.5 57.2 temperature [°F] 14.0 19.4 23.0 28.4 32.0
82.4 59053 59637 59637 59637 60222 93.2 41003 43602 46201 47981 49760
86.0 59053 59637 59637 59637 60222 95.0 39847 42635 45400 47299 49174
89.6 57883 59637 59637 59637 60222 96.8 38614 41599 44584 46557 48530
93.2 56129 59053 59053 59053 59637 98.6 37302 40491 43681 45753 47825
95.0 54960 58368 58468 59053 59637 100.4 35907 39309 42711 44884 47057
96.8 53791 57883 58468 58468 59637 102.2 34428 38051 41673 43949 46225
100.4 50867 56714 57883 57883 59053 104.0 32863 36713 40564 42945 45325
104.0 47944 54375 56714 57299 58468 105.8 31208 35295 39383 41869 44356
107.6 - 51452 54960 56714 57883 107.6 29461 33794 38126 40720 43314
111.2 - 47944 53206 55545 56714 109.4 27620 32206 36793 39496 42198
114.8 - - 50282 53791 55545 111.2 25682 30531 35379 38193 41006
118.4 - - 46774 50867 53206 113.0 23645 28765 33885 36810 39735
131.0 - - - 47359 50282 120.0 - - 28004 31587 35176
L B R
H
Table 1.5 p. 17 shows the unitary cooling load at full load and Table 1.6 p. 17 shows the cooling capacity multiplication cor-
in stable operation, depending on cold water outlet tempera- rectional factors at full load and in stable operation, depending
ture to the system and outdoor temperature, referring to ACF on cold water outlet temperature to the system and outdoor
60-00 LB unit. temperature, referring to ACF 60-00 HR unit for cooling mode
Please consider that, according to the actual cooling request, only, without heat recivery.
the unit may often need to operate under partial load conditions Table 1.7 p. 17 shows the same data, referring to the ACF 60-00
and in non stationary operation. HR unit in simultaneous operation for cooling and heat recovery.
Please consider that, according to the actual cooling request,
Table 1.5 ACF60-00 LB cooling capacity [Btu/hr]
the unit may often need to operate under partial load conditions
Ambient air Chilled water outlet temperature [°F] and in non stationary operation.
temperature [°F] 14.0 19.4 23.0 28.4 32.0
23.0 52007 52217 52426 52801 53176 Table 1.6 A
CF60-00 HR - Cooling capacity multiplication correction fac-
24.8 52007 52217 52426 52801 53176 tors in cooling mode (no recovery) for external air tempera-
26.6 52007 52217 52426 52801 53176 tures and water flow rates different than the nominal ones
28.4 52007 52217 52426 52801 53176 Operating mode: cooling only
30.2 52007 52217 52426 52801 53176 Ambient air Chilled water outlet temperature [°F]
32.0 52007 52217 52426 52801 53176 temperature
37.4 41 44.6 48.2
33.8 52007 52217 52426 52801 53176 [°F]
35.6 52007 52217 52426 52801 53176 32 0.98 0.99 1.01 1.03
37.4 52007 52217 52426 52801 53176 41 0.98 0.99 1.01 1.03
39.2 52007 52217 52426 52801 53176 50 0.98 0.99 1.01 1.03
41.0 52007 52217 52426 52801 53176 59 0.98 0.99 1.01 1.03
42.8 52007 52217 52426 52801 53176 68 0.98 0.99 1.01 1.03
44.6 52007 52217 52426 52801 53176 77 0.97 0.99 1.01 1.03
46.4 52007 52200 52392 52784 53176 86 0.90 0.98 1.01 1.03
48.2 52007 52183 52358 52767 53176 95 0.67 0.87 1.00 1.02
50.0 52007 52166 52324 52750 53176 104 — — 0.88 0.93
51.8 51965 52127 52290 52733 53176 113 — — 0.67 0.78
53.6 51904 52080 52256 52716 53176
55.4 51822 52022 52221 52699 53176
57.2 51718 51952 52187 52681 53176
Table 1.7 A
CF60-00 HR - Cooling capacity multiplication correction fac-
59.0 51588 51884 52181 52678 53176
tors in cooling+recovery mode for external air temperatures
60.8 51430 51793 52157 52666 53176 and water flow rates different than the nominal ones
62.6 51241 51677 52113 52644 53176 Operating mode: cooling and heat recovery
64.4 51020 51533 52047 52610 53172 Ambient air Chilled water outlet temperature [°F]
66.2 50763 51360 51957 52563 53169 temperature
37.4 41 44.6 48.2
68.0 50469 51155 51841 52503 53166 [°F]
69.8 50134 50915 51696 52423 53149 32 0.97 0.98 1.00 1.02
71.6 49757 50638 51520 52314 53107 41 0.97 0.98 1.00 1.02
73.4 49334 50322 51311 52174 53038 50 0.97 0.98 1.00 1.02
75.2 48864 49965 51067 52002 52937 59 0.97 0.98 1.00 1.02
77.0 48343 49564 50785 51795 52805 68 0.97 0.98 1.00 1.02
78.8 47771 49117 50464 51551 52637 77 0.96 0.98 1.00 1.02
80.6 47143 48622 50101 51267 52432 86 0.89 0.97 1.00 1.02
82.4 46458 48076 49694 50941 52188 95 0.73 0.91 1.00 1.02
84.2 45713 47476 49240 50571 51901 104 — 0.89 0.95 0.96
86.0 44905 46822 48738 50155 51571 113 — — 0.80 0.85
87.8 44033 46109 48186 49690 51194
89.6 43093 45337 47580 49174 50768 Following Tables show the unitary recoverable heat output at
91.4 42084 44502 46919 48605 50291 full load and in stable operating mode, depending on the tem-
perature of the thermal input fluid to the recuperator and the
outdoor temperature for different water flow rates to the recu- Table 1.10 A
CF60-00 HR - Heat capacity of the heat recovery unit for
perator, referring to the ACF 60-00 HR unit. conditions other than nominal ones; flow rate = 6.6 GPM
Consider that in the absence of a refrigeration request no recov- Heat capacity [Btu/hr] (flow rate = 6.6 GPM)
erable heat output will be available. Hot water return Ambient air temperature [°F]
Table 1.8 A
