Вы находитесь на странице: 1из 61

Jenin Hospital -BOQ-

Construction of the First and Second floor in Jenin Hospital -BOQ-

Consultants: -AL-Ta'meer engineering office for studies and consultants Joint Venture with -Kittani E/M Consultants

Civil

1/19

Jenin Hospital -BOQSection 1 * -BOQPreliminary works prior to the construction of the new floor The contractor shall, when pricing the rates of this bill, take into consideration to include and allow for the costs or expenses of all requirements stipulated herein below or in the preambles, drawings and the specification of the tender. The contractor should visit the site to verify the amount of work and consider all other works for the proper construction of the new floor. The disposal& demolished materials shall be carried out from the construction zones through special arrangements to external hospital yards to avoid disturbances/ noises or dust spreading down the floors or neighboring areas. the contractor is responsible for the disposal of all demolished and removed materials from the site to a dump site approved by the municipality. The contractor should coordinate with the client for any possible material or elements that need to be preserved and handed over to the client stores. The preserved elements such as steel doors& widows, steel grills, steel hand rails, steel steps and metal protections for fans shafts& service openings shall be re installed for the new construction as directed by the engineer. while the other materials should be handed over to the client stores. The contractor should take all measures to protect the hospital belongings from any damage or disturbance to its functioning systems and to ensure the safety of the hospital users during the construction stage, The contractor shall protect the underneath floors from leakage or penetration of rain water from the roof above which the new floor will be constructed. Therefore, special arrangement and protection zone shall be erected in full coordination with the hospital directorate and the engineer. The contractor should also protect all existing mechanical, drainage systems and electrical networks . This include the conduct of any necessary arrangements to ensure continuous functioning of these systems during construction stage. The contractor should also take all necessary shoring measures to protect the existing building elements during all stages of work until safely completing all new construction work. The contractor should submit a clear methodology for the proposed stages of work and protection and shoring methods for the Engineers approval prior to commencement of works. Careful demolishing and reinstatement of existing structural elements for proper construction of the new floor works; all as sown in the demolishing plan and in accordance with the engineer's instructions. The work includes but not limited to : Unit QTY Unit Rate Total

Civil

2/19

Jenin Hospital -BOQSection 1.1 -BOQDemolishing and removal of all elements covering the steel reinforcement for the columns starters on the existing roof, such concrete, blocks, stone, filling materials....etc, including the preserving and cleaning of steel reinforcement for proper erection of the new columns (this is true for all existing columns including perimeter columns). Demolish and removal of concrete roof slabs for existing elevators shafts (roof & floor) including the protection and preservation of all existing finishing works, and all other electrical& mechanical utilities, fittings and equipments, machines. etc. The work also includes cuttings/ making new openings for elevators doors through the existing concrete walls to match the new proposed locations of the elevators and perform concrete filling/ patching/adjustment of the existing doors openings at the roof. the voids for the elevators shall be protected by rigid formwork or scaffolding through out the construction stage. Unit LS QTY 1 Unit Rate Total

1.2

M2

12

1.3

Demolishing and removal of the existing concrete/ block walls partitions, or external stone walls. The unit price shall include cost of demolishing of the other wall finishes in the machinery room at the existing roof level. The unit price shall also include dismantling and preserving the existing windows and doors . All as directed by the Engineer. as shown on detailed drawing S02 Demolishing and removal the finishing layers on top of the existing roof slabs including the sloped light weight concrete, and machine foundations. All as directed by the Engineer. (provisional)

L.S

1.4

M2

50

1.5

Dismantling and demolishing parts of the existing stone roof parapet, including the preservation of stone courses and existing steel reinforcement as shown on drawing S02 ditto, but only 30cm height as shown in drawings S04, detail 1'-1'. Careful dismantling and removal of the existing stone coping for the roof parapet and preservation for use in the construction of new stone parapet. All as directed by the Engineer. Enlarging the existing doors opening on grids (T - S /16) to be at the dimension of 2.2m wide and to the full height( from the ground level up to the suspended ceiling level), as shown on the plans. The unit rate includes cost of demolishing and the required finishing works around the opening. The unit rate shall also include cost of and dismanteling and removal of the existing doors. (D10)

M2

100

1.6

MR

26

1.7

MR

140

1.8

No

Civil

3/19

Jenin Hospital -BOQSection 1.9 -BOQDitto, but for door on grids( j/19-20) to be at the dimension of 2.05m wide and the full height from the ground level up to the suspended ceiling level. The unit rate shall also include cost of dismantling and preserving the existing door for re-use type D AL) as shown on the drawings. Make new doors openings, demolishing, and cutting doors in the wall on grids horizontally and grids vertically as mentioned below. The unit rate shall include cost of demolishing and finishing work complete and treatment around the opening. Opening doors in the first and second floor level on grids (S/27-28) to be at the dimension of 1.7 m width and height of 2.3m ( D09) opening doors in the first floor level on grids (T-S/16) at the dimension of 2.2 width and height from ground level to up to the suspended ceiling level. (D10) Opening window at the second floor on grids (T/17-19) and (T-U/19) to beat the dimensions of 2.0m*2.5m (W13)+(W12) enlarging the door at the first floor level and the window in the second floor level on grids (J/17-18) to be a door at the dimension of 2.05 width, and height from the ground level up to the suspended ceiling level. (D10), and preserving any existing mechanical work. Demolish the existing concrete slab to construct the new foundations for the escape staircase of dimension 5.101.9 m. The contractor shall be responsible for any damage of the mechanical pipes inside and outside the shaft. as shown on drawing Excavation for the foundations of the escape staircase; in any kind of soil, to the dimensions shown on the drawings and to the Engineers instructions. Price shall include cost of backfilling, with in 20cm layers and compaction to 95% according to modified AASHTO Density Test T-80,as shown on drawing Unit No QTY 1 Unit Rate Total

1.10

M2

M2

c.

M2

1.11

L.S.

1.12

L.S.

1.13

m3

10

1.14 1.15

Ditto, but only backfilling and compaction and with imported approved filling material. Perform soil test to determine the soil bearing capacity of the soil above which the foundation of the existing building rest. The test shall be carried out using core drill around the existing building and in accordance with the Jordanian code and Standards.

M3 L.S

10 1

Total of preliminary works carried to summary sheet

Civil

4/19

Jenin Hospital -BOQSection 2 Concrete Works The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the tender. All concrete works includes the supply of ready mix concrete, placing& casting, formwork & supports, reproping, shuttering, vibration, curing, testing and whatever needed for the completion of the works all in accordance to the standards, codes, specifications and as details shown in drawings. 2.1 Supply and cast reinforced concrete B300 for columns of various dimensions and locations, maximum size of aggregate 20mm as shown on drawings. Supply & cast concrete B300 for 36cm thick ribbed slabs including light weight block "ETONG" filling and drop beams as shown on drawings. The unit rate shall include cost of connecting the existing structural elements and the new slabs; including demolition stone works, cutting the existing stone in the areas where the new slabs are joined with the old slabs, making openings in the existing concrete walls, fixing steel plates and angles L909011mm plate, bolts M12@15cm Hilti HSL, applying an approved bonding agent such as NITOPONDEP,and all other the required work to make proper and sound connections. All in accordance with the drawings and engineer's instructions. M3 120 -BOQUnit QTY Unit Rate Total

2.2

M2

2980

2.3 2.4

Ditto, but for 20 cm thick solid slab for elevator Supply and cast reinforced concrete B300 for walls of various thickness, dimensions and different locations. The price includes cost of connecting the existing structural elements with the new walls including cost of bonding agents and other necessary works. All as shown on drawing S04 and the specifications. Ditto, but for 1 m high walls in bathrooms, price include reinforcement network 18mm@20cm vertical and horizontal. Supply and cast concrete B300 behind stone for backing the stone works, including concrete for stone lintels and where needed; all in accordance with the engineer instructions. Supply and cast plain concrete Grade 'B 200' for 10cm thick blinding under foundations for steel staircase. Supply and cast reinforced concrete Grade 'B 300' for steel staircase foundations.

M2 M3

12 280

2.5

M3

2.6

M3

53

2.7

M2

10

2.8

M3

Civil

5/19

Jenin Hospital -BOQSection 2.9 -BOQMaking dowels for connecting the steel reinforcement of the existing structural elements and the steel reinforcement of the new structure, where required and as per drawings and the engineer instructions. The unit rate shall include all the associated costs, such as : Drilling, injection, and anchorage steel reinforcing bars using approved bonding agents such as "Lokfix" material from Fosrock company. All per drawing S04 and the engineer's instructions; for the following work items: a. 10 mm bars steel reinforcement, holes diameter 14mm at 20cm depth. the quantity of "Lokfix" shall be at 19.6ml)/bar) b. 12 mm bars steel reinforcement, holes diameter 16mm and 30cm depth. (the quantity of lokfix shall be at 45.8ml/bar) c. 16 mm bars steel reinforcement, drilling diameter 20mm and at 30cm depth( the quantity of lokfix 58.2ml/bar). 2.10 Supply, and fix deformed high yield steel bar reinforcement of various diameters, characteristic strength FY=420N/mm2 for concrete reinforcement. All as shown on drawings and according to specifications. No 80 Unit QTY Unit Rate Total

No

40

No

30

TON

140

2.11

Supply and cast B300 Concrete for lintels above the block walls.

M3

50

2.12

Supply and cast concrete B300 for the machine foundations as shown on drawing No A39. The unit rate shall also include all necessary materials such as cork and steel angels.

