Академический Документы
Профессиональный Документы
Культура Документы
Pureballast 30 Flow 1000
Pureballast 30 Flow 1000
System Manual
English
PureBallast: Ballast Water Table of Contents
Treatment System
Safety 1
System Description 2
Printed 2014
Alfa Laval reserves the right to make changes at any time without prior notice.
Any comments regarding possible errors and omissions or suggestions for improvement of this
publication would be gratefully appreciated.
Copies of this publication can be ordered from your local AlfaLaval company.
Published by: : Alfa Laval Tumba AB
E-147 80 Tumba, Schweden
Telefon: +46 8 530 650 00
Telefax: +46 8 530 310 40
2 Safety information 7
2.1 General safety information 7
2.2 Specif c safety information 7
2.3 Personnel requirements 9
2.4 Warning signs used in the manual 9
3 Environmental issues 11
3.1 Unpacking 11
3.2 Other materials 11
3
1 Introduction
This chapter contains general safety and environmental information, personnel requirements and
explanations of symbols used for the PureBallast system.
This section contains safety information. This information must be read and understood before the
system is installed, operated and maintained.
• The PureBallast system is not EX proofed and must not be installed in areas where an
explosive atmosphere may occur.
• Use the equipment only for the purpose and parameter range specified by Alfa Laval.
• Use only Alfa Laval genuine spare parts.
• Always read and follow the documentation that is included in shipment of components and
spare parts regarding handling, safety and disposal.
• Mobile cell phones must not be switched on within an area of 1 meter from an open cabinet door.
• Before installation, read applicable sections in chapter 6. Installation instruction and drawings.
• Before operation, read the Preparations and conditions section for applicable instructions in
chapter 3. Operating instructions and control system description.
2.2 Specif c safety information
The following safety information apply for the areas and components below. This information is also
stated in the Preparations and conditions section for applicable instructions.
• Before maintenance, read the Preparations and conditions section for applicable instructions in
chapter 7. Service manual. Essential safety information is stated before instruction to routines
that might involve any danger.
• Before maintaining the PureBallast system, the following valves must be locked in closed
position: V201-3, V201-9, and V201-8.
• Components must be lifted using correct lifting tools (such as a fork-lift truck, a crane) and tackle
with a load capacity greater than the weight of the component. See the Technical data section
on page for information about weight. Any complementary lifting instructions must be followed.
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
Reactor module safety items
• Cut hazards: Sharp edges on broken UV lamps and quartz sleeves can cause cuts. Exercise
great care when handling them.
• Before installation, check that the UV lamps and quartz sleeves are not broken.
• Depressurize reactors and allow equipment to cool down completely before disassembling. Hot
water may escape from the reactor when removing the drain plug.
• Never handle UV lamps before they are completely cooled down. A hot UV lamp is under
high internal pressure, and the risk of bursting exists. A hot lamp could also cause a burn
if it is touched.
• The reactor must not be under pressure when dismounting the UV lamps.
• UV lamps radiate ultraviolet radiation when lit. Only operate the UV lamp when correctly
installed inside the reactor with end caps properly closed.
• UV lamps contain a small amount of mercury (less than 0.2 grams per lamp) and must be
handled with care. Please refer to national regulations regarding disposal of used lamps. If
a UV lamp is broken, mercury could be spilt. Remove mercury with a special tool such as a
syringe (or use pure sulphure to bind the mercury for easy collection).
• Potential hazards / Grounding: The mains protective grounding wire must be connected to the
terminals in accordance with the diagram (class 1 power supply).
Valve safety items
• Actuators must not be pressurized at any time during installation as it may result in injury.
• Lock valve in closed position before maintenance.
CIP safety items
• CIP liquid: Risk for eye and skin irritation. Avoid contact with eyes and wear protective
gloves. Follow general rules when handling of cleaning agents regarding ventilation, personal
protection etc.
• Before disassembling the pump, the pneumatic hoses must be disconnected, and the extension
pipe must be removed and blocked.
• Always wear protective eye glasses and gloves while working on the pump.
Ancillary component safety items
• Control panels may only be cleaned when set in wipe mode. This is to prevent unintended
functions from being triggered by buttons pressed during cleaning.
• Temperature switch, temperature transmitter and level switch. The external surface may be hot.
Care must be taken to avoid possible burns.
Personnel installing, maintaining or repairing components must be of one of the following categories:
DANGER
!
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
NG
WARNI
!
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
ON
CAUTI
!
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
NOTE
NOTE indicates a potentially hazardous situation which, if not avoided, may result in property damage.
This section contains general rules regarding environmental issues. However, local rules and
regulations should be consulted for detailed handling of each material.
3.1 Unpacking
• Packing material consists of wood, plastics, cardboard boxes and in some cases metal straps.
• Wood and cardboard boxes can be reused, recycled or used for energy recovery.
• Plastics should be recycled or burnt at a licensed waste incineration plant.
• Metal straps should be sent for material recycling.
3.2 Other materials
• Rubber and plastics should be burnt at a licensed waste incineration plant. If not available they
should be disposed to a suitable licensed land fill site.
• Metal parts should be sent to a licensed handler for material recycling.
• Seal rings should be disposed of in a licensed land fill site. Check the local regulations.
• Worn out or defected electronic components should be sent to a licensed handler for material
recycling.
• The operator panel contain the following components with substances that might be hazardous
to health and the environment: lithium battery, electrolytic capacitor and display. They shall
be recycled according to local regulations.
• Used lithium batteries from the control unit are considered hazardous waste and should be
disposed of accordingly.
• Used UV lamps can be handled and disposed of in the same way as fluorescent lamps. Please
refer to national regulations.
• Used quarts sleeves should be disposed of as ordinary glass.
2 Process overview 9
2.1 Start-up 10
2.2 Ballasting 11
2.2.1 Power optimization 11
2.2.2 Backflush 12
2.2.3 Ballast after-treatment (CIP) 14
2.3 Deballasting 15
2.3.1 Deballast after-treatment (CIP) 15
3.3 Filter 24
3.3.1 Filter working principle 24
3.3.2 Filter description 24
3.3.3 Backflushing for different dirt loads 27
3
3.6 Main valves 33
3.7 Flow meter 34
3.8 Pressure monitoring device 34
3.9 Sampling devices 34
4
1 Introduction
This contains general information about the PureBallast system and its components.
2 SystemOverview
Not in illustration:
The UV lamps are powered by the LDC (via LPSs, lamp power supplies). The AOT reactor has
one dedicated LDC.
Flow is monitored by the flow meter and regulated by the control valve. The control valve also
regulates pressure during backflushing of the filter.
The AOT reactors are cleaned using the CIP (cleaning-in-place) module, which first rinse the AOT
reactor with fresh water, and then circulates CIP liquid through the AOT. At the end of the process
the AOT reactor and the filter (filter preservation) is filled with fresh water from the CIP.
The complete system and ongoing processes is controlled and monitored from the control cabinet.
Control can also be performed from remote control panels and the ship’s ISCS, via the remote
interface.
The by-pass valve makes it possible to by-pass the entire system, for example to secure ballast
operation if the system is not functioning. The valve is controlled from the ISCS (integrated ship
control system).
1.3 Abbreviations
The table below is a list of abbreviations used in this manual.
Abbreviation Explanation
AOT reactor The main component, where the water is treated using advanced
oxidation technology
Abbreviation Explanation
EX Explosion-proof
UV Ultra violet
This section gives an overview of the main processes performed by PureBallast. In the flow chart
illustrations, involved pipes are marked in bold.
2.1 Start-up
Ballasting and deballasting begins with a start-up phase. There must be available power for
the system. If power management is integrated, this will be confirmed automatically. If power
management is not integrated, this is confirmed manually.
During start-up, the UV lamps are warmed up for 90 seconds. Cooling water is pumped through the
AOT reactor to secure that the UV lamps are not overheated. The flow is monitored by the flow
meter to secure that there is enough flow to cool the UV lamps. If flow deviates from parameter set
values, an alarm is issued and the system is shut down.
2 Startup
2.2 Ballasting
After the start-up, when the lamps are ready, the operator is requested to start the ballast pump.
The ballast water is pumped from the sea chest to the filter, that removes larger particles and
organisms. This also reduces the amount of sediment build-up in the ballast water tanks. The
organisms and sediments caught in the filter are flushed overboard via regular filter backflush
operations. The water is finally led to the AOT reactor, which produces radicals and UV light
that breaks down and neutralize the organisms.
2 FullBallast
Ballasting
The purpose is to save power by dimming the lamps to minimum power required to fully treat the
water. The UV lamps are regulated individual on all AOT reactors between 50 % and 100 % of
full effect.
• During start-up and the first two minutes of ballast/deballast, the UV lamps are lit to 100 % to
ensure treatment before values from the UV sensor are stable.
• Pause: UV lamps are dimmed to 50 % during pause and lit to 100 % for 2 minutes when
process is resumed.
• Stop: UV lamps are lit to 100 % for 10 seconds before they are stopped. This will prolong
the life of the lamps.
• Low UV intensity: See Actions at low UV intensity below.
• Broken UV lamps: See Operation with broken UV lamp below.
If the UV intensity falls below minimum (defined in parameter p221) for one AOT reactor, a warning
is issued, but process continues. When UV intensity falls below limit defined in the type certificate,
a new warning is issued and a log is written to the event log. The operation continues but does
not fullfill the type approval certificate. However, the flow is decreased so that the treatment shall
correspond to the type approval requirements. The operator will have do decide to continue or
stop the operation.
If a UV lamp breakes a warning is issued and a log is written to the event log. The operation
continues but does not fullfill the type approval certificate. However, the flow is decreased to 80 %
of current flow for all AOT reactors and the UV lamps are lit to 100 %. These actions are taken so
that the treatment shall correspond to the type approval requirements.
2 Back-flush
Filter backflush
The AOT reactors are cleaned one at a time. First, the AOT reactor is rinsed with fresh water. Then
the cleaning-in-place (CIP) module circulates a biodegradable solution through the AOT reactor to
remove seawater scaling. After the cleaning is finished, the AOT reactor is filled with fresh water to
preserve the filter and prevent scaling, algae growth etc. Then the system continues with the same
procedure for the next AOT reactor. Finally, the filter is filled with fresh water to prevent scaling and
algea growth. The cleaning liquid is reused between the cleaning operations.
2 CIP
CIP process
2.3 Deballasting
After the start-up, when the lamps are ready, the operator is requested to start the ballast pump.
The water passes through the AOT reactor, but the the filter is bypassed since the water has
already been filtered during ballasting. The reason for treating the water a second time during
deballasting is to secure that the treatment is fully effective. The minor part of the organisms, which
were only injured during ballast, will be rendered totally harmless during the deballast.
The process flow and power optimization are controlled in the same way as during ballasting.
2 FullDeballast
Deballasting
The water used in the stripping process, must be filtered from particles larger than approximately 5
mm. The water passes through the PureBallast system as a regular deballasting process (with
the filter by-passed). The water is finally pumped into the sea.
If the system malfunction in connection with general cargo operation, ballast and deballast
operations should be avoided. In case untreated water is pumped to a ballast tank, this water shall
be discharged on open sea (according to regulations) and exchanged for treated water. Note that
full treatment requires treatment both during ballast and deballast.
The procedures concerning emergency and malfunction of the ballast water treatment system
should be implemented in the ships Ballast water management plan.
This section gives an introduction to the most important PureBallast system components and
their functions in the system.
2 10_2_1_1 Cell
1. Radical
2. Cell membrane
There are no chemical substances added to the process, and there are no toxic residuals created.
Since the water is not affected chemically there are no environmental impact, and the process does
not influence corrosion in any way.
The UV lamps get very warm, so they must be cooled whenever they are lit. To secure that there is
water in the reactor when the lamps are lit, each reactor is equipped with a level switch. The level
switch also secures that enough CIP liquid is pumped into the reactor during the CIP process. To
secure that the lamps are adequately cooled by the ballast water, each AOT reactor is equipped
with one temperature transmitter that shut down the reactor at 60 °C, completed with a temperature
switch that automatically shuts down the reactor if the temperature reaches 65 °C.
A UV sensor monitors the UV lamp efficiency in relation to the water transmittance inside the AOT
reactor. Based on this input, the power to the UV lamps are regulated between 50 and 100 % of full
capacity. The UV lamps will be dimmed to lowest possible level, where they are still effective.
Note, that the lamps are always lit with full effect during start-up and the first two minutes of full
ballast to secure full efficiency independent of transmittance. The lamps are also turned up to full
effect for 10 seconds before stop and normal shut down. This method will prolong the UV lamp life
time.
The illustration below show the main components for the AOT reactor.
AOT reactor
The humidity in the cabinet is monitored by a liquid sensor. If a leakage from the heat exchanger
is detected, a warning is issued, the reactor is shut down and the cooling water inlet valve to
the LDC is shut.
The LDC can be placed up to 150 meters (cable length) from the AOT reactor. The main breaker
cut the power to the LDC and the AOT reactor.
2 LDC
1. Fan
2. Heat exchanger
3. Lamp power supplies (LPS)
4. Fuses
5. Cooling water inlet and outlet
6. Main breaker
7. Status lights and reset button
3.3 Filter
2 FilterHydac
1. Geared motor
2. Water outlet
3. Pressure transmitter, outlet
4. Filter control cabinet.
5. Pressure transmitter, backflush line
6. Backflush outlet
7. Pressure transmitter, inlet
8. Water inlet
To secure efficient filtration, the filter performs a self-rinsing backflush operation at time set intervals
or when triggered by indication of dirt in the filter. Pressure drop over the filter is monitored by
pressure transmitters on the filter inlet and outlet. Dirt is detected by an increased differential
pressure drop caused by particles in the filter. When the differential pressure reaches a parameter
set value, an automatic backflush operation starts.
The backflushing does not interrupt the filtration process, since all filter candles are not cleaned
at the same time. The not cleaned filter candles continue the filtration of the ballast water. It is
also possible to start backflush manually from the control system.
Step 1: The flushing arm is positioned under the first filter candle to be backflushed. The purpose
of the flushing arm is to collect the backflush water and lead it, with the flushed particles, to the
backflush line. From this point, this filter candle is not used for filtering.
A valve on top of the filter candle is opened to
lead water through the filter candle from the top
downwards. The water flow through the filter
candle down to the flushing arm, flushes particles
from the filter candle walls and lead them to the
backflush line.
2 BackFlush1
2 BackFlush2
In water with low dirt load, the backflush cycle is started by the time trigger (default: every 30
minutes). As long as the pressure is below 0.85 (0.085 MPa) bar, there is no need for the pressure
triggered backflush. See examples below.
6 Dirtload1 Hydac
6 Dirtload2 Hydac
In more dirty waters the backflush cycle will be triggered when pfilter reaches 0.85 bar, which
indicates dirt in the filter candles.
After each backflush, the backflush timer is reset. The filter will be backflushed again after 30
minutes or when ∆pfilterreaches 0.85 bar, whichever comes first.
In the example below, three backflushes are triggered due to high differential pressure over the filter.
After that, there is not so much dirt build up, so the next backflush is performed after 30 minutes.
6 Dirtload3 Hydac
In conditions with heavy dirtload, the system will perform more frequent backflushes to keep the
filter clean.
Also, the 0.85 limit might be exceeded. In this case the self rinsing cycle will run continuously
until the problem is solved and the pressure has returned below 0.85 bar. It is OK that the flow
momentarily fluctuates in an irregular curve, but it is important that the curve stabilizes.
In the example below, a series of backflushes are performed (approx. every 4 minute). After that
the pressure rises above 0.85 where the filter is backflushed constantly. After that, the normal
control is resumed, where the filter backflush is triggered by pressure (2 times) or by time (last
backflush in the example.
6 Dirtload4 Hydac
Over time, the filter candles will undergo a long term build-up of particles that are not removed by
backflushing. One effect of this is that “normal” pressure will increase over time. Therefore, the
maintenance schedule state that the candles shall be inspected and manually cleaned once a year.
The extent of the long term dirt build-up is dependent on the water conditions. In the great majority
of cases this will not cause any problems – cleaning once a year is enough. But in exceptional
cases (vessels trading very muddy waters) it might be necessary to clean the filter candles more
often. If the pressure triggered backflushing is performed with short intervals, we suggest that the
filter candles are manually cleaned more often than once year.
During a cleaning cycle, the CIP module rinse the reactor with fresh water and circulates a CIP
liquid through the AOT reactor. The low-pH CIP liquid removes scaling, calcium chlorides, metal ion
build-up and chemical fouling on the lamps’ quartz glass sleeves. After finished cycle, the liquid
is returned to the CIP module tank; the CIP liquid is reusable for a great number of cycles. The
sequence is finalized by filling the AOT reactor with fresh water. A backflow preventer secures
that no CIP liquid is mixed with the fresh water.
To secure that there is enough CIP liquid for the process, the level switch in the reactor indicates
when it is filled with CIP liquid. To prevent intrusion of water in the fresh water system, a backflow
preventer is used in the CIP module.
• Pump P320-1 circulates the CIP liquid in the AOT reactor and fills it with fresh water.
• Pump P321-5 drains water (sea and fresh water) overboard from the reactor, via the drain line.
2 CIP module
CIP module
1. Deaeration valve
2. Valve block
3. Regulator
4. Pump (CIP liquid)
5. Backflow preventer
6. Pump (reactor drain)
7. Tank for CIP liquid
2 CC
The control system store all alarms and relevant events for at least 24 months. The memory has
a vast safety margin but when it is full, data will be deleted starting with the oldest logs. Logged
information can be exported to a USB memory stick.
There are three alternative ways to monitor and control PureBallast: Main panel, remote control
panel (optional) and remote interface (optional).
If two PureBallast systems are installed on a vessel, two control systems are needed.
every aspect of the control system. It allows the operator to monitor the system, to operate it
manually and automatically, and to set parameters. Please note that some of the operations are
password-protected.
2 MainPanel
2 RCP
Note that Alfa Laval does not supply the graphical user interface to handle PureBallast in the
ISCS, only the means to enable the integration.
2 RI
PureBallast control system’s main control panel integrated with the ISCS. The interface is only an example.
• Inlet valves: The inlet valves directs the water flow from the vessel’s ballast water system into
the PureBallast system. Different valves are used during ballast and deballast.
- System and f lter inlet valve (201–3): Inlet valve to PureBallast during ballast. The valve
directs the water flow through the PureBallast filter.
- Filter outlet valve (V201–32): The valve directs the water flow from the filter to the AOT
reactor during ballast.
- Inlet valve (201–9): Inlet valve to PureBallast during deballast. The valve directs the water
to PureBallast, but bypass the filter, since the water was filtered during ballasting.
• Control valve (V201–8): The valve have the following functions:
- Automatic regulation to maintain flow during operation so it does not exceed selected
certified maximum flow. Regulation is based on input from the flow meter.
- Automatic regulation to maintain pressure needed to perform backflush of the filter.
Regulation is based on input from the pressure transmitter.
- Outlet valve from the PureBallast system to the vessel’s ballast water system after treatment.
• PureBallast bypass valve (V212–31): Makes it possible to completely bypass the PureBallast
system. The valve is solely operated from the ISCS, but the valve positioning is (and must be)
indicated in the PureBallast control system. When PureBallast is bypassed, an event is written
to the event log. The component is optional to be included in Alfa Laval’s scope of supply.
• Cooling water inlet valve (V403-35): Supplies cooling water to the reactor to secure cooling of
the lamps and prevent overheating during start-up.
• Check valve (CV201): Ensures that there is water in the reacto at all times.
3.7 Flow meter
The flow meter (FIT201–1) monitors the process-flow during operation. It has two main functions:
• It monitor that the flow within the PureBallast system does not exceed its certified flow. If the
certified flow is exceeded a warning is issued.
• Via the flow transmitter, mounted on the flow meter, it sends valuable data to the PureBallast
control system, where it is displayed. Example of information: Current flow and data about
total amount of treated ballast water.
The flow meter consists of two main parts: A flow sensor, which is a pipe with four electrodes
detecting the flow. On top of the pipe, there is a terminal box, where the flow transmitter is
mounted. The flow transmitter monitors the flow and transmits the information to the PureBallast
control system.
• Pressure transmitter(PT201-16): Send current pressure information to the control system. The
control system use the information to take actions accordingly, for example issue warnings, shut
down the system or adjusting the control valve to obtain optimal pressure during filter backflush.
• Pressure gauge (PI201-18): Analogue displayed of current pressure.
• Needle valve (V201-15): Enables connection of external instruments for calibration.
• Safety valve (RV201): Relief of over pressure.
3.9 Sampling devices
The two sampling devices (Q201.1 and Q201.1) make it possible to take water samples to test the
water. One sampling device is installed before the water is treated and one after the water is
treated. This enables comparative tests of treated and untreated water. The component is optional
to be included in Alfa Laval’s scope of supply.
3
3.8 Page 3.2 – Trend (1 h) 37
3.9 Page 3.3 – Trend (1 h) - TT201-33 37
3.10 Page 3.4 – Trend (1 h) - TT401-2 37
3.11 Page 3.5 – Trend (1 h) - Power
optimization 37
3.12 Page 4.1 – System info 38
3.13 Page 4.2 – PLC controller I/O 41
3.14 Page 4.3 – Operation timers 42
3.15 Page 4.4 Operation timers AOT 44
3.16 Page 4.5 – Remote interface 1 45
3.17 Page 4.6 – Remote interface 2 46
3.18 Page 4.7 – Log box 1 47
3.19 Page 4.8 – Log box 2 48
3.20 Page 4.9 – LPS overview 49
3.21 Page 5.1–5.7 – Parameter pages 51
3.22 Popup windows 51
3.22.1 AOT popup 51
3.22.2 Filter popup 57
4 Operating instructions 59
4.1 Log in 59
4.2 Perform ballast 59
4.2.1 Start ballasting 60
4
4.3 Perform deballast 61
4.4 Pause ballast / deballast 62
4.5 Heel (internal transfer) 62
4.6 Backf ush f lter manually 63
4.7 CIP clean AOT reactor after ballast /
deballast 63
4.8 Stop ballast / deballast 64
4.9 Attend to alarms 65
4.10 Shut down and deactivate system 66
4.11 Reset system after shut down 67
4.12 Operate components manually 67
4.13 Operate UV lamps manually 69
4.14 Set ship specif c component ID 70
4.15 Export control system event log f les 71
4.16 Backup control system settings 73
4.17 Restore control system settings 74
4.18 Set control panel IP address 75
4.19 Set remote control panel
communication 76
4.20 Set remote interface communication 77
4.21 Test remote interface communication 78
4.22 Simulate power request 80
4.23 Set default parameters 80
4.24 Update control system softwares 81
4.25 Calibrate the control panel’s touch
screen sensibility 81
4.26 PID calibrate system 82
4.26.1 Calibrate pressure controlled regulation 82
5
5 List of logged information 85
5.1 Event log 85
6
1 Introduction
The control system is used to operate and monitor the PureBallast system. It also contains
functions for setting parameters, saving log files etc.
This chapter describes the control system. It includes general description of the control system
pages, step-by-step instructions and a process description with detailed information about the
components (valves, motors, pumps etc) involved in each step of respective process.
The following control system related information is given in other chapters of the manual:
- When overboard valves are requested to be opened/closed, this means that all valves
leading the flow from the PureBallast via one of the following pipes must be opened/closed:
201, 309 and 403 and 404. During CIP process, 460.1 must be opened.
- Such water as described above does not need to be transported overboard. For example,
the flow can be lead to the bilge tank. In such cases, all relevant valves leading the water
from the PureBallast system shall be opened.
• The input flow to the PureBallast system shall be as close as possible to the flow that has been
selected for an operation. This will reduce the stress and wear of the control valve.
1.1.1 Stripping
The first time a ballast tank is stripped, PureBallast must be by-passed.
If stripping is performed with a low flow for a long period of time, we recommend that stripping is
performed from the ballast tanks to a “collection tank”. After that it is possible pump the water
from this tank with full flow using the ballast pump, and finally empty it by stripping. Note: The
driving water used for stripping must have been treated once, so that all water that is flushed
overboard has been treated twice.
This will reduce the power consumption and UV lamp runtime. If all tanks are stripped (with a low
flow) the power consumption per treated cubic meter will be unnecessary high, since the power
consumption will be high in relation to the low flow.
Example: If a process is run with a flow of 100 m3/h for 10 hours, it will give a power consumption
of 1000 kwh, not including the ballast water pump. But if the same amount of water is collected
and then processed with a flow of 1000 m3/h using the ballast water pump, the power consumption
will be 100 kWh.
If external component signal for heeling mode is integrated between PureBallast and the vessel’s
ISCS, ongoing process will be paused and resumed automatically. The user is notified of started
and stopped heeling via warnings, and the event is logged.
If no external signal is integrated, the ongoing process must be paused manually. During pause,
cooling water is flushed through the AOT to cool the UV lamps. After completed heeling, the
operator must resume the paused process.
PureBallast is equipped with a by-pass valve. The valve can be used in case of emergency to
secure the ship, by allowing ballast water operations (ballast, deballast and internal transfers)
without involving the ballast water treatment system. The valve is controlled by the ISCS, not
PureBallast’s control system, but all valve activities are logged in the event log. Such valve is
required by the International convention for the control and management of ship’s ballast water
and sediments 2004.
If the system malfunction in connection with general cargo operation, ballast and deballast
operations should be avoided. Note that the system requires treatment both during ballast and
deballast.
If untreated water is pumped to a ballast tank, this water shall primarily be discharged to a reception
facility. When this is not possible, other discharge possibilities must be agreed with the port state
responsible for the waters where the ship is sailing and most importantly be agreed with the flag
state administration of the ship; the procedures concerning emergency and malfunction of the
ballast water treatment system should be implemented in the ships Ballast Water Management
Plan which must be approved by the flag state administration.
In PureBallast, a deballast process is run with the vessel’s ballast valves positioned so that the
• pump takes water from a ballast water tank with treated water and
• the water flow is directed either overboard or to another ballast tank.
Run the process for enough time so all water in the piping is treated. Time for this depends on pipe
size and length on board.
This section describes different login levels, overview of the system interface and how to navigate
and operate the control system.
Guest N/A Default mode of control system. This level is not password protected.
AlfaLaval N/A Full access. Password only available for Alfa Laval personnel.
The information below is only valid if remote control panels and/or remote interface is installed.
To switch command from one panel to another, you log in to the new panel. This is only possible by
using the same or higher login level as used in the active control panel. When control is about to be
changed from one panel to another, the following will happen:
• The inactive control panel will display a popup message informing that another control panel is
active (some one else is logged in). The popup gives the alternative to cancel or to continue. If
continue is chosen, control is swithced from the first panel to the new panel.
• The active panel will display a popup message informing that another the panel is inactive
and that control is taken by another panel.
On each control panel it is possible to see which panel that is active and which login level that is
used. A panel alias can be entered to clarify where the panel is installed, for example pump room,
bridge etc. See instruction Set remote control panel communication. This information is visible in
the upper right corner of the system according to syntax: login level@control panel.
3 ActivePanel
It is only possible to switch command between control panel and ISCS from a PureBallast control
panel. This is done by using the Local and Remote buttons, when logged in as Operator or higher.
Control status (local or remote) is indicated by a green light under the button that corresponds to
the system currently in command. In the ISCS, control status can be indicated by using the status
signal dedicated to this. It is recommended that this signal is implemented in the ISCS.
When remote interface is activated, PureBallast can only be controlled from the ISCS. It possible
to access the same pages and perform the same operations from the ISCS as for login level
Operator (to the extent that the systems are integrated. However, the following two tasks can only
be performed from a (any) control panel: Set parameters and switch control between control
panel(s) and ISCS.
When remote interface is activated, the panel(s) can only be used to monitor the system, export log
files and switch control between PureBallast control panel(s) and ISCS.
The PureBallast system manual does not give any information about how to run PureBallast from
the remote interface. This is due to the fact that the remote interface is custom-made. Please
refer to the vessel specific manual.
PureBallast can be operated from ISCS when the conditions below are met:
• The remote interface must be correctly installed, according to Remote interface implementation
guide.
• Remote interface must be activated (parameter p132) and communication settings must be
correct (parameter p700 – p704).
• The Test mode button must be deactivated (no checkmark on the button) in control system
page 4.5 Remote interface 1.
• Remote control must be activated. Check that the green lamp is lit under the Remote button
on the control panel. If not, press the button. The system must be in Standby mode to toggle
between local and remote operation.
Operation
• Heartbeat is updating. See that address +006 +077 are updating in control system page 4.5
Remote interface 1.
• There must be no active alarms for the AOT reactors to be used during operation. Always check
the alarm list (page 2.1 Alarm list in the control system) before operation.
The control system use a touch screen, where you tap the screen to “click” or drag objects. Do not
use sharp objects to touch the screen. When the screen is left idle it will go to screensaving mode.
Time is set in page 4.1 System info. The screen is activated again by touching it once. The touch
will not activate any button that might be placed where you touch.
