132/33 KV, 16 MVA PTR Cable Schedule (ER Panel (CSC-326 Diff.Relay) ABB HVBreaker + CGL LV BREAKER) at 132 KV SS Chennur
S.No Cable size
CABLE ROUTING
PURPOSE
1

6 x 2.5

6 x 2.5

6 x 2.5

4 x 2.5

4 x 2.5

FROM

TO

HVCT R-Phase
1S1
1S2
2S1
2S2
3S1
3S2

HVCT MB
1 - R - 1S1
2 - R - 1S2
3 - R - 2S1
4 - R - 2S2
5 - R - 3S1
6 - R - 3S2

HVCT Y-Phase

HVCT MB

1S1
1S2
2S1
2S2
3S1
3S2

7 - Y - 1S1
8 - Y - 1S2
9 - Y - 2S1
10 -Y -2S2
11- Y -3S1
12- Y -3S2

HVCT B-Phse
1S1
1S2
2S1
2S2
3S1
3S2

HVCT MB
13 - B - 1S1
14 - B - 1S2
15 - B - 2S1
16 - B - 2S2
17 - B - 3S1
18 - B - 3S2

HVCT MB
1 (C11)
7 (C31)
13(C51)
2 (C71)
Loop 2-8-14 to earth @ HVCT MB

Tr HV Relay Panel
TB 1.1 - C11
TB 1.2 - C31
TB 1.3 - C51
TB 1.4 - C71

HVCT MB
3 (A11)
9 (A31)
15 (A51)
4 (A 71)
Loop. 4-10 -16 - Earth @ HVCT MB

Relay Panel
TB 1.5 (A11)
1.6 (A31)
1.7 (A51)
1.8 (A71)

R-Phase CT secondaries
brought to HVCT MB.
((100/1A)

Y-Phase CT secondaries
brought to HVCT MB.

B-Phase CT secondaries
brought to HVCT MB.

HVCT first core for O/L, E/L Protection


5P 10 class

HVCT Second core for differential


Protection.

S.No Cable size

4 x 2.5

6 x 2.5

CABLE ROUTING
FROM

TO

HVCT MB
5 (D11)
11 (D31)
17 (D51)
6 (D71)
Loop. 6-12 -18 - Earth @ HVCT MB
132 KV CGL Spring charge Breaker
X1-101(J1)
X1-102(J2)
X2-2(K13)
X2-7(K21)
X2-8(K23)
X2-10(K41)

Control Panel
TB 1.1 (D11)
1.2 (D31)
1.3 (D51)
1.4 (D71)
Tr. Control Panel
TB 5.1 (K1)
5.2 (K2)
5.4 (K11)
5.7 (K25)
5.8 (K27)
5.10 (K33)

PURPOSE

HVCT 3rd Core for metering

+'ve 1
-'ve 1
Remote close
Remote trip TC1
Protection trip TC1 & Post close supervision
Preclose supervision TC1

Loop. 5.1-5.3 -5.6; 5.8 - 5.9 : 5.13-5.14;


@ Control Panel
7

6 x 2.5

132 KV CGL Spring charge Breaker

Tr. Control Panel

X1-101(J1)
X1-102(J2)
X2-7(K21)
X2-13(K53)
X2-26(K61)

TB 5.1 (K1)
5.2 (K2)
5.7 (K25)
5.13 (K57)
5.15 (K73)

+'ve 2
-'ve 2
Remote trip TC2
Protection trip TC2
Preclose supervision TC2

132 KV CGL Spring charge Breaker


X1-107(H1)
X1-108(H2)

ACDB
PH
N

AC supply to HV Breaker

132 KV CGL Spring charge Breaker


X4-201
X4-202
X4-204
X2-40
Loop. X4-201-203-X2-39 @ Breaker

Tr. Control Panel


TB 5.16 (L1)
TB 5.17 (L13)
TB 5.18 (L15)
TB 5.19 (L23)

Loop. 5.1-5.3 -5.6; 5.8 - 5.9 : 5.13-5.14;


@ Control Panel
8

2 x 2.5

6 x 2.5

+'VE
Breaker semaphore/Lamp Close
semaphore/Lamp Open
Spring Charge indication

S.No Cable size


10

11

11

12

13

4 x 2.5

6 x 2.5

6 x 2.5

6 x 2.5

2 x 2.5

CABLE ROUTING

PURPOSE

FROM
132 KV CGL Spring charge Breaker
X2-19
X2-20
X2-12
Loop X2-19-11 @ Breaker

TO
Tr. Control Panel
4.19 (L121)
4.20 (L177)
4.22 (L181)