CF60-00 HR - Heat capacity of the heat recovery unit for temperature to
59 68 77 86 95 104 113
the recovery [°F]
conditions other than nominal ones; flow rate = 2.2 GPM
68 96991 102455 109286 — — — —
Heat capacity [Btu/hr] (flow rate = 2.2 GPM) 86 75134 81964 88795 93269 100406 105871 110993
Hot water return Ambient air temperature [°F] 104 50886 60107 66596 72368 80257 87429 93917
temperature to 122 30224 38592 44295 50203 56931 64137 71377
59 68 77 86 95 104 113
the recovery [°F] 140 10929 17076 22779 28346 34152 40982 47813
50 92210 92893 93576 93917 95283 96308 97333
158 — — 10587 14344 21174 29029 33469
68 72743 75134 76978 78549 80188 83330 85379
86 52628 55667 58570 61644 65162 68577 72231
104 35859 39275 42007 46071 50954 55667 61507 Table 1.11 A
CF60-00 HR - Heat capacity of the heat recovery unit for
122 21857 24248 27356 31761 37567 43714 50818 conditions other than nominal ones; flow rate = 8.8 GPM
140 9563 12226 15368 18783 25033 31420 40982
Heat capacity [Btu/hr] (flow rate = 8.8 GPM)
158 — — 8196 8982 13831 21003 30395
Hot water return Ambient air temperature [°F]
temperature to
59 68 77 86 95 104 113
the recovery [°F]
Table 1.9 A
CF60-00 HR - Heat capacity of the heat recovery unit for
68 97333 104709 110993 — — — —
conditions other than nominal ones; flow rate = 4.4 GPM
86 76158 83399 91868 97333 — — —
Heat capacity [Btu/hr] (flow rate = 4.4 GPM) 104 51228 61302 72094 78549 85106 92210 99040
Hot water return Ambient air temperature [°F] 122 30258 39275 47813 54643 59902 66596 76158
temperature to 140 14002 17144 24111 29678 35859 42690 49520
59 68 77 86 95 104 113
the recovery [°F] 158 — — 12704 17076 22882 29712 35859
68 92210 99040 102797 106895 109286 — —
86 71719 78208 83604 85755 89546 95625 102455
104 47983 54643 61473 65162 71719 78549 85584 Table 1.12 A
CF60-00 HR - Heat capacity of the heat recovery unit for
122 27765 34083 41426 45149 53004 59868 65640 conditions other than nominal ones; flow rate = 11.0 GPM
140 10246 16051 21447 25682 34152 40299 46105
Heat capacity [Btu/hr] (flow rate = 11.0 GPM)
158 — — 8538 11953 19330 23906 31078
Hot water return Ambient air temperature [°F]
temperature to
59 68 77 86 95 104 113
the recovery [°F]
68 103924 — — — — — —
86 81281 88795 102455 — — — —
104 57033 64888 76295 82613 88795 97572 102455
122 36884 41255 49520 58058 63454 71104 79061
140 17452 21345 26331 31112 38113 45798 55736
158 — — 13285 18100 23906 30737 39275
18
2 Transport and positioning
Figure 2.1 Instruction for lifting Incorrect ventilation may affect efficiency and cause
damage to the appliance.
The manufacturer shall not be liable for any incorrect
choices of the place and setting of installation.
Acoustic issues
▶ Pre-emptively assess the appliance's sound effect in connec-
tion to the site, taking into account that building corners, en-
closed courtyards, restricted spaces may amplify the acous-
In the event of handling with forklift or pallet truck, tic impact due to the reverberation phenomenon.
comply with the handling instructions shown on the
packing.
2.4 MINIMUM CLEARANCE DISTANCES
The appliance is type-approved for external installation. Clearances around the appliance
Do not install inside a room, not even if it has openings. There must be a minimum clearance of 4 feet horizontally from
In no event start the appliance inside a room. electric meters, gas meters, regulators, and relief equipment and
in no case the appliance can be located above or below these
GA Unit ventilation items unless a 4 feet horizontal distance is maintained.
The minimum clearance distances shown in Figure 2.2 p. 19
The aerothermic appliance requires a large space, venti- (bar any stricter regulations) are required for safety, operation
lated and free from obstacles, to enable smooth flow of and maintenance.
air to the finned coil and free air outlet above the mouth
of the fan, with no air recirculation.
24”
36”
36”
When the appliance is installed in close proximity to buildings, flues, outlets and other such vents. It is important that the ap-
keep the appliance away from the roof edge drip line. In no case pliance is located so that hot or contaminated air IS NOT drawn
should the appliance be placed within 6 feet of any external air into the air intakes of the unit (Figure 2.3 p. 20).
intakes of the building. For installations on balconies or roofs,
the appliance should not be located within 8 feet from chimney
Figure 2.3 Clearances from vent outlets, chimney flues and air intake openings
6 FT. MIN.
8 FT. MIN. 8 FT. MIN. 6 FT. MIN
54”
38”
20
3 System design
3 SYSTEM DESIGN
22
3 System design
1 At standard ARI 590 conditions: 54 °F entering fluid temperature, 44 °F leaving fluid temperature, 95 °F ambient temperature, 0.0005 fouling.
2 Pressure drops may vary with individual glycol manufacturer’s products. The information provided for pressure drop is typical but installing contractor / project engineer is responsible for
verification of pressure drop correction based on specifications of glycol used.
Responsibility of the user/operator/installer always compliant with what reported in Table 3.2 p. 23
or is not.