M3

15

Total of Concrete Works carried to civil summary

Civil

6/19

Jenin Hospital -BOQSection 3 Stone Works The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs and expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. The price includes scaffolding, formworks, supports, cutting, trimming, chamfering, galvanized anchors& pins, angles as specified and flush pointing works composed of cement and sand (1/2) with approve additive for better workability, tightness and water proofing. The stone finishing and dressing for the new stone works shall be similar to that rendered at the lower floors of the existing hospital building. The unite rate shall also include cost of all required stone pieces, (such as windows and doors jambs, sills, lintels, corners, key stones, any other special stone pieces etc..); all as per the stone works rendered in the lower floors of the existing hospital and to the engineer instructions. Accordingly, no separate cost allowance for the stone pieces. The unit rate shall also include the cost of pointing the stone work. 3.1 Supply and install 5 cm thick 30 cm wide Taltish or Mattabah stone courses from first quality Jama'een as shown on detailed drawings. M2 500 -BOQUnit QTY Unit Rate Total

3.2

Ditto, but 4 cm thick for stone cladding. The rate includes cost of B200 concrete backing, anchors and 6 mm steel mesh. The rate includes all anchoring details as shown on drawings. Supply and install 8-10 cm thick stone coping , 35-40 cm wide, for the roof parapet copping "Jama'en stone" . The price includes stone pointing. Re-install the stone coping which was dismantled and preserved from the existing parapet.

M2

1200

3.3

MR

50

3.4

MR

300

Total of Stone Works carried to civil summary

Civil

7/19

Jenin Hospital -BOQSection 4 -BOQBlock Work: The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. Supply and construct 10cm hollow concrete block in cement and sand mortar (1:4). The price includes cost of cutting, anchors, bonding, jointing, utilities openings complete as per drawings, specifications and as directed by the engineer. Ditto, but 20 cm hollow concrete block . Ditto, but 15 cm hollow concrete block . Supply and cast B300 concrete lintels or griddles and dummy columns above block works at door or window level across the whole length of block walls and in places as directed by the engineer. The price including shuttering and the supply & installation of steel reinforcement 4nos of 12mm dia. and with stirrups 8mm @ 20 cm c/c Supply and install 3 cm "Randopan" extruded polystyrene boards for external stone walls, of density 24 kg/m3 as shown on drawings. M2 3100 Unit QTY Unit Rate Total

4.1

4.2 4.3 4.4

M2 M2 M3

1000 450 50

4.5

M2

450

Total of Block Works Carried to Summary Sheet

Civil

8/19

Jenin Hospital -BOQSection 5 -BOQPlastering Works: The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. Unit QTY Unit Rate Total

5.1

Supply and install internal plastering for walls, columns, arches drop beams, softies of slabs & beams, shaft walls etc ,composed of 3 coats, a bond coat 1:1, base coat 1:4, and finish coat 1:5 as specified. The price includes the corner beads, casing beads, metal lath, scaffoldings, shuttering, bonding agents and the requirements as specified . Ditto, but supply and install internal plastering for ceiling Ditto but supply and install external plastering for parapet wall, external walls or shafts and wherever needed composed of 3 coats a bond coat 1:1, a base coat 1:4 and a finish coat 1:2 with water proofing materials all as specified.

M2

4250

5.2 5.3

M2 M2

930 400

Total of Plastering Works carried to Summary

Civil

9/19

Jenin Hospital -BOQSection 6 -BOQFlooring and Covering Works: The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. Supply and install 30x30x3cm Terrazzo floor tiles similar to Halonim # 75 or equally approved. Rate includes 30cm x 10cm x 1 cm skirting, 3 cm cement sand mortar (1:3 ), sand fill materials , cuttings, fittings, trims, grouting with cement and polishing, all in accordance with the specifications and applicable Standards. Supply and install 20x20cm glazed ceramic class (A) tiles of different colors, as per UNDEFA, ROCA make-Spain or equal, for walls cladding . The tiles shall be laid and fixed to the walls in patterns, style and forms of grouting& jointing as directed by engineer using approved adhesive materials. The price also includes the cost of surface preparation to receive tiles, which shall include two coats of cement plaster (scratch and float coat), approved adhesive materials, grouting, aluminum protection angles as approved by the engineer. Ditto, but 30x60cm ceramic tiles class (A) for walls cladding, as per HDC, GAYA make-Spain or equal. The tiles shall be laid and fixed to the walls in patterns, style and forms of grouting& jointing as directed by the engineer using approved adhesive materials. Price includes the cost of surface preparation to receive tiles, which shall include two coats of cement plaster (scratch and float coat), approved adhesive materials, grouting, protection angles as approved by the engineer. Ditto, but anti bacteria ceramic 20x20cm class (A) closured wall tiles for surgery& sterile stores using special adhesive materials and anti fungus grouting materials as per manufacturer instructions and in accordance with the MOH requirements and related Standards. ditto, but for floor 7mm thick. Supply and install non slip ceramic floor tiles class (A) 20x20*0.8cm of different colors, as per UNDEFA, ROCASpain or equal. The price includes the mortar (1:3) with water proofing materials, the sand white cement fill material, cutting& trimming around floor utilities and pointing as specified. the tiles shall be laid and fixed in patterns, style and forms of grouting& jointing as directed by the Engineer. Ditto, but 30*30*0.8 cm granite porcelain floor tiles of different colors as made by TAU, VENATTO ceramic, Matt finish or equivalent, the tiles shall be laid and fixed in patterns, style and forms of grouting& jointing as directed by the Engineer. M2 2000 Unit QTY Unit Rate Total

6.1

6.3

M2

1000

6.4

M2

1200

6.5

M2

900

6.6 6.7

M2 M2

400 250

6.8

M2

500

Civil

10/19

Jenin Hospital -BOQSection 6.9 -BOQSupply and fill special filling material made of "sand and Etong gravel" for the areas of deep fill under the floor tiling( in the first floor). All as directed by the engineer and according to the drawings. Supply and install 2cm thick "Perlato" marble for cladding the elevator walls. The rate include cuttings, recesses for utilities, cut pieces, rounding, jointing& polishing, anchoring& all fixing accessories. Supply and install 3cm thick local marble, and the width according to door frame width, local polished cut stone for window thresholds with mitered edge as shown on drawings. Supply and install anti static PVC flooring type "Teraclean", 2mm thick or equivalent for surgery room and for sterile stores. The price includes the installation of skirting and copper mesh under tiles every 30cm using 1cm wide copper strip. This mesh should be connected with the earth system of the building. The pvc flooring should be fixed using conductive adhesive and complete seal of joints all in accordance to manufacturer instructions and MOH regulations standards. The Installations for pvc flooring, skirting, terminations with walls/outer& inner corners shall be strictly implemented by professional and in accordance to the manufacturer's recommendation. Ditto, for sterile area but without copper strips. Supply and install VINYL Anti static flooring type Armstrong 2mm thick or equivalent for surgery rooms, sterile stores and as directed. The price includes the installation of skirting and copper mesh under tiles every 30cm using 1cm wide copper strip . This mesh should be connected with the earth system of the building. The pvc flooring should be fixed using conductive adhesive and complete seal of joints all in accordance to manufacturer instructions and MOH standards. Ditto, for sterile area but with out copper strips. Unit M3 QTY 50 Unit Rate Total

6.10

M2

10

6.11

M2

20

6.12

M2

250

6.12 6.13

M2 M2

20 50

6.14

M2

20

Total of wall and floor cladding Works carried to Summary Sheet

Civil

11/19

Jenin Hospital -BOQSection 7 -BOQWater Proofing The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. Supply and install water proofing membrane 5mm thick covered with quartz granules, Pazkar or equivalent, for main roof, machines roofs, stairs roofs, parapet walls and where required the price includes the application of primer coat GS474 at a rate of 25 kg /m2, installation of 15*15cm angle fillet, grooves, groove sealant, groove cover, joints over lapping, backing sheets or pieces all around external& internal corners, roof drains, machines foundations or up stands, roof door thresholds and silver paints along the joints and all necessary material and workmanship to complete the works as shown in the drawings and as per manufacturer instructions and the specifications. Supply and apply three coats of bitumen (25/75) at rate of 500g/m2 for each layer with two layers of fiberglass including primer coat GS474. The price includes 5*5cm angle fillet with smooth sand cement mortar(1:3) and 5cm thick sand cement screed with water proofing agent (surface preparation layer before applying the water proofing coats). Supply & install aluminum metal sheet flashing to cover the vertical and horizontal expansion joints including polystyrene filler, sealant , rubber packing rod, fixing with galvanized screws every 30cm and all accessories. M2 1900 Unit QTY Unit Rate Total

7.1

7.2

M2

150

7.3

M.R

200

7.4

Supply and cast light weight foam concrete of density 1000kg/m3 for forming the roof slopes. The unit rate shall include cost of applying 2 cm cement screed layer above the light weight concrete. Supply and apply two coats of water-proofing coats, similar to "Bonzal" or equally approved, on the concrete surfaces of the stone work backing (or on concrete walls behind stone cladding). The unite rate shall include preparing the concrete surface to receive required water proofing coats.

M2

1300

7.5

M2

1400

Total of Water Proofing carried to summary Sheet

Civil

12/19

Jenin Hospital -BOQSection 8 Carpentry Works


The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract.