+'VE
SF6 Low.
General lock out

132 KV CGL Spring charge Breaker


X4-205

Tr. Relay panel


TB7.3 (K203)

No contact for differential relay

X4-206

TB7.4 (K205)

X4-209

TB7.13 (K403)

X4-210

TB7.14 (K411)

33KV MEGAVIN SPRING CHARGE VCB

Tr. Control Panel

TB 4(J3)

7.1(K101)

+VE} 1 DC supply to Breaker

TB 5(J4)

7.2(K102)

-VE } 1

TB 8(K15)

7.4(K111)

Remote close

TB 10(K7)

7.7(K125)

Remote Trip TC1

TB 9(K5)

7.8(K127)

Protection trip TC1

TB 11(K5A)
33KV MEGAVIN SPRING CHARGE VCB
TB 4(J3)
TB 5(J4)
TB 10(K7)
TB 14(K305)
TB 16(K305A)
Loop 7.1-7.3-7.6: 7.8-7.9: 7.13-7.14 @
panel

7.10(K133)
Tr. Control Panel
7.1(K101)
7.2(K102)
7.7(K125)
7.13(K157)
7.15(K173)

Pre close supervision TC1

Breaker
TB 23 (L1)
24 (L3)
25 (L5)
26 (L7)

Control Panel
7.16 (L51)
7.17 (L73)
7.18 (L75)
7.19 (L83)

33KV Breaker

ACDB

No contact for HV O/L & E/L relay

+VE} 2 DC supply to Breaker


-VE } 2
Remote Trip TC2
Remot trip TC2
Protection trip TC2

+VE
Breaker close
Breaker open
Spring close indication

S.No Cable size

FROM
TB 20 (H3)
TB 21 (H4)
14

15

16

17

2 x 2.5

2 x 2.5

6 x 2.5

6 x 2.5

CABLE ROUTING

DC Panel
+'VE
-'VE

TO
Phase
Neutral
Tr. Control Panel
TB 3.3 (J101)
TB 3.4 (J102)

PURPOSE
AC supply to Breaker

DC supply to control panel.

AC Panel
Phase

Tr. Control panel


TB 3.1 (H01)

Neutral

TB 3.2 (H02)

HV Isolator
+VE
NC
NO

Tr. Control Panel


5.21 - L1
5.23 - L5
5.22 - L3

LV Isolator

Tr. Control Panel

+VE

7.20 - L 51

+VE

NC

7.22 - L 55

Iso semaphore open

NO

7.21 - L 53

Iso semaphore close

AC supplyto control panel.

+VE
Iso semaphore open
Iso semaphore close

18

6 x 2.5

LV CT R-Phase
1S1
1S2
2S1
2S2
3S1
3S2

LV CT MB
1 - R1S1
2 - R1S2
3 - R2S1
4 - R2S2
5 - R3S1
6 - R3S2

R-Phase CT secondaries brought to


LV CT MB 400A

19

6 x 2.5

LV CT Y-Phase
1S1
1S2
2S1
2S2
3S1
3S2

LV CT MB
7 - Y 1S1
8 - Y 1S2
9 - Y 2S1
10 - Y 2S2
11 - Y 3S1
12 - Y 3S2

Y-Phase Ct secondaties broought to


LV CT MB.

20

6 x 2.5

LV CT Y-Phase
1S1
1S2
2S1
2S2

LV CT MB
13 - B 1S1
14 - B 1S2
15 - B 2S1
16 - B 2S2

B-Phase CT secondaries brought to


LV CT MB.

S.No Cable size

21

4 x 2.5

22

4 x 2.5

23

4 x 2.5

CABLE ROUTING

PURPOSE

FROM
3S1
3S2

TO
17 - B 3S1
18 - B 3S2

LV CT MB
1 (C111)
7 (C131)
13 (C151)
2 (C177)
Loop. 2-8-14 to Earth @ LV CT MB.
LV CT MB
3 (A111)
9 (A131)
15 (A151)
4 (A 171)
Loop 4-10-16 earth @ LVCTMB

Tr. Relay Panel


TB 1.9 C111
1.10 C131
1.11 C151
1.12 C171

CT 1st core for O/L & E/L protection.


5P 10 class

Tr Relay Panel
TB 1.13 (A111)
TB 1.14 (A131)
TB 1.15 (A151)
TB 1. 16 (A171)

CT second core brought for diferential


protection.
PS class

LV CT MB
5 (D111)
11 (D131)

Tr Control Panel
TB 1.5 (D111)
TB 1.6 (D131)

LV CT 3rd core for metering

17 (D151)

TB 1.7 (D151)

6 (D171)

TB 1.8 (D171)

Loop. 6-12-18 to Earth @ LV CT MB.