The installer, operator and user must assure system wa-
ter quality (Table 3.2 p. 23). Failure to comply with the
Table 3.2 Chemical and physical parameters of water
manufacturer's guidelines may affect operation, integ-
rity and life of the appliance, voiding the warranty. Chemical and physical parameters of water in heating/cooling systems
For any further detail, please contact directly Parameter Measurement unit Required value
Robur Corporation Evansville, IN, Phone (812) 424-1800; pH / > 7 (1)
Fax (812) 422-5117. Chlorides ppm < 125 (2)
°f < 15
Total hardness (CaCO3)
System water characteristics °d < 8.4
Free chlorine or water hardness may damage the appliance. Iron ppm < 0.5 (3)
Copper ppm < 0.1 (3)
Adhere to the chemical-physical parameters in Table 3.2 p. 23
Aluminium ppm <1
and the regulations on water treatment for residential and in-
Langelier’s index / 0-0.4
dustrial heating systems.
Harmful substances
Free chlorine ppm < 0.2 (3)
Robur is not liable for ensuring that water quality is
Fluorides ppm <1
24
4 Electrical installer
4 ELECTRICAL INSTALLER
In the following Section please refer to "L" as "L1" and circulating pump with no request from the appliance.
to "N" as "L2".
Isolation relay
The water circulation pump of the water/primary circuit To connect the three-pole power supply cable (Figure
must mandatorily be controlled by the appliance's elec- 4.1 p. 26):
tronic board (S61). It is not admissible to start/stop the 1. Access the electrical board of the appliance according to
the Procedure 4.2 p. 25.
2. Connect the three lead-in wires to the terminal block 4.4 SET-UP AND CONTROL
(TER) in the electrical panel on the machine.
3. Provide the earth ground lead-in wire longer than live
Control systems, options (1) or (2)
ones (last to be torn in the event of accidental pulling).
Two separate control systems are provided, each with spe-
Figure 4.1 W
iring for a single unit with pump absorbed current less cific features, components and diagrams (Figures 4.3 p. 27,
than 4 A 4.6 p. 29):
▶ System (1), with DDC control (with CAN bus connection).
▶ System (2), with an external request.
SCH
CAN bus communication network
The CAN bus communication network, implemented with the
6 cable of the same name, makes it possible to connect and re-
TER motely control one or more Robur appliances with the DDC con-
PUMP trol device.
It entails a certain number of serial nodes, distinguished in:
▶ Intermediate nodes, in variable number.
4 5 ▶ Terminal nodes, always and only two (beginning and end).
Each component of the Robur system, appliance (GAHP, GA, AY,
...) or control device (DDC, RB100, RB200, ...), corresponds to a
3 2
F
GS 1 node, connected to two more elements (if it is an intermedi-
ate node) or to just one other element (if it is a terminal node)
L N
through two/one CAN bus cable section/s, forming an open lin-
1 General switch ear communication network (never star or loop-shaped).
2 Use a 15 A time lag fuse on L wire
3 Ground pin CAN bus signal cable
4 Ground cable has to be connected by a suitable eyelet to the ground The DDC controller is connected to the appliance through the
pin into the electrical panel, and fixed to it by the proper preset nut. CAN bus signal cable, shielded, compliant to Table 4.1 p. 26
5 L, N wiring to the terminal board must be done respecting the correct
(admissible types and maximum distances).
polarity
6 Jumper closed For lengths ≤650 ft and max 4 nodes (e.g. 1 DDC + 3 GAHP), a
simple 3 x 18 AWG shielded cable may even be used.
GND is the common signal wire, and not a ground con- Figure 4.2 Connection of the CAN bus cable to the electronic board
nection.
26
4 Electrical installer
Figure 4.3 CAN bus connection for systems with one unit
A DDC Direct Digital Control
A SCH S61 controller
J1 Jumper CAN bus in board
J21 Jumpers CAN bus on DDC board
GND L H JUMPER J21 H,L,GND Data signal wires (ref. cables table)
P8
A Terminal node connection (3 wires; J1 and
JUMPER J1
H L GND
P8 J21 = "closed")
B CAN bus cable shield
C Insulating tape to protect the shield of the
CAN bus cable
D Eyelet terminal and fixing screw
GND L H
P8
THMFTHRF TCN TA TG TA1 TA2 SRT1 SRT2 JP12
SP1
A2
JTAG
A1
TF
P6
TL
GND
H
L
JP11
F2
FL
1 234 1 23 45 6
3 2 1
24 ac1
6 5 4
J10
DDC
F1
0 V
BK WHBR CONTACT L N L N N L R WY 0
SCH
D
B
Figure 4.4 CAN bus connection for systems with multiple single units
1 23 45 6
1 234
DDC
D
C
E
SCH
A2 A1 TF TL FL 24 ac1 0 V 24ac2
R WY 0
F3
F1
6 5 4
3 2 1
JUMPER J1 JP12
IGN.
NO 230V 230V BOX
N L
SRT2
JTAG
PUMP MAIN
P8
L N
SRT1
THMFTHRF TCN TA TG TA1 TA2
B
BK WHBR CONTACT L N
GND L H
FAN
F2
SCH
A2 A1 TF TL FL 24 ac1 0 V 24ac2
C
B
R WY 0
F3
F1
P8
GND L H
P6
6 5 4
3 2 1
JTAG
L N
BK WH BR CONTACT L N
FAN
Place the CLOSED J21 Jumpers (Detail A) if the node is terminal External request
(one connected CAN bus cable section only), or OPEN (Detail System (2) see also Paragraph 1.6 p. 13.
B) if the node is intermediate (two connected CAN bus cable It is required to arrange:
sections). ▶ Enable device (e.g. thermostat, timer, switch, ...) fitted with a
voltage-free NO contact.
Figure 4.5 Connection of the CAN bus cable to the control panel
How to connect the external request
A B
JUMPER J21 JUMPER J21 Connection of external request is effected on the S61
H L GND H L GND board located in the electrical panel inside the unit
P8 P8
(Figure 4.6 p. 29):
1. Access the electrical board of the appliance according to
DDC DDC the Procedure 4.2 p. 25.
2. Connect the voltage free contact of the external device
(Detail CS), through two wires, to terminals R and Y
(respectively: common 24 V AC and cooling request) of
electronic board S61. It is recommended to use a cable
DDC Direct Digital Control with the correct number of color-coded 18 AWG wires.