The illustration below shows the main areas and function buttons on the screen.
3 1.1
Tabs: The top and side tabs are used to choose which page to display in the screen. Pages are
referred to as a number and a name, for example 2.1 Alarm list. The first number refers to selected
top tab, counted from left to right. The second number refers to selected side tab, counted from top
to bottom. Selected tabs are indicated by a white color.
Top tabs: Contain the main function areas of the control system: Overview, alarm lists, trend
indication, system information and parameters.
Side tabs: Contain sub pages for the area selected in the top tab. Available side tabs change
depending on which function area that have been selected in the top tab.
Popup windows: Are used to display or enter detailed information. It is possible to move a popup
by touching the name bar and drag it. A popup is closed either by touching confirming entered
information by touching a function button (OK, Conf rm, etc.) or the X icon in the top right corner
(data is not saved).
Data entry f elds: A white field indicates that it is possible to enter data. When the field is touched,
a keyboard is displayed, which is used to enter information. Enter data is confirmed by touching the
Enter button. To close the keyboard without saving data, touch the Esc button.
Tables: Individual table rows, for example an alarm, can be selected by pressing them. Column
widths can be adjusted. Press the column border in the head area and hold the finger on the screen.
Function buttons: Function buttons are used for main processes and control of the system. They
are placed att the bottom of the screenare and are always visible, but only available when colored
dark blue. Some buttons are dependent on parameters. For example, the Remote and Local
buttons are only visible if remote interface is activated.
Status indication – Button color: The buttons appear in different colors, indicating status:
Grey The function is disabled, for example if higher login level is required for the
function.
Status indication – Button light: After a function button is pressed, a light under the button is lit
to indicate status for the activated function:
Yellow Command will be processed when possible in the data work flow.
Yellow, blinking Command is paused.
Button Description
Button Description
3StopButtonBlue
Pause ballast or deballast process. This is only possible during full ballast
or full deballast. The button can be hidden, using parameter p137. Allowed
length of a pause is parameter set (p138). After defined time, the paused
3Pause
process is stopped.
3CIP
Activate operation from control panels, instead of remote interface (if option
is used). The button is only enabled in standby mode.
2 LocalButton
2 RIbutton
Sets the control system in manual mode, which enables manual operation
of the system and its components. When activated, the light flashes yellow.
The button is displayed for login level Advanced operator or higher. For
3 EnableManual detailed information see Manual mode on page 103.
3Wipe
Activate night light for the panel. Night light makes the panel less bright.
Toggles between night light and day light.
3 Night Degree of brightness, is set in the Night light level field in page 4.1 System
info.
Alarms and warnings for components are displayed in the flow chart and popups:
Active alarm.
3Alarm
Active warning.
2 Warning
This section describes the pages used for operation. Note that this section does not cover the
parameter pages. Please refer to chapter 4. Parameters.
The main areas are the Status box and the Flow chart.
3 1.1
Process and sub process Process: Ongoing process. Can be standby, ballast, deballast
and CIP.
Processed volume (m3) Amount of water processed during ongoing process. Value
remain until next process is started.
Certif ed f ow (m3/h) Certified flow (m3/h) selected for operation. The information is
updated after the warm up time has passed and a AOT reactor
is used for process. This is also the flow the system is aiming
to keep.
Current f ow (m3/h) Ballast water flow in the system, indicated by flow transmitter
FIT201-1. The system aims for the selected flow minus
parameter p111 Undershoot certified flow, which can be set
as a safety margin.
Flow selection Flow (m3/h) selected for operation. Flow is set using the arrow
buttons.
Relevant information regarding ongoing process and component status can be monitored directly
in the flow chart. Flow in pipes is indicated by coloring of the pipes and component status are
displayed by color indications. Pressure, flow and control valve opening percentage are displayed
directly on component.
Detailed information about components can be monitored in popups (by tapping the component):
AOT reactor see page 51; filter see page 57. CIP open page 1.3 CIP status, see page 25). The
popup contain status for sub components, for example valves, motors and UV lamps in the AOT
reactor.
Booster pump for AOT reactor (P403–1) and LDC (P401–1) are only displayed if these components
are used and activated in the parameter pages.
In manual mode (login level Advanced operator or higher) it is also possible to operate components
manually: If a component is pressed, a popup window is displayed from which the component
can be operated.
Status indication
Mixed colors = Mixed water, for example ballast water and fresh water.
Status indication for balast water pump (not part of Alfa Laval’s scope of
supply).
3 PumpReq
Status indication
Green = Feed back that pump is running, either via hard wired feedback,
remote interface or the confirmation popup.
Status indication for overboard valve(s), and other relevant valves for the
process (not part of Alfa Laval’s scope of supply).
Green = Feed back that valve is open, either via hard wired feedback, remote
interface or the confirmation popup.
Grey = Closed.
Status information for bypass valve(s) V212–31 and external bypass valves
(not part of Alfa Laval’s scope of supply). These valves are operated from the
ISCS, due to safety reasons.
3Manual1
This page is only relevant if more than one AOT reactor is installed.
Note, that if parameter p131 Automatic AOT selection is activated, it is only possible to change
flow during operation, not in standby mode.
Normally, flow is handled from page 1.1 Overview, and this page is used during commissioning and
faultfinding when it is necessary to start individual AOT reactors.
The main areas of the page are the Flow selection, AOT selection and Status.
3 1.2
Elements Description
Modify button Enables active selection of individual AOT reactors. When pressed, the
buttons for respective AOT reactor turns blue and are possible to use.
AOT 1, 2, 3 button One row for respective installed AOT reactor with current status indicated
in the columns.
Status indication:
3.2.3 Status
The area displays current status for the flow:
Elements Description
Current f ow Ballast water flow in the system, indicated by flow transmitter FIT201-1.
Certif ed f ow Maximum allowed flow as set in Flow setpoint or limited by the number of
AOT reactors selected in AOT selection popup. If a smaller filter is installed,
the ballast flow can be lower than the AOT reactor capacity.
The information is updated after the warm up time has elapsed and a AOT
reactor is used for process. (Before that it is not used for treatment, and
therefore not part of the certified flow.)
The page also display time remaining for ongoing CIP process. If no CIP required process has been
started after a ballast or deballast operation, the time remaining before CIP must be performed is
displayed.
3 1.3
Row Content
Process and sub Process: Ongoing process. Can be standby, ballast, deballast and CIP.
process
Sub process: Sub steps of ongoing process, for example “Start-up” during
Ballast process.
Row Content
AOT Each row display CIP status for every installed AOT reactor
Filter preservation This row indicate status and time for the filter preservation process, that
starts after completed CIP. During filter preservation, the CIP fills the filter
with fresh water for preservation purpose.
Total Total estimated time for a complete CIP process including filter preservation.
Column Content
CIP error Red square: Indicates that there is an active alarm for the component.
Check alarms on page 2.1 – Alarm list.
Status indication
Yellow = CIP required. During ongoing CIP process, yellow indicates that
the AOT reactor is waiting for CIP process to start.
Column Content
Estimated time Time remaining CIP time. If CIP process has not been started, total time is
displayed. During CIP process, the time is counting down continuously.
The CIP process takes about 25 minutes per AOT reactor, if default
parameters are used.
Required CIP Time before a CIP process must be performed after ballast or deballast.
countdown The time disappears when the CIP process is ready. Time is displayed for
the AOT with shortest time left to required CIP.
3 1.4
Column Content
Process and sub Process: Ongoing process. Can be standby, ballast, deballast and CIP.
process
Sub process: Sub steps of ongoing process, for example “Start-up” during
Ballast process.
Max power Maximum power consumption for the number of selected AOT reactors.
consumption The value is updated when a process is started.
Measured power Power consumption during process. Value calculated based on number of
consumption used AOT reactors.
Power status
Column Content
Pure Ballast always asks for power before the UV lamps are lit during ballast
or deballast start-up. When a request has been sent, the vessels power
management performs a power check before the generator is started.
The page can also be used to troubleshoot the power management system integration by sending
and checking each signal.
Buttons Content
Request Press to manually simulate request for a power step. The button is
displayed for login level Advanced operator or higher.
Set run Press to manually simulate run signal for a power step. The button is
displayed for login level Advanced operator or higher.
- A = Alarms stop the ongoing process, which can be restarted after the problem has been
attended to.
- W = Warnings are notification of a status change, request for action or a problem that must be
attended to. Warnings allow the process to continue.
For detailed information about alarms and warnings see chapter 5. Alarms and faultfinding.
3 2.1
The main areas of the page are the Alarm list and the Function buttons:
Column Content
Text Descriptive alarm text written as: Area-Alarm type AlarmID Alarmtext.
Example: AOT2 A138 Error in LDC cabinet.
Acknow- The time the alarm/warning was acknowledged. The alarm/warning remains
ledged time in the alarm list until the causing condition is resolved. For example a high
temperature alarm will remain visible, until the temperature is below the limit
value for the alarm/warning.
The table below shows status indication for alarms and warnings in the alarm list.
Button Function
Ack selected Acknowledge selected alarm (row). Press a row to indicate it, and press the
button to acknowledge it.
3 2.2
Column Content
Text Same as in Page 2.1 Alarm list.
Normal time The time the value that caused the alarm returned to normal.
3 3.1
Trends can be plotted for the following components (identified by item number) and key values:
Filter diff. pressure Bar Differential pressure over filter, indicated by pressure
transmitter 201–71 and 201–72.
Y axis: The scale and unit used for the Y axis is set in the Settings popup for respective component.
For details, see the Component area section below.
Settings Press the button to make settings for the component’s curve. Settings are
button done in a popup.
3 TrendCurveSet1Nr
1: Press (not slide) the button to display or hide trend curve in the diagram.
An I indicate displayed, and an O indicates inactive.
2: Press the entry field to change start and stop value for the components Y
axis scale (when this component’s scale setting is used).
3: Press this button to use this component’s scale setting in the diagram.
4. Press the entry field and increase or decrease the number of decimals in
the component area.
Value Current value for the component is displayed in the gray field. (This
corresponds to the diagram.)
Buttons Content
Export long- Export trend curve history as a csv file. The file can be sent to Alfa Laval for
term trend advanced trouble shooting.
data to USB
Insert a USB memory in USB panel port on the cabinet door. Press Export
long-term data to USB button. Wait for the message “Exporting database
table …” to disappear. The file has been downloaded to the USB memory,
in a folder named DatabaseExport.
3 TrendCurveTime
Press one time unit (year, moth, day etc) and then press – or + to set time.
See page 3.1 Trend (15 min.) for information about function, fields and buttons.
See page 3.1 Trend (15 min.) for information about function, fields and buttons.
See page 3.1 Trend (15 min.) for information about function, fields and buttons.
See page 3.1 Trend (15 min.) for information about function, fields and buttons. See chapter 2.
System description, section Power optimization for details.
• AOT UV setpoint: The UV intensity the system is aiming to attain by increasing or decreasing
power effect to the LPS controlling the dimming of the UV lamps. The setpoint is based on
actual transmittance and is updated every 15 seconds.
• UV measurement: Actual UV intensity (W/m2) measured by UV sensor QT201–50. If intensity
is lower or higher than needed, the power to LPS will increase or decrease to attain setpoint
for UV intensity.
• Power output: Actual LPS power to UV lamps. The power is adjusted to attain the setpoint for
UV intensity based on measured water transmittance. Output is adjusted based on input from
UV sensor QT201–50. Power can be 50–100 %.
3 4.1
HMI info CPU: Control panel’s usage of the central processor unit (CPU) in
percent of total capacity and temperature (°C). The control panel will
shut down when the CPU reaches 100 °C.
Used storage: PLC flash card’s used storage in percent and MB.
Storage used for the event and alarm log.
iX version: N/A.
Setup button: Opens popup to set IP address for the main panel and
the remote control panels (optional). Requires login level AlfaLaval.
HMI date and time UTC Date and time: Only used if GPS is not connected to the control
system. If so, time is retrieved from the GPS. Requires login level
Advanced operator.
Set button: Set time and date for the main control panel. Remote
control panels are updated with this time within 15 minutes after
syncronization.
HMI Backlight Screen saver timeout: Defines time before the panel is set to
screen save mode. This is set individually per control panel.
Night light level: Defines percent of full light for the night light
mode. Night light is activated by the Night function button.
PLC Info CPU temperature (°C): Temperature of the central processor unit
(CPU) in the PLC.
Backup and restore Settings to/from USB panel: Export and inport information to the
USB panel port on the cabinet door.
Set default button: Set all parameter values to the default values.
Requires login level Advanced operator.
Export log f les Export button: Opens the Export log f les popup to export (copy)
event log files and alarm list.
Remote control panels Remote control panel settings button: Open a popup used for
setting IP addresses for remote control panels (optional). See
instruction Set control panel IP address on page 75.
Note that this page is only intended for Alfa Laval’s personnel and only visible and available for
login level AlfaLaval.
3 4.3
Row Unit
Row Unit
3 4.4
AOT 1–3: Total runtime for the UV lamps in Lap time for installed UV lamps, since
Lamps on respective AOT reactor. the counter was reset after previous
reset at UV lamp change.
For detailed information about addresses, information and format, see chapter 6. Installation
description and drawings, section Remote interface integration (optional).
3 4.5
Test mode Activates test mode. Communication can be sent between the
ISCS and PureBallast’s PLC without actually affecting the control
system (start process etc). To send information, enter desired
digits in the entry field.
For detailed information about addresses, information and format, see chapter 6. Installation
description and drawings, section Remote interface integration (optional).
3 4.6
3 4.7
Column Content
To enter a vessel ID: Press the entry field or the document icon for the
component, and enter the ID using the keyboard displayed on the screen.
Position: For each valve, it is possible to connect two signals to log feedback
on open, closed or both. If signal “Closed” is used for a valve, the event log
Column Content
will make a record each time the valve is detected closed, and each time it is
detected not closed.
Status Active signal is indicated with a green light on the I/O icon.
Logging Two parameters per valve defines if opened and/or closed signals are
connected for respective position (valve). If parameter is set to Active,
activities for the component is logged in the event log.
See page 4.7 Log box 1 for information about function, fields and buttons.
3 4.8
3 4.9Obe
Column Content
Lamp OK Status: Green = UV lamp lit and LPS is OK. Red = LPS in fault state.
Voltage fault Status: Red = Too low incoming power to the LPS.
Column Content
Air temp fault Status: Red = Temperature in LPS is higher than 55 °C.
In manual mode (login level Advanced operator or higher) it is also possible to operate components
manually. If the component is pressed, a popup window is displayed from which the sub
components can be operated. Operation of UV lamps in LPS control popup requires login level
Advanced operator.
AOT status: Status indication for the AOT reactor: ”Stopped” or “Started”.
AOT illustration
Component Description
Grey = Off.
Yellow = Starting.
Green = Started.
Component Description
Valves For status indications, see Status indication – Component color in section
Flow chart on page 21.
LDC status
Component Description
Open the LPS control popup, which enables manual operation of individual
UV lamps. Requires login level Advanced operator to see the button and
manual mode open the popup. See LPS control popup and instruction
Operate UV lamps manually on page 69.
3 LPSctlrbut
Open the LPS status popup, which gives an overview of status for UV
lamps and LPSs.
3 LPS StatusBut
LDC fan setpoint Fan rotation in percent of full effect. Fan effect is based on need for cooling.
Heat exchanger Indicates if the valve for LDC cooling water (SV401–51) is open.
valve Status indication: Green = Open . No indication = Closed.
The popup is used for to manually start the UV lamps in the AOT reactor. See instruction Operate
UV lamps manually on page 69. The popup is displayed when the LPS control button is pressed
in the AOT popup. Requires login level Advanced operator to see the button and that manual
mode is activated to open the popup.
The AOT reactor is equipped with 16 UV lamps. In each lamp drive cabinet (LDC) is 16 lamp
power supplies (LPS) that supplies power to one UV lamp each. The lamps can be operated
individually in manual mode.
NGE R
! DA
• Manual start of the UV lamps is only allowed (and possible) when there is water in the AOT
reactor (indicated by level switch LS201-29), and the water temperature is below 60 °C. All
necessary items – cooling water flow, water temperature, and power management – must be
supervised and verified by the authorized trained personnel operating the system. Improper
operation of this function could seriously damage the equipment and injure personnel.
Component Description
AOT number Information is displayed for the AOT reactor selected in the AOT number
field.
Enables manual operation of the LPSs to light the UV lamps. The button is
displayed for login level Advanced operator or higher. The button enables
manual lcontrol of UV lamps.
3 ManModeBut
Component Description
LPS 1–16 Press one button (1–16) to start or stop UV lamp 1–16 manually, controlled
by the LPS.
Status indication:
Start all LPS, and thereby all lamps for the AOT reactor. Requires that the
Manual mode button is pressed.
3 StartLPSBut
Stops all LPS, and thereby all lamps for the AOT reactor.
3 StopLPSBut
The popup gives detailed information about UV intensity for AOT reactors and power for LPSs. The
information is mainly used for advanced trouble shooting by Alfa Laval’s personnel.
3 LPS popObe
LPS status
Component Description
AOT Information is displayed for the AOT reactor selected in the AOT number
field.
Fail safe Displays if LPSs is active and powered on. UV lamps can only be lit if an
LPS is active. When a critical alarm (e.g. no water in the AOT reactor) is
issued, the fail safe function inactivates the LPSs and cut the power.
Component Description
LPS 1–16 Actual effect from each LPS to respective UV lamp. Green = LPS/Lamp
on. Gray = LPS/Lamp off.
Power optimization
Component Description
Manual power Manually set effect to LPS. Requires that the system is set in manual
output mode.
In manual mode (login level Advanced operator or higher) it is also possible to operate components
manually. If the component is pressed, a popup window is displayed from which the sub component
can be operated. When manual mode is deactivated the system will return to standby mode: All
manually operated components will return to their status prior to the manual operation.
Component Description
Diff. pressure Indicates differential pressure over the filter (PT201–71 minus PT201–72).
When the pressure reach the value set in parameter p305, a backflush
is triggered.
Start backf ush Press the button to start a manual backflush. See instruction Backflush
filter manually on page 63.
Pipes, valves and For status indications, see Status indication – Component color in section
motor Flow chart on page 21.
This section contains step-by-step instructions for operating the PureBallast system. Please read
and follow the preparations and conditions carefully, as well as any danger or warning notes.
• Control system pages used in the instructions: See section Control system — Detailed page
descriptions.
• Login levels required for different procedures: See section Login levels on page 11.
• Detailed information about components (valves, motors, pumps etc) involved in each step the
process. See section Detailed process description.
4.1 Log in
Follow the steps below
1. Press the expand button on the Log in tab in the top right corner of the screen.
Result: The log in menu is displayed.
2. Press the expand button on the left drop down menu to display available users. Press desired
user.
Result: A keyboard is displayed.
3. Enter password and press Enter. (See section Login levels on page 11.)
• The Alarm list (page 2.1) must be controlled to verify that there are no alarms needing attention.
• All ballast system valves outside the PureBallast system must be set in the correct positions
for ballasting. The valve after the ballast pump must be closed (not part of Alfa Laval’s scope
of supply).
• Flow must have been selected before a process can be started. If parameter p131 is activated
maximum flow is automatically selected, and flow can only be changed during process
according to instruction Change ballast / deballast flow on page . If parameter p131 is
deactivated last selected flow is used. Otherwise, flow is selected on page 1.1 Overview or
1.2 AOT and flow selection.
• There must be available power for the system. If power management is integrated, this will
be handled automatically. If power management is not integrated, confirm available power
manually.
2. Wait for the message “Open valves ...”. Open relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Ballast start-up starts, with cooling water cooling the lamps during warm-up.
3. Wait for the message “Confirm ballast pump started”. Start the pump and then press the
button in the popup to confirm the action. Note! This component is outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
Result: Cooling stops and ballasting starts.
4. When desired amount of water has been processed, press the function button Stop.
Result: Ongoing process is stopped and the lamps are switched off. An automatic filter
backflush is performed.
5. Wait for the message “Close valves ...”. Close relevant valves and then press the button in
the popup to confirm the action. Note! These valves are outside outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
6. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
NOTE
A CIP cleaning process must be performed after ballasting. It can be done immediately or within 30 hours
from the f rst operation after the previous CIP process. If no CIP process is performed within the time limit,
a warning is issued and an entry is made in the control system log f le. Operations after the warning does
not fullf ll the type approval certif cate.
Note that it is possible to run ballast operations during the 30 hours. Complete status information regarding
CIP is displayed in page 1.3 CIP status. A CIP process is started manually according to instruction CIP
clean AOT after ballast / deballast on page 63.
• The Alarm list (page 2.1) must be controlled to verify that there are no alarms needing attention.
• All ballast system valves outside the PureBallast system must be set in the correct positions
for ballasting. The valve after the ballast pump must be closed (not part of Alfa Laval’s scope
of supply).
• Flow must have been selected before a process can be started. If parameter p131 is activated
maximum flow is automatically selected, and flow can only be changed during process
according to instruction Change ballast / deballast flow on page . If parameter p131 is
deactivated last selected flow is used. Otherwise, flow is selected on page 1.1 Overview or
1.2 AOT and flow selection.
• There must be available power for the system. If power management is integrated, this will
be handled automatically. If power management is not integrated, confirm available power
manually.
Follow the steps below:
2. Wait for the message “Open valves ...”. Open relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Deballast start-up starts, with cooling water cooling the lamps during warm-up.
3. Wait for the message “Confirm ballast pump started”. Start the pump and then press the
button in the popup to confirm the action. Note! This component is outside the PureBallast
system control. (The popup is not displayed if the component feedback is integrated with
the control system.)
Result: Cooling stops and deballasting starts.
4. When desired amount of water has been processed, press the function button Stop.
Result: Ongoing process is stopped and the lamps are switched off.
5. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
6. Wait for the message “Close valves ...”. Close relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
NOTE
A CIP cleaning process must be performed after deballasting. It can be done immediately or within 30 hours
from the f rst operation after the previous CIP process. If no CIP process is performed within the time limit,
a warning is issued and an entry is made in the control system log f le. Operations after the warning does
not fullf ll the type approval certif cate.
Note that it is possible to run deballast operations during the 30 hours. Complete status information regarding
CIP is displayed in page 1.3 CIP status. A CIP process is started manually according to instruction CIP
clean AOT after ballast / deballast on page 63.
• This is only possible in sub process full ballast or full deballast. This is indicated by the lit
Pause button.
• Allowed length of a pause is parameter set (p138). After defined time, the paused process
is stopped.
Follow the steps below:
2. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: Ongoing process is paused. The UV lamps remains on at reduced power and cooling
water is run through the AOT reactor to cool the lamps. Pause mode is indicated by yellow light
under the Pause button and blinking yellow under the function button Ballast or Deballast.
5. Wait for the message “Confirm ballast pump started”. Start the pump and press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: The process is resumed.
• This requires that a signal for heeling mode is integrated between PureBallast and the vessel’s
ISCS.
• This is only possible in sub process standby, full ballast and full deballast.
• Allowed length of heeling is parameter set (p138). After defined time, the system is stopped.
Follow the steps below:
1. Activate heeling from ISCS, which means that a heeling signal is sent to PureBallast.
2. In PureBallast: Wait for the message “Stop ballast water pump”. Note! This component is
outside the PureBallast system control. (The popup is not displayed if the component feedback
is integrated with the control system.)
Note: If you you need the ballast pump for heeling, confirm the request without stopping the
ballast water pump.
Result: System goes to heeling mode (ongoing process is paused). The UV lamps remains on
at reduced power and cooling water is run through the AOT to avoid overheating of the lamps.
During heeling, the yellow light under the Pause button is lit and the yellow light under the
function button Ballast or Deballast is blinking.
5. Wait for the message “Confirm ballast pump started”. Start the pump and press the button in
the popup to confirm the action. (The popup is not displayed if the component feedback is
integrated with the control system.)
Result: The process is resumed.
If system shut down is activated during the CIP process, the CIP liquid is drained to the CIP tank.
Water in the AOT reactors is drained overboard.
• The system must be in standby mode. This means that this operation cannot be executed
during ballast or deballast.
• Complete status information regarding CIP is displayed in page 1.4 CIP status. The page
displays remaining time for ongoing CIP cycles, remaining time before individual AOT reactors
are required to be CIP:ed etc.
• If a ballast operation has been performed since the last CIP process, the process is completed
with a filter preservation, where the filter is filled up with fresh water.
Follow the steps below:
2. Wait for the message “Open valves ...”. Open relevant valves and then press button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
Result: The automatic CIP process starts. The CIP process takes about 25 minutes for one
AOT reactor, if default parameters are used.
3. Wait for the message “Close valves ...”. Close relevant valves and then press button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
1. When desired amount of water has been processed, press the function button Stop.
To get a smooth stop, the flow from the ballast pump can be reduced, but not more than 50 %.
Result: Ongoing process is stopped and the lamps are switched off. If ballasting, an automatic
backflush is performed before the system is stopped.
2. Wait for the message “Stop ballast water pump”. Stop the pump and then press the button in the
popup to confirm the action. Note! This component is outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
3. Wait for the message “Close valves ...”. Close relevant valves and then press the button in the
popup to confirm the action. Note! These valves are outside the PureBallast system control.
(The popup is not displayed if the component feedback is integrated with the control system.)
NOTE
A CIP cleaning process must be performed after ballasting and deballasting. It can be done immediately or
within a 30 hours. When time is about to elaps, a warning is issued. If no action is taken within the time
limit, an entry is made in the control system’s log as a deviation from a correct handling of the system. Note,
that it is possible to perform processes during these 30 hours. Complete status information regarding CIP is
displayed in page 1.3 CIP status.
4 AlarmActive
4 AlarmAcknow
• If the alarm is caused by a faulty AOT reactor, the AOT reactor will shut down but the process
will continue with remaining AOT reactors.
NG
WARNI
!
• Never reset an alarm without first finding and attending to the problem.
• Requires login level Operator or higher.
• For color indication of alarms. See page 32.
Follow the steps below:
3. If the process continues: Consider if the process shall be terminated. Take action to eliminate
what has caused the alarm.
4. After the problem has been dealt with Press the Ack all button to acknowledge all alarms, or
press the alarm row and press Ack selected button to acknowledge only this alarm.
Result: The alarm will change color to indicate change of status. See section Page 2.1 Alarm
list in this chapter. The acknowledge time is updated, and the Normal time will be updated
when the problem is resolved.
3 Emergency stop
One of the following methods can be used to abort any ongoing operation and stop the system:
Action Method
3StopButtonBlue
System stop Press the Stop button (2) on the control cabinet door.
Result: Ongoing process is stopped and valves are returned to starting
position as fast as possible. Note: The power is still on.
Action Method
System stop If an external system stop button has been installed and integrated, it
(External button) will function as the system stop above.
The system may only be reset after the reason for shut down is known. If the reason is not known,
follow the instruction Attend to alarms.
Manual on control cabinet: Turn the main breaker (1) and acknowledge the alarm in the control
system. Release the button on the control cabinet.
Automatic in LDC: Follow the instruction below if a reactor has been shut down by temperature
switch TS201-60 (alarm A137) or if the cabinet or system has been shut down by a blackout or
electrical faults in the cabinet:
1. Make sure that the main breaker (A) on the LDC door is turned on.
2. Press the blue reset button (B) on the LDC door (when the reactor has cooled down or when
the power is back on).
3. Acknowledge all alarm related to the shut down in the control system.
Valves are recommended to be operated via the PureBallast control system. It is also possible to
open/close them manually according to instruction in chapter 7. Service manual, section Operate
valves manually.
• Filter motor (M709-43) NOTE: Hydac filter motor can only be started from the filter cabinet.
press the F5 button to start a backflush sequence for the motor.
• CIP pump for CIP liquid (P320-1)
• CIP pump for draining (P321-5)
• Booster pump, LDC cooling (401–1), if installed
• Booster pump, AOT reactor cooling (403–1), if installed
• UV lamps in the AOT reactor
• UV lamp effect.
Preparations and conditions
3 PopValve
4. Press (not slide) the Hand button icon to enable manual operation of the component.
Result: The open and closed buttons turn blue for operation. A hand icon is also displayed on
the component in the popup and the flow chart to indicate that it is manually operated.
5. Operate the component using the open/run (left) and closed/not running (right) buttons in
the popup.
6. Press Hand button to stop manual mode for the component and the X button to close the popup.
or
Press the X button to close the popup and let the component remain in manually set status.
The popup is closed, and a hand icon is displayed by the component to indicate it is manually
operated.
NGE R
! DA
• Manual start of the UV lamps is only allowed (and possible) when there is water in the AOT
reactor (indicated by level switch LS201-29), and the water temperature is below 60 °C. All
necessary items – cooling water flow, water temperature, and power management – must be
supervised and verified by the authorized trained personnel operating the system. Inappropriate
operation of this function could seriously damage the equipment and injure personnel.