-BOQ-

Unit

QTY

Unit Rate

Total

8.1

Fabricate, supply and install the following wooden doors complete with the metal frames, all necessary fixing accessories, glazing, heavy duty roller hinges, stoppers, louvers, grills, the required hydraulic closures, hardware, protection panels and ironmongery , painting of the frame and the exposed wooden surfaces of the door panels, the unit rate shall also include all the works described herein below: The wooden door leaf shall be 45mm thick with required filling, and glasses, class A plywood facing on each side, the hard wood "Zan" 52*35 mm for the exposed surfaces tongued and grooved in the internal wooden fillings, sealing strips around door panel, and door closure German made where shown and required on the drawings, all as shown on the drawings.

Supply and install of heavy duty hinges, locks, cylinders are "Yardini" or equivalent. locks to toilets-vacant/ occupied "Yardini " type 7008 all doors shall be provided with master key system. The hierarchy shall be specified before the supply of lock sets. Door handles shall be steel handles similar to Hewi type zg1113bb and type fbg 1113 or equivalent. The color to be selected by the Engineer. Supply and installation of formed galvanized steel frame 1.5mm thick of required width according to the wall thickness, buckets for cylinders& locks, recess for hinges with backing plates , rubber knobs, side anchoring& bottom bracing and concrete filling as specified in drawings. The frames shall be fabricated and assembled by specialized manufacturer with all required accessories. Door protection 1.5 mm thick stainless steel U shape for the both sides as shown on drawings. Doors protections (where needed as per drawings of 2mm "Deco sheet" SPM or equivalent) including all necessary fittings & fixings complete as per manufacture recommendations, the color will be as per Eng. approval. Supply and installation of PVC inflammable 'Taraflex' or equivalent 2mm thick cladding on both sides of the door panels. All exposed edges , louvers and door frames are" Zan" wood and should be painted with 3 coats of liquor paint. the metal doors frames shall be painted with primer coat of meginol special gray 270-004 and two coats of polyour matt oil. the color shall be selected by the engineer. Door filling material should not be less than 80%. Rate for smoke proof doors include 100% filling , sealing strips around door panel including the bottom of panel. All as per the Standard.

* *

* *

8.1.1 8.1.2 8.1.3 8.1.4

D01 ( 1.20 * 2.10 m) D02 ( 1.00 * 2.10 m) D03 ( 0.85 * 2.10 m) D04 ( 0.85 * 2.10 m)

No. No. No. No.

31 11 30 9

Civil

13/19

Jenin Hospital -BOQSection 8.1.5 D05 ( 0.85 * 2.10 m) -BOQUnit No. QTY 17 Unit Rate Total

8.1.6 8.1.7 8.1.8 8.1.9 8.1.10 8.1.11 8.1.12 8.1.13 8.2.12 8.2

D06 ( 0.80 * 2.10 m) D07 ( 0.85 * 2.10 m) D09 ( 1.80 * 2.10 m) D10 ( 2.40 * 2.75 m) operate electrically with door closure. Ditto, but D10 ( 2.05 * 2.75 m) Ditto, but ( 2.20 * 2.75 m) Ditto, but ( 2.15 * 2.75 m) Ditto, but ( 2.30 * 2.75 m) Wooden door as per drawing plan No A19 for the electrical room. Nurse station ,and kitchen desks and cabinets Fabricate, supply and install the following units, as per drawings with all fixing accessories, drawers, shelves, hardware, and ironmongery with a master key and made of: 18mm or 30mm thick plywood for wall hung and lower cabinets, plastic laminated " top quality from outside and laminated with regular Formica from inside, 12mm thick sandwich panel for shelves laminated with regular Formica. For dimensions refer to detailed drawings.

No. No. No. No. No. No. No. No. No.

4 7 6 6 2 2 1 1 1

8.2.1.a

Room No. 166&251 kitchen lower and upper cabinets including granite counter top "Local marble" with top& bottom skirting, beads, polishing, rounding, jointingetc and all preparatory woks for the installation of the required sink and sanitary fixtures.. Ditto, but for Room No.207 Ditto, but for Room No.146 Ditto, but for Room No.246 Ditto, but for Nurse Station As shown in Drawing A20,A21,A22 Information's Desk Room No. 110 Nurse station Room No. 139 Nurse station Room No. 210 Nurse station Room No. 244 Nurse station Room No. 155 Nurse station Room No. 154 Nurse station Room No. 216 Electrical cabinets of different sizes.

No.

8.2.1.b 8.2.1.c 8.2.1.d 8.2.2 8.2.2.a 8.2.2.b 8.2.2.c 8.2.2.d 8.2.2.e 8.2.2.f 8.2.2.g 8.2.2.h

No. No. No.

1 1 1

No. No. No. No. No. No. No. No.

1 1 1 1 1 1 1 16

Total of Carpentry Works Carried to Summary Sheet

Civil

14/19

Jenin Hospital -BOQSection 9 -BOQSuspended ceiling The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. Rates for all suspended ceilings works includes suspension system with anchors to the structure, L& Z, main& main profiles, omega profiles. clips, gaskets and all necessary fittings in accordance to the manufacture technical data and related standards covering this type of works, The rate includes also cutting and preparation for installing lighting fixtures, ceiling recess, maintenance openings, grills, ceiling utilities... etc. Supply and install suspended ceiling for bathroom, utilities and wet areas made from 30cm non perforated formed galvanized metal trays of 0.6mm thick and 45mm high. The trays should be supplied pre painted and oven cured. The unit rate shall also include acoustic rock wool mats, 25mm thick and 25kg/m3 density, wrapped in black non inflammable dust proof sags in accordance with specifications and the related Standards. Ditto, but perforated sheets(12%-20%) perforation and of 40cm wide. The unit rate shall include cost of the of 25mm thick rock wool. Supply and install 60*60cm suspended ceiling for operating room, ECOPHONE HYGIENE Type Protect "A" (non perforated). The price should include galvanized suspension system with anchors to the structure, bacterial resistant, moisture resistant, with standing relative humidity up to 95% at 30c fire resistant tiles, including access panels, fittings, fixing, installation of a closed cell gasket between the grid and panel including retention clips to insure good seal , complete all as specifications and drawings. Ditto, but for clean room areas type "Clima Plus USG" class 100 ceilings or equivalent. Ditto, but 60x60cm acoustic tiles suspended ceiling, type Armstrong Georgian drop type or equivalent. Supply and install vertical and horizontal gypsum boards 12mm thick for walls and ceiling cladding and for other decorative works. The price shall include all decorative beams, edges, recessed slab, squares, cuts, suspension& structural profiles-- etc to any shape and patterns to complete the works as approved by the engineer. Supply and install 60x60cm fiber glass ceiling tiles, coated with pvc type F4 in the drawing, acoustic tiles suspended ceiling, Armstrong or equitant. The unit rate shall include galvanized suspension system with anchors including access panels, fixing, fittings and all accessories complete Total of Suspended Ceiling Works carried to Summary Sheet M2 160 Unit QTY Unit Rate Total

9.1

9.2

M2

700

9.3

M2

200

9.4 9.5 9.6

M2 M2 M2

170 925 60

9.7

M2

220

Civil

15/19

Jenin Hospital -BOQSection 10 -BOQPainting Works: The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. Type of paint shall be in accordance with the specification and the applicable Standards. The contractor should allow in his pricing that the engineer will use as many different colors or combination of colors to meet an approved color scheme. All paint works should conform to manufacturer instruction regarding number of coats , rate of application or drying time 10.1 10.2 Supply and apply cement sand filling layer to the ceiling and walls above false ceiling level. (provisional) Supply and apply emulsion paint on plastered walls composed of two coats of putty and 3 coats of " supercryel " emulsion paint. Supply and apply polysid paint. Supply and apply oil paint for walls composed of two coats of putty, one coat of under coat and 2 coats of " polyour". M2 M2 3780 200 Unit QTY Unit Rate Total

10.3 10.4

M2 M2

780 3800

Total of Painting Works carried to Summary Sheet

Civil

16/19

Jenin Hospital -BOQSection 11 -BOQMetal Works: The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. Aluminum Works Fabricate supply and install the following powder coated aluminum doors & windows made of "Napco 4500" profiles, or equivalent, for the side hung casement or bottom hung windows. Napco profile 7700 for sliding windows three rails Napco or equivalent, Napco profile 2200 complete with double glazing 4:9:4 mm, silicone, handles, locks and oplite fly screen. Shop drawings must be submitted. All as shown in drawings and approved by the Engineer . Aluminum windows W1, 7700 of overall dimensions 130x165cm, the lower part is fixed and the upper part sliding as shown on drawings. Aluminum windows W1', 7700 of overall dimensions 130x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W2, 7700 of overall dimensions 110x165cm, the lower part is fixed and the upper part is sliding as shown on drawings. Aluminum windows W2', 7700 of overall dimensions 110x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W3, 4500 of overall dimensions 80x105cm, as shown on drawing plan Aluminum windows W4, 4500 of overall dimensions 60x105cm, as shown on drawing plan Aluminum windows W5, 7700 of overall dimensions 130x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W6, 7700 of overall dimensions 120x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W7, 7700 of overall dimensions 130x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W8, 7700 of overall dimensions 105x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W9, 7700 of overall dimensions 140x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W10, 7700 of overall dimensions 100x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W11, 2200 of overall dimensions 345x195cm&0.551.95cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Unit QTY Unit Rate Total

11.1

11.1.1

No.

67

11.1.2

No.

11.1.3

No.

15

11.1.4

No.

11.1.5 11.1.6 11.1.7

No. No. No.

5 2 2

11.1.8

No.

11.1.9

No.

11.1.10

No.