GND Common data
L Data signal LOW
H Data signal HIGH
J21 Jumpers CAN bus on DDC board
A Detail of "terminal node" case (3 wires; J21 = jumper "closed")
B Detail of "intermediate node" case (3 wires; J21 = jumper "closed")
P8 CAN port/connector
28
4 Electrical installer
R2
TER
PUMP
4 5
3 2
F
GS 1
SCH Electronic board
L N
R Common
Y Cooling request terminal
Components NOT SUPPLIED 1 General switch
CS External request 2 Use a 15 A time lag fuse on L wire
3 Ground pin
4 Ground cable has to be connected by a suitable eyelet to the ground
pin into the electrical panel, and fixed to it by the proper preset nut.
hermostat location
T 5 L, N wiring to the terminal board must be done respecting the correct
If the external request is a thermostat, it should be located on an polarity
inside wall about 54 inches above the floor. It should be located 6 Jumper open
so that it will no be affected by any of the following items:
▶ discharge air from a supply grille
▶ drafts 4.5.2 Heat recovery exchanger circulating pump
▶ direct sunlight through a window or glass door
To be controlled through a relay available in the electrical board
▶ electrical appliances such as television, radio or lamps
of the appliance (Figure 4.8 p. 30).
The thermostat should be located so that it senses the average
temperature of the climatized space. The thermostat should be
mounted according to the manufacturer’s instructions (pack-
aged with the thermostat). Thermostats using a mercury bulb
switch must be level. If the thermostat has a built-in heating an-
ticipator, this must be set as required by the heating unit load.
Figure 4.8 Recovery exchanger pump connection 4.6 WITH MORE THAN ONE GA ACF UNIT
SP1 GND L H
Figure 4.9 p. 30 shows typical wiring for 2 or more GA ACF
SRT1 SRT2 JP12
P8
units.
THMF
THRF
TCN
TA
TG
TA2
TA1
A2
It is always necessary to provide a safety transformer (secondary
JTAG
A1
SELV) and a respective control relay.
TF
The transformer is required to feed N.O. contacts with low volt-
P6
TL
JP11
age current, for safety reasons: when doing maintenance and a
unit is shut off, these contacts could still remain fed.
F2
FL
0 V 24ac1
J10
3 2 1
6 5 4 F1
In this case, no matter if pump current absorption is more or less
F3
than 4 A.
24ac2
NO PUMP MAIN IGN.
FAN CONTACT 230V 230V BOX R W Y O
BK WH BR L N L N N L
SCH
11
14
R1
BY THE INSTALLER
KPs T
KPc
KPt T
IP
L
PMR
N ~1
3 3
4 4
30
5 First start-up
5 FIRST START-UP
First start-up entails checking/setting up the combus- the control device provided (DDC, or external request).
tion parameters and may exclusively be carried out by ▶ Appliance defects or faults caused during transport or instal-
a Robur AT. NEITHER the user NOR the installation tech- lation.
nician is authorised to perform such operations, under ▶ Gas smell.
penalty of voiding the warranty. ▶ Non-compliant mains gas pressure.
▶ Antifreeze monoethylene glycol not added to the system
water (Paragraph 3.6 p. 23).
▶ All situations that are potentially hazardous.
5.1 PRELIMINARY CHECKS
Should any abnormal installation situations be found, the AT
can carry out the first start-up, but the appliance will be kept
Preliminary checks for first start-up switched off until the user/installer fully follows the manufac-
Upon completing installation, before contacting the AT the in- turer’s directions/instructions.
staller must check: These situations may be:
▶ Water, electrical and gas systems suitable for the required ▶ Installations which show situations in contradiction to the
capacities and equipped with all safety and control devices directions/instructions of the manufacturer in part or fully.
required by the regulations in force. ▶ All situations that may involve operation abnormalities.
▶ Absence of leaks in the water and gas systems.
▶ Type of gas for which the appliance is designed (natural gas Non-compliant system and corrective actions
or LPG). Should the AT find any non-conformities, he must:
▶ Supply gas pressure complying with the values of Table ▶ Inform the user/installer of any installation anomaly.
5.1 p. 32, with max tolerance ±15%. ▶ Inform the user/installer of any situation that is judged to be
▶ Power supply mains complying with the appliance's rating hazardous for the appliance and for people.
plate data. ▶ Inform the user/installer of any missing documentation re-
▶ Appliance correctly installed, according to the manufactur- lating to the system.
er's instructions. ▶ Indicate, in relation to the reports made, any corrective mea-
▶ System installed in a workmanlike manner, according to na- sure to be taken on the plant, which the installer will have to
tional and local regulations. carry out in order to proceed with the first start-up.
Should the AT find any non-conformities, the user/installer is
Before performing the first start-up, the AT is required to: bound to perform any corrective procedures required by the AT.
▶ Check that the whole system has been set up in accordance After performing the remedial actions (the installer's responsi-
with its design, following the instructions supplied by the bility), if the AT deems that safety and conformity conditions are
manufacturer and respecting current regulation. The project in place, first start-up may be effected.
must have been carried out by a skilled professional. The positive result of the first start-up (in site) is only reflect-
▶ Check personally that all of the connections (hydraulic, gas ing the good operation of the appliance and DDC (if used) but
and electrical) of the appliance (and of the DDC, if any) have doesn’t involve any responsibility concerning the correct execu-
been made correctly. tion of the system.
▶ Check that the necessary conditions for system compliance
effectively exist (as per the declaration consigned to the user The length of the warranty is dependent upon the
by the qualified firm that has carried out the installation of installation and start-up of the unit by Authorized
the appliance). Technicians (AT). See warranty card for complete de-
▶ Check that the water pressure and flow in the hydraulic cir- tails.
cuit and the static supply network pressure are correct, as
indicated by the manufacturer.
The declaration of compliance certifies that the system 5.2 FIRST START-UP OPERATIONS
conforms to current regulations. This declaration is a To carry out the first start-up of the appliance, it is necessary to
compulsory document, and as such must be issued by perform the operations described below, proceeding according
law to the owner by the qualified firm that has carried to the following sequential order.
out the installation of the appliance.
