Вы находитесь на странице: 1из 1

POWER ELECTRONICAL

High Voltage Dielectric Diagnostics


http://www.powerelectronical.com/

PESCGF100/50 SF6GasFilledStandardCapacitor100pF/100kV
InsulatedStandardCapacitorsareindispensableineverymodernhighvoltagelaboratoryandtestfieldwhereitoccupiesawide rangeofimportantfunctions. The SF6 insulated standard capacitor is used as Capacitance standard in measuring bridge circuits to measure the Dielectric Dissipation Factor (Tan) of all types including cables, capacitors, bushings, instrument transformers and power transformers. Furthermore,itcanbeusedashighvoltagecapacitorforvoltagedividercircuitsforhighvoltagetransformertest. TheSCGFseriesstandardcapacitorscanalsobeusedasthehighvoltagesectionofacapacitivedivider.Thisallowshighaccurate voltagemeasurementse.g.suchasthoserequiredforlossmeasurementsonpowertransformer. PowerElectronicalsstandardcapacitorsinsulationisofthehighestaccuracyandreliability.Theresultreflectatrueadvantagein highvoltagemeasurementsespeciallyathighhumiditylevels.

TheSF6insulatedStandardCapacitorisalsousedinconjunctionwithourCapacitanceandTanDeltameasuringbridges(e.g.PE ACDF1,andPEMCDF6)asacomparisonstandardforexactmeasurementsoftheCapacitanceandTanDofHVequipmentlike cables,transformers,bushings,capacitors,etc.Thecapacitorisprovidedwithatopelectrodewhichallowspartialdischargefree interconnectionstotheotherelementsoftheHVcircuit. TheSF6insulatedstandardcapacitorisdesignedforindoorserviceandisportable.ThestandardcapacitorsoftheSCGFseriesare usedfor: *Exactmeasurementsofthecapacitanceandtandelta *ExactmeasurementsofACvoltages(ACdivider) *ApplicationsinvolvingPartialDischargemeasurements(requiringPDfreecouplingcapacitors)

Specifications

RatedVoltage TestVoltage Capacitance TanDelta FrequencyDrift PDlevel GasPressure OperatingTemp Humidity TempCoefficient PressureCoefficient

100kV 120kV 100pF+1% <5X105(0.00001or0.001%) <1X105(0.00001or0.001%)) <5pC 350+50kPa minus5degCto+45degC <75%RH 3X105/degC 2.2X103/kPa

StandardAccessories
StandardCapacitorwithtopelectrode1no, Dimensions1100mm(H)X450mm(dia)withbase. Mobilebaseframe1no TestReport1no
NotePowerElectronicalreservestherighttochangeproductspecificationsforcontinualimprovement.Pleaseorderafreshcopyofspecsfromcontact@powerelectronical.com,beforeplacing neworders.JurisdictionlimitswithinterritoryofRepublicofIndiaonly.

Weight30kgs(approx)

OurotherProductsare AutomaticCap&TanDeltatestsystem10kV/12kV ManualC&DFtestsystem12kV AutoOilBreakdownVoltageTester80kV/100kV MotorisedOilBDVset0100kV

AutomaticOilResistivity&DFtestsystem InsulationTesters(10Mto15T,2%accuracy) HighVoltageBreakdowntesters(10kV50kV) SF6GasfilledStandardCapacitors(upto1000kV)

PREVENTION is better and cheaper than CURE Trust the experts!!

D-24, Classic Indl Premises, MIDC Ambad, Nasik 422010, MH, India. Tel : +91 253 6602387 Fax : +91 253 6602388 Email : contact@powerelectronical.com