11.1.11

No.

11.1.12

No.

11.1.13

No.

Civil

17/19

Jenin Hospital -BOQSection 11.1.14 -BOQAluminum windows W12, 7700 of overall dimensions 110x165cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Aluminum windows W13, 7700 of overall dimensions 200x165cm, the lower is fixed and the middle part is sliding as shown on drawings. Aluminum windows W14, 7700 of overall dimensions 225x195cm, the lower and upper parts are fixed and the middle part is sliding as shown on drawings. Wooden glass windows for the Incubators, the price shall include 6mm glass, the Ironmongery and carpentry works as per drawings. Detail C2 as per plan No A32 Ditto, but for blood bank Detail C1, as per plan No A31 Steel Works Supply and install the following steel doors and frames, as per details. The price should include the following : Galvanized steel, galvanized sheet cover , braces, frame, insert, rubber, hinge, fire cylinder type SN2000, and rock wool. The price includes painting two coats of antirust paint and powder coating paints. MD1 ( 1.00 * 2.10 m) As shown in drawing No A25 Steel structure for escape staircase: Supply, fabricate and install a complete steel structure for the emergency staircase, as per drawings A29 and A30. The contractor shall submit shop drawings to for the engineer's approval before fabrication the structure. The unit rate shall cover all associated costs to install a safe steel structure, including the steel plates and anchors, 3mm chequered plates for steps and landings, steel columns 10*10*4 mm( No.1), steel profiles H1050.5 cm for landings and flights (No.2), solid rectangular bars 1.41.4 cm@11cm for handrail (No.3), 2.55 cm rectangular steel section for handrail(No.4), steel section 52.5 cm(No.5), and all required material and workmanship to install the complete structure in accordance with the drawings and the Engineer approvals.The unit rate shall also include cost of painting the steel structure with three coats of oil paint, complete. No. 4 Unit No. QTY 2 Unit Rate Total

11.1.15

No.

11.1.16

No.

11.1.17

No.

11.1.18 11.2

No.

11.2.1 11.4

LS

Total of Metal works carried to summary sheet

Civil

18/19

Jenin Hospital -BOQSection 12 Other Works The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the costs or expenses of all requirements stipulated in the preambles, drawings and technical specification of the contract. -BOQUnit QTY Unit Rate Total

12.1

Supply and install Avis curtain rail, complete with all fixing accessories, Aluminum carrier main profile and locks.

Mr.

450

12.2

corner protection similar to type "SPM" or equally approved "5cm5cm and height 2.00 m as detail plan No A25 wooden wall guards to wall protections at the beds level cut to size according to the site requirements as made by (SPM ) or equivalent, including all necessary fittings & fixings complete as per manufacture recommendations, the color will be as per Eng. approval, as detail plan No A25. Supply and install a wooden wall guards for corridors with all fixing accessories as per the detailed drawings and engineer instructions. color to be selected by the Engineer, as detail plan No A25.

No.

235

12.3

M2

34

12.4

Mr.

504

Total of Other Works carried to Summary Sheet Civil 19/19

Jenin Hospital Electrical BOQ Electrical Works DESCRIPTION UNIT Important Notes: All materials and accessories to be used shall be according to the Approved Manufacturer List attached to the tender Documents. Preamble *-This Section shall be read in conjunction with general and particular electrical technical specifications, the Electrical Drawings, Addendums and invitation to bid conditions except where otherwise indicated. *-The unit price for all items in this Section shall include for Supplying, installation, connecting, testing, and commissioning of electrical works and materials, unless otherwise specifically mentioned or instructed by Engineer. *-All Civil and Finishing Works related to the concerned item shall be included in the unit price. *-Preparing of (coordinated )shop drawings and submitting to Engineer for approval, coordination with other activities, material storage, removing away from site the remnant of electrical works and handling over the electrical works to local electrical distribution authority. is contractor responsibility. *-light points/power point considered to include single core (S.C.) cables, conduits, (from related DB) boxes and variant types of control switches and socket outlets. *-All embedded and surface mounted PVC conduits to be flexible type of min. 20mm dia. *-All parts of PVC conduits above false ceiling (conduit & boxes) to be of fire retardant types. *-Separate conduit colors to be used to enable systems recognition *- Electrical cables up to mechanical equipment, to be supplied, installed connecting to mains, testing and to be commissioned by electrical contractor, cables termination to mechanical equipment to be carried on by mechanical contractor. Sec. 13.1) - Electrical Points. The electrical power supply from electrical switchboard to first point in circuit shall be included in the unit price of that point (by means of wires, cables or leads in self extinguishing conduits and cables). All as per specifications and as required. Supply, install and connect standard lighting point internal or external, in slab or over false ceiling, to include a 19 mm diameter conduit, 1.5 or 2.5 sq.mm cross-section leads or cable, and, as required single , double, two way or push button lighting switch , and outlet for luminaries with junction box and terminals. Ditto but for emergency lighting point

ITEM

Qty

U/Price

Amount

13.1.1

Comp.

400

13.1.2 13.1.3

Comp.

120 150

Comp. Supply, install and connect a 16A wall socket point - to include a 19 mm dia. Conduit, (3x2.5) sq.mm cross-section leads or cables, and as required 16 A wall socket .(for regular power or UPS sockets) Ditto as item 13.1.3 but double socket. Ditto as item 13.1.3 but with water proof socket. Ditto as item 13.1.4 but with water proof cover. Supply, install and connect a three-phase (5x16) A, single-circuit wall socket point, to include a 23 mm diameter conduit, (5x2.5) sq.mm cross section leads or cables and a (5x16) single-circuit wall socket accessory . Electrical Comp. Comp. Comp. Comp.

13.1.4 13.1.5 13.1.6 13.1.7

40 60 20 5

1/11

Jenin Hospital Electrical BOQ ITEM 13.1.8 DESCRIPTION Supply, install and connect Intercom connection point (Price includes 19 mm diameter conduit with a standard Intercom cable, leading from point to the Intercom section in LV box). Supply, install and connect Public Address System connection point (Price includes 19 mm diameter conduit with cable, leading from point to the LV box or to the nearest point). Supply, install and connect Fire Alarm connection point (Price includes 19 mm diameter conduit with cable, leading from point to the LV box or to the nearest point). Supply, install and connect TV connection point (Price includes 23 mm diameter conduit with cable, boxes , and the socket outlet leading from point to the LV box). Supply, install and connect SAT connection point (Price includes 23 mm diameter conduit with cable, boxes , and the socket outlet leading from point to the LV box). Supply, install and connect Nurse Call connection point (Price includes 19 mm diameter conduit with cable, leading from point to the nurse call station). Supply, install, connect, test and commission complete data point including boxes, 23mm dia. conduits, RJ-45 (3M) socket outlet with 8 pins being crimped and also earth pin for (Cat 6A) FTP (4x2x23) data cables as per drawings, specification and related codes. UNIT Qty U/Price Comp. 36 Amount

13.1.9

Comp.

35

13.1.10

Comp.

105

13.1.11

Comp.

19

13.1.12

Comp.

19

13.1.13

Comp.

125

13.1.14

Comp.

40

13.1.15 Supply, install and connect Telephone socket point in a 23 mm conduit Comp. - to include a 23 mm diameter conduit from nearest telephone cabinet to accessory output in junction box, standard socket telephone accessory, and standard 2x2x.5mm2- telephone lead, inserted from cabinet to accessory including connection at both ends. 13.1.16 Supply, install and connect point for thermostat to include a 19 mm diameter conduit installed on one side near socket for fan coils and termination with a suitable box on other side at thermostat output. 3 mm thick Nylon draw-string shall be inserted inside conduit. 13.1.17 Supply, install and connect Emergency push-button point, to include a 19 mm diameter conduit, (3x1.5) sq.mm cross-section leads, and a dual contact emergency push-button installed in a box with frame, transparent plastic cover to be broken in case of emergency, and engraved bakelite "sandwich" type sign, per plan (box such as TELEMENIA model ZAS-E25). 13.1.18 Supply, install and connect power point for bed head units, the price to include BHU junction box , 3x2.5mm2 NYY cable and 23mm dia conduit from electrical switchboard to BHU junction box with all required accessories and materials. 13.1.19 Supply, install and connect Point as above, but by a 3x1.5 sq.mm NYY cable and16mm dia conduit. 13.1.20 Supply, install and connect Point as above, but by a 6 sq.mm crosssection grounding lead and 23 mm diameter conduit. 13.1.21 Supply, install and connect Point as above, but for communication, by a 23 mm conduit diameter conduit. 13.1.22 Supply, install and connect Point as above, but for telephone in B.H.U, by a 23 mm conduit and standard 2x2x.5mm2- telephone lead. 13.1.23 Supply, install and connect Point as above, but for data, by a 23 mm conduit and standard CAT 6 lead. 13.1.24 Supply, install and connect lighting point for the suspended lighting fixtures in the delivery rooms, the price shall include 19 mm dia. conduit and 3*2.5 sq.mm cable or lead. Comp.

50

40

Comp.

No.

260

No. No. No. No.

115 115 115 115

No. No.

115 10

Electrical

2/11

Jenin Hospital Electrical BOQ ITEM DESCRIPTION 13.1.25 Supply, install and connect Point as above, but by a 4 sq.mm crosssection grounding lead and 23 mm diameter conduit for the operating theater lighting fixtures. (Provisional Items) for any required works not included in the mechanical works items 13.1.26 Supply, install and connect a 16A Power Point including 16A (1PH) isolator switch, conduits, boxes and cables for the fan coil units , the works all according to drawings, specifications and Engineer instructions. 13.1.27 Ditto as item 13.1.26 but for the Exhaust fans on the roof. 13.1.28 Ditto as item 13.1.26 but for Booster Pumps. 13.1.29 Ditto as item 13.1.26 but 16A ( 3PH) for Booster Pumps. UNIT No. Qty 2 U/Price Amount

No.