First start-up operations
Abnormal or hazardous installation situations ▶ Open the gas supply tap to the system and check that there
Should any hazardous installation situations be found, the AT is no smell of gas (indicating possible leaks).
shall not perform first start-up and the appliance shall not be ▶ Close the gas tap and check the static gas mains pressure
commissioned. (Paragraph 5.3 p. 32).
These situations may be: ▶ Prepare the appliance for the gas pressure adjustment
▶ Appliance installed inside a room. (Paragraph 5.4 p. 32).
▶ Failed compliance with minimum clearances. ▶ Power up the appliance, after:
▶ Insufficient distance from combustible or flammable materi- check one final time that there is no smell of gas
als. activating the external mains switch (GS), provided by
▶ Conditions that do not warrant access and maintenance in the electrical system installer on a suitable panel, mov-
safety. ing it to the ON position
▶ Appliance switched on/off with the main switch, instead of ▶ Power up the DDC, if provided.
▶ Switch on the appliance by means of the provided control Specific gravity of natural gas
device (DDC or external request). MJ/m³ Btu/CU.FT.
0.55 0.60 0.65 0.70
▶ Adjust the gas pressure to the appliance (Paragraph 37.78 1014 2.50
5.4 p. 32).
▶ Check the dynamic gas mains pressure (if possible on the ap- The conditions referred to by the Table 5.1 p. 32 above are for
pliance that is furthest from the point where the system is the guidance of the installer and the CSA design certification
connected to the gas mains), by performing the following does not cover the conditions described therein.
points in order:
stop the appliance For propane gas appliances, follow the same instructions
connect the manometer (Paragraph 5.4 p. 32) as given for natural gas. The manifold pressure for pro-
reactivate the appliance pane gas should be 4.8 inch WC and adjustment is made
read the dynamic mains pressure on the manometer and at the gas valve regulator. Manifold pressure at 94.900
check that this value satisfies the requiments of Table Btu/hr. input using 0.14” nozzle.
5.1 p. 32
▶ Carry out the regulation of the operating parameters of the The following Table 5.2 p. 32 summarizes nozzles and mani-
system. fold pressures for different types of gases.
In the first activation stage, on the display of the electronic
board of the appliance (and/or on the display of the DDC, if any), Table 5.2 Manifold pressure and nozzle diameter
an operating code may be displayed (Table 8.1 p. 40). Gas type natural gas LPG
Manifold pressure 2.5 inch WC 4.8 inch WC
5.3 CHECK THE STATIC GAS MAINS Nozzle diameter 0.21” 0.14”
PRESSURE
Gas pressure adjustment procedure (Figure
Procedure for checking the static gas mains pressure 5.1 p. 32)
(Figure 5.1 p. 32)
1. Turn main gas valve knob to the "OFF" position.
1. Turn main gas valve knob to the "OFF" position. 2. Remove the plug on outlet end of gas valve and attach
2. Remove the plug on the gas pressure intake of gas valve pressure tap and manometer.
and attach pressure tap and manometer. 3. Switch on the appliance and close control switch.
3. Turn main gas valve knob to the "ON" position. 4. Wait for the burner to start up. Due to the presence of
4. Read the value of the static gas mains pressure on the air inside the piping, it may be that the burner does not
manometer and compare it with the required value: start at the first three attempts and, failing to do so, the
– 5 inch WC for natural gas ignition system is locked out. If this happens reset the
– 11 inch WC for LPG ignition system (Paragraph p. 38). Repeat until all the
5. Turn main gas valve knob to the "OFF" position. air is purged from the piping and the burner ignites.
6. Remove manometer and pressure tap. Replace plug in 5. When the burner ignites read the manometer and
gas valve. compare the value to the required pressure (Table
5.1 p. 32).
5.4 GAS PRESSURE ADJUSTMENT 6. If necessary change the manifold pressure using the gas
valve regulator. The regulator is built into the gas valve.
The manufacturer supplies the appliances already adjusted for a Remove the seal screw and turn adjusting screw clock-
particular type of gas. The type of gas can be checked and easily wise to increase pressure or counterclockwise to reduce
identified by looking at the marking label inside the appliance. pressure. Replace seal screw after adjustment.
Nevertheless, before starting the appliance it is necessary to 7. Open control switch and make sure that the appliance
check and adjust if necessary the gas input (HHV) to the burner. is off.
Using the Table 5.1 p. 32 below, arrange the proper manifold 8. Remove manometer and pressure tap. Replace plug in
pressure according to the local gas heating value (BTU content gas valve.
per cubic foot) and specific gravity. Table 5.1 p. 32 is based on 9. Turn on the appliance by closing control switch. Check
the correct natural gas input (HHV) for the model by manifold all gas connections with soap for leaks.
pressure in inches of water column (inch WC).
Figure 5.1 Gas valve
Table 5.1 M
anifold pressure [inch WC] based on gas input (HHV) of
REMOVE CAP SCREW FOR
94.900 Btu/hr using a 0.21" nozzle PRESSURE PRESSURE ADJUSTMENT
REGULATOR
Specific gravity of natural gas ADJUSTMENT OUTLET
MJ/m³ Btu/CU.FT. PRESSURE
0.55 0.60 0.65 0.70 INLET TAP
32
5 First start-up
5.5 GAS CHANGEOVER 9. Adjust the gas pressure for the gas to be used following the
instructions reported in Paragraph 5.4 p. 32.
10. Replace the sticker indicating the type of gas for which the
Only an authorised technician can perform the gas unit is preset with the new one, which indicates the type ac-
change operation. tually being used.
If the type of gas indicated does not correspond to the type to
Figure 5.2 Gas valve
be used (natural or propane gas) by the appliance, it must be
converted and adapted to the type of gas to be used.
The gas nozzle must be changed (Table 5.2 p. 32) and the gas
valve must be converted.
Gas change procedure (Figure 5.3 p. 33)
F
F
A
air/gas
mixer
B B
G
C
gas valve G
H
D C E
Firmware
The appliance's electronic board (S61) display and setting (parameters) or control (reset).