Follow the steps below:
1. Go to page 1.1 Overview. Press the Manual function button to activate manual mode.
3. Select which AOT reactor to operate in the AOT number entry field.
4. Open, in stated order, the following valves to fill the AOT reactor with water: 201-19, 404-36
and 403-35.
Result: The AOT reactor is now filled with water through the cooling water line 403.
5. Wait until the AOT reactor is filled with water, indicated by the level switch (LS201–29) turning
green.
7. Press the Manual mode button to enable manual operation of the UV lamps.
9. If desired, the UV lamps can be dimmed manually: Press the LPS status button in the AOT
reactor popup. Press the Manual output filed, and enter desired percentage between 50
and 100 %. The LPS will give the entered percentage of full effect to the UV lamps. This is
indicated in the Power output field.
• If remote control panels (option) are used, enterd IDs will be displayed on all panels.
• Requires login level Advanced operator.
Follow the steps below:
3 ShipIDComp
Information to be Description
exported
Event log The event log includes all important events in the PureBallast system. The
log also include components connected via the log box. Intended to be
used mainly by service technicians.
Event log - Contains a selection of the complete event log, relevant to comply with
Certif cate the IMO regulations.
Alarms and A list of all alarms and warnings that has been issued from the control
warnings system. Intended to be used mainly by service technicians.
For specific information about logged events, see section List of logged information on page 85.
• Events are only copied, hence they will remain in the control system.
• The log and alarm files are stamped with the system name and serial number entered in page
4.5 Installation parameters.
• The easiest way of reading the log file is to use the program Visualog, but the file can also be
read in Exel. See Read event log in Excel below.
Follow the steps below:
3 ExportLog
3. Wait for message: Insert USB in PLC. Insert a USB memory in USB PLC port on the cabinet
door.
4. Chose one of the following alternatives to decide time interval for the information to be copied:
• Accept suggested default time interval in the Start and End fields. Default start date is the
oldest file in the system, and default end date is today’s date.
• Select the Specify time interval box, and enter desired interval in the Start and End fields.
5. Press one of the following function buttons: Events, Cert events or Alarms. (The Update
export is only used when updating softwares.)
Result: The information is copied to the USB memory indicated by a green checkmark on
the button during copying.
6. Wait for the message "Export OK" to appear. If desired, export next category of events using
the function buttons.
Result: A folder named PureBallast has been saved to the USB. It contains three sub folders:
Alarm, Cert and Event. The folder corresponding to your export choices contains a CSV file.
4. Wait for the OK / Close button to turn blue again. If the backup was successful, the last line
shall state "Backup done".
Result: A folder named PureBallast backup has been saved containing the backup files.
3. Press the Restore button in page section Backup and restore, Settings to/from HMI USB.
Result: A popup is displayed and the process is started.
5. Read the second last line in popup: If the restore was successful, it shall state "Restore done".
8. The control panel must be rebooted. At the rear side of the control panel: Pull out the power
cable from the 24V DC port, and insert it again.
3 USB
3 IPaddress
Enter the IP address according to the list below. Also check that correct setting is done for Port
2 in the Port 2 tab.
3 IPaddress
5. Press OK.
6. Reboot the panel to update communication with the new IP address. Make sure that the new
IP address is displayed on page 4.1 System info.
7. Repeat this instruction for all installed control panels, both main and remote control panels, if
installed.
8. Follow the instruction Set remote control panel communication to activate remote control panel.
1. On the main panel in the control cabinet: Go to page 4.1 System info.
3 RCP communication
5. Press the Panel alias field for the new control panel. Use the keyboard to enter a name, for
example the location it is placed.
Note: Panel alias for all control panels shall be entered (with the same wording) in all panels
to be displayed in a correct way.
If remote control panels are not used, any added control panels shall be deleted from the list.
To delete a connected panel: Select it a panel in the hand side and press the delete (X) icon. If a
keyboard is displayed, pres Esc to remove it.
2. Set parameters to match ISCS’s RTU server data according to the information in chapter 4.
Parameters, section 5.7 – Remote interface.
Test communication
1. Go to page 4.5 Remote interface 1. Make sure that the system is not in test mode (no
checkmark on the button). If not, press the Test mode button to deactivate it. Make sure that
Local operation is activated. If not, press the Local function button.
2. Check that the heartbeat signal is updated in both systems (+006 and +077). Also check
that values are read from the PureBallast system, for example temperature (address +116
and +117).
This will confirm that the systems communicate.
Values are entered and displayed in the control system as actual values, but are sent to ISCS using
the binary numeral system. This information is found in group Data to ISCS and Cmd/status to
ISCS on page 4.5 Remote interface 1, and is indicated by a unit (m3, hour, second, kW etc).
The following addresses does not display correct values in page 4.5:
2. Enter actual values in the in the input field for the address to send simulated information to
the ISCS. Information in decimal form, for example processed volume, is written as actual
values. Information in binary form, for example command status, is written as a bit pattern.
The key for the bit pattern is found in chapter 6. Installation description and drawings, section
System interfaces.
3. Make sure that values and status information is displayed correspondingly in the ISCS.
In the ISCS, activate input commands corresponding to the addresses displayed in page 4.5. (Note
that address 006 does not need to be tested; it was tested at the beginning of this procedure.)
2. Make sure that the command is received in page 4.5. Use the directory of addresses to see
that the bit pattern is updated correctly.
3. In the control panel, restore all changed values after the communication test. If not, commands
might be executed involuntarily, when the system is set to online again. Most important is that
address 001 displays ”00000000”.
Alarms and warnings are tested by simulation in control page 4.5 Remote interface 1 and 4.6
Remote interface 2. Use the alarm list to identify addresses and bit patterns for the alarms.
You want to simulate alarm W40 (Process pressure too low). When you find W40 in the table, you
use the column heading to see which address the alarm shall be sent to and the row heading to
see which bit in the bit pattern that shall be high. For W40 the signal shall be sent to address
+902, and bit 12 shall be high.
Translate the bit to a bit pattern: Bit 12 is the 13th digit from the right (the first digit from
right is counted as zero, second digit counted as 1 etc). This gives the following bit pattern:
0010000000000000.
AOT reactor alarms/warnings: Each installed AOT reactor has a unique address:
1. Enter the desired bit pattern in the input field for the address.
3. If common alarm and warnings are used, make sure that address +070:7 and +070:8 are
updated. It is only necessary to check this for the first alarm.
6. Press the Test mode button to set the system in online mode (no check mark on the button).
Press the Remote function button if you want to activate remote control.
2. Press the hand button in the Request column for a row with power step for desired number of
AOT reactors. For details, see description of page 1.4 – Power request.
3. Press the Request button for the row to simulate power request signal.
Result: Status is updated to “Requested” in the Request column.
7. Press the Set run button to deactivate the simulate running signal.
1. Pull out the power cable from the 24V DC port on the rear side of the control panel.
2. Open the small cover on the rear side. Turn DIP switch 1 to position ON.
7BeijerMODE
3. Re-connect the power cable. Wait for a cross is displayed on the screen.
4. Press the cross until it changes position. Repeat until the menu is displayed again.
Result: Calibration is ready.
During ballast and deballast operation, the control valve is PID regulated based on input from the
flow transmitter FIT201-1 to maintain stable flow. Desired flow is defined as selected certified flow
for the operation minus the Undershoot percentage set in parameter p111.
During backflush, the control valve is PID regulated based on input from the pressure transmitter
PT201-16 to maintain stable pressure for efficient backflush. Desired pressure is defined in
parameter p304.
The second goal is to shorten the time from backflush trigger to start of actual backflush. This is
done by shortening the time in p310 (Backflush initial delay) that is done after the movement of
V201-8 has been calibrated.
This instruction shall be read together with the example after the instruction.
1. Perform a backflush.
2. Open page 3.1 Trend (15 min) and analyze the trend curve for V201-8.
Before the backflush, the valve shall move as fast as possible to a steady position where it
creates required pressure. If not, parameter p166 shall be adjusted.
3. Adjust parameters, and perform a new backflush.
4. See if the curve has improved. Repeat until satisfactory result has been achieved.
5. See if the time between backflush initiation and backflush can be shortened . If possible, adjust
parameter p310. See parameter p310 in the example below.
Example
In this example, five backflushes are performed. After the first four backflushes, the PID parameters
where changed for pressure regulation to adjust the movement of the control valve V201-8 before
the backflush.
The illustration is taken from page 3.1 Trend (15 min). Backflush is indicated by the movement
of the backflush valve 309-1 (pink line) and the movement of control valve V201-8 is indicated
by the blue line.
1st backflush Parameter p166 is set to 0.30. But it takes too long time for V201-8 to get into
position to create desired pressure (1). The curve slops downwards in a long bend,
which means that it takes time for V201-8 to find correct position.
2nd backflush Parameter p166 was adjusted to 0.6. This made the valve movement much faster
in the beginning, shown by the steep curve at the beginning. But then a more slow
regulation starts, shown by the soft slope (2). This was a change for the better, but
3rd backflush Parameter
not enough.p166 was increased to 1.2 which resulted in a satisfactory valve
movement (3): A fast movement, followed by a minor adjustment. A small
overcompensation can be noted (curve goes too low), that might be adjusted by
decreasing the value to 1.1.
4th backflush During the first backflushes, parameter p310 was set to 60 seconds. The parameter
defines time between a backflush is triggered and it actually starts. But now, when
V201-8 is calibrated, this time can be shortened. Before the fourth backflush
parameter p310 is set to 15 seconds. The shortened time span is indicated by
the braces in the illustration.
5th backflush No parameter was changed. This backflush is only showed to confirm that the
parameter setting is OK and that the curve (5) for V201-8 is basically the same as
for backflush three and four (3 and 4).
3 CalibExample
Alarm history and important events are logged in the control system. The log also include
components connected via the log box (optional).
The control system store all alarms and relevant events for at least 24 months. The memory has
a vast safety margin but when it is full, data will be deleted starting with the oldest data. Logged
information can be exported to a USB memory stick. See Export control system log files on page 71.
Event log certif cate: Contains events relevant to the IMO certificate. Those events are the
ones that are GPS stamped in the table below, with exception for events regarding the log box
(5010—5220).
The GPS stamp column indicates if the event is stamped with GPS position (Y=yes, N=no).
5010 Log box: Valve V01 position change: [X]. 1=Closed. 0=Not closed. Y
5011 Log box: Valve V01 position change: [X]. 1=Open. 0=Not open. Y
5020 Log box: Valve V02 position change: [X]. 1=Closed. 0=Not closed. Y
5021 Log box: Valve V02 position change: [X]. 1=Open. 0=Not open. Y
5030 Log box: Valve V03 position change: [X]. 1=Closed. 0=Not closed. Y
5031 Log box: Valve V03 position change: [X]. 1=Open. 0=Not open. Y
5040 Log box: Valve V04 position change: [X]. 1=Closed. 0=Not closed. Y
5041 Log box: Valve V04 position change: [X]. 1=Open. 0=Not open. Y
5050 Log box: Valve V05 position change: [X]. 1=Closed. 0=Not closed. Y
5051 Log box: Valve V05 position change: [X]. 1=Open. 0=Not open. Y
5060 Log box: Valve V06 position change: [X]. 1=Closed. 0=Not closed. Y
5061 Log box: Valve V06 position change: [X]. 1=Open. 0=Not open. Y
5070 Log box: Valve V07 position change: [X]. 1=Closed. 0=Not closed. Y
5071 Log box: Valve V071 position change: [X]. 1=Open. 0=Not open. Y
5080 Log box: Valve V08 position change: [X]. 1=Closed. 0=Not closed. Y
5081 Log box: Valve V08 position change: [X]. 1=Open. 0=Not open. Y
5090 Log box: Valve V09 position change: [X]. 1=Closed. 0=Not closed. Y
5091 Log box: Valve V09 position change: [X]. 1=Open. 0=Not open. Y
5100 Log box: Valve V10 position change: [X]. 1=Closed. 0=Not closed. Y
5101 Log box: Valve V10 position change: [X]. 1=Open. 0=Not open. Y
5110 Log box: Valve V11 position change: [X]. 1=Closed. 0=Not closed. Y
5111 Log box: Valve V11 position change: [X]. 1=Open. 0=Not open. Y
5120 Log box: Valve V12 position change: [X]. 1=Closed. 0=Not closed. Y
5121 Log box: Valve V12 position change: [X]. 1=Open. 0=Not open. Y
5130 Log box: Valve V13 position change: [X]. 1=Closed. 0=Not closed. Y
5131 Log box: Valve V13 position change: [X]. 1=Open. 0=Not open. Y
5140 Log box: Valve V14 position change: [X]. 1=Closed. 0=Not closed. Y
5141 Log box: Valve V14 position change: [X]. 1=Open. 0=Not open. Y
5150 Log box: Valve V15 position change: [X]. 1=Closed. 0=Not closed. Y
5151 Log box: Valve V15 position change: [X]. 1=Open. 0=Not open. Y
5160 Log box: Valve V16 position change: [X]. 1=Closed. 0=Not closed. Y
5161 Log box: Valve V16 position change: [X]. 1=Open. 0=Not open. Y
5170 Log box: Valve V17 position change: [X]. 1=Closed. 0=Not closed. Y
5171 Log box: Valve V17 position change: [X]. 1=Open. 0=Not open. Y
5180 Log box: Valve V18 position change: [X]. 1=Closed. 0=Not closed. Y
5181 Log box: Valve V18 position change: [X]. 1=Open. 0=Not open. Y
This section gives a detailed description of the PureBallast processes. The processes are divided
into three main processes, with sub processes, with indications of automatic and manually initiated
steps.
• Ballast
• Deballast
• CIP
• Deactivate system
• Change flow (set flow before a ballast or deballast process)
• Manual mode.
3 BallastProcess
2. Request from control system to open overboard (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
3. Overboard valve opened by operator and confirmed in control system. (Handled automatic, if
external component signal is enabled.)
Component activities:
• - Start P401-1 (booster pump for LDC cooling water) (if used)
- Open V403-35 (cooling water inlet)
- Open V201-32 (filter outlet)
• Start P403-1 (booster pump for reactor cooling water) (if used).
4. Power management
Automatic power request from PureBallast to vessel’s power management system (if
integrated).
5. UV lamp warming
Component activities:
1. Component activities:
• Start automatic control of control valve (V201-8) based on input from the pressure transmitter
• Open V309-1
• Start M709-42.
• Stop M709-42
• Close V309-1
• Start automatic control of control valve (V201-8) based on input from the flow meter.
3. Differential pressure check. If necessary, the process is repeated.
1. Operator pause the ballast process manually. Pause can also be initiated by an external signal,
for example when heeling is initiated from the ISCS. In this case, the process is resumed
automatically when the heeling signal is deactivated.
2. Set V201-8 (control valve) to parameter (p113) set opening percent.
3. Request from control system to stop ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
4. BW pump stopped by operator and confirmed in control system. Component activities:
• - Open V404-36 (AOT reactor outlet, cooling water) on running AOT reactors
- Stop counter: Accumulated water
- Open V403-35 (cooling water inlet)
• Start P403-1 (booster pump for reactor cooling water) (if used)
- Close V201-3 (filter inlet)
- Close V201-20 (reactor outlet) on running AOT reactors
- UV lamps dimmed to 50 %
• Close V201-8 (control valve).
5. System in pause mode
6.
Resume ballasting
Operator resumes the ballast process manually.
Component activities:
• Stop P401-1 (booster pump for LDC cooling water) (if used)
• Stop P403-1 (booster pump for reactor cooling water) (if used), only needed if stop from
pause mode
• Stop counter: Accumulated water
• - Close V403-35 (cooling water inlet), only needed if stop from pause mode
- Set V201-8 (control valve) to parameter set opening percent.
- Close V201-32 (filter outlet) Delay: the longes time between of p146 and p119.
• UV lamps are lit at 100 % for 10 seconds, then switched off.
• Stop counter: UV lamp runtime
• - Close V201-19 (reactor inlet)
- Close V201-20 (reactor outlet)
• Automatic withdrawal of power allocation (if integrated).
2. Filter backf ush
Backflushing of filter starts, including the following activities:
• - Start automatic control of control valve (V201-8) based on input from the pressure
transmitter
- Open V309-1
- Start M709-42.
3. Backflush is performed. Approximate duration: 20 seconds.
• - Stop M709-42
- Close V309-1.
4. Request from control system to stop ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
5. BW pump stopped by operator and confirmed in control system.
3 DeBallastProcess
• - Start P401-1 (booster pump for LDC cooling water) (if used)
- Open V403-35 (cooling water inlet)
• Start P403-1 (booster pump for reactor cooling water) (if used).
4. Power management
Automatic power request from PureBallast to vessel’s power management system (if integrated).
5. UV lamp warming
Component activities when power has been granted:
1. Operator pause the deballast process manually. Pause can also be initiated by an external
signal, for example when heeling is initiated from the ISCS. In this case, the process is resumed
automatically when the heeling signal is deactivated.
Component activities:
2. Request from control system to stop ballast water pump (outside the PureBallast system
control). (Handled automatic, if external component signal is enabled.)
Component activities:
4. Resume deballasting
Operator resume the deballast process manually.
Component activities:
5. Request from control system to start ballast water pump” (outside PureBallast system).
(Handled automatic, if external component signal is enabled.)
6. BW pump started by operator and confirmed in control system.
Component activities:
• Stop P401-1 (booster pump for LDC cooling water) (if used)
• Stop P403-1 (booster pump for reactor cooling water) (if used), only needed if stop from
pause mode
• Close V403-35 (cooling water inlet), only needed if stop from pause mode
• Set V201-8 (control valve) to parameter set opening percent
• Close V201-9 (main inlet valve) Wait for feed back “closed” or delay according to p 115.
• UV lamps are lit at 100 % for 10 seconds, then switched off.
• Stop counter: UV lamp runtime
• - Close V201-19 (reactor inlet)
- Close V201-20 (reactor outlet)
2. Request from control system stop ballast water pump (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
3. BW pump stopped by operator and confirmed in control system.
3 CIPprocess
• - Stop P321-5
- Close V571-1 (CIP, deaeration valve)
- Close V460-2 (CIP, drain valve)
- Close V321–2 (AOT reactor, upper CIP return valve)
- Close V320–4 (AOT reactor, lower CIP return valve).
6.4.8 Repeat
When CIP process is done for the first AOT reactor, the remaining AOT reactors with status CIP
required are processed in the same way.
1.
Component activities when all required AOT reactors are processed:
• - Open V310-1
- Open V309-1
- Start M709-42.
2. Component activities after the filter is filled:
• - Stop M709-42
- Close V309-1
- Close V310-1.
3. Request from control system to close overboard valve (outside PureBallast system). (Handled
automatic, if external component signal is enabled.)
4. Overboard valve closed by operator and confirmed in control system.
• Operate components from the flow chart. Tap a component to operate it from the displayed
popup window. The following components can be operated: valves, motors, UV lamps etc,
digital output signals.
• Operate and simulate power management.
The following limitations exist for manual mode:
• Requires login level 2. The Manual mode button is only displayed for login level 2.
• Flow in pipes is not indicated in flow chart.
• Can only be activate from standby mode.
• No automatic processes can be run.
To activate: Press the Manual mode button in page 1.1 Flow chart and follow the instructions
Operate UV components manually and Operate UV lamps manually.
To deactivate: Press the Manual mode button again in page 1.1 Flow chart or log out. All forced
outputs and manual changes are reset and the system goes to Standby mode.
1.1 Introduction
This is a quick guide to the most common routines performed in the PureBallast control system.
More detailed instructions are found in the PureBallast manual.
• The Alarm list (page 2.1) must be controlled to verify that there are no alarms needing attention.
• Flow must have been selected before a process can be started. If parameter p131 is activated
maximum flow is automatically selected, and flow can only be changed during process
according to instruction Change ballast / deballast flow on page . If parameter p131 is
deactivated last selected flow is used. Otherwise, flow is selected on page 1.1 Overview or
1.2 AOT and flow selection.
• There must be available power for the system. If power management is integrated, this will be
done automatically. If power management is not integrated, confirm this manually.
1.2 Ballast and deballast
Follow the steps below
3. Wait for the message “Open valves ...”. Open relevant valves and then press the button in
the popup to confirm the action. (The popup is not displayed if the component feedback is
integrated with the control system.)
4. Wait for the message “Confirm ballast pump started”. Start the pump and then press the button
in the popup to confirm the action. (The popup is not displayed if the component feedback is
integrated with the control system.)
5. When desired amount of water has been processed, press the function button Stop to end
the process.
1
1.4 CIP clean AOT 1 Quick guide to PureBallast operations
6. Wait for the message “Close valves ...” and “Stop ballast water pump”. Handle accordingly.
(The popups are not displayed if the component feedback is integrated with the control system.)
7. Perform a CIP process if no operation is planned soon. A CIP process must be performed
within 30 hours after operation.
An alarm is indicated by a audible signal and by a blinking warning icon in the control panel.
• Never reset an alarm without first finding and attending to the problem.
Follow the steps below:
3. If the process have stopped: Take action to eliminate what has caused the alarm.
4. If the alarm is caused by a faulty AOT module, the ballast/deballast process has to be restarted
with another AOT according to the Perform ballast instruction.
5. If the process continues: Consider if the process shall be terminated. Take action to eliminate
what has caused the alarm.
Press the Ack selected or Ack all button after the problem has been dealt with.
• The system must be in standby mode. This means that this operation cannot be executed
during ballast or deballast.
• Complete status information regarding CIP is displayed in page 1.4 CIP status. The page
displays remaining time for ongoing CIP cycles, remaining time before individual AOTs are
required to be CIP:ed etc.
Follow the steps below
3. Wait for the message “Open valves ...”. Open relevant valves and then press button in the
popup to confirm the action.
Result: The automatic CIP cycle starts. The CIP cycle takes about 25 minutes per AOT.
2
1 Quick guide to PureBallast operations 1.5 Export control system log files
4. Wait for the message “Confirm overboard valve closed”. Close the valve and then press button
in the popup to confirm the action.
3. Wait for message: Insert USB in PLC. Insert a USB memory in USB PLC port on the cabinet
door.
4. Chose one of the following alternatives to decide time interval for the information to be copied:
• Accept suggested default time interval in the Start and End fields. Default start date is the
oldest file in the system, and default end date is today’s date.
• Select the Specify time interval box, and enter desired interval in the Start and End fields.
5. Press one of the following function buttons: Events, Cert events or Alarms.
Result: The information is copied to the USB memory indicated by a green checkmark on
the button during copying.
6. Wait for the message "Export OK" to appear. If desired, export next category of events using
the function buttons.
Result: A folder named PureBallast has been downloaded. It contains three sub folders:
Alarm, Cert and Event. The folder corresponding to your export choice contains a CSV file.
3
Chapter: 4. Parameters
System manual — PureBallast 3.0 Flow 1000
3
1 Introduction
This chapter contains information about parameters in the control system and flow transmitter.
It covers:
This section describes all parameters set in the PureBallast control system.
NOTE
• Parameters in bold can only be changed by login level AlfaLaval. Parameters in normal text can
be changed by login level Advanced operator.
• The parameter settings can be exported to a USB memory for safety backup, and be restored
from a backup. See chapter 3. Operating instructions and control system description for
instructions.
Parameters are valid for PLC software version V3.0.7.
The installation specific parameters are set to reflect the specific installation and shall normally only
be checked and adjusted at first start up, during preparations for commissioning.
The installation specific parameters are found in the pages listed below:
- p200, p201, p208 and 216: Time-out parameters for draining and filling AOT reactor.
These parameter are evaluated during the commissioning preparation test and adjusted if
necessary.
NOTE
• These instructions require login level 2 or 3. Level 2 gives access to set parameters, with
exception from crucial parameters, which requires level 3.
Follow the steps below:
2. To see allowed range (maximum and minimum values) and change setting, press the blue
button (with the parameter ID). A button pair is displayed.
4 ParaIntervalSet
Press the ≥ sign to display range. Entered parameter value must be within defined setting
range.
4 MinMax
4. Enter the setting and confirm by touching the Enter button. To close the keyboard without
saving data, touch the Esc button.
If the parameter is set with a drop down menu, select desired choice by touching the value.
Result: The setting is saved directly, it is now safe to leave the page.
4 5.1
The following information is displayed: Parameters in bold can only be changed by login level
AlfaLaval.
p100 High pressure, 7.00 1–10 bar Setpoint for shut down due to high
shutdown trigger pressure at PT201-16. Default value
(PT201-16) shall be used.
p101 High pressure, 6.00 0–10 bar Setpoint for warning due to high pressure
warning trigger at PT201-16. Default value shall be used.
(PT201-16)
(6 bar = 0.6 MPa)
p103 Low pressure, 0,0 -1–2 bar Setpoint for warning due to low pressure
warning trigger at PT201-16.
(PT201–16)
(1 bar = 0.1 MPa)
p104 Max pressure 6 6/10 bar Defines maximum pressure for the
(PT201–16) system, measured by pressure indicator
PT201-16 for the system.
p105 Transition trigger, 50 10– m3/h Defines which flow that must be
ballast flow 500 established, before the process goes
established from ballast start-up to full ballast.
(FIT201-1)
p113 Min % open for 20 10–100 % During ballast and deballast, valve
V201-8 V201–8 handles the automatic pressure
and flow control.
p115 Maximum travel 10 2–30 sec Maximum time system will wait for filter
time for valves bypass valve to close, when system is
stopped after deballast.
p116 Low flow shut 10 10–90 % Set point for shut down due to low flow,
down limit defined as percent of certified flow.
(FIT201-1)
p117 Max delay of CIP 6 0–24 hrs Define max delay, in hours, before a CIP
cycle, hours process must be performed after ballast
or deballast. Default value shall be used.
p118 Max delay of CIP 1 0–30 day Define max delay, in days, before a CIP
cycle, days process must be performed after ballast
or deballast. Default value shall be used.
p119 Valve travelling 5 1–10 sec Maximum time for V201–8 to go from
time for 201-8 opened to closed, and vice versa, before
a warning is issued.
p120 V201–8 PID 0.30 0.00 – N/A Defines proportional gain (Pf) value used
proportional gain 10.00 for PID regulation of V201–8 during
ballast and deballast.
p121 V201–8 PID 7.00 0–100 sec Defines integral time (If) value used for
integral time PID regulation of V201–8 during ballast
and deballast.
p122 V201–8 PID 0.0 0.0–100.0N/A Defines derivate gain (Df) value used for
derivative gain PID regulation of V201–8 during ballast
and deballast.
Normal value: 0.
p126 LDC after-cooling. 5 0–60 min Defines how long after a ballast or
(Stop delay for deballast process the booster pump shall
401-1, if installed) run to cool the LDC.
p138 Timeout: Time 5 1–30 min Defines maximum time a ballast and
in Pause before deballast process can be manually
going to Stop paused. After defined time, the process
is stopped.
p140 Timeout: 5 1–30 min Time the control system will wait for
Request "Confirm confirmation signal from ISCS, hard
overboard valve wire or manually in popup before
open" displaying message that operation was
not performed.
p141 Timeout: Request 5 1–30 min Time the control system will wait for
"Confirm ballast confirmation signal from ISCS, hard
pump started" wire or manually in popup before
displaying message that operation was
not performed.
p143 Timeout: Power 60 1–300 sec Time the control system will wait for
granted signal not confirmation signal from ISCS that the
received operation was performed.
p144 Timeout: Start-up 60 30–300 sec Time the control system will wait for
ballast flow accepted minimum flow (p105) to be
established established before automatic stop.
p146 Timeout: Main 5 0.1–15.0 sec Maximum time system will wait for filter
valve travel time outlet valve to close, when system is
stopped after ballast.
4 5.2
The following information is displayed. Parameters in bold can only be changed by login level
AlfaLaval.
• Not used
• Hardwire ranged
• Hardwire fixed
• Remote interface (requires that p132
is activated)
p128 Max time 60 15–240 Sec Define max delay before the system
communication shuts down after communication is
p129 Booster pump Not N/A Drop Defines if a booster pump (not part of Alfa
(P401-1) for LDC used list Laval’s scope of suppy) is used to create
cooling water sufficient cooling water flow to the LDC.
p130 Booster pump Not N/A Drop Defines if a booster pump (not part of
(P403-1) for used list Alfa Laval’s scope of suppy) is used to
reactor cooling create sufficient cooling water flow to the
water AOT reactor.
p132 Remote interface Not N/A Drop Defines if remote interface (optional) is
via modubus used list used and connected via modbus.
p135 External system Not N/A Drop Defines if an external system stop button
stop used list (or signal) is installed.
p137 Hide Pause Not N/A Drop Defines if the Pause button is visible or
button used list hidden in the control system. If activated,
the button is hidden.
p161 Time interval for 1.0 0.1 – Min. Time interval to update the amount (m3)
log event 331 60.0 of ballast water treated in log file.
p162 Time interval for 1.0 0.1 – Min. Time interval to update the amount (m3)
log event 341 60.0 of deballast water treated in log file.
p165 Additional Not N/A Drop Defines if a third additional by-pass valve
by-pass signal used list is used. The signal gives information if
3 the valve is opened during process, so
that PureBallast is by-passed.
p166 Pressure PID 0.60 0.00 – N/A Defines proportional gain (Pf) value used
proportional gain 10.00 for PID regulation of V201–8 during
backflush.
p167 Pressure PID 7.0 0.0 – sec Defines integral time (If) value used
integral time 100.0 for PID regulation of V201–8 during
backflush.
p168 Pressure PID 0.0 0.0 – N/A Defines derivate gain (Df) value used
derivate gain 100.0 for PID regulation of V201–8 during
backflush.