24

25

26

4 x 2.5

2 X 2.5

2 X 2.5

E-111

Tr HV/LV Control panel


TB 2.1 (E111)

E-131

TB 2.2 (E131)

E-151

TB 2.3 (E151)

E-171
Loop. 2.1 - 2.9(E11)
2.2 - 2.10(E31)
2.3 - 2.11(E51)
2.4 - 2.12(E71) @ Control Panel.

TB 2.4 (E171)

From existing Feeder Panel

R PT

PTMB

1A
1B

1-R -1A
2- R-1B

Y PT
1A

PTMB
3-Y -1A

132 KV PT Supply to Control Panel

33KV PT Seconderies brought to


PT MB

S.No Cable size

27

28

2 X 2.5

4 x 2.5

FROM
1B

TO
4-Y-1B

B PT
1A
1B

PTMB
5-B -1A
6-B-1B

From 33KV PT MB

Tr HV/LV Control panel


TB 2.5 (E311)
TB 2.6 (E331)
TB 2.7 (E351)
TB 2.8 (E371)

1-E-311
3-E-331
5-E-351
2-E-371
Loop. 2.5- 2.13(E211)
2.6 - 2.14(E231)
2.7 - 2.15(E251)
2.8 - 2.16(E271) @ Control Panel.
2-4-6-Earth @ PTMB
29

12 x 2.5

CABLE ROUTING

PTR marshaling Box

PURPOSE

33 KV PT Supply to Control Panel

Relay Panel
TB 8 - 27 K 201

+ VE For Alaram

- 31 K 253
- 34 K 259

OTI - Alaram
OTI - Trip

- 30 K 251

WTI - Alaram

- 33 K 257

WTI - Trip

- 36 K 263

Buch Alaram

- 32 K 255
- 37 K 265
- 38 K 267
- 35 K 261

MOG
Buch Trip
OSR
PRV Trip

- 7 K 223

OLTC PRV

S.No Cable size

CABLE ROUTING
FROM

TO

PURPOSE

S.No Cable size

CABLE ROUTING
FROM

PURPOSE

TO

INTER PANEL WIRING


1

2 x 2.5

Control panel
3.23 H1
3.24 H2

Relay panel
3.23 H1
3.24 H2

AC supply looped between control +


relay panel

4 x 2.5

3.25 J1
3.26 J2
3.5 J11
3.6 J12

3.25 J1
3.26 J2
3.5 J11
3.6 J12

DC supply

4 x 2.5

2.1 E111
2.2 E131
2.3 E151
2.4 E171

2.1 E111
2.2 E131
2.3 E151
2.4 E171

Loop for HV protection


132 KV PT

4 x 2.5

2.5 E 311
2.6 E 331
2.7 E 351
2.8 E 371

2.5 E 311
2.6 E 331
2.7 E 351
2.8 E 371

Loop for under Voltage protection


33 KV PT

12 x 2.5

3.7 K7
3.8 K5
3.9 K21
3.10 K 27
3.11 K51
3.12 K57
3.17 K107
3.18 K105
3.19 K121
3.20 K 127
3.21 K 151
3.22 K 157

3.7 K7
3.8 K5
3.9 K21
3.10 K 27
3.11 K51
3.12 K57
3.17 K107
3.18 K105
3.19 K121
3.20 K 127
3.21 K 151
3.22 K 157

Inter panel connections for


HV, LV CB control circuit.

S.No Cable size

12 x 2.5

6 x 2.5

CABLE ROUTING
FROM

TO

4.1 L121
4.2 L123
4.3 L125

4.1 L121
4.2 L123
4.3 L125

4.4 L127
4.5 L131
4.7 L 133
4.8 L 135
4.9 L 137
4.10 L141
4.11 L 143
4.12 L145

4.4 L127
4.5 L131
4.7 L 133
4.8 L 135
4.9 L 137
4.10 L141
4.11 L 143
4.12 L145

4.13 L 147
4.14 L 151
4.15 L 153
4.16 L 157
4.17 L 171
4.18 L 175
4.25 L 185

4.13 L 147
4.14 L 151
4.15 L 153
4.16 L 157
4.17 L 171
4.18 L 175
4.25 L 185

PURPOSE

Inter panel wiring for announciation

Inter panel wiring for announciation

S.No Cable size

10

CABLE ROUTING
FROM

TO

PURPOSE