The menu entries will be identified on the display of the elec-
Figure 5.4 Electronic board S61 tronic control board through a number, where its maximum
value is 3 digits (lined up at right).
A C The visualization is characterized by the presence (on the 1st
digit of display) of the menu identification number (example:
indicates entry 0, menu 0; indicates entry 2,
B menu 0).
Menu for the user (but for the installer and AT as well)
▶ The menu "0.", display only, for functional data detected in
real time.
▶ The menu "1.", display only, for current values of appliance
parameters.
▶ Menu "2.", control, to execute flame control unit reset opera-
tions, reset errors (Paragraph 7.5 p. 38).
▶ Menu "3.", display and setting, to set the value of some sys-
The S61 electronic control board has three fuses for cir- tem parameters (e.g. water setpoint temperature); the val-
cuit protection. If the electronic control board does not ues are initialized by the AT at first start-up.
start up or the finned coil fan does not run, remove power It is accessed without password.
from the unit and check the condition of the fuses. Menu for the installer or AT (not accessible to the user)
▶ Menu "4.", "5.", "6." and "9." are password-protected. These are
The S61 board requires a 10 A (condenser fan) and two specific sections, exclusively intended for qualified person-
2 A fuses (electrical board). The size of the fuse is labeled nel (installer or AT).
on the electronic control board next to the respective ▶ Menu "7." is display only and intended for the manufacturer.
fuse holder. ▶ Menu "8." is empty, it may be selected but not used.
The maximum current carrying capacity of the N.O. Special key for the knob
Contact is 4 A. (Paragraph 4.5 p. 29).
To access the menus and parameters of the S61 board,
use the special standard supplied key. The key allows the
Isolation relay knob to be operated through the suitable hole in the
electrical panel cover, operating safely away from live
An isolation relay must be used to separate the appli- components.
ance’s transformer from any additional equipment hav- Always keep the key for future uses.
ing a transformer or damage to the S61 board will occur.
Isolation relays must have a 24 V AC coil, which does not How to access the menus and parameters
present more than 0.25 A load to the control circuit.
Before Starting:
Display (1) Power supply switch on.
The 4-digit display of the S61 board (Detail A Figure 5.4 p. 34) (2) Display of the S61 board showing in sequence the
is as follows: detected water temperature data (if the appliance is in
▶ The first digit (on the left, green) indicates the menu num- normal operation), or the flashing malfunction and fail-
ber (e.g. "0.", "1.", "2.", ... "8."). ure codes (if the appliance is in failure).
▶ The last three digits (on the right, red) indicate a code or a To access the menus and parameters of the S61 board,
value for a parameter, among those included in the selected proceed as follows (see also Figure 5.4 p. 34):
menu (e.g. "__6" "_20", "161"). 1. Remove the front panel by removing the fixing screws.
(e.g. menu+parameter "1.__6", "2._20", "3.161"). 2. Remove the cover of the electrical board to access the
S61 board knob.
Knob 3. Act on the knob by means of the special key through the
One of the following actions may be done with the S61 board suitable hole.
knob (Detail B in Figure 5.4 p. 34): 4. Press the knob once to display the menus: the first menu
▶ Enter the menu list (by pressing the first time). is displayed, "0." (= menu 0).
▶ Scroll the menu list, or a series of parameters in a menu (by 5. Turn the knob clockwise to scroll down and display the
turning). other/subsequent menus; the menu numbers will be
▶ Select a menu or a parameter (by pressing). displayed in order, "1.", "2.", ... , "6." ... or "E" (= exit).
▶ Modify and confirm the setting of a parameter (turning and 6. Select the menu of interest (e.g. display "2.___" = menu
pressing). 2) by pressing the knob; the first parameter code will be
▶ Execute a command (by pressing). displayed, in menu order (e.g. display "2._20" = param-
▶ Exit a menu and go back to the higher level by selecting the eter 20 in menu 2).
letter “E” which is displayed at the end of the menu list or of 7. Turn the knob clockwise to scroll down the other param-
a series of parameters in a menu. eters in the menu; the codes will be displayed in order
The letter "E" is displayed at the end of the menu list or of a series (e.g. display "2._20", "2._21", ... "2._25" = parameters 20,
of parameters in a menu, and indicates the exit to go back to the 21, ... 25 in menu 2), or letter "E" (= exit) at the end of
higher level by pressing the knob. the list.
8. Select the parameter of interest (e.g. with code 075 in
Menus and Parameters menu 3) by pressing the knob; the figure previously as-
The menus may be display only (functional data or parameters), signed to the parameter will be displayed, read only or to
34
5 First start-up
be set (e.g. the figure "44" for parameter 075 in menu 3 flame are constantly monitored to assure proper system opera-
= water temperature setpoint at 44 °F); if instead of a fig- tion. When the call for flame has ended (24 V removed from “W”
ure/setting it is a command, a blinking code is displayed terminal on ignition control), the gas valve is de-energized im-
(e.g. "reS1" for the flame lockout reset command). mediately. The ignition control then senses loss of flame and de-
9. Press the knob to reconfirm the figure; or rotate the knob energizes the pre-mixer blower.
to modify the figure, and press at the end to confirm or To reset the flame controller lockout, refer to the procedure giv-
set the new figure; if however, it is a matter of controlling en in Paragraph p. 38.
an appliance operation, press the knob to execute it.
10. To exit a parameter menu or the menu list and go back
5.7 MODIFYING SETTINGS
to the higher level, turn the knob to display the letter "E"
for exit, then press the knob again.
11. Place the cover back on the electrical panel opening and Modify settings via the DDC
fit the appliance's front panel back on. If the device is connected to the DDC control, refer to the
relevant manual to modify settings.
5.6.1 Flame controller
If any information (menu, menu entries, parameters
Figure 5.5 Flame controller and/or values, etc.) is visualized on the display in flashing
mode, it means that this information couldn’t be entered.
FC±
DIAGNOSTIC LED When information is not available, the display visualizes
.
“W” TERMINAL
“R” TERMINAL How to raise/lower the water temperature setpoint
The water temperature setpoint establishes the outlet tempera-
ture to the system (water output from the appliance), or inlet
from the system (water input in the appliance). The temperature
is pre-set by the AT upon first start-up.