Normal value: 0.
4 5.3
The following information is displayed. Parameters in bold can only be changed by login level
AlfaLaval.
p200 Timeout: AOT 2 1–10 min Time the control system will wait for
draining confirmation that an AOT reactor is
drained before an alarm is issued.
Recommended setting: Approximately 1
minute more than actual drain time.
p201 Timeout: Reactor 2 1–10 min Time the control system will wait for
cooling water confirmation that cooling water has filled
(LS201-29) the AOT reactor before an alarm is
issued.
p202 High temp, 60 10–100 ºC Setpoint for high water temperature alarm,
alarm trigger indicated by temperature transmitter in
(TT201-33) AOT reactor. Default value shall be used.
p204 Low temp, 0 0–40 ºC Setpoint for low water temperature alarm,
alarm trigger indicated by temperature transmitter in
(TT201-33) the AOT reactor. Default value shall be
used.
p206 Alarm delay for 5 0–10 sec Delay before alarm is issued after setpoint
sensor TT201-33 temperature (p202 and p204) is reached.
p208 Timeout: CIP fluid 5 1–15 min Setpoint for max time to fill an AOT
fill-up time AOT reactor with CIP liquid during CIP process
before an alarm is issued.
p210 UV lamp warm-up 90 0–90 sec Warm up time for UV lamps before full
time ballast or deballast starts. Default value
shall be used.
p211 UV lamp cooling 120 30–300 sec Cooling time for UV lamps after ballast or
time deballast. Default value shall be used.
p212 Timeout: UV 200 10–200 sec Time the control system will wait for
lamp ignition confirmation signal that UV lamps are
ignited. If no lamps are ignited or if
less lamps than set in parameter p213
are ignited, the AOT reactor will be
automatically stopped. Default value
shall be used.
p215 Alarm delay for 5 0–10 sec Delay before shutdown when there is no
LS201-29 water in an AOT reactor, indicated by
level switch in AOT reactor (LS201-29).
Default value shall be used.
p216 Timeout: Fluid 5 2–10 min Setpoint for max time to fill an AOT
fill-up time AOT reactor with fresh water during CIP
process before an alarm is issued.
p221 Low UV intensity 550.0 0.0 – W/m2 Setpoint for warning due to low UV
warning trigger 500.0 intensity indicated by UV sensor
QT201–50 in the AOT reactor. This
warning will be logged in the Event log.
p231 Cabinet 40.0 20.0 – °C Setpoint for LDC cooling fan regulation.
temperature 60.0 When the temperature is below setpoint,
low threshold the fan is running at 15 % of full effect.
(TT401-2)
At setpoint the fan effect is increased
proportional to temperature from 15 %
up to 100 % at temperature set in p232.
Default value shall be used.
p232 Cabinet 45.0 20.0 – °C Setpoint for running the LDC cooling fan
temperature 60.0 at 100 %.
high threshold
(TT401-2)
p234 UV control 0.10 0.00 – N/A Defines proportional gain (Pf) value used
proportional gain 100.00 for PID regulation of UV lamp effect.
Default value shall be used.
p235 UV control 15 0–100 sec Defines integral time (If) value used for
integral time PID regulation of UV lamp effect.
p236 UV control 0 0–100 sec Defines derivate gain (Df) value used for
derivative time PID regulation of UV lamp effect.
4 5.4
The following information is displayed. Parameters in bold can only be changed by login level
AlfaLaval.
p301 High filter 1.5 0.0- bar Setpoint for high pressure warning,
differential 2.0 indicated by pressure transmitter
pressure, PT201-27.
warning trigger
(PT201-27) (1.5 bar = 0.15 MPa)
p304 Required 2.50 1.00– bar Defines pressure needed for efficient
pressure to 5.00 backflushing. This pressure must be
start backflush attained to start backflush.
(PT201-16)
This parameter also defines setpoint for
desired pressure during backflush: To
maintain this pressure, control valve
p305 Backflush trigger, 0.85 0.00– bar Setpoint for automatic start of filter
differential 2.00 backflush due to dirt in the filter, indicated
pressure by differential pressure transmitter on the
(PT201-27) filter.
p310 Backflush initial 10 0–60 sec Time from backflush trigger until backflush
delay is started. During this delay the control
valve is PID regulated to create the
required pressure defined in parameter
p304.
p311 Backflush delay 2.0 0.0– sec Defines for how many seconds the
(p305 during x 10.0 differential pressure defined in p305 must
sec). last, before automatic backflush starts.
p313 Differential 5 0–30 sec Time constant for low pass filter used for
pressure the differential pressure over the filter.
measurement The low pass filter is used to smoothen
filter the effect of sudden changes in differential
pressure (primarily pressure peaks after
completed backflush).
p315 Filter type 6000 100 – m3/h Parameter p314 should be set before this
6000 parameter. Available alternatives depend
on selection in p314.
p316 Max filter 6 6 – 10 bar Defines maximum pressure for the filter
pressure pressure indicators.
4 5.5
The following information is displayed. Parameters in bold can only be changed by login level
AlfaLaval.
p400 CIP cycle time 15 1–60 min Duration of circulation of CIP liquid
during a CIP process.
4 5.6
The following information is displayed. Parameters in bold can only be changed by login level
AlfaLaval.
System name N/A N/A N/A Possibility to enter a system name for
the system, for example Vessel name.
If two systems is installed information
about starbord and port side.
Serial number N/A N/A N/A Enter the PureBallast serial number.
p112 Maximum flow 1200 0– m3/h The parameter shall be set according to
(FIT201-1) 10000 pipe dimension for the flow meter pipe.
p131 Automatic AOT Not N/A Drop Defines if AOT reactors shall be
selection used list automatically selected for process.
p213 Allowed no. of 0 0–1 No. If more lamps than set in this parameter
failed UV lamps are broken, operation will be denied.
per AOT reactor
If a UV lamp fails the flow is set to 80
% of current flow. The UV lamps are
lit to 100 %. A warning is issued and a
log is written to the event log, and the
operator will have do decide to continue
or stop the operation.
p217 AOT reactor size 300 N/A Drop Defines size of the AOT reactor, defined
list as max capacity (m3/h).
Alternatives: 300, 600 and 1000.
p150 EX proof system Not N/A Drop Defines if the EX proof version of
used list PureBallast is installed. This affects
both installation and control system.
p500 Log box Not N/A Drop Defines if the log box (optional ) is
used list installed to monitor and log external
valves and pumps, that are not part of
Alfa Laval’s scope of supply.
4 5.7
The following information is displayed. Parameters in bold can only be changed by login level
AlfaLaval.
Parameters for the ISCS modbus RTU server data shall be set according to the information below.
p700 Interface type RS485 N/A Drop Defines communication (cable) type
list used for communication between the
ISCS and PureBallast.
p701 Baud rate 9600 N/A Drop Defines baud rate in bits per second.
list
The parameter can be changed, but
it is not recommended. Note, that the
information must be the same in ISCS
and PureBallast control system.
p703 Data bits 8 N/A Drop Defines data bits per character.
list
Alternatives: 7 or 8.
This section describes the parameters set in the parameter pages in the flow transmitter, installed
on the flow meter.
General (non-installation specific) parameters are preset to function for all systems. They must only
be adjusted, by Alfa Laval, if required by performance reasons or similar. They are checked during
preparations for commissioning and shall normally not be adjusted after start up.
4FTPanel
Buttons used:
2. Press Padlock.
Result: A line appears under the first zero.
7. Check that the parameter is set to the same frequency as used on the vessel. (Ask the crew
for information):
a: To change: Press Padlock.
b: Press Change to change (toggle) the setting.
c. Press Padlock to set the value.
Flow direction
(Direction of flow measured in the flow meter.)
Set Qmax
(Measuring range for the flow meter: the analog outputs and the frequency output.)
9. Check that the parameter is set according to the flow direction in the pipe.
a: To change: Press Padlock.
b: Press Change to change (toggle) the setting.
c. Press Padlock to set the value.
11. Check that the parameter is set according to pipe dimension for the flow meter pipe:
100 – 300
150 – 300
200 – 700
250 – 1200
300 – 1200
350 – 1700
400 – 2200
450 – 3300
500 – 3300
600 – 3300.
a: To change: Press Padlock.
b. Press Select to select digit to change (A line is placed under the changeable digit).
c. Press Change to change (toggle) the digit.
d: Press Padlock to set the value.
17. Press Padlock to display the setting. Check that the parameter is set to “On”.
a: To change: Press Padlock.
b: Press Change to change (toggle) setting.
c: Press Padlock to set the value.
18. Press Forward until Current output (mA setting) is displayed. Check that the parameter is
set to “4-20 mA”.
a: To change: Press Padlock.
b: Press Change to change (toggle) setting.
c: Press Padlock to set the value.
This section describes the parameters (DIP switch settings) set in the LPS, installed in the lamp
drive cabinet (LDC). Each LPS is set to identify the individual LPS in the installation.
Switch 1-3 shall always be in position off. Switch 4-8 is set to identify the individual LPS according
to the table below. Only position ON is indicated. For empty cells in the table, the switch shall be
in position OFF.
LPS 1–16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
SW 1
SW 2
SW 3
SW 4 ON
SW 5 ON ON ON ON ON ON ON ON
SW 6 ON ON ON ON ON ON ON ON
SW 7 ON ON ON ON ON ON ON ON
SW 8 ON ON ON ON ON ON ON ON
Example
4 LPSdip
NGE R
! DA
• Switch off the main breaker on the LDC door. The LPS has high voltage/power (600 V) inside
and on the lamp power connector, even when UV lamps are not lit.
• The LDC contains a fan, which can cause injury if in operatoin.
Follow the steps below
1. Unscrew the plastic lid (1) over the DIP switches on the fron of the LPS.
7 LPSdip
2. Use a small screw driver to change position of the swithces according to the table under
instruction DIP switch settings.
3
1 Introduction
This chapter covers information about alarms and warnings, together with information about how
to solve the problems causing the alarms to trip. The chapter also contains a list of solutions for
problems that may occur, but that is not indicated by any system.
• control system
• lamp power supply (LPS)
• flow meter (with fault finding instruction)
• I/O system and X20 modules.
See chapter 3. Operating instructions and control system description to find information about
the alarm pages and how to attend to alarms.
This section lists all alarms and warnings related to the PureBallast system.
3Alarm
The icon in the alarm tab starts to blink.
2 Warning
The icon is displayed by the faulty component, if applicable.
Alarm and warning: Active but not acknowledged.
All alarms are displayed in the control panel’s page 2.1 Alarm list and are sorted in order of
occurrence; most recent alarm at the top of the list.
Column in Description
table
Alarm ID Identification number of the alarm. The number is also indicated in the control
system alarm list.
- A = Alarms stop the ongoing process, which can be restarted after the
problem has been attended to.
- W = Warnings are notification of a status change or a problem. Warnings
allow the process to continue.
• 1: If the alarm contains three digits, the first digit indicates component
according to: 1=AOT reactor and 2 =Filter. If the alarm contains two digits,
the alarm is general and is not connected to a specific component.
• 00: Unique number for the alarm/warning.
Alarm text / The text displayed in the control system. Note that AOT reactor number is
Problem indicated by “x” in the table, instead of the actual AOT reactor number. In the
control system alarm text, the actual AOT reactor number is stated for the AOT
reactor concerned.
For problems not indicated by an alarm, the text gives a general explanation
of a problem that can occur.
Trigger / Trigger: Source of the alarm or warning, identified by the input sensor’s item
Parameter number or equivalent.
Parameter: The parameter controlling the alarm, when applicable.
Delay: Time before the alarm is activated after the condition of the alarm is met.
Comments: Additional information or explanations.
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A01 Process Trigger: PT201-16 Delay: 30 sec. Ballast water pump Check pressure and flow from
pressure too Parameter: p100 gives too high ballast pump(s). If the pressure
high (PT201-16). Comment: Pressure pressure. exceeds set value: Adjust incoming
Automatic stop. transmitter PT201-16 pressure to PureBallast.
9
Control system
10
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A03 Process Trigger: PT201-16 Delay: 30 sec. Signal missing 1. Check fuse F45 in Control
pressure or pressure cabinet to see what circuit
signal missing Comment: Error transmitter PT201-16 caused the fuse trip.
(PT201-16). in system pressure malfunction.
2. Use the circuit diagram to
Control system
W04 Process Trigger: PT201-16 Delay: 30 sec. See possible cause See A01.
pressure too Parameter: p101 for A01.
high (PT201-16). Comment: Pressure
higher than parameter
set limit.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A10 Process flow Trigger: FIT201-1. Delay: 5 sec. Signal missing or flow 1. Check fuse F45 in Control
signal missing Parameter: N/A transmitter FIT201-1 cabinet to see what circuit
(FIT201-1). Comment: Error in malfunction. caused the fuse trip.
system flow sensor.
2. Use the circuit diagram to
check the fuse setting, adjust
according to figures in circuit
transmitter display,
message error)
11
Control system
12
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W12 Process Trigger: FIT201–1 Delay: 30 sec. Flow rate higher than Reduce the incoming ballast water
flow higher Parameter: N/A selected certified flow to the PureBallast system.
than certified flow, for the number
(FIT201-1). of AOT reactors in
Control system
A13 Process flow too Trigger: FIT201–1 Delay: 20 sec. Flow too low. • Increase flow.
low (FIT201-1). Parameter: p116
• Make sure the ballast water
Automatic stop. Comment: If flow
is less than set in from the ballast pump is
parameter p116, the directed to PureBallast. When
system is shut down. OK the process will continue
automatically.
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
process description.
A14 Process Trigger: FIT201-1 Delay: Set in Control valve V201–8 See alarm A17.
flow too low Parameter: p105 parameter p144. malfunctions.
during start-up
(FIT201-1). Flow too low. See alarm A13.
Automatic stop.
2.1
13
Control system
14
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A17 Valve error Trigger: Limit switch Delay: 15 sec. Fuse tripped. 1. Check fuses F43 in control
(V201-3). GS201-3. cabinet to see what circuit
Parameter: N/A. Comment: Error on caused the fuse trip.
valve V201–3.
2. Check relay K1 and K2 on
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
actuator.
3. Check that compressed air
pressure is according to
requirements in chapter 6.
Installation description and
drawings, section Connection
list.
A23 Valve error Trigger: Limit switch Delay: 15 sec. See possible cause Check relay K5 and K6 on module
(V201-9). GS201-9. for A17. X10.
2.1
15
Control system
16
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A29 Valve error Trigger: Limit switch Delay: 15 sec. See possible cause
(V201-8). GS201-8. for A17.
Parameter: N/A. Comment: Error on
control valve V201–8. • Sensor error. 1. Check open indication in the
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A33 Bypass valve is Trigger: Limit switch Delay: 15 sec. The valve has been If not opened intentionally, close
open (V212-31). GS212-31. opened manually or valve V212-31.
Parameter: N/A Comment: If the valve via the ISCS.
(not controlled by
PureBallast) is opened, See possible cause
any ongoing process is for A17.
A35 Valve error Trigger: Limit switch Delay: 15 sec. See possible cause
(V212-31). GS212-31. for A17.
Parameter: N/A Comment: Shutdown
of all steps except CIP.
The alarm does not
prevent completion or
start of CIP process.
W40 Process Trigger: Pressure Delay: 2 sec. Ballast water pump Check that pressure and flow
pressure too low transmitter: gives too low from ballast pump(s) is according
(PT201-16). PT201-16. pressure. to requirements in chapter 6.
Parameter: p103. Installation description and
drawings, section Connection list.
17
Control system
18
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A48 System stop Trigger: Stop button Delay: None. Process has been
Control system
A49 System stop Trigger: Stop button Delay: None See A48.
activated during on control cabinet
CIP (Stop Parameter: N/A
button).
A50 System stop Trigger: External Delay: None. Process has been
activated stop button on control stopped by external NOTE
(External stop cabinet (or signal). stop button or signal
button). Parameter: p135 from the ISCS Find out the reason why the process
(integrated ship has been stopped before releasing the
control system). button and starting another process.
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W58 Fuse tripped in Trigger: Control Delay: None. Possible reasons: 1. Check fuse F43–F45 in control
control cabinet. cabinet. • cabinet to see what circuit
Parameter: N/A caused the fuse trip.
• short circuit
2. Use the circuit diagram to
• overheated fuse
locate the component or find
the reason that caused the fuse
A66 Additional Trigger: External Delay: 5 sec. The valve has been If not opened intentionally, close
bypass valve system. opened manually or the valve.
1 is open. Parameter: p163 Comment: If the valve via the ISCS.
(not controlled by
PureBallast) is opened,
any ongoing process is
stopped.
This alarm is not
issued when the valve
is opened during mode
standby, heeling or
pause.
19
Control system
20
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A69 Remote system Trigger: External Delay: 5 sec. PureBallast is If valve is not opened intentionally,
reports system system. bypassed via the close the valve.
is bypassed. Parameter: ISCS.
Control system
A71 Ballast water Trigger: Control Delay: Set in Faulty connection of Check that all electrical connections
pump is system timer. parameter p141. signal cable. are OK. Check that the signal
not running. Parameter: p141. wiring is according to information in
Automatic stop. Comment: Feed back chapter 6. Installation description
signal “BW pump is and drawings, section External
running” is deactivated component signal integration.
A75 Overboard valve Trigger: Control Delay: Set in See possible cause
is not open. system timer. parameter p140. for A71.
Automatic stop. Parameter: p140
2
Comment: Feedback
“overboard valve is
OPEN”.
A77 Error on all Trigger: AOT Delay: None An active alarm exist Check page 2. Alarm list to for
operating reactors on all installed AOT related alarms.
AOT:s. Parameter: N/A Comment: All reactors. It can be
Automatic stop. AOT reactors are the same error for
deactivated. all AOT reactors, or
different errors.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A79 Power is Trigger: Control Delay: Set in Power management Investigate if the reasons for not
not granted. system timer. parameter p143. master system not granting power is outside the
Automatic stop. Parameter: p127. granting power. PureBallast system.
Comment: No
power steps have Feedback signal from See A71.
been granted within power management
6. Installation description
and drawings, section Power
management system integration.
W80 Power is not Trigger: Power Delay: None. See possible cause
fully granted. management system. for A79.
Flow capacity Parameter: p127. Comment: Not all
reduced. requested power steps Not enough power Continue process with lower flow
are granted. Triggered has been granted. capacity or try later.
if number or requested
power steps does
not match number of
granted power steps.
2.1
W82 Heeling mode Trigger: Heeling Delay: 2 sec. Heeling mode has
requested (internal transfer) been activated by
by operator. requested in control Comment: The system external system.
Automatic system. is set in pause mode.
pause. Parameter: N/A If operation has not
been requested: See
A71.
21
Control system
22
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W83 Heeling mode Trigger: Heeling Delay: None. See possible cause
cancelled (internal transfer) not for W82.
by operator. requested in control Comment: Process
Process system. is resumed after being
Control system
A91 PLC lost Trigger: Control Delay: 60 sec. Panel is switched off 1. Switch on the panel.
communication system PLC. or faulty.
2. Restart the panel. See problem
with all control Parameter: N/A Comment: After
60 seconds of lost 1 B in the general problems list
panels.
communication, on page .
ongoing process is 3. Replace if faulty.
stopped in a controlled
way and the system Wrong software Check that the HMI and PLC
is shut down. This version software have the save program
message is visible in version. This is visible in control
the control panels and system page 4.1 System info.
saved in the log after
the communication is Wrong network Check settings for each panel
restored. But, W92 will setting according to chapter 3, section Set
be visible in the master control panel IP settings.
control panel.
Check that the remote control
panel is added in the main panel
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W92 Master control Trigger: Control Delay: 30 sec. Master panel is See A91.
panel lost system PLC. switched off or faulty.
communication Parameter: N/A Comment: After
with the PLC. communication is lost, Faulty cable See A91.
ongoing process is connection.
stopped in a controlled
A93 Heart beat signal Trigger: Control Delay: Set in To operate PureBallast when communication is down,
from remote system PLC. parameter p128. follow the steps below:
interface is not Parameter: p128
updating. Comment: After 1. Set the system to Local mode: Press the Local button
communication is on the control panel.
lost between ISCS
2. Run the system from the control panel. Note that you
and PLC, ongoing
will need to confirm two messages from the control
process is stopped in a
panel during operation: "Confirm ballast pump started"
controlled way and the
and "Confirm overboard valve open".
system is shut down.
3. Restore these settings when the communication is
The Heartbeat field working.
in page 4.5 Remote
4. Make sure that the system is not in test mode in page
interface, indicates
4.5 Remote interface (no check mark on the Test
communication.
mode button).
23
Control system
24
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W95 PLC battery low. The voltage in the Replace PLC battery in the control
List of alarms and warnings
W96 GPS signal not Trigger: Control Delay: 5 sec. Faulty electrical Check that the signal wiring
valid. system PLC. connection. is according to in chapter 6.
Parameter: p160 Installation description and
drawings, section GPS signal
integration and Control cabinet /
Interconnection diagram
W97 PLC error in Trigger: N/A Delay: 2 sec. Error in module. Check the LED error indication for
control cabinet. Parameter: N/A the electronic modules in the LDC.
See section I/O system and X20
modules on page 55.
25
Control system
26
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W100 AOT [x]: AOT Trigger: AOT Delay: Set in High temperature • Check that the inlet valves
temp too high temperature parameter p206. due to obstacles or (V201-19.x, V403-35) and
(TT201-33). transmitter TT201-33. error in one or more outlet valves (V201-20.x,
AOT shutdown. Parameter: p202 Comment: If components involved. 404-36.x) open properly by
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W101 AOT [x]: AOT Trigger: AOT Delay: Set in See possible cause
temp too low temperature parameter p206. for W100.
(TT201-33). transmitter TT201-33.
AOT shutdown. Parameter: p204. Sea water too cold; See to that incoming water is
temperature below 0 warmer than 0 C°.
C°.
C°.
W102 AOT [x]: Trigger: AOT Delay: Set in parameter Signal missing 1. Check fuse F42 in LDC to see
AOT temp temperature p206. or transmitter what circuit caused the fuse
signal missing transmitter TT201-33 TT201-33.x trip.
(TT201-33). error. malfunction.
2. Use the circuit diagram to
AOT shutdown.
Parameter: N/A. check the fuse setting, adjust
according to figures in circuit
diagram if necessary and reset
fuse.
3. Use the circuit diagram to
locate the component or find
the reason that caused the fuse
trip and attend to it.
4. Check cables to the
component. See AOT /
Circuit diagram and Lamp drive
cabinet (LDC) / Circuit diagram
in chapter 6. Installation
2.1
27
Control system
28
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W107 AOT [x]: LDC Trigger: LDC Delay: 15 sec. No cooling water to Check that cooling water supply
Control system
W109 AOT [x]: Trigger: LDC Delay: 5 sec. Signal missing or 1. Check fuse F42 in LDC to see
LDC cabinet temperature transmitter TT401 what circuit caused the fuse
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
damaged.
6. Replace transmitter TT401.
7. Restart the process from the
beginning.
W111 LDC air Trigger: Delay: 15 sec. LDC faulty. Check page 2. Alarm list to for
temperature too Temperature related alarms.
high (TT401–2) transmitter TT401–2.
2.1
29
Control system
30
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W113 LDC cabinet Trigger: Delay: 5 sec. Signal missing or flow 1. Check fuse F42 in Control
temperature Temperature transmitter TT401-2 cabinet to see what circuit
missing transmitter TT401–2. malfunction. caused the fuse trip.
(TT401–2) Parameter: N/A
2. Use the circuit diagram to
Control system
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W116 AOT [x]: AOT Trigger: Level sensor Delay: Set in Signal missing or 1. Check fuse F43 in LDC to see
fluid level LS201-29. parameter p215. sensor LS201-29.x which circuit that caused the
signal missing Parameter: N/A malfunction. fuse trip.
(LS201-29).
2. Check relay KS02.
3. Use the circuit diagrams for the
31
Control system
32
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W117 AOT [x]: AOT Trigger: Level sensor Delay: Set in No fluid in AOT 1. Control that correct valves
fluid missing LS201-29. parameter p215. reactor. are opened for current
(LS201–29) in Parameter: N/A process. See Detailed process
manual mode Comment: The AOT description in chapter 3.
Control system
W118 AOT [x]: CIP Trigger: Level sensor Delay: Set in No fluid in AOT 1. Check that valves V320-2,
flow missing LS201-29. parameter p215. reactor “x”. V320-4.x, V321-4 and 321-2.x
(LS201-29). Parameter: p208 LS201-29.x is open and close correctly.
indicating dry
2. Check that pump P320-1
condition.
is functioning correctly. See
problem 6D−6I in the general
problems list on page .
3. Hint: Valves can be manually
operated. See the instruction
Operate valves manually
2
in chapter 3. Operating
instructions and control system
description.
Note that the manual
operations are password-
protected and must only be
performed by authorized
trained personnel. The
PureBallast equipment or
connected equipment can be
irreparably damaged if handled
incorrectly.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Too low level in CIP Refill the tank with CIP liquid. See
tank. instruction Change and refill CIP
liquid in chapter 7. Service manual.
W119 AOT [x]: No Trigger: Level sensor Delay: Set in No liquid in 1. Check that pressure flushing
freshwater LS201-29. parameter p215. AOT reactor “x”. water in pipe 310 is according
filling in AOT Parameter: p216 LS201-29.x is to requirements in chapter 6.
(LS201-29). indicating dry Installation description and
condition. drawings, section Connection
2.1
list.
33
Control system
34
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W120 AOT [x]: AOT Trigger: Level sensor Delay: Set in Fluid in AOT reactor Restart the process from the
was not drained LS201-29. parameter p215. “x”. LS201-29.x beginning.
(LS201-29). Parameter: p200 is indicating wet
condition.
reactor LS201-29.x
malfunction.
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W122 AOT [x]: Fuse Trigger: LDC cabinet Delay: 1 sec. Fuse in LDC has Check fuse F42–43 in LDC cabinet
tripped in LDC for AOT tripped or has been to see what circuit caused the fuse
cabinet. Parameter: N/A switched off. trip. Check according to bullets.
W126 AOT [x]: MCB Trigger: LCD x-1 Delay: 1 sec. Motor circuit breaker 1. See LPS alarms in section
tripped in LDC Parameter: N/A (MCB) for an LPS in Lamp power supply (LPS) on
cabinet. Comment: AOT.x has tripped or page 48.
MCB=Motor circuit has been switched
breaker. AOT reactor 2. Check Q101–Q116 in LDC and
off.
is deactivated. respective cables and LPS unit.
3. Use the circuit diagram to
2.1
35
Control system
36
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W128 AOT [x]: LDC Q117. Delay: 5 sec. Motor circuit breaker Check Q117 in LDC.
cabinet fan (MCB) F1 in control
alarm cabinet has tripped
or has been switched
off.
W129 AOT [x]: LDC Trigger: Water Delay: 5 sec. Leakage in cooling Repair.
cabinet water sensor LS below water piping.
alarm. heat exchanger in Dry wet areas in the cabinet.
LDC. Remove the sensor and dry it with
Parameter: N/A paper.
cabinet.
List of alarms and warnings
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W130 AOT [x]: LPS Trigger: Lamp Delay: 2 sec. • LPS malfunction. Check LED indication on the LPS
sum alarm. power supply in AOT that triggered the alarm. See LPS
• Number of broken
reactors LDC. alarms in section Lamp power
UV lamps exeeds
Parameter: N/A supply (LPS) on page 48.
number set in
parameter p213. Check which lamps that are broken
W131 AOT [x]: UV Trigger: Lamp power Delay: 1 sec. One or more UV lamp Check which lamps that are broken
system failure. supply. is broken. in column Lamp OK in page 4.9
Too many failed Parameter: p213. Comment: AOT LPS overview.
lamps. reactor is deactivated.
Change according to instruction in
chapter 7. Service manual.
W132 Estimated UV Trigger: AOT reactor Delay: 1 sec. Lifetime for UV Recommended to change all lamps
lamp lifetime lap time. lamps are too after 3000 hours of operation.
exceeded. Parameter: p218. exceed according
to estimated lifetime Change according to instruction
in parameter. Replace UV lamp and quartz
sleeve in chapter 7. Service
2.1
manual.
