Академический Документы
Профессиональный Документы
Культура Документы
The purpose of this technical bulletin is to highlight common problems with dual fuel
tanks and the effect of both static and dynamic fluid head on the operation of the
quick-fill system.
Figure 1 below depicts the effect of dynamic head loss between 2 fuel tanks, linked
by pipe or flexible hose. The magnitude of the loss is a factor of the length of pipe,
the number and nature of fittings within that length, the flow-rate, and the internal
diameter of the pipe. The greater the amount of dynamic head loss, the greater the
differential between fluid level and internal pressure of each tank. Unlike static
head, dynamic head as the term suggests occurs only when fluid is moving.
The difference in fluid level i.e. static head, between each tank is proportional to the
amount of dynamic head loss between the tanks. The greater the loss, the greater
the liquid level disparity.
The problems associated with high levels of dynamic head loss between dual tanks
causing preferential filling of the near-side tank are:
The quick-fill vent may be removed from the near-side tank, and replaced with a
venting pipe linking the top regions of both tanks (see Figure 1b) thus eliminating
spillage from the near-side tank. This can only be achieved provided the dynamic
head loss is minimised between both tanks and there is no way which the two tanks
can be hydraulically isolated from each other, thus preventing the over-
pressurisation of the near-side tank.
Figures 2 and 3 below depict the effect of static head with dual tanks. The
magnitude of static head is a factor of the difference in height that exists between 2
points. Both applications shown require additional modifications outside those
normally associated with quick-fill equipment, notably the vent pipe linking the
ullage regions of both tanks and the absence of a quick-fill vent on the lower tank.
The situation shown in Figure 2 occurs when positive static head exists between the
near-side (lower) and far-side (upper) tanks. A vent pipe must be installed linking the
top of the lower tank to the ullage gap in the upper tank. Neglecting dynamic losses
in the pipework linking both tanks, the pressure in the lower tank will be greater
than that contained in the upper tank - the difference being equal to the static head
between each tank.
Figure 3 occurs when negative static head exists between the near-side (upper) and
far-side (lower) tanks. As in Figure 2, a vent pipe must be installed linking the top of
the lower tank with the ullage gap in the upper tank. Again, neglecting dynamic
losses in the pipework linking both tanks, the pressure in the lower tank will be
greater than that contained in the upper tank - the difference being equal to the
static head between each tank.
Note: any additional fittings or pipework linked to either tank will be momentarily
pressurised with the tank contents during the final stages of the refuelling process.
Care must be taken to ensure all such additions are rated to the certified pressure of
the tanks themselves.
Note that due to the requirement of a receiver on each side of the locomotive and
other unique details, rail installations will require specialist advice from Banlaw
personnel.