40

No. No. No.

10 10 4

No. 13.1.30 Supply, install and connect a 25A Power Point including 25A (3PH) isolator switch, conduits, boxes, cables for the Package Unit, the works according to drawings, specifications and Engineer instructions.

Total Sec. 13.1)- Points.carried to summary. Electrical 3/11

Jenin Hospital Electrical BOQ ITEM DESCRIPTION UNIT 13.2 - Conduit, Rigid Piping and Excavation Works Supply, install and connect Self-extinguishing type plastic conduit, processed over or under plaster or inside castings, including junction boxes, unions, connectors, etc. including excavation , backfilling , sand , tape , manholes and covers and galvanized draw-strings, ready for use (for works not included in points works). 23 mm diameter. 29 mm diameter. 36 mm diameter. 50 mm diameter. 4" diameter. 6" diameter. ML ML ML ML ML ML Qty U/Price Amount

13.2.1 13.2.2 13.2.3 13.2.4 13.2.5 13.2.6

50 50 50 50 50 50

13.3.1 13.3.2 13.3.3 13.3.4 13.3.5 13.3.6 13.3.7 13.3.8 13.3.9

Total sec. 13.2) - Conduit, Rigid Piping and Excv..carried to summary Sec. 13.3) - Cables Supply, install and connect XLPE non-armored type thermoplastic copper cables, including insertion into conduit or attachment to structural elements or laying in ductwork, including all associated materials, insulation materials, unions, and connection of cable at both ends. 3x240+120sq. mm+120sq.mm Cu. M.L. 3x185+90mm2+90mm2 cable 3x150+95mm2+95mm2 cable 3x95+50mm2+50mm2 cable 3x70+35mm2+35mm2 cable 3x50+25mm2+25mm2 cable 5x16 sq.mm cross section. 5x10 sq.mm cross section. 5x6 sq.mm cross section. M.L. M.L. M.L. M.L. M.L. M.L. M.L. M.L. M.L. M.L. M.L.

35 30 80 110 50 50 50 210 100 100 50 50

13.3.10 5x4 sq.mm cross section. 13.3.11 3x2.5 sq.mm cross section. 13.3.12 3x1.5 sq.mm cross section.

Total Sec. 13.3) - Cables carried to summary Electrical 4/11

Jenin Hospital Electrical BOQ ITEM DESCRIPTION UNIT Sec. 13.4) - Structural Elements, Cabinets and Ductwork Supply and laying of the following horizontal/vertical heavy duty cable tray/cable ladder systems according to BS EN 61537 and NEMA VE 22000 made of heavy gauge hot deep galvanized (after fabrication) perforated sheet steel with original angles, elbows and T pieces and ready made suspension to ceiling/wall or shaft wall system including fixing and suspension accessories in approved manner as per drawings, specifications and related cods as following: 40/6 cm. 30/6 cm. 40 cm. ladder M.L. M.L. M.L. Qty U/Price Amount

13.4.1 13.4.2 13.4.3

150 50 10

Total 13.4) Structural Elements, Cabinets.. carried to summary Sec .13.5 ) Grounding Systems Sec. 13.5.1) - Lightning System Supply, install, connect, test and commission lightning protection system including air terminal, pulsar, 30/2mm copper tape, testing point in CI box and 125/5mm Cu strip ready to connect 3rods with all accessories, surge arrestor for MDB, surge arrestor for Patch Panels and earth rods with pits and covers as per specification, and related code. Sec. 13.5.2) - Operational Theaters Grounding Supply, install, connect, testing and commissioning of the following operation theater stand alone earthing system including copper mesh under antistatic tiles, 25mm2 cable up to earth rod, earth rods, earth pit, soldering and all necessary accessories, as per drawings, specifications and related codes. Sec. 13.5.3) - Building Grounding (Provisional Item) Supply, install, connect and test the earthing system including cables , rods , pits ,checking boxes ,main earthing box with equipotential bus bars ,and connecting to the existing foundation earthing ready for operation according to specifications, drawings and engineers instructions . Sec.13.5.4) Grounding for metal works Supply, install, connect, test and commission earthing for all mechanical, electrical and false ceiling metal structure works as per specification, and local electrical utility requirements.

13.5.1

L.S

13.5.2

L.S

13.5.3

L.S

13.5.4

L.S

Total 13.5)Grounding Systems.. carried to summary Electrical 5/11

Jenin Hospital Electrical BOQ ITEM a. DESCRIPTION UNIT Sec. 13.6) - Electrical Switchboards Supply, install and connect the electrical switchboards to the site, including all associated materials and labor, as described in the technical specifications. Cabinets with no access from the rear, made up of transparent polycarbonate cells, or sheet-metal cabinets with a 25% surplus space. The switchboards are to be placed on the floor, in a niche against the wall. Main supply lines enter from the switchboard bottom, top or side, while outgoing lines exit the switchboard from both its bottom and top sides. Price to include all structural elements required in order to install the switchboard, including bus-bars, terminals, wiring, bolts, clamps, etc. and for the equipment listed below. The switchboards shall contain accessories shall be according to the approved manufacturer list. Prices for supply, installation and connection of various accessories including all associated labor and materials such as bus-bars, terminals, wiring reinforcements, mounts, engraved "sandwich" type identification plates, etc. including connection to mains supply complete ready for use. The price shall include connection of the distribution board to the existing MDB. SMSB-F SMSB-S DB-F1 DB-F2 DB-F3 DB-F4 DB-F5 DB-F6 DB-LAB1 Qty U/Price Amount

b.

c. d.

e.

f. g.

h. 13.6.1 13.6.2 13.6.3 13.6.4 13.6.5 13.6.6 13.6.7 13.6.8 13.6.9

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

13.6.10 DB-LAB2 13.6.11 DB-S1 13.6.12 DB-S2 13.6.13 DB-S3 13.6.14 DB-S4 13.6.15 DB-S5 13.6.16 MDB-UF 13.6.17 MDB-US 13.6.18 DB-OP

Electrical

6/11

Jenin Hospital Electrical BOQ ITEM DESCRIPTION 13.6.19 DB-M 13.6.20 DB-I 13.6.21 DB-Lift 13.6.22 MCC for ch. Pumps UNIT Unit Unit Unit Unit Qty 1 1 1 2 U/Price Amount

Additional MCCB,s (Provisional) 13.6.22 Supply, install, connect, testing and commissioning of the following Moulded Case Circuit Breakers (MCCB) in existing MDB, the breakers to be equipped with thermo magnetic protection (TM-D) with short circuit rupturing capacity not less than 35KA to achieve cascading, this shall include all necessary accessories. a. b. 400A TP MCCB Adj 400-630A 320A TP MCCB Adj 300-400A Unit Unit 1 1

Total sec. 13.6) Electrical Switchboards..carried to summary.

Electrical

7/11

Jenin Hospital Electrical BOQ ITEM a. DESCRIPTION UNIT Sec. 13.7- Luminaries Supply and Installation Supply, install, connect, test and commission complete lighting fixture, including all supports, lamps , approved connections, suspension system, clamps, Magnetic Control Gears, electronic starters and Electronic Ballast as per below description, fire retardant internal conductors and/or cables, and all other accessories necessary as per drawings, specifications and related standards. All lamps shall be of the energy-saving type (18,36, 58 Watts). Type A.4X18W recessed fluorescent with HF. electronic ballast control gear, body made of enameled sheet steel with double parabolic satib brite aluminum louver Type B.2X36W recessed fluorescent with HF. electronic Ballast Control gear, body made of enameled sheet steel with OPAL diffuser Qty U/Price Amount

b. 13.7.1

Unit

130

13.7.2

Unit

60

13.7.3

Type C.2X36W surface mounted fluorescent with HF. electronic ballast control gear, body made of enameled sheet steel with OPAL diffuser TypeD: 2X18W PL/ 860 R & CT circular. Ceiling mounted IP54 with class (A3) electronic Control Gears . Type E. Ditto but wall mounted.

Unit

110

13.7.4

Unit

55

13.7.5 13.7.6

Unit

20 20

Type I.4x24W T16 Recessed 60x60cm module with sheet steel body Unit white coated to resist oil, vapor, chemical substances disinfectant and cleaning agents, and double parabolic satin brite louver with glare limitation with painted anodized aluminum frame and 4mm safety glass suitable for clean rooms IP65 and HF. Control gear with self regulating breather. Type J 4x18W recessed lighting fixture with prismatic diffuser and white painted sheet steel body IP65 Unit

13.7.7

13.7.8

Type EX 1x8W recessed 3 Hrs duration Exit sign complete with Ni cad Unit batteries and Legend single or double sided

10

13.7.9

Supply, install, connect and commission of complete self contained, Unit non-maintained Emergency Lighting Kit as per list of approved manufacturers. The kit shall provide 3 hours operation after mains failure for 1x18/1*36 watt lamps with nickel cadmium battery replaced within fitting container. internal wiring to be of fire retardant type as per specifications, drawings and related standards.