37
Control system
38
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A137 AOT [x]: High Trigger: TS201-60 Delay: 1 sec. No flow in AOT See W100.
temperature Parameter: N/A reactor or too low
(TS201-60 Comment: AOT flow. After problem has been attended
tripped) and/or reactor is deactivated. to, the LDC needs to be reset.
Control system
LDC powered
off. Reset LDC
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
A138 AOT [x]: PLC Trigger AOT reactor Delay: 2 sec. Error in module. Check the LED error indication for
error in LDC x. the electronic modules in the LDC.
cabinet. Parameter: N/A Comment: AOT See section I/O system and X20
reactor is deactivated. modules on page 55.
W140 CIP schedule Trigger: Control Delay: Set in CIP not performed Control CIP status on page 1.3 CIP
W150 AOT [x]: Low Trigger: UV sensor Delay: 20 sec. Low UV intensity in Check water.
UV intensity QT201-50. AOT reactor.
(QT201-50) Parameter: p220 and Comment: The It is also possible to fill the reactor
p221. warning is issued if with fresh water to rule out muddy
the UV intensity falls water as reason for the warning.
below value set in
parameter p221. Quartz sleeves dirty. Run CIP process, and try again.
39
Control system
40
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W152 AOT [x]: UV Trigger: UV sensor Delay: None. See chapter 2. System overview,
W153 AOT [x]: UV Trigger: AOT reactor. Delay: None. See chapter 2. System overview,
lamp fail. System Parameter: p213 section Operation with broken UV
flow reduced. lamp.
W161 AOT [x]: LPS Trigger: LPS Delay: 1 sec. Faulty connection of Check the three cable connectors
communication Parameter: N/A electricity or signal on the LPS .
error. AOT cable.
shutdown.
Wrong LPS setting. Check that the DIP switches
are correctly set for every LPS.
See chapter 4. Parameters,
section Lamp power supply (LPS)
parameters.
2.1
41
Control system
42
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W162 AOT [x]: Trigger: None. Delay: None. Motor circuit breaker Replace.
Circuit breaker Parameter: p239 (MCB) is broken.
communication Warning is active
error. if parameter p239 Faulty modubus Check modubus cable W1 and W2.
Control system
W163 AOT [x]: Lamp Trigger: LPS in AOT Delay: 20 sec. Broken UV lamp. Change according to instruction in
error feedback reactor’s LDC. chapter 7. Service manual.
from LPS. Parameter: N/A Comment: No lamp
feedback when it is Faulty connection of Check UV lamp power cable.
requested to be started UV lamp cable.
by the LPS.
W164 AOT [x]: LPS Trigger: LPS in AOT Delay: 20 sec. Faulty LPS. Check page 4.9 LPS power
error feedback reactor’s LDC. overview and LED indication on the
from LPS. Parameter: N/A Comment: No LPS LPS that triggered the alarm. See
feedback when it is LPS alarms in section Lamp power
requested to star its supply (LPS) on page 48.
lamp. AOT reactor is
deactivated If the power is on but there are
no indication, the LPS is probably
broken.
2
W165 AOT [x]: LPS in Trigger: LPS in AOT Delay: 1 sec. One or more of the Check page 4.9 LPS power
fault state. reactor’s LDC. below: overview and LED indication on the
Parameter: N/A Comment: AOT LPS that triggered the alarm. See
reactor is deactivated. • Air temp fault LPS alarms in section Lamp power
• Driver fault supply (LPS) on page 48.
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
• Broken UV lamp
Fan fault and temperature faults
can be caused by something that
is preventing the fan from rotate.
Parameter: N/A
W171 Valve error Trigger: Limit switch Delay: 15 sec. See possible cause
(V201–20) GS201–20. for A17.
Parameter: N/A
W180 LDC ring Trigger: LDC. Delay: None. Faulty connection of Check that the power link (LAN)
redundancy signal cable cable from the control cabinet (in a
error Parameter: N/A loop to all LDCs) and back is OK.
1. Press ESC.
2. Make sure that “Processdata” is highlighted and press
ESC. (If not, use the arrow buttons to highlight the row.
43
Control system
44
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W306 Filter differential Trigger: Pressure Delay: 2 sec. Filter is clogged. Backflush manually from control
pressure transmitter PT201-27 system. If not sufficient, clean
too high on Boll filter. the filter candles according to
(PT-201–27) Parameter: p301, instruction in chapter 7. Service
p314. manual.
closed.
45
Control system
46
2.1
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
W308 Filter pressure Trigger: Pressure Delay: 30 sec. Signal missing 1. Check fuse F43 in LDC to see
signal missing transmitter PT201-71 or component which circuit that caused the
(PT201-71) on Hydac filter. Comment: Alarm malfunction. fuse trip.
Parameter: p314. deactivated in Standby.
2. Use the circuit diagram to
check the fuse setting, adjust
according to figures in circuit
diagram if necessary and reset
fuse.
3. Use the circuit diagram to
locate the component or find
the reason that caused the fuse
trip and attend to it.
4. Check cables to QT201-50.x.
2
Alarm Alarm text Trigger / Parameter Description Possible cause What to do?
ID
Parameter: p314.
W314 Backflush failed Trigger: Hydac filter. Delay: 15 sec. See W308.
to start (timeout). Parameter: p314.
W500 Log box hard Trigger: Log box Delay: 10 sec. Faulty cable Check connections and cable for
ware error. (optional). connection. power cable (W10) and Ehternet
Parameter: p314. cable (W104) between Control
cabinet and Log box.
Fuse in the log box Check fuse F02 and F03 in the log
has tripped or has box.
been switched off.
47
Control system
2.2 Lamp power supply (LPS) 2 List of alarms and warnings
5 LPSledG
5 LPSledY
• LPS temperature too high (> 50° C).
• LPS fan faulty.
Lamp error. Possible causes:
5 LPSledR
• Two lamp ignition failures.
• Broken UV lamp.
• Loose cables to UV lamp.
Lamp on.
5 LPSledB
5 LPSledB2
• Faulty DIP switch setting on one or more LPS. This fault occur after a 10 seconds
delay after start.
• Voltage on the fail safe is missing.
4FlowT_Alarm
Alarm time is displayed as time elapsed since the error occurred, and is showed as days, minutes
and hours.
Alarms and status are displayed in two lists, accessible from the Service mode screen in the flow
transmitter:
Yes: Go to step 5.
No: The tranmsitter is defect. Change.
Yes: Go to step 7.
No: Go to step 6.
7. The transmitter is OK. Check the following: Settings, application, installation, sensor, earthing,
connections etc.
8. The transmitter still not OK? Change settings according to chapter 4. Parameters, section
Flow transmitter parameters.
9. If the problem cannot be detected or corrected, the transmitter must be replaced according to
the instruction Mount flow transmitter. Note that it is not necessary to reset parameters in the
new transmitter. The settings are stored in the Sensorprom unit. When the new transmitter is
replaced, settings are downloaded automatically.
Buttons used:
2. To enter password (1000): Press Padlock. (A line appears under th e first zero.)
- Press Change to change the first 0 to 1.
- Press Padlock to set the value.
- Result: The “Basic settings” menu appears after two seconds.
4. Press Padlock, and then Forward until the “Error pending” menu appears.
7C Indicates flow Unde- N/A. Measuring flow Select empty pipe cut-off
with no flow fined sensor (pipe)
in pipe empty
7I Too low flow N/A. Clogged sensor Dismount sensor tube and
signal electrodes in clean 4 sensor electrodes
sensor tube
Red Blinking Error: Internal sensor error or sensor Replace the component.
corroded.
All modules are identified on the front, for example “X20 DO 6529” in the illustration below. To the
right, the stat indication LEDs are visible, for example “r, e, X, I” in the illustration below.
5X20
NOTE
• Note that all status indications are not valid for all modules.
• The meaning of a status indication might vary for some modules. These variations are specified
in the Description column.
• Module BC083, CP3485-1 and IF1082-2 are described in separate tables below the generic
table.
The table contains the following columns and information:
Module BC0083
Module CP3485-1
Module IF1082-2
The status/error light is a green/red dual LED. The interface can be operated in two moedes: Either
in Powerlink V mode or as an Ethernet TCP/IP interface. Status light depends on mode. For
TCP/IP mode, only SE green is valid.
Module DIF371
This section contains problems that can occur, but is not indicated by an alarm.
1A The system does not start. Main breaker Q1 on control Turn on the breaker and measure that incoming 24 V DC to
The control panel does and LDC cabinet turned off, the control panel is present.
not light up. or power not connected to the
control panel.
General problems
Fuse F42 tripped. 1. Check fuse F42 in control cabinet to see what circuit
caused the fuse trip.
2. Use the circuit diagram to check the fuse setting, adjust
according to figures in circuit diagram if necessary and
reset fuse.
3. Use the circuit diagram to locate the component or find the
reason that caused the fuse trip and attend to it.
Fuse F41 in control cabinet 1. Check fuse F41 in control cabinet to see what circuit
tripped. caused the fuse trip.
2. Use the circuit diagram to check the fuse setting, adjust
according to figures in circuit diagram if necessary and
reset fuse.
3
Control panel error due to Let the panel dry and try again.
damp.
1B Control panel is not Abnormal operating condition. 1. Restart the control panel: Cut the power by removing the
displaying a normal page. power cable at the back of the control panel. Wait 30
seconds, and reconnect the cable again.
2. Restart the entire PureBallast system: Cut the power by
switching of the main breaker on the control cabinet. Wait
30 seconds, and switch on the main breaker again.
Wrong software version Check that the HMI and PLC software have the save program
version. This is visible in control system page 4.1 System info .
HMI software problem Re-load the HMI software according to the software Release
note.
1C PureBallast can not be Communication is broken See the What to do column for alarm A93.
controlled or monitored between ISCS and PLC.
from the ISCS’ graphical
user interface via the
remote interface (optional)
5 PanelCommunicationError
These messages can appear alone or in combination. The message does not appear in remote control panels (option).
65
66
3.1
Problem Description Possible cause What to do?
ID
3.2 Filter
Error with the differential Dismantle the component and inspect/attend to.
pressure gauge electric
switches.
Valves for differential pressure Open the two valves (ball cocks) connected to PT201-27.
gauge PT201–27 (Boll) are
closed.
Valves for air pressure to valve Open the valve (ball cock) connected to V309-1.
V309-1 are closed.
5B Excessive backflushing The filter house is not properly Deaerate using the deaeration valve V201-50 on the filter lid.
or long backflushing deaerated.
sequences (general)
Damaged filter candle. Check filter candles for damage. Replace if necessary.
Large obstructions have Open the filter and remove the obstructions. See chapter 7.
entered the filter. Service manual, section Filter.
3
3.3 CIP
Air pressure too low due to Adjust setting with the manual valve under the valve block on
incorrect setting on valve block the CIP module.
on CIP.
The diaphragm in the CIP pump Examine the pump. See chapter 7. Service manual, section
is broken. Repair CIP pump.
Pump is clogged. Examine the pump. See chapter 7. Service manual, section
Repair CIP pump.
6B Too high consumption of Leakage in the CIP tank, CIP Locate leakage and attend to.
CIP liquid (> 1 cm/AOT pump, pipes or AOT reactor.
reactor cycle).
6C CIP liquid is not returned Insufficient pump capacity 1. Increase airflow to the pump to increase pump capacity
to CIP tank. (P321-5). with the manual valve under the valve block on the CIP
module.
2. Check that pump P321-5 is functioning correctly. See
problem 6D−6I in this chapter.
6D CIP pump does not run • The air pressure is to low Examine the pump and attend to problem. See chapter 7.
Service manual, section Test CIP pump.
• The air connection is
blocked
• Muffler is blocked
• Air valve is defect
• Dirt in the pump chamber
• Diaphragm breakdown
6E CIP pump runs irregularly • Valve balls are blocked Examine the pump and attend to problem.
• Sealings are defect in air
valve or center block
• Diaphragm breakdown
6F Insufficient CIP pump • Suction connection blocked Examine the pump and attend to problem.
suction or not tight.
• Muffler is blocked
6G Bad flow or pressure in • Pressure fall in incoming air Examine the pump and attend to problem.
CIP pump
• Suction or air connection
blocked
• Muffler is blocked
• Air valve is defect
• Valve balls worn out/broken
• Air in liquid Diaphragm
breakdown
6H CIP pump leakage Screws on the housing not Tighten the screws.
properly fastened
71
CIP
3.4 Valve V201–8 3 List of problems and solutions
8A Signal change has no effect on Faulty air supply Check air supply to the valve and tubing to the actuator.
the actuator position See chapter 7. Service manual, section Proportional
valve for instructions regarding the proportional valve.
8B Signal change results in actuator Connection or signal problem • Check coupling between proportional valve and
running to end positions actuator.
Signal and positioning problems. • Inaccurate positioning. Adjust position sensor. See chapter 7. Service manual,
List of problems and solutions
8C
section Calibrate positioner on V201-8.
• Input signal fluctuates.
Check electric connection.
3.4
Valve V201–8
73
Chapter: 6. Installation description and drawings
System manual — PureBallast 3.0 Flow 1000
3 Technical data 11
3.1 PureBallast system 11
3.2 PureBallast components 12
3.3 Working pressure and pressure drop 14
3.3.1 Working pressure during ballast operation and
during backflush 14
3.3.2 Pressure calculation 15
4 Installation guidelines 17
4.1 Preparations and conditions 17
4.1.1 Safety information 17
4.1.2 General installation requirements 17
4.1.3 Installation of components supplied by shipyard 18
5 System interfaces 25
5.1 Remote control panel integration
(optional) 25
5.2 Remote interface integration (optional) 27
5.2.1 Communication between PureBallast PLC and
remote interface 27
5.2.2 Directory of addresses 28
3
5.3 Power management system integration 45
5.3.1 Overall power request process 46
5.3.2 Power steps and power signals 46
5.3.3 Power management installation 47
6 Start-up procedures 53
7 Drawings 55
7.1 Graphic symbols used in drawings 56
7.2 General drawings 57
7.2.1 Flow chart 57
7.2.2 Connection list 58
7.2.3 Electrical system layout (2 pages) 64
7.2.4 Air distribution 66
7.2.5 Quality specification / Compressed air 67
7.2.6 Quality specification / Water 68
7.2.7 Quality specification / CIP liquid 69
4
7.4 Electrical drawings 92
7.4.1 Control cabinet / Interconnection diagram (7 pages) 92
7.4.2 Control cabinet / Circuit diagram (20 pages) 99
7.4.3 Control cabinet / Cable list 119
7.4.4 Lamp Drive Cabinet (LDC) / Interconnection
diagram (2 pages) 120
7.4.5 Lamp Drive Cabinet (LDC) / Circuit diagram (14
pages) 122
7.4.6 Lamp Drive Cabinet (LDC) / Cable list 136
7.4.7 AOT reactor / Interconnection diagram (2 pages) 137
7.4.8 AOT reactor / Circuit diagram (3 pages) 139
7.4.9 AOT reactor / Cable list 142
7.4.10 AOT reactor and LDC / Lamp power cable 143
5
1 Introduction
This chapter contains information about how the PureBallast system is to be installed and drawings.
The information is presented as installation guidelines per component, relevant standards and
drawings. The chapter is opened with a summary of the main technical data.
Enter vessel specific information in the table below. This will facilitate reading information and
drawings in this document, since some drawings include information for all system sizes /
dimensions, and the document contains information for options only used by on some vessels.
Data Value
This section states technical data for the complete PureBallast system and for individual
components. In some cases references are given to data in drawings included in this chapter.
Water requirements See section Quality specification / Water on page 68 and data for
different components in the Connection list on page 58.
• Sea water: Used for cooling UV lamps in the AOT reactor during
start-up.
• LT (low temperature) fresh water: Used for cooling the lamp drive
cabinet (LDC) during operation.
• Fresh water: Used for flushing and filling up of AOT reactors after
treatment.
System f ow Flow range ballast (m3/h): 190 → Flow range deballast (m3/h):
1000 100 → 1000
Based on maximum:
• 100
Note: PureBallast only use the power needed for efficient
treatment. During operation, the UV lamps are lit to between
50 and 100 % of their capacity, depending on measured water
transmittance.
• 1 kW (Control system including PLC, 24 V feeding, CIP motor
supply, filter motor supply)
UV intensity power The water is fully treated at UV intensity > 380 W/m2. UV intensity is
limit measured by UV transmitter QT201–50.
The system have been tested and found to give full treatment of the
ballast water when the measured UV intensity is above the value
380 w/m2.
AOT reactor Pressure drop See data for different components in Connection
list on page 58.
Tank volume 250 liters. Note: Total tank volume is 300, but
shall only be filled to max 250.
Remote control panel Dimensions See Control panel / Dimension drawing on page
(optional) 90 and on Control panel integration page 25.
3.3.1 Working pressure during ballast operation and during backf ush
During ballast operation, the ballast water flow goes through the filter and AOT reactor which
gives an approximate maximum pressure drop of 0.70 bar at maximum flow rate. Note that piping
outside the PureBallast system is not included. The pressure drop over the filter fluctuates between
approximately 0.2−0.85 bar depending on dirt load in the filter. The differential pressure over the
filter is monitored by one pressure transmitters on the filter inlet 201 and one on the filter outlet 201.
When the differential pressure reaches a parameter set limit (default is 0.5 bar), a backflush
operation is started automatically. To secure sufficient backflush flow, the pressure at pfilter
inlet must be at least 1.0 . For detailed information about backflush, see chapter 2. System
description, section Filter.
6 Working_Pressure_Hydac
During ballast operation, the ballast water flow goes through the AOT reactor which gives a
maximum pressure drop of 0.70 bar (not including vessel’s piping), as described in the table below.
Note that the total pressure drop only includes the PureBallast components, not the vessel’s piping
before the first PureBallast component (Q201.1 ) or after the last (V201–8).
Note that 0.50 bar is the default limit value for parameter p305
(Backflush trigger), which defines maximum allowed differential
pressure over the filter. Note that this parameter can be adjusted,
but only by Alfa Laval during commissioning.
AOT ≤ 0.20 bar pAOT: 0.20 bar (0.02 MPa) including PureBallast valves. Piping
reactor is not included, since it is installation specific.
Total ≤ 0.70 bar ≤ 0.70 bar (0.07 MPa) if parameter p305 is set to 0.50 bar.
During backflush, the ballast water flow goes through the filter and AOT reactor, and the backflush
discharge flow goes through the filter and pipe 309.
A pressure calculation must be done to secure sufficient backflush flow in pipe 309 and to secure
that the ballast water pump can overcome the pressure drop (see table below). Note that the
calculated total pressure drop only includes components from the PureBallast inlet valve V201–2
to the backflush over board valve.
Backf ush ≥ 1.0 bar Difference between filter inlet “201” and filter backflush outlet
differential “309”.
pressure
∆P309 Calculated The pressure drop for pipe 309 is installation specific and must
be calculated.
To ensure that pfilter inlet is 1.0 bar, the total pressure drop must be calculated according to the
formula below:
This section covers requirements for installing different components of the system.
NG
WARNI
!
• Read chapter 1. Safety.
• Installation must be done by a fully trained professional installer.
• Damages related to transport and installation should be recorded.
• All components must be installed and marked as specified in dimension drawings, flow charts
and other drawings included in this manual.
- General drawings – overall and principle information for system layout (pipes, components,
electricity, air and water).
- Dimension drawing – detailed component information (dimensions, sizes etc).
- Electrical drawings – detailed electric information (circuit diagrams, cable lists etc).
• Connection list
• Quality specification for water
• Quality specification for compressed air
• Installation guidelines
• Electrical drawings
4.2 AOT reactor
Follow the guidelines below when installing the reactor module.
• The AOT reactor must be fixated at the bottom and supported at the top to carry the weight
of the component. Use the upper and lower fixing holes (1) in the support structure to fixate
the component to the steel construction of the hull. If this is not enough, completing stays has
to be made. There are four fixing holes on each side at the bottom and four at the top, after
the lifting beam has been removed.
6 AOT installation
• Prepare the inlet piping first. Then mount the AOT reactor onto the inlet flange and secure it.
Finally install the outlet piping onto the top of the AOT reactor.
• We recommend that the installation of the reactor is planned to be supported by its lifting point
until the units lower part is completely secured to the foundation and inlet flange.
• No fixtures should be attached to the reactor housing by welding, since this will damage or
distort the reactor, and potentially affect the biological performance of the component.
• The AOT reactor must be earthed. The earth nut is indicated as “791” in the dimension drawing.
4.3 Filter
Follow the guidelines below when installing the filter.
• The component must be placed on a firm level surface. The legs of the component can be
bolted or welded in place on a steady foundation.
• Pipe 309 (filter backflush overboard line), with its valve, must be correctly connected.
• The component must be earthed. The earth nut is indicated as “791” in the dimension drawing.
• The filter motor must be mounted, if it is not mounted at delivery. See chapter 7. Service
manual, section Mount filter gear motor for instructions.
• The electrical cable is connected from the control cabinet to the CIP valve block. See chapter 7.
Service manual, section Connect electrical cables to valve block.
• The component must be earthed. The earth nut is indicated as “PE bolt” in the dimension
drawing.
• The component must be placed on a firm level surface. The legs of the component can be
bolted or welded in place on a steady foundation.
• The deaeration pipe after deaeration valve V571-1 must reach approximately 2 meters higher
than valve V321-2 at the AOT reactor to avoid water spillage during CIP process. It is
recommended that the deaeration pipe is led to a scupper to collect eventual (minor) water
spillage.
• Connections to the flanges must be made so that the connection is not exposed to any moment
or load. This is particularly important when connecting the plastic flanges.
NOTE
• System interfaces (optional) must be integrated according to section System interfaces on page :
• Recommendation: Make notes of the actual connections made to the vessel’s systems with part
number and cable number in the electrical drawings. The drawings are prepared with indicated,
empty squared for this purpose. The electrical diagrams are found in the Drawings section.
These notes can be used to make notes of the exact connections done during installation to
simplify future faultfinding.
• Electrical cables must be properly routed and supported according to applicable regulations.
• Cable entries to cabinets must be sealed, using the built in cable glands. See instruction
Cable glands in chapter 7. Service manual.
• Cabling shall be done according to specification in Electrical system layout on page 64, and
the electrical drawings. This includes cable routing, cable types and cable marking to simplify
identification and fault finding.
• Power cables shall be separated from signal and bus cables. Distance between them reduces
electrical noise transfer.
- If placed on a cable rack, place power and signal cables on opposite sides.
- If cables are routed in tubes due to narrow space, the power and signal cables shall be
routed in separate tubes.
• EMC: Cables shall be peeled down to the cable shield. The nut holding the cable must be in
contact with the screen bar.
Cabinets – General
LDC cabinet
• The cabinets maximum distance (cable length) to the AOT reactor: 150 meters.
• The component must be placed on a firm level surface. The legs of the component can be
bolted or welded in place on a steady foundation. It is possible to detach the cabinet from the
bottom frame to facilitate installation. The cabinet shall also be attached to the bulkhead using
the attachment bolts on the top of the cabinet.
• Cables can be lead to the cabinet either from the floor or from the side of of the cabinet,
depending on which is most convenient. If needed, the location of the cable gland cassette
and the cover is exchanged.
• Power cable W201.1 to be connected to main switch board: Max Icu 50 KA.
• Signal cables W210A and B to be connected from X1 in LDC to A side junction box on the AOT
reactor. Cables from junction box to components are pre-assembled.
• Lamp power cables W211A-D (included in scope of supply) shall be connected from X2 in
LDC to the (B side) junction box on the AOT reactor. (Cables from junction box to lamps
are pre-assembled.)
• The lamp power cable should not be winded. If it is to long, cut it before it is connected. .
• It is possible to dismount the doors during installation: Slide the red catch on the hinge
backwards and release the locking mechanism.
Control cabinet
• The ballast water flow direction must be according to the arrow on the flow sensor.
• The flow transmitter must be mounted on the flow sensor pipe. It is not pre-assembled from
factory. See chapter 7. Service manual for instructions.
• A drain solution (not part of Alfa Laval’s scope of supply) must be attached to safety valve
RV201. The valve shall be drained to a scupper, with a solution which always allows water to
be drained from the valve. See Pressure monitoring device / Dimension drawing.
• Inlet and outlet pipes must be correctly connected. They must also be pressure approved by a
classification society or equivalent, or be tested under supervision of a classification society
and/or at the ship yards pipe shop etc.
• Pipes shall be designed to carry the weight of the component and media.
• A bypass valve (optional part of Alfa Laval’s scope of supply) must be installed. The bypass
valve (V212-31) shall be connected to the the vessel’s ISCS, to enable control of the valve, and
PureBallast control system to indicate valve position. See Control cabinet / Interconnection
diagram on page 92.
• If PureBallast can be bypassed using other valves (apart from V212-31), status signals from
them must be connected to the control cabinet. All bypass cases must be logged.
Three additional bypass valves can be handled, identified as additional bypass valve 1, 2 and 3.
If more valves are used, they must be connected in series, which means that they are handled
as one regarding alarms and logging in PureBallast.
Signal cables for additional bypass valves are installed according to section External component
signal integration.
• The yellow position indicator on actuators must be in line with the valve throttle. For pipes with
dimension 400, the red position indicator on the actuator coupling (see drawing) must also be in
line with the throttle. The position indicator must be in line with the pipe when the valve is open.
If not correct, change according to instruction in chapter 7. Service manual for instructions.
• Valves shall be opened when installed. This is important to avoid that the rubber gaskets are
squeezed and damaged during installation.
• Valve actuator’s pneumatic lines must be correctly connected and supported. See chapter
7. Service manual for instructions.
• Valve actuators electric connectors must be correctly connected.
- If delivered by Alfa Laval: Must be mounted with the pin pointing in the flow direction (see
drawing on page 84).
- Flanges for connecting the sampling devices must be installed before the pipe is coated.
• Components shall be connected to air supply that meets the requirements or the Quality
specification / Compressed air 67. Air shall always be connected.
This section covers guidelines for how to install and integrate the following, if used:
- Ethernet cable – Type: Cat 5e (or better). Max length: 100 meters. One free Ethernet
connection point (X13) in the switch in the control cabinet.
- Fiber cable – Type: Multi-mode fiber cable with LC connector. Max length: 500 meters.
Ports: Two free ports in the switch in the control cabinet.
If fiber is used, a network switch must be used, since the cable to the panel must be of
Ethernet type. One network switch and a 1.5 meter Ethernet cable is delivered with each
remote control panel.
• If more remote control panels are to be installed than there are free fiber ports in the control
cabinet, one of the delivered network switches can be used for connection. From this switch,
it is possible to connect more panels using the free ports. Keep in mind that the cable to the
panel must be of Ethernet type. The extra switch shall be placed close to the first remote
control panel so the 1.5 meter Ethernet cable can be used.
• External network switch including a terminal to handle the communication, placed near the
remote control panel. We recommend to use the external network switch close to the remote
control panel, even if it is not necessary (if there are free ports in the control cabinet).
• Network switch in control cabinet. It is installed if remote control panels have been ordered, but
can also be installed at a later stage.
• A signal device must be installed according information in section Cabinets and cables on page
20. Not part of Alfa Laval’s scope of supply.
Switches and cables are installed according to instructions in chapter 7. Service manual, section
Remote control panel (optional).
PureBallast’s PLC communicate with the vessel’s ISCS via the remote interface. Data is sent to
and from dedicated addresses via modbus. Data can be commands, values (sum of bits), alarms
and status information. The data is then presented in the ISCS according to the vessel’s graphical
standard. It is possible to present all information (all addresses) or a selection. Data is sent as
binary code, with exception for time, which is sent as hexadecimal code.
• Cable W602 to be connected from connection terminal (X15) in control cabinet to ISCS.
• Modbus connection from ISCS to PureBallast connection terminal X15 in the control cabinet.
Connection standard: RS485 (or RS422, not described in electrical drawings) according to
Control cabinet / Interconnection diagram. Recommended max length: 500 meters.
• Implementation of remote interface signals in the ISCS according to the guidelines in this section.
• Communication settings must be done according to chapter 3. Operating instructions and
control system description, section Set remote interface communication.
• Parameter p132 and p128 must be set in the control system.
• After installation and integration, the function of the remote interface must be verified according
to chapter 3. Operating instructions and control system description, section Test remote
interface communication.
• A signal device must be installed according to information in section Cabinets and cables on
page 20. Not part of Alfa Laval’s scope of supply.
Reference information about the logical flow of the PureBallast processes can be found in chapter
3. Operating instructions and control system description, section Detailed process description.
Modbus settings
The ISCS modbus RTU server data shall be set according to the table below:
Slave ID 10 N/A
PureBallast
is slave
and ISCS is
master.
The following terms are used to explain the signals in the tables below:
Address:Bit The start address is 40000. Individual address and bit for each signal (data), is
written as “Address:Bit”, for example +073:14. Values for an address is written
as “Address=Value”, for example 015=125.