If the appliance is not connected to a DDC control, to
When power is supplied to the appliance (to the “R” terminal on
raise/lower the water temperature setpoint with the S61
the ignition control box), ignition control will reset, perform a
board, proceed as follows:
self-check routine, flash the diagnostic LED, and enter thermo-
stat scan state.
When the control switch is closed, the electronic control board 1. Access menu 3 under parameter 75 (= water tempera-
will energize the ignition control box starting the ignition se- ture setpoint) by rotating and pressing the knob; "3._75"
quence (24 V applied to the “W” terminal on the ignition box). must be displayed (procedure Paragraph 5.6 p. 33).
The ignition control box will check the differential air pressure 2. Display the parameter value by pressing the knob; the
switch for open contacts. If the differential air pressure switch previously set value is displayed (from 37.4 to 77 °F); to
contacts are closed and stay closed for 30 seconds, an airflow reconfirm the pre-existing value press the knob again,
fault will show. The diagnostic LED on the ignition control box otherwise go to step 3.
indicates this fault. In this mode, the ignition control box pre- 3. Turn the knob to modify the value, increasing or decreas-
mixer blower will not start. ing it, and press it to set the new value.
If the pressure switch contacts are open, the ignition control box 4. Exit menu 3, and from the menu list, by selecting and
pre-mixer blower will instead start. An airflow fault will occur pressing letter "E" twice, and go back to the normal dis-
if the air pressure switch contacts remain open for 30 seconds play of detected temperature data.
after the pre-mixer blower start. The diagnostic LED on the igni-
tion control box indicates this fault. In this mode, the ignition Do not modify complex settings
control box will keep the pre-mixer blower energized.
If the air pressure switch contacts close after the pre-mixer blow- Specific technical and system knowledge is required for
er starts (normal operation), a pre-purge delay begins and the complex settings. Contact an AT.
ignition sequence continues.
Next, the ignition control box energizes an ignition transformer
that generates a high-intensity spark at the igniter to ignite the
gas/air mixture. Simultaneously, the gas valve is energized, al-
lowing the flow of gas to the burner.
The ignition control box continuously monitors the flame sen-
sor for ignition. If the flame sensor detects flame, the ignition
transformer is de-energized immediately and the gas valve and
pre-mixer blower remain energized.
Should the burner fail to light, or flame is not detected during
the first trial for ignition, the gas valve and ignition transformer
are de-energized and the ignition control box begins an inter-
purge delay before another ignition attempt. The control will
attempt two additional ignition trials (total of 3 ignition trials)
before going into lockout. Upon lockout, the gas valve will de-
energize immediately and the pre-mixer blower will turn off.
The thermostat (“W” terminal), air pressure switch and burner
6 NORMAL OPERATION
This section is for the end user. chilled water, according to climate control needs.
▶ If the appliance is controlled by a DDC, refer to the relevant
manual.
▶ If the appliance is controlled by external request (e.g. ther-
6.1 WARNINGS
mostat, timer, switch, ... with voltage-free NO contact), the
appliance is switched on/off by the ON/OFF positions of the
General warnings external control device.
Do not switch the appliance on/off with the power sup- Do not modify complex settings
ply switch. This may be harmful and dangerous for the
appliance and for the system. Specific technical and system knowledge is required for
complex settings. Contact an AT.
Checks before switching on
6.4 EFFICIENCY
Before switching on the appliance, ensue that:
gas valve open For increased appliance efficiency:
appliance electrical power supply (main switch (GS) ON) ▶ Keep the finned coil clean.
DDC power supply (if any) ▶ Set minimum water temperature to the actual system re-
water circuit ready quirement.
▶ Reduce repeated switch-ons to the minimum (low loads).
How to switch on/off ▶ Program appliance activation for actual periods of use.
The appliance may be turned on/off in cooling mode, to produce ▶ Keep water and air filters on plumbing and ventilation sys-
tems clean.
7 MAINTENANCE
36
7 Maintenance
appliance by means of the control device (DDC or ex- Figure 7.1 Section view showing proper fan height
ternal request) and wait for the end of the shutdown
cycle, then disconnect power and gas supply, by acting 3
on the electrical disconnector and gas valve.
1” 1/4
Lubrication of condenser fan, hydraulic pump, and pre-
mixer motor is not recommended.
2
The efficiency checks and every other "check and main- 1
tenance operation" must be performed once a year.
1 Section view
2 Mounting strap
Responsibility for efficiency checks, to be carried out for 3 Fan blade edge - top panel
Note: some details have been removed for clarity
the aims of restricting energy consumption, lies with the
system manager.
7.2.2 Condenser fan height check 6. Pry bottom of burner tube out to clear bottom of generator
For proper airflow, the distance between the top edge of the fan housing. Pull burner down and out to remove it from gen-
blade and the top panel must be 1” 1/4. erator housing.
If the fan is at an improper height, adjust the location of the
mounting strap around the fan motor. Be careful not to distort or damage the burner tube or
the flame sensor / ignition electrodes assemblies in the
Make sure the two gaskets are positioned correctly and Locked-out appliance
that the generator housing is properly sealed. An external intervention (reset or repair) is required due to an
appliance fault or problem with the system.
11. Replace the front panel. ▶ A reset may be enough for a temporary and provisional fault.
12. Restore the gas and electrical supply. ▶ For a fault or breakdown, alert the maintenance technician
13. Start the appliance to check for correct operation. or AT.
Reset
7.3 EXTRAORDINARY MAINTENANCE
There are two options for resetting a fault:
1. If the appliance is connected to a DDC you may act through
The operations described in this paragraph must be car- the control device, as described in the relevant manual.
ried out as and when necessary. 2. You may act directly from the S61 board as described below
(if the appliance is controlled with external request, this is
▶ Adding water and antifreeze to the system water the only option).
If it should be necessary to add water to the system, add a suit-
able quantity, making sure that the minimum pressure is the re- How to perform reset from the S61 board
quired one (Paragraph 3.8 p. 24).