80

Total sec. 13.7 )Luminaries Supplycarried to summary Electrical 8/11

Jenin Hospital Electrical BOQ ITEM DESCRIPTION Sec 13.8- Nurse Calling System Note: All equipment items for the nurse- calling system shall be according to the approved manufacturer list.. The work to include the supply of the equipment specified, installation of same, connection, wiring, commissioning and all other details, as specified in the technical specification and drawings. Master station 30- call master type . Master station 20- call master type. Master station 30- call master type. Reset button . Bedside call switch. Metal jack for Bed side call switch. Corridor lamp. Call button Ceiling mount 180mm O(7-1/8"O) UNIT Qty U/Price Amount

13.8.1 13.8.2 13.8.3 13.8.4 13.8.5 13.8.6 13.8.7 13.8.8 13.8.9

Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit Unit

1 2 3 30 130 130 34 2 30 30 8

13.8.10 Moisture resistant pull cord switch . 13.8.11 Power supply . Total Sec.13.8) Nurse Calling System Carried to Summary Sec 13.9-Fire Alarm System Supply install and connect complete in place and in an operable manner the fire alarm system . The work is to include the supply of the equipment specified, installation of same connection, wiring, cables, commissioning and all of the details and connecting to the existing system as specified in the technical specifications and drawing type shall be according to the approved manufacturer list. this include adding one loop operating and control module to enable controlling extension fire alarm sensors. 13.9.1 (Provisional Item) Main addressable fire alarm control panel for 500 addressable points, expandable up to 1000 points with batteries and charger such as QS4 or equivalent approved Manually operated alarm call point . Indoor fire alarm siren . Ionization smoke detector. Intelligent heat detector. (Provisional Item) Automatic telephone dialer such as DL-125C 24v DC Magnetic Door Holder for fire doors

Unit

13.9.2 13.9.3 13.9.4 13.9.5 13.9.6 13.9.7

Unit Unit Unit Unit Unit Unit

8 6 100 5 1 3

Total Sec. 13.9) Fire Alarm System Carried to Summary Electrical 9/11

Jenin Hospital Electrical BOQ DESCRIPTION UNIT Sec 13.10 - Intercom System Note: All equipment items for the intercom system shall be according to the approved manufacturer list.. Work is to include the supply of the equipment specified installation of same, connection, wiring, commissioning and all other details, as specified in the technical specifications and drawings. 13.10.1 Hands free master station . Unit 13.10.2 Power supply adaptor . 13.10.3 Door phone adaptor . 13.10.4 Door station . 13.10.5 Power supply adaptor . 13.10.6 Door release . 13.10.7 AC transformer for door release . 13.10.8 Digital keypad 13.10.9 12V AC power supply transformer Unit Unit Unit Unit Unit Unit Unit Unit ITEM Qty U/Price Amount

6 6 6 6 6 6 6 6 6

Total of Sec 13.10) Intercom System carried to summary Sec 13.11- Public Address System Supply, install, test and commission a public address system, the system shall be according to the approved manufacturer list, including all required connections with the existing system of the Hospital including all required cables, boxes and conduits complete ready for work. 13.11.1 9/6 watt ceiling loudspeaker, 8 round with metal grille, screw mount. Unit

35

Total of Sec 13.11) Public Address System carried to summary Sec-13.12- Telephone System 13.12.1 Supply install and connect main telephone cables from the low voltage Job boxes in all the new floors to the main low voltage box in each proposed floor and from the main low voltage box to the telephone exchange of the Hospital. Rate to include 2 NO's. 36 pair cables, conduits, terminal blocks and all accessories as specified in the technical specification and drawings complete ready for work and covering all telephone sockets in the proposed building with all required materials. Total of Sec 13.12) Telephone System carried to summary Sec- 13.13- LV Boxes Supply install and connect the following LV boxes. Rate to include all required materials,condiuts,wires, cables and accessories manufacturing from galvanized sheet metal sheets , painted with the same color of the switch boards all as specified in the technical specification and drawings. 13.13.1 SMLVB Approximate dim.2 (80x60x25) cm No. 13.13.2 LVB Approximate dim.( 60x60x25) cm No. 1

2 8

Total of Sec-13.13) LV Boxes carried to summary Electrical 10/11

Jenin Hospital Electrical BOQ DESCRIPTION UNIT Sec- 13.14- UPS System 13.14. Supply install and connect uninterruptible power supply (U.P.S.) system, consisting of a charger/rectifier unit, a solid-state inverter unit, and a static bypass transfer switch, Power and control connecting cables between the U.P.S. system and the battery bank, including protective devices, all in accordance with the technical specifications .The UPS System back up time 15 min. (Complete and ready for work, including all required materials and connections) 13.14.1 40KVA No. 13.14.2 30KVA 13.14.3 15KVA Total of Sec-13.14) UPS System carried to summary 13.15 Patch Panels (PP) (Provisional Item) Supply, install, connect, test and commission the following Cat6 Patch Panels with switch and air PP in between complete with 10U cabinet, power distribution unit, patch cables, rack accessories and all accessories as per specifications and drawings. No. No. No. LS LS No. 1 1 3 1 1 2 No. No. ITEM Qty U/Price Amount

1 1 1

13.15.1 PP-F(10U) 13.15.2 PP-S (10U) 13.15.3 24 port patch panel 13.15.4 Patch cables 13.15.5 Backbone cable between P.Panels 13.15.6 Power strip

Total of Sec-13.15) Patch Panels (PP) carried to summary Electrical 11/11

Section-14: Mechanical Bill of Quantities Item Preamble a- The contractor shall, when pricing the rates of this bill, take into consideration to include and allow for the costs and expenses of all requirements stipulated herein below, drawings and the specifications of the tender. b- The contractor should visit the site to verify the amount of work and familiarize himself with the nature of work for proper construction of the new floors. c-The surplus & demolished materials shall be removed out from the site to a dump site approved by the municipality through a pre-coordinated manner to ensure minimal noise and dust pollution within the vicinity and to avoid obstruction for hospital activities. The contractor should coordinate with the client for any possible materials or elements that need to be preserved and handed over to the client stores. d- The contractor should also take all necessary shoring measures to protect the existing building elements during all stages of work until safely completing all new construction works. The contractor should submit a clear methodology for the proposed stages of work and protection and shoring methods for the Engineers approval prior to commencing the works. Careful demolishing and reinstatement of existing structural elements for proper construction of the new floor works; all as shown in the demolishing plan and in accordance with the Engineer's instructions. The contractor is requested to equally consider the following notes when quoting his prices: 1- The price shall include all required chipping in concrete walls, cutting holes (any diameter), excavation, backfilling and cement covering as specified. 2- The contractor must keep the existing HVAC system running throughout the construction period. Any interruption needed to complete the work should be coordinated with the hospital management 3-The Contractor is requested to read the bill of quantities in conjunction with the set specifications, drawings, addendums and contract conditions. 4- (S & I) implies supply and install, including testing, adjusting, balancing, .all the way to a successful operation, including the commissioning. Description Unit Quantity Rate Amount

Mechanical

1/27

Section-14: Mechanical Bill of Quantities Item Description Waste and drainage system: 14.1 S&I PVC pipes (UAP, Royal, or equally approved (E.A)) for air conditioning drainage network. Price includes all kinds of digging in concrete slabs and walls, supports, hangers and all rubber joints and sealants, syphones and connection to floor drain and flexible connections and all types of fittings. All done according to drawings, specifications and approval of the Engineer. 2" 11/2" 11/4" S&I UPVC similar to (Al-Hill-Egypt) or E.A for waste or stand pipes, running exposed along partitions, false ceiling, walls, shafts, under tiles or laid in walls. Price include all type of fittings, supports, hooks, connection to existing sewage and drainage system, stainless steel fasteners and all excavation and quarrying. Connections to be done according to specifications, drawings, and the approval of the Engineer. 6" pipe 4" pipe 3" pipe 2" pipe (S&I) 4" diameter Al-Hill UPVC (or EA) floor drain with 15x15cm square chrome plated cover (high quality), and multi inlet adjustable trap. The rate shall include excavation and backfilling for all connections with drain pipes and fixtures, all done according to drawings, specifications and approval of the Engineer. Ditto, but connection box 4"/2", all done according to drawings, specifications and approval of the Engineer. S&I heavy duty non adjustable 11x11 cm floor clean out with UPVC body, with gas and water tight ABS plug and frame, complete with all needed elbow and all types of fittings, all done according to drawings, specifications and the approval of the Engineer. Diverting of existing drain water risers and connecting to nearest existing sewage manhole including excavation, backfilling, with all needed elbows and all types of fittings, all to be done according to drawings, specifications and the approval of the Engineer. M.R M.R M.R M.R No 10 170 40 200 60 M.R M.R M.R 120 23 240 Unit Quantity Rate Amount

14.1.1 14.1.2 14.1.3 14.2

14.2.1 14.2.2 14.2.3 14.2.4 14.3

14.4 14.5

No No

10 30

14.6

LS

Total of Section-14: Waste and Drainage Systems carried to Summary sheet

Mechanical

2/27

Section-15: Mechanical Bill of Quantities Item 15 Roof drain system: All dismantled materials and parts of the existing systems on roof, which are not needed for future extension, should be turned in to the hospital authorized personnel. Similar materials and parts of the systems, which are to be used for the extended works, shall be kept at the contractor's disposal and custody. Description Unit Quantity Rate Amount

15.1

UPVC pipe S&I UPVC pipes and fittings as per Al-Hill-Egypt or E.A. The rate shall include all needed connections to existing rain water pipes and all types of fittings, all done according to drawings, specifications and the approval of the Engineer.