Bits are the Signal reference number. Bits are right aligned in the table.
Function Name of the function. The name corresponds to the text used in the
PureBallast control system HMI. Parenthesis gives reference to the control
system page where the information is used/displayed. For further information
about respective piece of information, see chapter 3. Operating instructions
and control system description.
Description Additional information, for example specific conditions that must be met before
a command can be sent.
The addresses below are used to send commands and status information from ISCS to PureBallast.
Example of data: Command to start a ballast process and feedback that the ballast water pump
is running.
+001 Commands
Condition: All signals for +001 must be high until PureBallast return an
accept or reject signal (see +140).
Bit 6 Ack all alarms and Command: Acknowledge all alarms and warnings.
warnings (2.1)
Condition: Signal shall be high so long it can be
assumed that it is received by the PureBallast,
considering the installation specific conditions.
Bit 7 Apply new flow (1.1 Confirm activation of new flow selected using
and 1.2) address +003 (Selected flow).
+002 Feedback
+003 Select AOTs) (1.1, If set during standby: Defines which flow to be
1.2) used when ballast or deballast is started. If set
during ballast or deballast: Defines that the flow
shall be increased or decreased to the new flow.
+005 Power granted (1.4) Only relevant if PureBallast is integrated with the
vessel’s power management system.
Bit 0–4 Power granted 1–4. Bit 1–3: Power granted for the number of AOT
reactors sent.
The addresses below are used to send data from PureBallast to ISCS.
+050 Processed volume (1.1) Value: Processed volume [m3] during current
ballast or deballast process. The value is resets
during next start-up.
+053 Selected AOTs (1.2) Value: Number of AOT reactors selected for
operation.
+054 Number of AOTs ready Number of AOT reactors that are ready for use
(1.2) in process.
+056 Current max f ow (1.1, 1.2) Maximum flow in m3/h for process, based on
number of selected AOT reactors and filter
capacity.
+057 Current time - Low (4.1) Value: Seconds since 1970-01-01 00:00,
in combination with address +058. Sent as
hexadecimal code.
+059 Remaining time for CIP Value: Total estimated remaining time (hours) for
(hours) (1.3) all CIP sequences and filter preservation
+060 Remaining time for CIP Value: Total estimated remaining (minutes) time
(min) (1.3) for all CIP sequences and filter preservation.
+061 Remaining time until CIP Value: Hours before CIP must be performed.
req. (hours) (1.3) Displayed per AOT reactor.
+062 Remaining time until CIP Value: Minutes before CIP must be performed.
req. (min) (1.3)
For details, see +061.
+067 Power consumption (1.1, Only relevant if PureBallast is integrated with the
1.4) vessel’s power management system.
The addresses below are used to send commands and status information from PureBallast to ISCS.
Example of data: Process mode (standby, ballast, CIP), acceptance of command from ISCS, and
request to ISCS to start ballast pump.
/ Bit
Bit 7 Sum alarm Common alarm indicating that one (any) alarm is
active. Alternative to implementation of individual
alarm signals and hardwired common alarm.
Functions in the same way as hardwired external
signal “Common alarm”.
+071 Commands
Bit 0 Start ballast water pump Request to ISCS to start ballast water pump:
(1.1) Address values.
1=Request to start.
0=Request to stop.
Bit 1 Open overboard valve (1.1) Request to ISCS to open overboard valve:
Address values:
1=Request to open.
0=Request to close.
+072 Process mode (1.1, 1.3) Status: Address values: Values indicating
system mode.
0=Booting
1=Standby
2=Ballast
3=Deballast
4=CIP
5=Emergency stop
6=Manual mode
+073 Subprocess mode (1.1, 1.3) Status: Address values: Values indicating
system mode.
0=None
1=Start-up ballast
2=Full ballast
3=Backflush
4=Pause
5=Stop with backflush
6=Increasing ballast flow capacity
7=Decreasing ballast flow capacity
8=Start-up deballast
9=Full deballast
10=Pause deballast
11=Stop deballast
12=Increasing deballast flow capacity
13=Decreasing deballast flow capacity
14=AOT reactor drain 1 – Sea water
15=AOT reactor fill 1 – Fresh water
16=AOT reactor drain 2 – Fresh water
17=CIP
18=AOT reactor fill 2 – Fresh water
19=Preservation filter – Fresh water
20=Heeling mode
21=CIP drain
22=Stop (If ballast process is stopped before
mode Full ballast, no backflush is performed.)
+075 Power request [1–4] (1.4) Only relevant if PureBallast is integrated with the
vessel’s power management system.
Bit 0–4 Power request [1–4] (1.4). It is only necessary to use signals (bits) to cover
the need for power request. This is defined by
the number of AOT reactors, alternatively use
of common power.
+076 Power running [1–4] (1.4) Only relevant if PureBallast is integrated with the
vessel’s power management system.
The addresses below are used to send status information for components to ISCS.
/ Bit
+080 Main valve status (1.1, 1.3 and popups for AOT reactor and filter)
+084 Filter status (Filter popup) Only valid for Filter type 1 = Boll filter.
The tables below lists all alarms and warnings sent from PureBallast to the ISCS. Each alarm is
defined as a specific bit. The bit is set to 1 when the alarm is activated. The alarm IDs refer to alarms
described in chapter 5. Alarms and faultfinding, where texts to be displayed in ISCS can be found.
Example: If data at address 40902 is 000010000000100, this means that alarm W04 and warning
A33 are active (bit 2 and 10).
Common alarms and common warnings (+900 and +901) indicate that there exist a common alarm
for the area or component specified.
Example of alarms and warnings: Process flow too high, valve error, component signals missing.
Bit
9 A29 W80
10 A33 W82
11 A35 W83
12 W40 A91
13 A48 W92
14 A49 A93
15 A50 W95
The addresses below are used to send status information, alarms and warning for AOT reactors
and LDC to ISCS.
Status information
Addresses for data regarding AOT reactor and respective LDC are separated in number series to
distinguish information for individual AOT reactor/LDC, if more than one.
Example of data: Status for AOT reactor and LDC and their components, for example temperature,
UV intensity and valve status.
/ Bit
Bit 1 AOT ready (1.2) Status: AOT reactor is ready, which means that
there exist no critical alarms or warnings for the
AOT reactor (110:5, 120:5 and 130:5 = 0).
0=Not ready.
Bit 2 AOT selected (1.2) Status: AOT reactor selected for process by
operator. In PureBallast, the AOT reactor is
visible in the list AOT reactors selected for
process in 1.3.
Bit 5 AOT sum alarm (1.2 and Status: Common alarm indication for AOT
AOT popup) reactor. The AOT reactor is not ready.
Bit 6 AOT sum warning (1.2 and Status: Common warning indication for AOT
AOT popup) reactor. If the warning is not critical, the AOT
reactor may have status AOT ready.
Bit 7 AOT CIP required (1.3) Status: CIP status for AOT reactor: 0=Not
required. 1=Required.
Bit 8 AOT CIP ongoing (1.3) Status: CIP status for AOT reactor: 0=CIP not
ongoing. 1=CIP ongoing.
Bit 9 AOT CIP error (1.3) Status: Error for AOT reactor during CIP process.
+112 / +122 AOT LPS status 1 (4.9 and Status: Status per individual LPS in the AOT
/ AOT popup) reactor.
+132
Bit 0–15 In AOT reactor 300 m3/h: Only bit 0–9 is used.
+113/ AOT LPS status 2 (4.9 and Status: Status per individual LPS in the AOT
+123/ AOT popup) reactor.
+133
In AOT reactor 300 m3/h: Only bit 0–9 is used.
Status: Address value:
+115/ LDC water temperature Value: LDC cooling water temperature in cabinet
125/ (AOT popup) indicated by TT401-1.
135
Condition: See +114.
+116 / +126 LDC air temperature (AOT Value: LDC air temperature in cabinet indicated
/ +136 popup) by TT401-2.
+118 / +128 Power output (4.9) Current LPS power consumption (50-100 %).
/ +138
Alarms and warnings for individual AOT reactors and LDCs are separated into different number
series according to the list below:
Example of alarms and warnings: High temperature, fuse tripped, communication error for LPSs.
Bit
5 W111 W1831
11 W120 W160
12 W122 W161
13 W126 W162
14 W128 W163
15 W129 W164
The communication is either handled by the remote interface (if the option is integrated) or via
hardwires between the vessel’s ISCS and PureBallast’s control cabinet. It is also possible to use
hardwire, even if remote interface is integrated.
• Integration and connection of signals must be done according to the guidelines in this section.
Signals are defined to handle all combinations of power step (amount of power) and function
(request, grant and run). More than one signal can be sent (or received) at the same time to
achieve, for example step 1 and 2 to request power for 3 AOT reactors.
As an alternative, it is possible to use power step 4 (common) that always will be used, regardless
of the number of AOT reactors used for a specific process. The common power is defined as the
number of installed AOT reactor times the defined power consumption for one AOT reactor.
Note that It is only necessary to connect enough signals to cover the number of AOT reactors
installed on the vessel. If one AOT reactor is installed it is only necessary to connect step 1 for
request, granted and running.
After installation, the signals need to be tested. This is done by simulating signals from the control
system, page 1.4 Power request. See chapter 3. Operating instructions and control system
description, instruction Simulate power request.
Each signal that is used must be activated in the control system page 5.2 – Main parameters 2.
Output indicates signal from PureBallast and Input indicates signal from ISCS.
Common alarm (strongly Output What: Output signal from PureBallast that there is an
recommended to be (any) active alarm. An alarm stops down ongoing process.
integrated)
How: Active alarm = Open circuit. If an alarm is already
present and a new alarm is issued, the signal will go low
for three seconds, and the be reactivated as high.
Common warning Output What: As common alarm, but for warnings. A warning is
a notification of status change or a problem.
External system stop Input What: Input signal to PureBallast to stop the system.
If extra buttons (not part of AL scope of supply) to stop
PureBallast are desired on board. The power is still on.
Heeling mode (internal Input What: Input signal to PureBallast to to enter heeling mode.
transfer) Equal to pushing the Pause button in control system.
Additional bypass 1 is Input What: Input signal to PureBallast that an external bypass
open valve (not part of Alfa Laval’s scope of supply).
Request ’’Start BW Output What: Output signal from PureBallast to request opening
pump’’ of relevant valves (not operated by PureBallast). After
process is stopped, the signal goes low to request that
the valve are closed.
Feed back ’’Ballast Input What: Input signal to PureBallast to confirm that the
water pump is running’’ ballast pump is started.
Request “Open Output What: Output signal from PureBallast to request opening
overboard valves” of relevant valves (not operated by PureBallast). After
process is stopped, the signal goes low to request that
the valve are closed.
Relevant valves: 201, 309 and 403 and 404 (and 460.1
during CIP process). Note that the signal is mainly
intended for the valves apart from those leading to and
from pipe 201
Feed back ’’Overboard Input What: Input signal to PureBallast to confirm that relevant
valve is open’’ valves are open.
Booster pump (P401-1), Output What: Output signal from PureBallast to request start of
for LDC cooling the LDC cooling pump for line 401. Pump P401-1 is used
during ballast, deballast, pause and heeling mode.
Booster pump (P403-1), Output What: Output signal from PureBallast to request start of
for AOT reactor reactor the AOT reactor cooling pump for line 403. Pump P403-1
cooling is used during start-up, ballast, deballast, pause and
heeling mode.
PureBallast running Output What: Output signal from PureBallast that a process is
running.
Input signals
Chosen input signals must be connected from the control cabinet according to Control cabinet /
Interconnection diagram on page 92.
Output signals
Chosen output signals must be connected from the control cabinet according to Control cabinet /
Interconnection diagram on page 92. Output signals are connected via potential free relays.
The GPS must be connected to the module X20IF1030 in the control cabinet, using an NMEA
(RS422) serial interface with the following settings:
For details, see the illustration below (based on the Control cabinet / Interconnection diagram on
page 92).
6 GPS
The actions below must be performed after installation, before system is put into operation. This
is important to avoid that the filter and the AOT reactor is damaged by material from the ballast
tanks or remainders from the installation. These actions shall be performed both for new builds and
retrofit installations.
Before the system is operated the first time the actions below must be done.
NOTE
• All pipes leading to PureBallast must be well flushed to avoid that debris harm the filter and
AOT reactor quartz sleeves.
• All ballast water tanks must be well cleaned before PureBallast is tested or put into operation.
This is valid both for new builds and retrofit installations.
First operation
• During the first operation, the filter shall be bypassed, to avoid that debris harms the filter
elements.
• We recommend that a strainer is used during the first operations, to avoid that debris harms
the system.
• The first time a tank is stripped, PureBallast must be bypassed, to avoid that debris harms
the system.
This section contains drawings for the PureBallast system. It is divided into three main parts:
• General drawings – overall and principle information for system layout (pipes, components,
electricity, air and water).
• Dimension drawing – detailed component information (dimensions, sizes etc).
• Electrical drawings – detailed electric information (circuit diagrams, cable lists etc).
See the Contents section at the beginning of this chapter to get an overview of included drawings.
573644
Main components
Q201.2 As above.
V201-25
IP201-7 IP converter
S201-7 Strainer
201 Filter inlet / outlet • Ref. filter connections drawing on page 71.
V320-4 CIP / Drain • Ref. AOT reactor dimension drawing on page 70.
V310-6 Valve
V310-8
CV310-7 Strainer
V321-1 Valve
V321-4
6 Working_Pressure_Hydac
∆pf lter - Filter pressure drop, depending on filter contamination. (dynamic and
static pressure).
0.05 – 0.85 bar — Normal operation.
0.85 bar — Filter backflushing sequence triggered.
∆pAOT - AOT reactor pressure drop (dynamic and static pressure).
∆pf lter inlet - 1.0 bar + p309: Required pressure to establish effective back flushing
of filter.
∆p309 - Pressure drop, (dynamic and static pressure), line 309 (back flush over
board).
9005353_Page_1
9010001
553407
590773
594956
7.3 Dimension drawings including technical 7 Drawings
data
9004714_p2
74 586502
Book No.9010183 02, rev. 2
7 Drawings 7.3 Dimension drawings including technical data
9007182
9008467
9007178
9008463
9007180
9008465
9007176
9008461
590066 1
590066 2
590066 3
9005331
88 9005261_p1
Book No.9010183 02, rev. 2
7 Drawings 7.3 Dimension drawings including technical data
9005261_p2
595261_p1
595261_p2
9005343_Page_23
9005343_Page_24
9005343_Page_25
9005343_Page_26
9005343_Page_27
9005343_Page_28
9005343_Page_02
9005343_Page_03
9005343_Page_04
9005343_Page_05
9005343_Page_06
9005343_Page_07
9005343_Page_08
9005343_Page_09
9005343_Page_10
9005343_Page_11
9005343_Page_12
9005343_Page_13
9005343_Page_14
9005343_Page_15
9005343_Page_16
9005343_Page_17
9005343_Page_18
9005343_Page_19
9005343_Page_20
9005343_Page_29
120 9005345_Page_16
Book No.9010183 02, rev. 2
7 Drawings 7.4 Electrical drawings
9005345_Page_17
122
9005345_Page_01
Book No.9010183 02, rev. 2
7 Drawings 7.4 Electrical drawings
9005345_Page_02
9005345_Page_03
9005345_Page_04
9005345_Page_05
9005345_Page_06
9005345_Page_07
9005345_Page_08
9005345_Page_09
9005345_Page_10
9005345_Page_11
9005345_Page_12
9005345_Page_13
9005345_Page_14
136
9005345_Page_18
Book No.9010183 02, rev. 2
7 Drawings 7.4 Electrical drawings
9005379_Page_5
9005379_Page_6
9005379_Page_2
9005379_Page_3
142
9005379_Page_7
Book No.9010183 02, rev. 2
7 Drawings 7.4 Electrical drawings
143
9007280
Book No.9010183 02, rev. 2
7.4 Electrical drawings 7 Drawings
8 Shutdown and storage
This section describes requirements for decommissioning and storage. The rules must be followed
when the system shall be shutdown for a long period.
A copy of the decommissioning report must be placed inside the control cabinet. The report must
include all important information from the decommissioning, for example notes and information
about where to find stored components.
8.1 Decommissioning
Follow the process below to decommission the PureBallast system. Note that if there is a freeze
risk, the system must be completely emptied of water.
8.2 Protection
Perform the actions below to protect the system:
• Protect all electrical cabinets from humidity with Silica gel or similar.
• Protect all metal surfaces from corrosion attacks with anti-rust oil. The oil must have long
lasting effective treatment for external surfaces.
• Disconnect the air supply to the CIP module. Use service valve if possible, otherwise plug
the air supply inlet.
• Disconnect and drain the membrane pumps (P320-1, P321-5 or P460-7). Rinse with fresh
water and reconnect the pump.
• Articles made of rubber or plastics (for example seals) must not be treated with antirust oil.
• Protect pressure monitoring device etc. from mechanical damages. The following components
are recommended to be removed and stored safely: PT201-27, PT201-16, and PI201-18.
• Protect components equipped with circuit boards from condensation. Recommendations:
- Remove IP201-7 and FIT201-1 and store in a non condensing environment.
- Remove and store the display for FIT201-1.
- Protect the flow sensor with silica gel or similar. Protect the sensor with the supplied plastic
cover.
• Change the battery in the control panel. If not, the stored log information can be lost during
storage.
• Put all pneumatic valves in open position.
• Every 3 months, operate each valve by close/open exercise. This will keep the valves and
actuators in best condition.
Note that control valve V201-8 must be exercised manually at the same time as the IP201-7 is
removed. Use a wrench to apply appropriate torque.
1. Locate the decommissioning report stored inside the control cabinet. Use this report to the
re-commissioning of the PureBallast system.
2. Clean away the anti-rust oil with a solvent, for example, white spirit.
3. Assemble items that have been disassembled.
4. If applicable: Remove the silica gel bags from all units.
5. Before the system can be activated, it must be checked according to the commissioning
checklist.
This section contains information about how to handle PureBallast components during transport,
delivery and installation.
• Always read and follow the documentation included in shipment of components and spare
parts regarding handling, safety and disposal.
• Handle the delivery with care in order not to damage the equipment or cause personal injuries.
• If the PureBallast system is stored before installation, make sure to store the components
according to the Shutdown and storage section.
NG
WARNI
!
• Components must be lifted using correct lifting tools (such as a forklift truck, a crane) and tackle
with a load capacity greater than the weight of the component stated in the section below.
• Any complementary lifting instructions must be followed.
• Components must be empty when lifted.
• The AOT reactor, filter, CIP and control cabinet must be lifted according to the instructions
in the following sections.
6 AOT Lift
9.2.2 Filter
Weight of filter (empty with adaptor plates on flanges): 980 kg. A=103 cm.
6 FilterLift
Follow the instruction to raise the filter to standing position and to lift it for transportation.
1. When the filter is resting in the bottom of the wooden case: Attach a 2 string-round sling to
the two upper lifting bolts.
6 FilterLift Hydac2
2. Use a lifting gear to raise the filter to upright position. Use the bottom filter legs as turning point.
3. When the filter is in upright position: Attach a 3 string-round sling to all three lifting bolts.
6 FilterLift Hydac
9.2.4 Cabinets
Use intended lifting attachment at the top of the cabinet.
6 CabinetLift
2 Maintenance schedule 9
2.1 Calibration schedule 11
2.2 Serial number information 12
2.2.1 Indicating serial number 12
2.2.2 Example 13
4 AOT reactor 23
4.1 Safety information 23
4.2 Replace UV lamp and quartz sleeve 24
4.2.1 Disassemble UV lamp 24
4.2.2 Disassemble quartz sleeve 27
4.2.3 Assemble quartz sleeve 27
4.2.4 Check for leaks after quartz sleeve assembly 28
4.2.5 Assemble UV lamp 28
3
4.3 Internal inspection of AOT reactor 29
4.4 Dismount and mount lamp power
supply (LPS) 30
4.5 Test LPS installation 32
5 Filter 33
5.1 Remove f lter cover and f lter candles 35
5.2 Mount f lter candles and f lter cover 35
5.3 Replace f lter candles 36
5.4 Clean f lter candles 37
5.5 Change sacrif cial anode 37
6 CIP module 39
6.1 Change and ref ll CIP liquid 39
6.1.1 Change CIP liquid 41
6.1.2 Refill CIP liquid 41
7 Flow meter 49
7.1 Mount f ow transmitter 49
7.2 Change direction of f ow transmitter 51
7.3 Change direction of f ow transmitter
control pad 52
7.4 Clean f ow meter electrodes 54
8 Valve actuator 55
8.1 Preparations and conditions 56
8.1.1 Tightening torques for actuators 56
4
8.2 Dismount actuator 57
8.3 Mount actuator on valve 57
8.4 Change direction of actuator – without
position sensor (V404–36, V320–4 and
V321–2) 59
8.5 Change direction of actuator – with
switch box (V201–3, V201–9, V201–32,
V212–31 and V403–35) 60
8.6 Change direction of actuator – with
position sensor (201-19 and 201–20) 60
8.7 Change direction of actuator – with
positioner (201–8) 62
8.8 Mount pilot valve on actuator 62
8.9 Adjust valve end position 63
8.10 Adjust valve traveling speed 64
8.11 Calibrate positioner on V201-8 66
9 Ball valve 69
9.1 Replace seals in ball valve 69
10 Level switch 71
10.1 Mount level switch 71
10.2 Dismount level switch 72
10.3 Test level switch 72
12 Control panel 75
12.1 Clean control panel 75
12.2 Replace control panel 75
12.2.1 Dismount the panel 75
12.2.2 Mount the panel 76
5
13 Remote control panel (optional) 79
13.1 Mount and connect network switch for
remote control panel 79
13.2 Mount and connect network switch for
remote control panel (retrof t) 81
6
1 Introduction
This chapter contains information and instructions about how to service the PureBallast system.
Instructions are sorted per component. The chapter is opened with a maintenance schedule
covering checks and services that must be performed with specified intervals.
NGE R
! DA
• Before maintaining the PureBallast system, the power supply must be switched off, to avoid
accidental starts. See instruction Abort operation and deactivate the system in chapter 3.
Operating instructions and control system description.
NOTE
• All maintenance and calibration activities must be recorded in the vessel’s maintenance log.
This is required by the ballast water convention. It is therefore recommended that the activities
in the maintenance and callibration schedules below are entered in the vessel’s general
maintenance system.
• Always read and follow the documentation that are included in shipment of components and
spare parts regarding handling, safety and disposal.
• Before maintaining the PureBallast system, the following valves must be locked in closed
position: V201-3, V201-9, and V201-8. See instruction Lock valve in closed position on page 20.
• Follow local regulations for electrical installation and grounding (earthing).
• Follow rules when handling CIP liquid agent, regarding ventilation, personal protection etc.
• Point of contact: To order service or spare parts, contact your local Alfa Laval office. For
more information, see www.alfalaval.com.
The maintenance
Follow this maintenance schedule to secure performance, safety and durability of the system and
its components. The schedule is sorted per component. The table refers to instructions usable
when performing the respective action.
AOT reactor Outer inspection Once a year. If necessary, See Spare parts
of seals for change according catalogue for
leakage. to Open AOT service kit.
reactor.
Filter Inspection and Once a year. See Remove filter Replace filter
cleaning of filter insert. candles, if
insert, including damaged.
filter candles.
See Spare parts
catalogue for
service kit.
CIP liquid level Rule of thumb: See Change CIP If the CIP liquid
check. Once every 3 liquid or Refill CIP is low but the pH
months. liquid. value is below
Depending 3, CIP liquid and
on number of water can be added
AOT reactor to fill up the liquid
and ballasting level in the tank.
frequency, the liquid Note: pH value
check might have to must be checked
be performed more afterwards to
regularly. secure correct pH
value.
Flow meter Clean flow meter Once a year. See Clean flow
electrodes. meter electrodes.
Control opening Once a year. See chapter 7. Open and close the
and closing end Service manual, valves and inspect
stops. section Valve visually.
actuator for
instructions.
1. Connect a calibrated portable ultrasonic flow meter close to the flow meter.
2. Establish flow in the system.
3. Compare value indicated in control system and measure equipment.
AOT reactor 1. Depressurize and drain the reactor: Remove the drain plug at the bottom
components of the AOT reactor.
Temperature TT201–33
transmitter
2. Dismount the transmitter and place in water with known temperature
(TT201-33)
(calibrated measure instrument).
Temperature 3. Compare value indicated in the control system and measure equipment.
switch (TS201-
TS201-60
60)
4. Dismount the switch and place in water with temperature < 65 ˚C.
Level switch
(LS201-29) 5. Check that alarm A137 is displayed in the control system.
LS201-29
Temperature Place a calibrated thermometer inside the cabinet and compare after 30
transmitter in minutes.
LDC (TT401)
Serial numbers shall be used at error reporting and other contacts where a specific component is
discussed.
• Serial number for the complete PureBallast system. See label on the side of the control cabinet.
• Serial number for the component in question. If the component is installed on, or in, another
component, the number for the mother component shall be stated.
• Item number for the component. The item number identifies a unique component in the system.
It begins with a letter abbreviation indicating the component type, for example: LS (level switch),
P (pump) and PI (pressure gauge). A complete list of abbreviations is found in chapter 6.
Installation description and drawings, section Connection list.
2.2.2 Example
If the level switch is faulty, the following information shall be stated:
7 PB 591098_SerialNo
AOT reactor
7 AOT Snr
Filter
7 FilterSnr Hydac
• Control cabinet
• Lamp drive cabinet (LDC): Inside top left
door.
7 CC Sernr 591773#1
NOTE
7 LDC sernr
NOTE
Flow meter
NOTE
7 FM snr 576179_manual 2
This section covers instructions on how to open, close and lock/unlock valves manually.
Avoid operating valves manually. Valves are normally operated from page 1.1 Overview in
the control system (manual mode). See chapter 3. Operating instructions and control system
description for instruction.
1. Identify which button (illustrated on page 45) on the valve block that controls the valve. The
lower button operates the inner hose under the valve block, and vice versa. Also see the
sticker under the valve block.
2. Press the button on the valve body with a screw driver to operate the valve.
Valves can be operated using the position screw on the pilot valve.
Position 0 Closed (default position). If the position screw is in position 0 and the valve is
closed, it can be manually opened. But if the position screw is in position 0 and
the valve is opened, it cannot be manually closed.
Position 1 Opened.
1. If there is limited access to the screw, it is possible to remove the DIN connector.
4. When done, turn back the screw to position 0. If the DIN connector was removed, connect it
again.
• Note that the end positions of the end stop bolts are factory adjusted and must not be readjusted.
Follow the steps below
1. Set the valve to closed position from the control system. Control the position indicator, to make
sure. The yellow position indicator is in line with the valve throttle (indicating open when
the position indicator is in line with the pipe).
2. Disconnect power and compressed air. Verify that the valve is not under pressure.
3. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Measure exactly how far out the end stop bolt (4) is from a reference surface, for example the
actuator house. Make a note of the distance. This information is needed when unlocking
the valve.
5. Open the locking bolt (3) and turn them a couple of turns.
6. Screw the end stop bolt (4) to its bottom position and tighten the locking bolt.
8. Slide the safety cover over the end bolts and lock the safety cover with the pad lock.
• Note that the end positions of the end stop bolts are factory adjusted and must not be readjusted.
Follow the steps below
1. Disconnect all power and compressed air. Verify that the valve is not under pressure.
2. Open the padlock (2) on the actuator and remove the safety cover (1) from the bolts (3, 4).
7 576075_lock_manual
4. Adjust the end stop bolt (4) to the same position (distance from reference surface) as before
locking the valve, according to the notes made during locking.
NOTE
• It is important to adjust the ends stop bolt to the correct position. Otherwise the actuator
may be damaged.
5. Tighten the locking bolt (3).
7. Slide the safety cover in position over the end stop bolts. Lock the safety cover with the pad
lock.
NGE R
! DA
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
• UV lamps radiate ultraviolet radiation when lit. Only operate the UV lamp when correctly
installed inside the AOT reactor with end caps properly closed.
• Never dismount or handle UV lamps before they are completely cooled down. A hot UV lamp is
under high internal pressure, and the risk of bursting exists. A hot lamp could also cause a
burn if it is touched.
ON
CAUTI
!
• Before installation, check that the UV lamps and quartz sleeves are not broken.
• UV lamps and quartz sleeves are fragile and can easily become damaged. Exercise great care
when handling them. Do not apply vibrations or shock to the UV lamp. This can cause breakage
and shorten lamp life. Broken glass/quartz can also cause severe cuts. Always use protective
eye glasses and clean cotton gloves when handling UV lamps and quartz glass sleeves.
• UV lamps contain a small amount of mercury (less than 0.2 grams per lamp) and must be
handled and disposed of with care. Used lamps UV can be handled and disposed of in the same
way as fluorescent lamps. Please refer to national regulations. If a UV lamp has accidentally
been broken, mercury could be spilt. Remove mercury with a special tool such as a syringe
(or use pure sulphure to bind the mercury for easy collection).