Always add the correct amount of antifreeze glycol, depending To perform the reset directly from the S61 board:
on the minimum external temperature of the installation area 1. Access Menu 2 under Parameter "__0", to reset flame lock-
(Paragraph 3.6 p. 23). out (Error E12), or Parameter "__1" for any other generic
reset, turning and pressing the knob; "2.__0"/"2.__1"
must be displayed (procedure Paragraph 5.6 p. 33).
7.4 MESSAGES ON THE DISPLAY 2. Press the knob to display the flashing reset request (e.g.
"reS1" to reset flame block).
4 digit display 3. Press the knob again (the second time) to perform the
The S61 board of the appliance (Paragraph 1.5 p. 12, Figure reset; the reset request stops blinking, then "2._XX" is
5.4 p. 34) is fitted with a 4-digit display, visible through the displayed again (e.g. "2.__0"). The reset operation has
sight glass of the front panel. been performed.
▶ When the appliance is powered on, all the LEDs switch on for
4. Exit menu 2 and the menu list, by selecting and press-
3 sec, then the board name is displayed. ing letter "E" twice, and go back to the normal display of
▶ After another 15 sec, the appliance is ready to operate.
detected temperature data.
If, after these operations have been carried out, the appliance
Signals in normal operation does not start, first perform the following simple checks:
▶ Check that any external CS request (Paragraph p. 28) or
▶ During normal operation, water temperature values alter-
that the DDC (if connected and in controller mode) is in a
nate on the display: output, input and the difference be-
position that requires the operation of the appliance.
tween the two.
▶ Make sure that the main power supply switch (GS) fitted
Signals in the event of fault by the electrical installation technician on a suitable panel
(Figure 4.1 p. 26) is in the ON position.
In the event of fault the display blinks indicating an operational
▶ Check that the gas supply valve is open.
code (first letter on the display: "E" = error, or "U" = warning).
▶ Check that there are no further messages on the display.
The display rotates after the values of the outlet water tempera-
At this point, if the appliance still fails to start:
ture, the inlet and the difference between them.
▶ Refrain from proceeding by trials and errors. Instead, ask an
If multiple events are active, they are shown in sequence, or-
AT to intervene, communicating the operating code report-
dered by increasing code number.
ed by the appliance.
If warning or error events are active, the left green symbol,
▶ Disconnect the appliance from the gas and electric mains,
shown together with water temperature data, blinks.
interrupting the gas supply by means of the tap and the
If it is a permanent error or warning the appliance stops.
power supply by means of the main switch/disconnector
(Table 8.1 p. 40).
switch (Detail GS in Figure 4.1 p. 26).
▶ Wait for the contacted AT to arrive.
7.5 RESTARTING A LOCKED-OUT UNIT
38
7 Maintenance
7.6 PERIODS OF INACTIVITY disconnected from the power and gas mains, the active
antifreeze protection is missing, Paragraph 3.5 p. 23).
Avoid emptying the installation How to reactivate the appliance after long periods of
inactivity
Emptying the system may cause damage due to corro-
sion of the water pipes. Assure at least one of the two Before reactivating the appliance, the operator/mainte-
following conditions: nance technician of the system must first of all:
1. sufficient antifreeze glycol (Paragraph 3.6 p. 23) Check whether any maintenance operations are required
2. empty the system, however taking care to fill it again fol- (contact the AT; see Paragraph 7.2 p. 37).
lowing the instructions in Paragraph 3.8 p. 24 Check content and quality of the water in the system, and
if necessary top it up (Paragraphs 3.8 p. 24, 3.7 p. 23
Prolonged periods of inactivity and 3.6 p. 23).
▶ Should you foresee to leave the appliance inactive for a long Ensure the flue gas exhaust duct is not obstructed, and
period of time, disconnect it from the electrical and gas that the condensate drain is clean.
mains. These operations must be performed by qualified After completing the above checks:
personnel. 1. Open the gas valve and ensure there are no leaks; should
gas smell be noticed, close the gas valve again, do not
How to deactivate the appliance for long periods of switch any electrical devices on and request intervention
time by qualified personnel.
2. Power on with the main power supply switch (GS, Figure
1. Switch the appliance off (Paragraph 6.2 p. 36). 4.1 p. 26).
2. Only when the appliance is completely off, power it off 3. Switch on the appliance by means of the provided
with the main switch/disconnector switch (Detail GS in control device (DDC or external request, Paragraph
Figure 4.1 p. 26). 4.4 p. 26).
3. Close the gas valve.
4. If necessary, add water with glycol (if the appliance is
8 DIAGNOSTICS
Diagnostics
8.1 OPERATIVE CODES
8
8
Code Description Warning Error Possible causes / Checks
Broken or short in sensor wire
Outlet chilled water temperature sensor faulty
16 NA Error can be reset via S61, DDC or power off Possible bad connection at control board
(THM)
If the problem persists, contact AT
Broken or short in sensor wire
Inlet chilled water temperature sensor faulty
17 NA Error can be reset via S61, DDC or power off Possible bad connection at control board
(THR)
If the problem persists, contact AT
Broken or short in sensor wire
Condenser outlet temperature sensor faulty
18 NA Error can be reset via S61, DDC or power off Possible bad connection at control board
(TCN)
If the problem persists, contact AT
Broken or short in sensor wire
Condenser inlet temperature sensor faulty
20 NA Error can be reset via S61, DDC or power off Possible bad connection at control board
(TG)
If the problem persists, contact AT
Installation, use and maintenance manual – GA ACF
Diagnostics
New parameter setting is required
85 Incorrect unit types NA Error can be reset via power off
If the problem persists, contact AT
41
42
Diagnostics
Code Description Warning Error Possible causes / Checks
86
87
Electronic board fault NA Error can be reset via power off If the problem persists, contact AT
88
89
Broken or short in sensor wire
90 Ambient temperature sensor fault (TA) NA Error can be reset via S61, DDC or power off Possible bad connection at control board
If the problem persists, contact AT
91 Electronic board fault NA Error can be reset via power off If the problem persists, contact AT
8
11/06/2020