15.1.1 15.1.2 15.2

4" pipe 3" pipe Roof rain water drain S&I Polypropylene (PP) Roof rain water drain size 4" with cover of 20x20 plastic mesh (REDI make or E.A) to be connected to rain water vertical pipes with all required fittings, price shall include the piping works until the connection to the vertical rain pipe, all done according to drawings, specifications and the approval of the Engineer.

M.R M.R

80 15

No

17

15.3

Roof vent S&I REDI or E.A. 4" roof vent with screened cap for vent stacks including connection to the vent pipe by solvent welding. The rate include all needed connection accessories, all done according to drawings, specifications and the approval of the Engineer. No 12

Total of Section-15: Roof Drain System carried to Summary sheet

Mechanical

3/27

Section-16: Mechanical Bill of Quantities Item 16 16.1 Description Sanitary Fixtures and Accessories: Wash basin S&I Porcelain wall hung Semi pedestal wash basin for patient toilets type SAN-REMO Ideal Standard (IS) or E.A of size 600x490 mm model A7460. The rate shall include fixing galvanized screws, white color PVC syphone Lipsky or EA, and all the needed accessories to complete the job as per drawings, specifications and the approval of the Engineer. 16.1.1 16.2 Ditto, But of size 550x450 Model A7450 or E.A. Mixers S&I Chrome plated gear mixer type CERADISC (IS) model A5390 or E.A complete with all the needed fixing accessories, sockets, copper adaptors and 3"/8" angle valves type (Giacomini or E.A.) for connecting with water pipes, all to be done as per the drawings, specifications and the approval of the Engineer. 16.3 W.C S&I Porcelain wall mounted W.C white color European type with P-trap as per SANREMO from IS or E.A. Price shall include all fixation and hanging brackets, 9-lt capacity concealed cistern, valves, fittings, hard solid seat and 13mm stop angle valves, chrome plated 13mm hose of 1 meter length c/w 13mm Chrome plated hand shower for wc (heavy duty) with spring nozzle outlet and all other required materials, including connection to drainage and water pipes, and including 3/8" angle valve (Giacomini or E.A.), all to be done as per the drawings, specifications and the approval of the Engineer. 16.4 Paper holder S&I stainless steel paper holder type BOBRICK model B-6699 or E.A for single roll fixed to wall with all needed fixing accessories, all to be done as per drawings, specifications and the approval of the Engineer. 16.5 Sink S&I stainless steel sink for kitchens of size 40x50 cm (single bowl) like (Rocca or E.A ) of thickness 18/10 Price shall include connecting to drain of system by 2" HDPE pipes inside sanitary blocks, also proper fixation to marble, all to be done as per drawings, specifications and the approval of the Engineer. 16.6 Chrome plated mixer S&I chrome plated mixer type Cerlaman (IS) A5396. With steel wire mesh, and connection to water supply with 3/8" angle valve type Giacomini or E.A., including all the required fittings, all to be done as per drawings, specifications and the approval of the Engineer. No. 4 No. 4 No. 44 No. 26 No. 44 No. 26 Unit Quantity Rate Amount

No.

18

Carried To Section-16 Collection Mechanical 4/27

Section-16: Mechanical Bill of Quantities Item 16.7 Sluice sink Supply and install 316 stainless steel gauge 12 sluice sink complete with chrome plated swivel - spout mixer type (IS) A5396 or E.A. with steel wire mesh. Price includes connection to water supply with 3"/8" angle valve type (Giacomini or E.A.), including all the required fittings, all to be done as per drawings, specifications and the approval of the Engineer. 16.8 Soap dispenser S&I Heavy duty soap dispenser type BOBRICK model B2111or EA. with all fixing accessories needed. All to be done as per drawings, specifications and the approval of the Engineer. 16.9 Towel paper holder S&I Heavy duty towel paper holder type 304 st st BOBRICK model B- 6699 or EA for single roll to be fixed at wall with all fixing accessories needed. All to be done as per drawings, specifications and the approval of the Engineer. 16.10 Janitor closet S&I Porcelain floor mounted janitor closet type (IS) model R3852or EA. The rate includes grilled cover, fixing screws, rubber and all needed fixing accessories. The rate shall include the supply and installation of 11/2" Flush valve type (IS) and Chrome plated single tap for cold water. All to be done as per drawings, specifications and the approval of the Engineer. 16.11 Shower gear mixer S&I Chrome plated shower gear mixer type CERADISC (IS) model A5394 or E.A and for the connecting rod model A3052 or E.A, compete with hand shower, flexible hose 150mm length, fixing anchor and all needed accessories, all to be executed as per drawings, specifications and the approval of the Engineer. Shower syphone S&I shower syphone heavy duty type Lipski or E.A. with round cover of 4" size. Shower seat S&I folding shower seat, padded seat, right hand seat type BOBRICK model B517 or E.A. Robe/clothes hook S&I single robe/clothes hook with concealed mounting type BOBRICK model B2116 or E.A. Soap dish S&I recessed soap dish type BOBRICK model B6607 or E.A. 16.11.5 Grab bar S&I horizontal two way grab bar for handicapped shower 914x1372 mm type BOBRICK model B-5837 or E.A. The rate shall include for fixing the bar at wall using special mortar mix. 16.12 Mirror S&I mirror with aluminum frame suitable to be used for hospitals with different sizes. The rate shall include fixing the mirror to wall and according to the provided drawings. Carried To Section-16 Collection Total of Section-16: Sanitary Fixtures carried to Summary sheet Mechanical 5/27 No 61 No 4 No 2 No 27 No 61 No. 1 Description Unit Quantity Rate Amount

No

34

16.11.1

No

34

16.11.2

No

34

16.11.3

No

61

16.11.4

No

61

Section-17: Mechanical Bill of Quantities Item 17 17.1 Description Domestic hot and cold water system: CPVC pipes Supply and install galvanized CPVC pipes (Al-Hill/Egypt) or EA made for domestic cold and hot water. The work includes all fittings, valves, required flow direction signs, TOLGO type hangers, all required fittings, connection to existing system and all needed accessories. 17.1.1 17.1.2 17.1.3 17.1.4 17.1.5 17.1.6 17.1.7 17.2 1/2" 3/4" 1" 11/4" 11/2" 2" 3" Thermal Insulation for hot water supply and circulation pipes Supply and install 9mm thick insulation for domestic hot water supply and circulation pipes type ANAVID or E.A. The work includes insulating all fittings, valves, non-return valve etc., and wrapping with 10cm plastic wrap, also required flow direction signs,. 17.2.1 17.2.2 17.2.3 17.2.4 17.2.5 17.2.6 17.2.7 1/2" 3/4" 1" 11/4" 11/2" 2" 3" M.R M.R M.R M.R M.R M.R M.R 35 80 60 45 30 50 10 M.R M.R M.R M.R M.R M.R M.R 75 150 130 100 90 95 20 Unit Quantity Rate Amount

Carried To Section-17 Collection

Mechanical

6/27

Section-17: Mechanical Bill of Quantities Item 17.3 Pipe Cladding Supply and install 0.5mm Galvanized sheet cladding for protection of exposed pipes for hot and air conditioning and heating systems including all screws, saddles, and fittings needed. The work also includes covering all valves, strainer, unions, nipples, fittings, hangers and all other needed accessories and marks to protect the pipes along their paths. 17.3.1 17.3.2 17.3.3 17.3.4 17.3.5 17.3.6 17.4 11/4" 11/2" 2" 21/2" 3" 4" Hot and cold water collectors Supply and install hot and cold water collectors type GIACOMINI or E.A. The collectors are installed above the ceiling of bathroom with all required hangers and supports, air vents, shut-off valves on the collectors inlets, records, and all required accessories to complete the job. M.R M.R M.R M.R M.R M.R 77 70 55 58 40 35 Description Unit Quantity Rate Amount

17.4.1 17.4.2 17.5

3/4" 1" XLPE pipes S&I crossed linked PE pipe 16mm pipe with 25 mm sleeve type Aquapex or E.A. The rate shall include all fittings eg: copper elbow inside walls (type GIACOMINI), 1/2" male and female adaptors and all needed accessories for connection between copper collectors to fixtures.