• Do not allow mercury to come in contact with your eyes or skin. Do not inhale mercury fumes.
• Free mercury must be kept in an airtight bottle, and must be disposed of according to
national regulations.
• In case of having inhaled mercury fumes, consult a doctor and follow medical instructions.
• When performing these routines, consider the need for service kits for UV and quartz sleeves,
containing O-rings, lamps, quartz sleeves etc. See Spare parts catalogue.
• Do not touch the glass of the UV lamp. Wear gloves and hold the lamp by the ceramic end
parts only. If a lamp is stained on its surface, wipe off the glass with a clean soft piece of cloth
soaked with alcohol. If not, it could cause breakage and shorten lamp life.
• Keep the UV lamp in its original protective cover and case when transporting, storing and
disposing of the lamp. Otherwise it could cause injury if the lamp breaks. Do not dispose of
original protective cover and case for the UV lamp, as they should be re-used for storage
and disposal. Mark cases with used UV lamps accordingly, so that they will not be mistaken
for new lamps.
4.2 Replace UV lamp and quartz sleeve
7 AOTexploded2
1. Cap
2. Cap nut
3. Bush
4. O-ring (inside bush)
5. Cable connector
6. Allen screw
7. Glass socket
8. O-ring
9. UV lamp
10. Quartz sleeve
• The PureBallast system must be turned off, and the power disconnected.
• After UV lamps have been changed, the runtime must be reset in page control system page 4.4
Operation timers AOT 1–3. Requires login level Advanced operator.
• Wait at least 10 minutes after completed ballast or deballast process, to allow the AOT reactor
to cool down to ambient temperature. If the UV lamps are hot they are under internal positive
pressure and may burst if broken.
NG
WARNI
!
• The AOT reactor must not be under pressure when dismounting the UV lamps.
NG
WARNI
!
• Burn hazard: UV lamps can be hot and cause burns.
Follow the steps below
1. Unscrew the cap nuts (2) holding the caps (1). There is one nut on each side of the AOT reactor
per UV lamp. If required, use a screwdriver on the nut, gently tapping with a hammer to release.
2. Carefully disconnect the two cable connectors (5) in both ends of the UV lamp (9).
7UVlampConnection
Carefully draw out the UV lamp (3) with the electric cable, by holding the electric cables in
both ends. When pulled out, only hold the UV lamp by the ceramic ends. Immediately after
removal, place the lamp in its protective cover.
If required, use a screwdriver to press on the ceramic end of the lamp inside the bush on the
other side while carefully pulling the electric cable at the other end.
7UVBushScrewdriver
5. If the quartz sleeves is not broken, mount the new UV lamp according to the instruction
Assemble UV lamp on page 28. If broken see the Preparations and conditions section above.
NG
WARNI
!
• Hot water may escape from the AOT reactor when removing the drain plug.
Follow the steps below
1. Close the AOT reactor inlet (V201-19.n) and outlet (V201-20.n) valves from the control system
set in manual mode.
2. Depressurize and drain the AOT reactor: Remove the drain plug at the bottom of the AOT
reactor.
4. Disassemble the UV lamp according to the instruction Disassemble UV lamp on page 24.
5. Loosen the three Allen screws (6) of the glass socket (7) on both sides; just a few turns to
release them.
6. Unscrew the Allen screws completely at one side. Carefully remove the glass socket, to avoid
breaking the quartz sleeve. Then remove the glass socket on the other side.
7. Remove the O-rings (8) on both sides. The O-rings are firmly stuck in their seat, and will be
damaged during removal, but shall be replaced at assembly. Use an angled or hooked O-ring
tool to loosen and remove the O-ring. Be careful to avoid to break the glass.
If the O-ring is hard to remove, try the following:
– Moisten the O-ring with acetone or denatured alcohol.
– Loose the O-ring in a couple of places before removing it.
– Perforate the O-ring to get a good grip.
9. Carefully clean the surface and remove any small parts, for example glass or rubber.
2. Wet the O-rings (8) with water and slip them over respective side of the quartz sleeve.
Check that the O-ring are positioned evenly on both sides. If not, they may be damaged
and cause leaks.
The O-rings shall not be pressed into position, the glass socket will press them into position
when fastened later.
3. Carefully mount the first glass socket on the quartz sleeve with three Allen screws evenly, but
do not tighten the screws. Note that the waxed screws must be used to avoid seizing.
7QuartzSleeve
4. Once the Allen screws (6) are evenly entered, carefully tighten them evenly to a torque of 7 Nm.
7. Follow the instruction Check for leaks after quartz sleeve assembly.
1. Pressurize the AOT reactor with water to between 2 and 4 bar (0.2 and 0.4 MPa).
• A leakage check must have been performed according to the instruction Check for leaks after
quartz sleeve assembly.
• Use waxed screws.
• New heat resistant O-rings must be used in the two bushes. Always replace used O-rings.
• Keep the UV lamp in its protective cover as long as possible. Do not touch the glass of the
lamp; hold the lamp by its ceramic end parts.
• Glass sockets and bushes must be dry and clean before mounting.
• After UV lamps hav e been changed, the runtime must be reset in control system page 4.4
Operation timers AOTs.
Follow the steps below
1. Mount the new heat resistent O-rings in the two lamp bushes (3).
4. Insert the other bush in the opposite side of the AOT reactor.
5. Make sure that the connection is clean to ensure good electric connection (no rust, burning or
fading on the connectors). Reconnect the two cable connectors for the UV lamp.
7UVlampConnection
6. Mount the UV lamp caps and tighten the cap nut at both ends of the UV lamp, by hand only.
Make sure that the electric cable is is not squeezed between the cap and the bush when the
cap is mounted. Slack can be pushed into the bush.
7. Re-fit the drain plugs at the bottom of the AOT reactor and/or at the flanges under the AOT
reactor.
8. Control the control system page 3.1 Alarm list, to make sure there is no alarm when after
the the lamp power supply is on.
• The AOT reactor must be depressurized and the AOT reactor must be emptied from water.
7 OpenAOT
1. Access hatch
2. Inspect the bottom of the AOT reactor to see if there are any dirt or larger particles. If so,
remove.
Note: Be careful not to break the quartz sleeves.
NG
WARNI
!
• Switch off the main breaker on the LDC door. The LPS has high voltage/power (600 V)
inside and on the lamp power connector, even when UV lamps are not lit.
• The LDC contains a fan, which can cause injury if in operation.
Follow the steps below
7 LPSmaint
1. Dismount LPS
Release two power connectors at the bottom of the LPS and the signal cable connector
at the top.
2. Loosen the nuts at the bottom (1) and the top (2) of the two rods holding the LPS. If necessary,
loosen nuts for adjacent LPS.
NOTE
Make sure not to drop the washer into the LPS. It may cause short circuit.
4. Mount LPS
Set the DIP switches on the LPS according to chapter 4. Parameters, section Lamp power
supply (LPS) parameters.
6. Reconnect the three connectors. Make sure the connectors sit tight.
9. Switch on the main breaker on the LDC door and check that both LPS:s function correctly
according to instruction Test LPS installation below.
NG
WARNI
!
• This instruction must be performed after cable connection. If not hazardous situation may arise
which, if not avoided, will result in death or serious injury.
DANGER
!
• Before operating the AOT reactor, make sure that there is water in the AOT reactor.
Follow the steps below
2. Check that there is water in the AOT reactor(s) (LS201-29). Check the LED on the level switch:
Steady yellow light indicates that there is water in the AOT reactor.
3. Switch on the main breaker on the LDC door. Switch on the power to the AOT reactor using
the switches on the breaker cabinet(s).
4. Start UV lamps one by one from the control system (set to manual mode). Make sure that the
UV lamps are lit. This is checked in the AOT reactor popup and on the LPS.
Note: It can take up to 150 seconds for the lamp to start.
5. Check LEDs on the LPS and the alarm list in the control system. Make sure that no alarms
have been triggered by the LPS.
4. Lift the retaining plate. Four threaded holes that can be used to attach lifting devices.
NOTE
• The plate must be level when lifted, to avoid damaging the gasket and filter candle O-rings.
• It is important not to turn the shaft, after the retaining plate has been removed. If the
rotation is changed, this will make the mounting much more complicated.
5. Remove the gasket under the retaining plate.
1. Make sure that the filter candle O-rings are in position in their groove.
2. Carefully insert the filter candles (11). Make sure that they are fitted in the hole in the lower
retaining plate and that they they snap into position.
3. Place the gasket (10) on the filter housing. Make sure that the hole (12) for the locking pin
(9) is not covered by the gasket.
4. Before re-fitting the retaining plate (8), note that the locking pin shall fit into the hole in the
retaining plate.
NOTE
7. Carefully lower the filter cover (2) onto the retaining plate.
NOTE
- Protective hood (4) fasten with four of the filter cover bolts (1)
- Motor (1)
- Galvanic protection between the filter cover, retaining plate and housing
- Connection plate for valve connections (5)
- Electrical connections to the motor and valves
- Air pipe, loosened (15)
- Safety valve pipe (16).
1. To replace filter candles, follow the Remove filter candles instruction on page 35, and simply
replace damaged elements.
1. Follow the instruction Remove filter cover and filter candles on page 0 to remove the filter
candles.
2. If there is scaling on the filter candles: Soak the filter candles in the cleaning agent and leave
them to soak for 1–3 hours. Read the Preparations and conditions section for instruction
Change and refill CIP liquid.
4. Spray the filter candles with water from the outside. Start at a distance of 100 cm and reduce
to 50 cm, which is the minimum distance. The water must not be warmer than 60 °C. Note: If a
high-pressure cleaner is used, the pressure must not exceed 100 bar (10.0 MPa). Minimum:
20 bar. If a cleaner with higher capacity than 100 bar is used, compensate by increasing the
distance.
4. Inspect the anode. Change if the anode has lost approximately 80 % of the zinc mass.
6. Fasten the lid on the filter and restore the valves in their original positions.
ON
CAUTI
!
• Risk for eye and skin irritation. Avoid contact with eyes and wear protective gloves. Follow
rules when handling CIP liquid agent, regarding ventilation, personal protection etc.
ON
CAUTI
!
• If Alpacon descalant offshore comes in contact with eyes or skin, rinse thoroughly with cold
water.
• Before usage, Alpacon descalant offshore must be visually checked. It shall be transparent
light pink in color.
• The instructions requires pH test equipment (paper indicator or pH meter). This is not a part of
Alfa Laval’s scope of supply.
• The pH value should be between 2.0 and 3.0. From the beginning, the pH value is approximately
2.0. When the pH value rises to 3.0 the cleaning liquid must be changed.
• Mixing ratio for Alpacon descalant offshore is 1 part concentrated Alpacon descalant offshore to
20 parts fresh water. Follow this mixing ratio, regardless of recommendation on label.
• The CIP tank shall be filled with maximum 250 liters. Min and max filling of CIP liquid can
be read on the CIP tank.
• Store the CIP liquid according to the instructions on the bottle. General guidelines are:
7 CIP 589741_description
CIP module
1. If the drain valve (3) is connected to bilge (or other) tank, follow the sub steps below.
Otherwise, go to step 2.
a. Open the manual drain valve V460-3 under the CIP tank.
b. Wait for the tank to be totally drained. Then close the drain valve.
2. If the drain valve is not connected to the bilge tank, the steps below can be followed. This
operation requires login level Advanced operator or higher.
a. Open valves V320-2 and V460-2 from the control valve, and V230–11 manually. Start
pump P321-5 (3) and P320-1 (4).
b. Wait for the tank to be totally drained. Then stop the pumps and close the valves in
reversed order. Go to step 3.
3. Open the cap (1) on top of the CIP tank and pour 12 liters of CIP cleaning agent into the tank.
4. Fill the tank with fresh water to the Max indication on the tank, approximately 240 liters.
5. Measure the pH value in the tank to secure that it is approximately 2.0. If not, adjust the
proportions: If the pH value is too high, add more CIP cleaning agent. Measure again.
6. Go to control system page 4.3 – Operation timers. Make a note of the number of AOT reactors
that has been CIPed since last time the CIP liquid was changed. Press the Reset button for
“Total number CIP:ed reactors”. Requires login level Advanced operator. If this is done each
time the CIP liquid is changed, it is possible to build up experience on how many AOT reactors
it is possible to CIP before it is time to change CIP liquid.
1. Measure the pH value in the tank. Based on the pH value, estimation must be done regarding
the proportions between Alpacon descalant offshore and water. Note that the mixing ratio is
stated under Preparations and conditions above.
2. Mix the cleaning agent with water separately. The result will get better than if mixed mix in
the tank.
3. Pour the mixed CIP liquid into the tank. Do not fill over Max indication on the tank.
4. Measure the pH value in the tank to secure that it is approximately 2.0. If not, adjust the
proportions: If the pH value is still too high, the CIP liquid must be changed. See the Change
CIP liquid instruction in this chapter.
ON
CAUTI
!
• Always wear protective eye glasses and gloves while working on the pump.
NG
WARNI
!
• Always disconnect the PureBallast system from the power supply before disassembling, and
secure it from being switched on.
• Before disassembling the pump, the pneumatic hoses must be disconnected, and the extension
pipe must be removed and blocked.
• Drain the pump from liquids.
• The pump should be placed horizontally on a work bench.
7 CIP pump
1. Remove the CIP pump from the CIP module and place it on a work bench.
3. Place the pump on the side that still has the nuts (the pump lays on the nuts) on a stable ground.
5. Carefully lift up the suction and discharge connections (13). You have the centre block (12)
and one of the housings with pin screws (14) left.
6. Upend the pump and carefully pull out the pin screws (14). Be careful not to damage the
diaphragms (15).
1. Put the house wall with the flat side down on a plane surface.
4. Place one of the pin screws on the inside (behind) the valve ball stopper on the lower valve
seat (21). Carefully pull out the valve seat in the housing.
5. Remove the valve ball (23) from the valve seat, buy using a pin screw: Press out the valve ball
stopper (22), which will release the valve ball.
• Have backup spares of the sealing (36) and backup O-ring (47). There is a risk that these parts
get damaged during this operation.
Follow the steps below
1. Press the diaphragms (15) to their neutral position (both have the same distance to the
centre block).
2. Hold one of the diaphragms (15) and unscrew the other. Then pull out the remaining diaphragm
with the diaphragm shaft (16).
3. Disassemble the circlips (27) which keep the air valve (61) on its place.
4. Press out the air valve. A wood shaft of a hammer can be used. Be careful not to damage the
sealing edges towards the diaphragm or the air valve.
5. If the shaft sealings (36) seem to be worn out, carefully remove them with a pointed tool.
2. Apply some soft soap solution on the air valve O-rings (30).
3. Push the air valve (61) into the housing. Make sure that the O-rings (30) remain in the right
position. Put the circlip (27) on the other side.
4. Put the diaphragm (15) with shaft (16) into the centre block. Screw the next diaphragm (15)
onto the shaft (16) and fix the holes.
1. Make sure that the O-rings (18) are placed on the in/outlet (13) before assembling of pump.
3. Make sure all pin screws (14) have one nut (37) and one washer (38) each. Nut should only be
put on one or two threads.
4. Put all the pin screws through the housing and then turn the housing so it rests on the nuts.
5. Put the centre block (12) to the housing with screws through the centre block. Be careful not to
damage the diaphragms.
6. Place suction and discharge connections (13) in their positions in the housing. Be careful not
to damage the O-rings (18).
7. Put the second housing (11) onto the pin screws (14). Make sure that suction/discharge
connections are in right direction. Be careful with the O-rings.
8. Fasten the nuts (37) crosswise by hand, with or without washers depending on how much of
the thread comes out. Turn the nuts gently with a tool to close the pump. If some of the nuts
were fastened without washer, unscrew those and put washers underneath. After a few weeks
operation a follow up draft of the nuts is recommended.
1. Open valves V320-2 and V460-2 from the control system, and V230–11 manually. Start
pump P321-5 (4) and P320-1 (4).
2. Observe if the motors sound and functions OK. If not, check installation and connections and
attend to and test again.
• The valve bodies does not have individual placing, they can be placed in any order.
DANGER
!
• Always disconnect the PureBallast system from the power and air supply before disassembling,
and secure it from being switched on.
7 Valve block
Valve block
1. Remove the scresw holding the valve bodies (2) and the signal plate (4).
4. Attach a new sealing on the new valve body and fasten the valve body to the valve block.
2. Attach the cables according to electrical drawing Control cabinet / interconnection diagram in
chapter 6. Installation description and drawings.
2. Operate the service air according to instruction Open and close valves manually (CIP valves)
on page 19 to blow out the dust.
1. Connect the hoses according to the signal plate (4) on the valve block.
• Flow sensor: A pipe with four electrodes detecting the flow. On top of the pipe, there is a
terminal box, where the flow transmitter is mounted.
• Flow transmitter: Monitors and transmits information to the PureBallast control system. The
flow transmitter is also used to set parameters for the flow meter. A Sensorprom in the flow
transmitter contains the data.
• If the flow meter is replaced, settings must be checked according to chapter 4. Parameters,
section Flow transmitter parameters.
• See chapter 6. Installation description and drawings, section Control cabinet / Interconnection
diagram for detailed information.
• It is recommend that a shielded power cable is used.
NG
WARNI
!
• Potential hazards / Grounding: The mains protective grounding wire must be connected to the
terminals in accordance with the diagram (class 1 power supply).
Follow the steps below
1. Remove and discard the lid from the terminal box on the flow sensor.
7 FM Lid
2. Fit PG13.5 cable gland for the power and signal cable.
3. Connect power and grounding to the following terminal positions marked on the circuit board:
1=+
2=–
Grounding.
4. Connect current output signals to the following terminal positions marked on the circuit board:
31 = +
32 = –
6. Mount the flow transmitter on the terminal box using the two screws. If other direction of the
flow transmitter is desired, please follow the instruction Change direction of flow transmitter on
page 51.
7 FM MountTM
7 FM MountTM
2. Disconnect the power supply (terminal positions 1, 2 and grounding) and output signal cables
(terminal positions 31 and 32) from the circuit board.
3. Remove the coil plug (1) from terminal positions 85 and 86. Remove the plug (2) from terminal
positions 82, 0 and 83.
4. Unscrew the two screws (indicated below) holding the circuit board to the terminal box and lift
up the circuit board.
Note that the sensorprom is mounted on the underside of circuit board; be careful not to loose
it. Sometimes, the sensorprom remains in its seat on the terminal box.
7 FM ScrewCricuit
5. Disconnect the grounding wire holding the circuit board to the terminal box.
• If the flow transmitter shall be turned 180°: Move the sensorprom (1 in the illustration
below) to the position on the opposite side of the circuit board and refit in reversed order.
• If the flow transmitter shall be turned 90°: Continue with next step.
6. Unscrew the four screws (2) on the terminal box to loosen it from the flow sensor.
7 FM LooseTB
7. Turn the terminal box to 90° and fasten it with the four screws.
7 FM LoosFrame
7 FMScrewPad
7 FM TurnPad
7 FMScrewPad
5. Snap-lock (a click is heard) the outer frame onto the control pad.
7 FM FastCover
It is important that the electrodes are clean to secure accurate output. If the four electrodes in the
flow sensor get dirty, it may result in inaccurate and varying output.
2. Close the main valves connecting the PureBallast pipe net to the vessel’s ballast pipe net and
secure it from being switched on. See instruction Lock valve in closed position on page 20.
3. Remove all the flange bolts on the flow meter, except one on each flange. Note that the
remaining bolts on each side must be in the same position on respective flange.
4. Loosen the nuts on the remaining bolts. Swing the flow meter outside the pipe.
Valve actuator with switch box for position feedback to control system
1. Switch box
2. Bracket
3. Actuator
4.
5. Bracket - Used for valves with dimension 400
6. Coupling with position indicator - Used for valves
with dimension 400
7. DIN connector
8. Position indicator
7 Actuator
1. Safety cover
2. Pad lock
3. Lower position for indicator screw
4. Upper position for indicator screw — with screw
5. Position indicator
6. Center screw
7. Bracket
8. Puck
9. Locking bolt
10. End stop bolt.
M5 05–06
M6 10–11
M8 23–25
M10 48–52
M12 82–86
M14 132–138
M16 200–210
M20 390–410
1. Remove the DIN connector to disconnect the power. Let the air connection remain.
Result: Valve goes to closed position (due to the air connection). The yellow indicators on the
puck shows position of valve: closed. The yellow position indicators are in line with the valve
throttle (indicating closed when the position indicators are in opposite line with the pipe).
2. Disconnect the air hose to the pilot valve. Verify that the actuator is not pressurized. Always
use caution and double-check that ports 2 and 4 are vented and are free from any accessory
and/or device.
3. If the actuator have a switch box at the top: Loosen the four screws holding the switch box to
the actuator. Remove the switch box together with its bracket.
4. Loosen the four hexagonal screws holding the actuator to the valve.
5. If the actuator is mounted on the valve with a bracket and coupling (dimension 400): Loosen
the screws holding the bracket to the valve. Make sure not to loose the coupling between the
valve and actuator when lifting the actuator.
ON
CAUTI
!
• The actuator must not be pressurized at any time during installation as it may result in injury.
• The valve must be in closed position.
• The valve position must not be adjusted during the routine.
• The utmost cleanliness is required during air supply connection to the actuator, that is, the
connecting pipe thread, fittings and seals must be clean and dirt-free.
• Before fitting onto the valve, make sure the actuator/valve is correctly orientated, depending on
which direction of rotation is required.
Follow the steps below
1. Note the position of the groove (2) of the valve stem (3). It indicates the position of the valve
throttle. The illustration shows a square variant, but octagonal versions exist.
7 ValveStem
2. Make sure that the lock pin (inside the valve stem) only travels in the allowed sector (1) and
that it does not pass the opening (5).
3. If the actuator is mounted on the valve with a bracket and coupling (dimension 400): First fit
the coupling on the valve stem. Make sure that the red position indicator on the coupling is in
line with the pipe when the valve is open.
4. Fit the actuator onto the valve stem (or the coupling). The actuator may only be positioned in
even 90° intervals in relation to the valve. It is not allowed to adjust the position by turning the
actuator by hand after it is fitted on the valve stem.
5. Mount the actuator on the valve with the four hexagonal screws. For each screw, one washer
and one spring washer shall be used. Tighten with torque according to the table Tightening
torques for actuators on page 56.
6. If the actuator have a switch box at the top: Make sure that the yellow position indicator under
the switch box is in line with the throttle (according to the groove in the valve stem). The yellow
position indicator shall be in line with the valve throttle (indicating open when the position
indicator is in line with the pipe). If not, remove the position indicator, turn it 90° and refit it.
Mount the switch box with the bracket on the actuator, using the four bolts.
8. Operate the valve to make sure it operates in the desired direction of rotation.
3. Note the position of the groove of the valve stem. It indicates the position of the valve throttle.
5. Unscrew the center screw (4) holding the puck (6) and a bracket (5).
7 ActDirectWithout
6. Lift the puck (6), rotate it 90° and fasten it with the center screw (4) and bracket (5).
7. Make sure that the yellow position indicators (3) is in line with the throttle (according to the
groove in the valve stem). The yellow position indicators shall be in line with the valve throttle
(indicating open when the position indicator is in line with the pipe). If not, remove the position
indicators, turn them 90° and refit.
3. Before mounting the switch box, change the position of the yellow position indicator, so it
is in line with the throttle.
This instruction is valid for the following valves: V201-19 and V201-20 on the AOT reactor.
1. Dismount the actuator from the valve according to instruction Dismount actuator on page 57.
Put the actuator on a work bench.
2. Disconnect the DIN connector (2) from the coil: First loosen the screw (1), and then pull up
the connector.
7 DisconDINcon
3. Unscrew the center screw (6) holding the puck (8) and a bracket (7).
7 DirActPosSnsr
4. Lift the puck (8), rotate it 90° so that one position indicator (5) with a screw is in contact with the
position sensor. Fasten the puck with the center screw (6) and bracket (7).
5. Move the screw on yellow position indicator to the top position and move the screw on black
position indicator to the bottom position.
6. Make sure that the position sensor have a maximum distance of 1 mm from the puck (7). The
position sensor and the position indicator screws must be close to give a signal. If not, loosen
the screws and adjust the position. Tighten the screws to fixate the position.
7. Fit the actuator onto the valve stem in its new position according to instruction Mount actuator
on valve on page 57.
8. Make sure that the yellow indicator (5) in line with the valve throttle according to the groove in
the valve stem.
11. Check that the installation is OK, by making sure that the A1 LED is lit on the position sensor
(visible from the side).
1. Dismount the actuator from the valve according to instruction Dismount actuator on page 57.
2. Fit the actuator onto the valve stem in its new position and mount it on the valve with the four
hexagonal screws. For each screw, one washer and one spring washer shall be used. Tighten
with torque according to the table Tightening torques for actuators on page 56.
3. The position indicator scale shall be correct, but make sure that the scale still indicates correct
opening percent according to the valve throttle position. If not, loosen the four bolts to the
bracket holding the switch box. Lift it and turn the scale so it is correct.
4. Refit the switch box. Make sure that the peg on the scale fits to the carrier on the puck
mounted on the actuator.
7 MountPilote
1. Check that the O-rings are fitted on the pilot valve, on the side facing the actuator.
2. Fit the pilot valve on in the actuator, so that the pin on the actuator fits the hole on the pilot
valve. The throttle valves (2 and 4) shall be directed downwards.
3. Mount the pilot valve with two Allen screws in the holes (1).
5. Fit the DIN connector (5) on the coil, including gasket. Then fasten the connector with the
screw (6).
7 576075_lock_manual
1. Note the exact position of the position indicator for reference after adjustment.
2. Open the padlock (2) on the actuator and remove the safety cover (1).
Result: Two sets of bolts are displayed. The right set adjusts closing position and the left
set adjusts open position.
4. Adjust end position by turning the end stop blot (4) with small turns.
– Clockwise decrease the end position.
– Counterclockwise increase the end position.
NOTE
6. Tighten the locking bolt (3) to fixate the position of the end stop bolt (4).
7 AdjustTravel
1. Operate the valve manually to check traveling speed according to the instruction in the Operate
valves manually on page 19.
7 201-8Positioner4
7 201-8Positioner
1. Make sure that the transmission ratio selector (6) is set to 90° according to sticker on the
component. If not: Adjust by pressing the bar with a screw driver.
2. Make sure that the Arrestor device wheel (1) is set to 90°. If not: Adjust by turning.
3. If the positioner display is empty (no power): Open V201-8 manually (approximately 1-5 %)
from control system to supply power to the positioner. One of two results may occur:
Alt 1: Menu 1 and “turn” should be displayed. If not: Press – button until it is displayed. Go
to step 4.
Alt 2: Menu 4 and “no” is displayed. Go to step 6.
6. Press the hand button (approx. 5 sec.) until a (any) menus is displayed. Press the hand
button till menu 4 is displayed.
7 201-8Positioner2
- Use a screw driver to loosen the yellow locking wheel (counter clockwise).
- Turn the adjustment wheel (5) by hand until a 0 is displayed between the “d” and the “U” as
shown in the illustration. Normally this is when the value in the screen is close to 0.
7 201-8Positioner3
11. Press the hand button until “VER” is displayed (approx. 5 sec.)
Result: “MAN” is displayed”.
Trouble shooting
7 BallV
32 = 1¼ 20–25 Nm 14.3 Nm
inches
2. With the valve in the open position (lever to be parallel to the axis of the pipe), remove all the
body bolts (19) except one.
3. Loosen the nut (20) on the remaining bolt. Swing the body outside the pipe.
5. Replace seals (5, 6, 7, 9, 10, and 24). They are available in a spare parts kit for the ball valve.
6. Mount in reverse order. The body bolts of the valve should be tightened evenly. Tighten
one-side snugly, then the one diagonally across. Repeat for the other bolts, bringing them all
down tightly in sequence. Make sure the maximum tightening torque is observed according
to the table above:
This section contains information about the level switch LS201-29 installed in the AOT reactor. For
information about status indications, see chapter 5. Alarms and faultfinding, section Level switch.
7LS Component
Level switch
NOTE
2. Seal the level switch with lock tight or equivalent pipe seal.
4. Identify the sensor align mark (▼) on the component. Make sure that it is positioned on the
upper side of the level switch.
5. Complete the seal carefully by tightening the component with a spanner. Use the spanner on
the hexagon flats, but not on the level switch body.
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the level switch body.
3. Remove the level switch and remove the old seal from the threads.
1. Make sure that the component i powered (the green LED shall be lit).
2. Hold a magnet to the test point indicated on the on the level switch, indicated below.
7LS Test
3. Make sure the level switch reacts to the magnet. The component is OK if the green and
yellow LED is lit.
This section contains information about the temperature switch TS201-60 and the temperature
transmitter TT201–33 installed in the AOT reactor. The two components are similar in design, so
the same instructions can be used.
