Академический Документы
Профессиональный Документы
Культура Документы
Z
Y
Z
A
Can be solved by mesh or nodal
Using per
unit system
Y
A
One-line equivalent
Y or
A
8
Worked example-3
What is the line current and power factor of a 3-ph 200V system feeding
balanced load of
(a) A-connected phase impedance of Z
A
=15 /15
(b) Y-connected phase impedance of Z
Y
=7.071/30
(c) consisting both (a) and (b)
Solution
(a) V
P
=200, I
P
= V
P
/15=13.333, I
L
= \3I
P
=23.094, pf
a
=cos(15)=0.966
(b) V
P
=200/\3, I
P
= V
P
/7.071=16.333=I
L
, pf
b
=cos(30)=0.866
(c) P
a
= \3V
L
I
La
cos(15) = 7727.4, Q
a
= \3V
L
I
La
sin(15) = 2070.6
P
b
= \3V
L
I
Lb
cos(30) = 4899.0, Q
b
= \3V
L
I
Lb
sin(30) = 2828.5
P
T
= P
a
+P
b
= 12626.4, Q
T
= Q
a
+Q
b
= 4899.1, S
T
= \(P
T
2
+Q
T
2
) =13543.5
S
T
=\3 V
L
I
LT
I
LT
=39.1A, power factor=P
T
/S
T
=0.932
Exercise:
Repeat the above with V
L
=380V, Z
A
=25/-20, Z
Y
=10/40
Ans: (a) 26.32A; 0.94 lead (b) 21.94A, 0.766 (c) 41.86A, pf=0.993
9
Measurement of 3-phase power
Both current & voltage coils are measuring phase values and
the W-reading is for R-phase only
Only applicable to star-load with accessible neutral
Repeat the measure for the power for Y- & B- phases
10
11
Two-Wattmeter method
Instantaneous power
= p
1
+ p
2
= i
R
(V
RN
-V
YN
) + i
B
(V
BN
-V
YN
)
= i
R
V
RN
+ i
B
V
BN
- (i
R
+i
B
) V
YN
= i
R
V
RN
+ i
B
V
BN
+ i
Y
V
YN
=3-phase power
since i
R
+i
B
+i
Y
=0
The derivation here assumes Y-connection.
In actual case, the load can be of any
combination
Y A
R
Y
B
For balanced Y-load only
if V
RN
=V
P
/0 , V
RY
=V
L
/30,V
BY
=V
L
/90
0
if I
R
=I
L
/-|, I
B
=I
L
/120-|
Worked example-4
A A-connected balanced load with Z
A
=15/30 and a Y-connected balanced load
with Z
Y
=10/-30 are both connected to a 3-ph 208V system. Find the line
current, the total system power and the two wattmeter readings.
Solution
Converting A to Y
Recall Z
A
=Z
1
Z
2
/(Z
1
+Z
2
+Z
3
): if Z
1
=Z
2
=Z
3
=Z
A
,
Z
Y
=Z
A
=Z
A
/3=5/30
Z
Y
and Z
Y
are in parallel such that Z
//
= Z /u
eq
= 3.78/10.9
V
P
=208/\3=120, I
P
=120/3.78=31.8, I
L
=31.8A,
P=\3V
L
I
L
cos(10.9)=11239W
To evaluate wattmeter readings:
Let V
RN
=120/0, V
RY
=208/30, I
R
=31.8/-10.9 ,
Angle between V
RY
and I
R
: u
1
= 10.9+30
W
1
=20831.8cosu
1
=4995W
V
BY
=208/90 , I
B
=31.8/12010.9
Angle between V
BY
and I
B
: u
2
=90-(120-10.9)= 10.930
W
2
=20831.8cosu
2
=6244W
Check: W
1
+W
2
=11239
12
In general, the 2 wattmeters readings are V
L
I
L
cos(u
eq
30) for balanced load