7 TS and TT
NOTE
1. Seal the component’s threads using lock tight or equivalent pipe seal.
3. Tighten the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
• The external surface may be hot. Care must be taken to avoid possible burns.
Follow the steps below
2. Loosen the component with a spanner. Use the spanner on the hexagon flats, but not on
the components body.
3. Remove the level switch and remove the old seal from the threads.
NOTE
• Control panels may only be cleaned when set in wipe mode. This is to prevent unintended
functions from being triggered by buttons pressed during cleaning.
Preparations and conditions
• Never use aggressive solvents, chemicals, scouring agents, pressurized air or steam jet.
Follow the steps below
2. Clean the display and surrounding front cover with a soft cloth and mild detergent. Do not
spray detergent directly on the control panel.
7BeijerScrews
4. Hold the panel on the outside so it does not fall out. At the same time: Slide the brackets
and remove them. Then remove the panel.
7BeijerBracket
2. Hold the panel on the outside so it does not fall out. At the same time: Attach the brackets on
the inside by sliding them into place.
7BeijerBracket
7BeijerScrews
4. Open the small cover on the rear side. Make sure that all DIP switches are in position OFF.
7BeijerMODE
7. Remove the laminated film, to avoid static electricity that could damage the terminal.
8. Make sure that the control panel is brought to ambient temperature before it is started. If
condensation forms, ensure that the operator panel is dry before connecting it to the power
outlet. Ensure that the voltage and polarity of the power source is correct.
9. Load new software to the panel according to instruction Update PLC software and Install
TA150 firmware in chapter 3. Operating instruction and control system description. Also
set communication according to Set control panel IP address and Set remote control panel
communication.
This section covers information on how to mount and connect communication components for the
remote control panel.
The information in this instruction is also given in the Control cabinet / Circuit diagram in chapter 6.
Installation description and drawings.
7 594060 RCP
7 RemotPanelCon
• If used, a network switch (3) is installed at a location of your choice, near the position of the
remote control panel.
• 24 VDC cables are not included in scope of supply. Use a cable with minimum cross section of
0.75 mm2, preferably halogen free and flexible.
• The remote control panel must have been mounted on a location of your choice. See Remote
control panel (optional) / Dimensional drawing in chapter 6. Installation description and drawings.
• Two wires are mounted between terminal and switch power contact (2) no 1=DC–, no 2=DC+,
cables are marked + and –.
• Prerequisites for cable length and cable types are stated in chapter 6. Installation description
and drawings, section Remote control panel integration (optional). Ethernet and fiber cable can
be used. This instruction is written for Ethernet, but if fiber is used use fiber cable and connect
them to the fiber ports instead of Ethernet ports.
• Switch off the PureBallast system and disconnect it from the power supply.
Follow the steps below
1. At the back of the remote control panel, fasten the Ethernet cable in Ethernet port 1. Fasten
the other end of the cable in the network switch’s Ethernet port number 1 (1).
2. Connect an Ethernet cable from the network switch near the remote control panel to the
network switch in the control cabinet (see position 1 in illustration on page 81). Also see cable
W501 in Control cabinet / Interconnection diagram.
3. If more than one remote control panel is installed, connect an Ethernet cable from Ethernet
port number 2 (1) in the network switch (near the remote control panel) to the second remote
control panel (or via a second network switch, if used).
4. Connect a 3 core cable from network switch terminals 4 (+), 5 (–) and 6 (GND) to the remote
control panel’s 24 VDC port (2).
7 591773 RI
1. Loosen the right end stop on the DIN rail at position (1).
3. Fasten the end stop to fixate the network switch at position (1).
4. On the PLC, disconnect the Ethernet cable (coming from the main control panel) from port IF2
and connect it to the network switch port: 1.
5. Connect an Ethernet cable in the IF2 on the PLC and connect the other cable end to the
network switch port: 2.
6. Connect wire 400 (DC–) to terminal 400 (3) and to network switch (1) terminal no: 1.
7. Connect wire 402 (DC+) to PLC terminal 15 (2) and to network switch (1) terminal no: 2.
8. Follow instruction Mount and connect network switch for remote control panel to connect
remote control panel.
1. Hold down the plastic clip on the top of the terminal block and pivot the block towards you.
7IO1_X025002A
3. Hold down the triangle on the top of the I/O board and loosen the board.
7IO2_X025003A
4. Pull the board straight out (otherwise it can fasten in one of its guides).
7IO3_X025004A
5. Compare the part number of the new I/O board to the old board, to make sure it is correct.
6. If changing more than one board at a time, check with the electrical diagram to ensure that
the boards are mounted in the right places.
7. Mount the new I/O board by pressing it straight into place. Make sure the board is firmly in
place, otherwise it will be impossible to mount the cable terminal.
7IO4_X025005A
8. Remount the terminal block. Make sure the clip on the bottom of the block fastens properly in
place on the axel on the bus holder.
7IO5_X025007A
9. Pivot the terminal block on the axel until the clip on the terminal block top fastens into place in
the I/O board.
7IO6_X025006A
1. Lubricate the inside surfaces of the frame with Roxtec Assembly Gel or equivalent, specially
in the corners.
7 Cable1
4. Peel off layers until you achieve a 0.1-1.0 mm gap between the two module halves when
held against the cable.
7 Cable2
7 Cable3
5. Lubricate all modules thoroughly, both on the inside and the outside surfaces.
7 Cable4
6. Insert the modules from the back of the frame opening. If possible, start with the largest
modules.
7 Cable5
7. Tighten the compression unit firmly to seal the frame. Maximum 10 Nm. A good indication is
when the lubrication is squeezed out between the modules.
7 Cable6
1. Adapt the seal to the cable by removing layers from the halves. The halves may not differ by
more than one layer.
7 LDC gland1
2. Achieve an approximate 0.1–1 mm gap between the halves when testing against the cable.
There shall be a visual gap.
7 LDC gland2
3. Lubricate thoroughly on the inside surfaces and sparsely on the outside of the seal.
7 LDC gland8
5. Tighten the Allen screws crosswise. The seal will compress and seal the transit.
2 Control Cabinet 6
2.1 Cabinet 10
2.2 I/O module 12
2.3 Relay module 14
4 Control panel 34
6 AOT reactor 38
6.1 AOT reactor JIS 42
6.2 Junction box 44
6.3 Junction box 46
6.4 Valve V201-19 and V201-20 48
6.5 Valve 50
7 Filter, RF10-35 52
7.1 Valve, V309-1 58
7.2 Electrical cabinet 60
3
12 Flow transmitter, A350 70
13 CIP module 72
13.1Pump P320-1 and P321-5 76
13.2Valve 78
13.3Valve block 80
13.4Air distribution 82
4
1 Important information
1 Important information
• State number of ordered parts. Note that the quantity in the tables do not states number of parts
delivered (only the how many of that parts that are included in the mother component).
• Safeguard your commitment to quality by always using genuine Alfa Laval spare parts.
Remember, Alfa Laval cannot accept responsibility for the failure of separator equipped with
non-original spare parts. We guarantee the quality and reliability of our products.
• When ordering, refer to part number listed in this catalogue and serial number, described in
chapter 7. Service manual, section Serial number information.
Book No. 5
PureBallast 3.0 Flow 1000
2 Control Cabinet
Machine unit number or
Subassembly description
9004429-
Ref Part No Description -80 Notes
Quantity
1 9006237 80 Cabinet 1 See page 10
3 9006852 01 Software, panel 1
4 595670 80 Panel 1
5 9006804 01 DIN-rail 35x15 1
6 9006805 01 DIN-rail 35x15 2
7 9006806 01 DIN-rail 35x15 1
8 221891 04 Lock nut 13
8.1 223101 47 Washer 13
9 582212 148 End stop (clip fix) 13
10 591103 60 Over current prot. Relay 1
10.1 591103 10 Auxiliary contact 1
11 591103 45 Breaker handles 1
12 582212 125 Power supply unit 1
13 9004299 04 Fuse 4
14 582212 67 Terminal, PIT 2,5-3PV 6
14.1 582212 60 Bus bar blue 1
15 582212 63 Terminal D-PIT 2,5-3L 1
16 591103 38 Contactor 1
16.1 591103 81 Relay, over current prot. 1
17 221701 03 Screw 4
18 9005006 80 I/O module 1 See page 12
19 582212 91 VIP-2, D 9SUB 2
20 582212 147 Patch panel 2
21 582212 104 Terminal PITTB 2,5 3
22 582212 102 Terminal PITTB 2,5 PE 1
23 582212 105 End plate D-PITTB 1
24 582212 104 Terminal PITTB 2,5 40
24.1 582212 171 Busbar 1/3/5-5, red 1 Connected: 11,15,19
24.2 582212 167 Busbar 20-5 Blue 1 Short end 15 pin, connected:
12,18,32,34,36,38,40
25 582212 105 End plate D-PITTB 1
26 582212 67 Terminal, PIT 2,5-3PV 4
26.1 582212 60 Bus bar blue 1
26.2 582212 03 Plug In Bridge 1
27 582212 63 Terminal D-PIT 2,5-3L 1
28 582212 168 Separating plate 2
29 582212 123 Power terminal block, 1
29.1 582212 86 Bus bar, blue 500mm 1 155mm
29.2 582212 87 Bus bar, red, 500mm 1 155mm
30 9002362 81 Relay module 3 See page 14
31 582221 90 PE Connection bar 1 245mm
32 582212 15 PE/SC Bar 1 500mm
33 593724 03 Distance screw 7
34 594009 03 Screw 5
36 583556 16 Cable channel 40x80 2
37 583556 17 Cable channel 40x80 1
38 9003522 07 Cable channel, 25x80 2
39 9003522 06 Cable channel, 25x80 1
41 591922 01 Cable seal 1
42 595361 01 Cable seal 1
44 223101 47 Washer 2 BRB 6,4x12x1,6 fzb
45 221803 02 Nut 2 M6M 6 fzb
46 582221 89 Cable fixing spiral 1
47 582356 18 Puschbutton switch 1
48 582212 155 Socket with USB 2
49 591103 36 Main breaker 1
51.1 596894 01 PE cable, 2,5mm² 1 L= approx. 500mm (door)
51.2 596894 01 PE cable, 2,5mm² 1 L= approx. 300mm (PE bar)
52 9009695 80 Fan 1
52A 9006853 01 Fan 1
6 Book No.
2 Control Cabinet
2690A
Book No. 7
PureBallast 3.0 Flow 1000
8 Book No.
2 Control Cabinet
2690A
Book No. 9
PureBallast 3.0 Flow 1000
2.1 Cabinet
Machine unit number or
Subassembly description
9006237-
Ref Part No Description -80 Notes
Quantity
2 9006246 01 Door 1
3 594009 01 Screw 6 MRX-Z5x6 fzb
4 26556 Spring washer 6 FBB 5,1 fzb
5 9006761 80 Mounting plate 1
6 70915 Spring washer 16
7 221891 05 Hexagon lock nut 12 M6M 8 fzb
8 221716 01 Screw 4
10 579385 01 T-handle 1
11 9003013 01 Rod Guide 2
12 593991 01 Latch 1
13 9003024 02 Rod for latching 2
15 223107 34 Spring washer 4 FBB 6,1 fzb
16 221891 04 Lock nut 4 M6M 6 fzb
19 593254 01 Retaining ring 1
22 221711 19 Screw 1 MC6S 6x25 fzb
23 593282 01 Washer 1 BRB 6,4x12x1,6 polyamide
24 221803 02 Nut 2 M6M 6 fzb
25 223101 73 Washer 1 BRB 6,7x16x1,5 fzb
26 593239 01 Nut 1
27 581688 01 Bracket 4
28 594488 01 Washer 4
29 221711 16 Screw 8 MC6S 6x16 fzb
30 223101 47 Washer 8 MRM 6,4x12x1,6 fzb
31 221891 04 Lock nut 8 M6M 6 fzb
32 587276 02 Washer 6
33 70560 Washer 6
34 221891 05 Hexagon lock nut 6 M6M 8 fzb
35 544465 04 Locking liquid 1 Loctite 270
10 Book No.
2.1 Cabinet 2 Control Cabinet
2718A
Book No. 11
PureBallast 3.0 Flow 1000
12 Book No.
2.2 I/O module 2 Control Cabinet
2772A
Book No. 13
PureBallast 3.0 Flow 1000
14 Book No.
2.3 Relay module 2 Control Cabinet
2692A
Book No. 15
PureBallast 3.0 Flow 1000
16 Book No.
3 Lamp Drive Cabinet
2774A
Book No. 17
PureBallast 3.0 Flow 1000
3.1 Cabinet
Machine unit number or
Subassembly description
9011549-
Ref Part No Description -80 Notes
Quantity
1 9003628 80 Cabinet 1 See page 22
2 9004211 01 Centrifugal fan 1
3 9004212 01 Inlet duct 1
4 9004213 01 Protection 1
5 9004506 80 Terminal block 1
6 9004214 01 Heat exchanger 1
7 590624 03 Temperature sensor 1
9 9004254 01 Check valve 1 Fully exchangable with 9008407.
9.2 595558 01 Wire 1
10 523127 04 Hexagon nipple 2
11 9004426 01 Hose 2
12 582356 30 Lamp green, compl. 1
13 582356 26 Signal lamp, White 1
14 582356 28 Button ill. blue, compl. 1
15 582356 27 Sign holder 3
19.1 582212 164 Phoenix Contact 16
19.2 582212 163 Phoenix Contact 16
19.3 582212 165 Phoenix Contact 16
20 582221 90 PE Connection bar 1 830mm
21 9006677 01 Filter 1
22 9004313 80 Main breaker 1
23 9005494 01 Transmitted handle kit 1
24 591103 46 Breaker door seal 1
25 591103 60 Over current prot. Relay 2
26 591103 54 Over current prot. Relay 16
26.1 591103 10 Auxiliary contact 16
27 591103 66 Bus bar 6
28 591103 64 Connection 3
29 591103 61 Self-res. short-circ. lim 3
30 582212 125 Power supply unit 1
31 9004299 04 Fuse 3
32 9004299 01 Relay safety 1
33 9004299 02 Relay safety 1
34 9004299 03 Relay safety 1
35 9006326 01 Temperature relay 1
36 582212 146 Interface relay, 24V 1
37 9004174 80 I/O module 1 See page 26
37.1 594728 01 Temperature sensor 1
38 9004507 80 Terminal block 1 See page 28
39 9004329 80 Liquid leakage amplifier 1
40 9004303 02 Sensor, liquid 1
41 582212 147 Patch panel 2
42 9004508 80 Terminal block 1 See page 30
43 582212 148 End stop (clip fix) 13
46 9004299 07 Terminal 3
47 582212 141 Cable holder 2
48 70560 Washer 3
49 221030 10 Screw 12
50 221803 02 Nut 5
51 221803 03 Nut 1
52 221891 01 Lock nut 2
53 221891 02 Nut 4
54 221891 04 Lock nut 4
55 221891 05 Hexagon lock nut 3
56 223101 03 Washer 2
57 223101 16 Washer 4
58 223101 17 Washer 1
59 223101 47 Washer 21
60 587276 02 Washer 3
18 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2775A
Book No. 19
PureBallast 3.0 Flow 1000
20 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2775A
Book No. 21
PureBallast 3.0 Flow 1000
3.1.1 Cabinet
Machine unit number or
Subassembly description
9003628-
Ref Part No Description -80 Notes
Quantity
1 9005142 80 Cabinet 1
1A 591874 04 Seal 1 Upper LPS rack, left
1B 591874 05 Seal 1 Upper LPS rack, right
1C 9003031 01 Condensation outlet 2 Cabinet floor and heat exchanger floor
2 9005143 80 Door, RH 1
3 9005144 80 Door, LH 1
4 221803 02 Nut 12
5 223101 47 Washer 12
6 9005145 80 Stand 1
7 9008903 05 Washer 12
8 221891 05 Hexagon lock nut 12
9 9003089 02 Vibration damper 2
10 223101 49 Washer 13x24x2,5 2
11 221726 10 Screw 2
12 9003394 01 Mounting plate 1
13 587276 02 Washer 15
14 221891 05 Hexagon lock nut 12
15 221716 01 Screw 3
16 9003390 01 Bracket, fan 1
17 223101 47 Washer 6
18 221030 10 Screw 6
19 9003401 01 Sheet, heat exchanger 1
20 223101 47 Washer 3
21 221030 10 Screw 3
22 9003186 01 Plug 1
23 9003410 01 Sheet, heat exchanger 1
24 223101 47 Washer 9
25 221030 10 Screw 9
27 593287 01 Pop rivet, multi grip 3
28 9003113 01 Cable seal 1
29 9003114 02 Cable gland 2
30 9002947 01 Yoke 18
31 9002942 01 Stud bolt 36
33 223101 47 Washer 72
34 221030 02 Screw 36
35 221891 04 Lock nut 36
42 221891 04 Lock nut 17
42.1 223101 47 Washer 17
58 587276 01 Washer 8
59 221851 05 Cap nut 8
60 591889 01 Cable tie mount 3
62 593780 01 Key 1
63 9003186 02 Plug 2
64 9006316 01 Cover, fan 1
66 221030 10 Screw 3
67 223101 47 Washer 3
69 9006322 01 Sheet 2
70 9006519 01 Cover 1
72 221891 02 Nut 20
73 223101 41 Washer, 4,3x9x0,8 20
74 9008424 01 Protection 3
76 221851 05 Cap nut 5
77 587276 01 Washer 5
79 221891 04 Lock nut 2
80 223101 47 Washer 2
82 223101 47 Washer 7
83 221891 04 Lock nut 7
88 587276 01 Washer 17
89 221851 05 Cap nut 17
22 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2700A
Book No. 23
PureBallast 3.0 Flow 1000
24 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2700A
Book No. 25
PureBallast 3.0 Flow 1000
26 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2702A
Book No. 27
PureBallast 3.0 Flow 1000
28 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2704A
Book No. 29
PureBallast 3.0 Flow 1000
30 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2705A
Book No. 31
PureBallast 3.0 Flow 1000
32 Book No.
3.1 Cabinet 3 Lamp Drive Cabinet
2377A
Book No. 33
PureBallast 3.0 Flow 1000
4 Control panel
Machine unit number or
Subassembly description
594060-
Ref Part No Description -80 Notes
Quantity
1 595670 80 Panel 1
2 595728 01 Switch 1
3 595673 02 Ethernet cable 1
5 582212 95 Terminal, PIT 2,5 TWIN 2
6 582212 96 Terminal, PIT 2,5 TWIN-PE 1
7 582212 04 End plate 1
8 582212 24 End stop 2
34 Book No.
4 Control panel
2311B
Book No. 35
PureBallast 3.0 Flow 1000
36 Book No.
5 Remote control panel - Network switch
2312B
Book No. 37
PureBallast 3.0 Flow 1000
6 AOT reactor
Machine unit number or
Subassembly description
9002700-
Ref Part No Description -82 Notes
Quantity
1 9002699 82 AOT reactor JIS 1 See page 42
2 9003748 80 Junction box 1 A-side
See page 44
3 9004960 80 Junction box 1 B-side
See page 46
4 221711 08 Screw 8
5 223101 32 Washer 8
7 9001357 03 Sensor 1
8 594412 92 Valve V201-19 and V201-20 1 V201-19
See page 48
8.1 594412 92 Valve V201-19 and V201-20 1 V201-20
See page 48
8.2 590667 01 V201-19 1
9 9011365 01 Hexagon head screw 32
10 223101 64 Washer 32
12 9006325 01 Thermometer, resistance 1 TT201-33
13 9006324 01 Temperature, switch 1 TS201-60
14 558663 04 Gasket washer 2
15 594171 01 Vibration limit switch 1 LS201-29
16 9005051 04 Cable 1 V201-19
16.1 9005051 07 Cable 1 V201-20
16.2 9005051 06 Cable 1 V320-4
16.3 9005051 08 Cable 1 V404-36
16.4 9005051 05 Cable 1 V321-2
17 9005052 01 Cable 1 GS201-19
17.1 9005052 05 Cable 1 GS201-20
17.2 9005052 07 Cable 1 QT201-50
17.3 9005052 10 Cable 1 TS201-60
17.4 9005052 09 Cable 1 TT201-33
17.5 9005052 08 Cable 1 LS201-29
18 526350 05 Plug 1
19 558663 03 Gasket washer 2
20 594413 80 Valve 1 V320-4
See page 50
20.1 594413 80 Valve 1 V321-2
See page 50
20.2 594413 80 Valve 1 V404-36
See page 50
21 2210463 03 Screw 12
22 223101 37 Washer 12
23 1761805 01 Safety valve, 6 bar 1 RV201-23
24 597049 01 Coupling, elbow 90 1
25 594707 02 Pipe 1
26 581534 01 Distributor 1
27 260321 25 Hexagon screw 2
28 592304 01 Plug 1
29 592304 02 Plug, 1/4 1
30 552801 50 Push-on connector 5
31 9004638 01 Clamp 1
32 2210296 02 Screw 1
33 223101 33 Washer 3
34 221803 27 Nut 1
35 9006320 80 Lamp cable 16 Marked acc. to circuit diagram. Incl.
cap, collet, gland and nut.
36 9006320 81 Lamp cable 16 Marked acc. to circuit diagram. Incl.
cap, collet, gland and nut.
37 595272 01 Tube, 6x1 mm 4
38 558710 02 Air Hose Nipple 5
39 597044 04 Cable 1
63 596103 01 Screw 4
95 554214 06 Cable tie 30
38 Book No.
6 AOT reactor
2688A
Book No. 39
PureBallast 3.0 Flow 1000
40 Book No.
6 AOT reactor
2688A
Book No. 41
PureBallast 3.0 Flow 1000
42 Book No.
6.1 AOT reactor JIS 6 AOT reactor
2685A
Book No. 43
PureBallast 3.0 Flow 1000
44 Book No.
6.2 Junction box 6 AOT reactor
2679A
Book No. 45
PureBallast 3.0 Flow 1000
46 Book No.
6.3 Junction box 6 AOT reactor
2680A
Book No. 47
PureBallast 3.0 Flow 1000
48 Book No.
6.4 Valve V201-19 and V201-20 6 AOT reactor
2686A
Book No. 49
PureBallast 3.0 Flow 1000
6.5 Valve
Machine unit number or
Subassembly description
594413-
Ref Part No Description -80 Notes
Quantity
1 590037 01 Valve, DN32 1
2 576075 21 Air actuator, SR101 1
3 576071 01 Pilot valve 1
4 585976 01 Coil, 24 V DC 1
5 594410 01 Valve connector 1
6 583012 01 Throttle valve, 1/4 2
Z 576075 71 Actuator spare part kit, DA/SR 101 1
50 Book No.
6.5 Valve 6 AOT reactor
2330A
Book No. 51
PureBallast 3.0 Flow 1000
7 Filter, RF10-35
52 Book No.
7 Filter, RF10-35
2693A
Book No. 53
PureBallast 3.0 Flow 1000
54 Book No.
7 Filter, RF10-35
2693A
Book No. 55
PureBallast 3.0 Flow 1000
56 Book No.
7 Filter, RF10-35
2693A
Book No. 57
PureBallast 3.0 Flow 1000
58 Book No.
7.1 Valve, V309-1 7 Filter, RF10-35
2698A
Book No. 59
PureBallast 3.0 Flow 1000
60 Book No.
7.2 Electrical cabinet 7 Filter, RF10-35
2752A
Book No. 61
PureBallast 3.0 Flow 1000
62 Book No.
8 Valve V201-3 and V201-9 - JIS A350
2710A
Book No. 63
PureBallast 3.0 Flow 1000
64 Book No.
9 Valve V201-32 and 403-35
2714A
Book No. 65
PureBallast 3.0 Flow 1000
66 Book No.
10 Valve V212-31 - JIS A350
2716A
Book No. 67
PureBallast 3.0 Flow 1000
68 Book No.
11 Valve, JIS A300
2712A
Book No. 69
PureBallast 3.0 Flow 1000
70 Book No.
12 Flow transmitter, A350
2363A
Book No. 71
PureBallast 3.0 Flow 1000
13 CIP module
Machine unit number or
Subassembly description
9002547-
Ref Part No Description -81 Notes
Quantity
1 9003450 01 Frame complete 1
2 590414 01 Tank 1
3 9004533 80 Pump P320-1 and P321-5 2 See page 76
4 9002825 80 Valve 6 See page 78
5 9003730 01 Valve housing 3
6 9002915 01 Check valve 2
7 9003732 01 O-ring 6
8 590313 01 Valve, angle seat 1
9 590476 01 Nipple, ISO-R 3/4-1/2 1
10 9005046 01 Backflow preventer 1
11 589526 07 U-bolt clamp, c-c 56,5 1
12 526350 06 Plug 1
15 9003172 80 Valve block 1 See page 80
16 9004479 80 Filter regulator 1
18 9003514 01 Speed controller 2
19 9004517 01 Reducer 2
20 9002962 01 Pipe #1 1
21 9002963 01 Pipe #2 1
22 9004237 01 Pipe #3 1
23 9003935 01 Pipe #4 2
24 9002964 01 Pipe #5 1
25 9002584 01 Pipe #6 1
26 9002586 01 Pipe #7 2
27 9003570 01 Pipe #8 4
28 9003949 01 Pipe #9 1
29 9002589 01 Pipe #10 1
30 9003792 01 Pipe #11 2
31 9002591 01 Pipe #12 1
32 9003837 01 Pipe #13 2
33 9004247 01 Pipe #14 1
34 9002592 01 Pipe #15 1
35 9003851 01 Pipe #16 1
36 9003853 01 Pipe #17 1
37 9003854 01 Pipe #18 1
38 9003863 01 Pipe #19 1
39 9003886 01 Pipe #20 1
40 9003888 01 Pipe #21 1
41 592649 01 Nipple 1
42 591675 01 Hose, 32 1
43 569038 05 Hose, 32 1
44 592665 01 Hose, 25 1
45 9003574 01 O-ring 6
46 9005743 01 Pipe clamp 5
47 599223 03 Hose clamp 38-50 10
48 599223 02 Hose clamp 32-44 3
49 592676 05 Insulation sheet, 10mm 4
50 592676 07 Insulation sheet, 5mm 7
51 592790 01 Insulation sheet 1
53 221716 02 Screw 2
54 221711 17 Screw 2
55 221701 04 Screw 4
56 223101 41 Washer, 4,3x9x0,8 4
57 221711 16 Screw 16
58 223101 47 Washer 16
59 587276 02 Washer 2
60 27345 Nut, M8 12
61 70560 Washer 19
62 9005147 01 Pipe #22 1
63 9005394 80 Air distribution 1 See page 82
72 Book No.
13 CIP module
2605A
Book No. 73
PureBallast 3.0 Flow 1000
74 Book No.
13 CIP module
2605A
Book No. 75
PureBallast 3.0 Flow 1000
76 Book No.
13.1 Pump P320-1 and P321-5 13 CIP module
2606A
Book No. 77
PureBallast 3.0 Flow 1000
13.2 Valve
Machine unit number or
Subassembly description
9002825-
Ref Part No Description -80 Notes
Quantity
Z 9003574 01 O-ring
78 Book No.
13.2 Valve 13 CIP module
2609A
Book No. 79
PureBallast 3.0 Flow 1000
80 Book No.
13.3 Valve block 13 CIP module
2607A
Book No. 81
PureBallast 3.0 Flow 1000
82 Book No.
13.4 Air distribution 13 CIP module
2608A
Book No. 83
PureBallast 3.0 Flow 1000
84 Book No.
14 Sampling device (QT201.1, QT201.1)
2780A
Book No. 85
PureBallast 3.0 Flow 1000
86 Book No.
15 Pressure monitoring device
2709A
Book No. 87
16 Cross reference list
+ Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
88 Book No.
PureBallast 3.0 Flow 1000
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Book No. 89
16 Cross reference list
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
90 Book No.
PureBallast 3.0 Flow 1000
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
Book No. 91
16 Cross reference list
Part No. Page Ref. Part No. Page Ref. Part No. Page Ref.
92 Book No.
PureBallast 3.0 Flow 1000
9007239 24 60 Z
9007239 25 60 Z0.1
9007239 26 60 Z0.2
9007794 01 42 36
9007810 80 39 ZA
9008374 01 19 73
9008382 80 19 74
9008383 01 32 1
9008383 02 32 2
9008383 03 32 3
9008383 04 32 4
9008383 05 32 5
9008383 06 32 6
9008383 08 32 9
9008383 12 32 7
9008383 13 32 8
9008387 01 32 11
9008388 01 32 16
9008424 01 22 74
9008672 80 7 68
9008693 01 32 12
9008903 05 22 7
9009416 01 42 38
9009521 80 39 Z
9009688 01 7 52B
9009695 80 6 52
9009696 80 7 53
9009714 01 23 90
9009912 01 48 8
9011365 01 38 9
9011549 80 16 1
Book No. 93