Eye Eye

30 106

M.R

1600

Carried To Section-17 Collection Total of Section-17: Domestic Hot and Cold Water carried to Summary sheet

Mechanical

7/27

Section-18: Mechanical Bill of Quantities Item 18 Fire Fighting System: Supply, install, and test the following items complete with the necessary fixing accessories as specified and as shown on drawings: 18.1 Fire cabinet Wall mounted fire cabinet 120x80x30 cm equipped with 1" swinging hose reel 25 m polystyrene hose 1" aluminum nozzle, 1" ball valve, 12 kg powder extinguisher, 2" linen hose (2 x 15 m) with quick coupling, 2" nozzle, 2" landing valve, 2" ball valve, and all required fittings and valves. The cabinet shall be locally made of minimum Gage-16 GI sheet with sturdy hinges, latches and locks, all with oven paint finish, while the described inner components of the cabinets should be as per Lahavot make or EA. 18.2 Sch.40 pipes Supply and install black steel Sch. 40 pipes jointed by welding for diameters above 2" and by threads for 2" pipes and below, all as made by MODGAL or E.A. The work also includes all valves, strainer, unions, nipples, fittings, hangers and all needed other accessories including painting with the final red color paint according to specifications and the approval of the Engineer. No. 6 Description Unit Quantity Rate Amount

18.2.1 18.2.2 18.2.3

3" 21/2" 2"

M.R M.R M.R

5 5 180

Total of Section-18: Fire Fighting system carried to Summary sheet

Mechanical

8/27

Section-19: Mechanical Bill of Quantities Item 19.1 HVAC System S&I of an air cooled chiller of capacity 110 Ton as made by York (USA), Daikin (Japan), Carrier (France), or EA. The chiller operates with friendly to Ozone refrigerant (R407-C) and runs with hermetic screw type compressor, leaving water Temperature = 7.2 C and inlet water Temperature = 12 C, all in accordance with the prevailing climate conditions of the city of Jenin. The unit shall be equipped with direct drive condenser propeller, condenser fan motor, heat exchanger, high and low pressure switch,anti freeze sensor, braided flexible connections, outlet water temperature sensor, return water temperature sensor, ambient temperature sensor, crank case heater, supply and return headers as shown on drawings, double regulating valves, filter drier, sight glass, service valves, water flow switch and pressure gage (high & low), electrical controllers and electrical control board with all required electrical connections,. The work includes but not limited to concrete base and all requirements for proper installation and operation, all done according to drawings specifications and approval of the Engineer. 19.2 Fan Coil Unit S&I ducted fan coil unit with forward curved fans as made by Daikin (Japan), Carrier (France), York (USA) or EA. The unit shall be with a single coil, stainless steel drain pan, and with all parts such as 3-way valve, inlet & outlet ball valves type GIACOMINI or E.A, strainer, inlet and outlet rubber flexible connections with braided steel, washable flat filter, multi speed electric motor and room thermostat with three speed switch (wall mounted type installed inside lockable protection box). The rate includes connecting the unit to piping. The units are categorized as follows: Cooling Load =3 kw Cooling Load =4.2 kw Cooling Load = 6.3 kw Cooling Load = 7.4 kw Cooling Load =8 kw Cooling Load = 9 kw Cooling Load = 10 kw Air Ceiling Diffusers S&I size 12"X12" aluminum supply air ceiling diffusers as made by Cooling Industries or E.A, four-way square type with removable core, key operated opposed-blade volume damper and equalizing grid, suitable for mounting flush with false ceiling. The unit price shall include connection to duct with flexible insulated duct of compatible diameter and of maximum 1 meter in length , and all accessories and works required to complete the work, all done according to drawings, specifications and approval of the Engineer. Ditto, but size 18"X18" Ditto, but size 9"X9" Ditto, but size 15"X15" Ditto, but size 16"X16" Ditto but 1-way wall mounted of sizes 18"X8" 10"X8" Carried To Section-19 Collection No. No. No. No. No. No. No. No. 4 10 5 5 6 8 2 62 Description Unit Quantity Rate Amount

N.O

19.2.1 19.2.2 19.2.3 19.2.4 19.2.5 19.2.6 19.2.7 19.3

19.3.1 19.3.2 19.3.3 19.3.4 19.4. 19.4.1 19.4.2

No. No. No. No. No. No.

44 29 5 2 39 9

Mechanical

9/27

Section-19: Mechanical Bill of Quantities Item 19.5 Aluminum Grills S&I exhaust air aluminum grills made by Cooling Industries or E.A, fixed 45-degree blades, double deflection, 1" thick frame, 3/4" spacing. The unit price shall include connection to duct, and all accessories and works required to complete the work, all done according to drawings specifications and approval of the Engineer. 19.5.1 19.5.2 19.5.3 19.5.4 19.6 6"X6" 9"X9" 12"X12" 16"X16" Operating Theatre Diffusers Supply and install perforated aluminum ceiling diffusers for the operating theatres of size 18"X18", ceiling module with neck size as shown on the drawings, flush face, adjustable 4-way deflectors, with integral or field fabricated plenum box, key operated opposed-blade volume damper and equalizing grid with plasma filter. The unit price shall include connection to duct via flexible connection not exceeding one meter in length, and all accessories and works required to complete the work as shown on the drawings and as per the specifications and supervision Engineer's instructions. No. No. No. No. No. 80 57 98 9 4 Description Unit Quantity Rate Amount

19.7

Packaged Units S&I modular, weather proof type 100% fresh air packaged unit for the operating theater, being double deck with plate heat exchanger constructed from Galv.sheet metal 1.5mm thick penta post with double skin panels on the evaporator side and insulated with injected polyurethane 2" thick as made by Daikin (Japan), Carrier (France), York (USA) or EA of capacity 12.4Ton. . The rate includes built-in heating battery of 18KW capacity made of stainless steel finned tube heating elements covering all the face area of the air flow and including all protection gadgets such as air flow switch, automatic and manual reset thermal cut-outs, and controlled via 4 stages controller. It should also include a built-in plate heat exchanger and return fan for energy recovery between the return (exhausted) air and the fresh air supply, built-in sound attenuators for the supply and return openings, built-in Hepa filter of 99.997% efficiency, drain siphon and all needed fixing accessories such as mounting base frame, damper motor at fresh air intake made by danfos or E.A and electrical connection. all to be according to drawings, specifications, and approval of the Engineer. Ditto as above but without humidifier Laboratories A.H.U of 20 ton capacity Sterilizing A.H.U of 10 ton capacity. Newborn A.H.U of 42 ton capacity. Ditto as in 19.7, but without plate heat exchanger and Hepa filter. First floor A.H.U of 14.5 ton capacity. Second floor A.H.U of 22.7 ton capacity. N.O 1

19.7.1 abc19.7.2 ab-

N.O N.O N.O

1 1 1

N.O N.O

1 1

Section-19: Mechanical Bill of Quantities Mechanical 10/27

Item 19.8

Section-19: Mechanical Bill of Quantities Description Thermostat Supply and install minimum two stage cooling and four stage heating thermostat for the packaged unit made by Honeywell or EA. Exhaust Air Fans S&I exhaust air fans (roof-mounted dome type) as manufactured by Vortice or E.A, all of sturdy industrial structure, galvanized steel parts and aluminum impellers, directly driven by IP 65 electric motors, powered by 380V/3phase/50Hz electric power supply. Price shall include all materials needed for complete installation, steel stands and protections, as well as, weather proof disconnect switch for maintenance needs, where all shall be done as per the detailed drawings, specifications, and Engineer's instructions. Exhaust:900 CFM roof mounted Exhaust: 1000 CFM roof mounted Exhaust: 300 CFM wall mounted (propeller type with gravity louver) Exhaust:1980 CFM roof mounted

Unit

Quantity

Rate

Amount

No.

19.9

19.9.1 19.9.2 19.9.3 19.9.4

No. No. No. No.

1 1 7 1

Carried To Section-19 Collection

Mechanical

11/27

Section-19: Mechanical Bill of Quantities Item 19.10 Air Ducts Supply and install single skin galvanized steel duct made according to SMACNA standard and requirements vis-a-vis support, sizing, branching, air tightening, jointing, etc, with 2" thick, 12kg/m3 density glass wool insulation wrapped with reinforced aluminum foil, which shall be confined in place by aluminum adhesive tape at the joints and spirally wound aluminum wire all around and along. The rate shall include all required hangers, supports, isolators, splitting dampers, canvas type flexible connections at units inlets and outlets, and all required accessories needed as shown on drawings, according to specifications, and to the Engineer's instructions. 19.10.1 Ditto, but with 0.6mm galvanized metal sheet cladding for protection of exposed duct work on roof including all screws and fittings needed, excluding the spirally wound aluminum wires, where the job shall be rendered according to SMACNA , all in accordance with the drawings, specifications and the approval of the Engineer. Exhaust Duct Supply and install galvanized steel duct for exhaust system made according to SMACNA. The rate shall include all required hangers, supports, canvas flexible connections and all required accessories made as shown on drawings, according to specifications, and to the approval of the Engineer. 19.12 A/C Piping Network Supply and install black steel Sch.40 pipes for the A/C network with 19mm Vidoflex insulation and nylon wrapping. The work also includes all unions, nipples, tees, elbows, hangers, required flow direction signs, and all other needed accessories to lay the pipe along its path, all done according to drawings specifications and approval of the Engineer. 19.12.1 19.12.2 19.12.3 19.12.4 19.12.5 19.12.6 19.12.7 19.13 3" 21/2" 2" 11/2" 11/4" 1" 3/4" Valves Supply and install isolation ball type valves as made by Giacomini for the A/C piping network, as follows: 19.13.1 19.13.2 19.13.3 19.13.4 19.13.5 19.13.6 19.13.7 3" 21/2" 2" 11/2" 11/4" 1" 3/4" Carried To Section-19 Collection No. No. No. No. No. No. No. 4 6 6 6 6 8 10 MR. MR. MR. MR. MR. MR. MR. 32 88 120 116 58 95 32 M 350 M 1300 Description Unit Quantity Rate Amount

95

19.11

Mechanical

12/27

Section-19: Mechanical Bill of Quantities Item 19.14 Chilled water pumps S&I circulating chilled water pumps (in alternating mode) as made by Grundfos, Salmson or E.A. The rate includes all fixing accessories , concrete mounting base and neoprene pads, flexible connections at inlets and outlets, pressure gages at inlets and outlets, strainers at inlets, globe valves at inlets and outlets, complete insulation for the related fittings, galvanized sheet metal shelter to protect the pumps from rain, flow direction signs. The price shall include also the electrical controllers and electrical power and control sub-board where needed, with the required electrical connection and all needed parts to complete the job according to drawings, specifications and the approval of the Engineer. Description Unit Quantity Rate Amount

19.14.1 19.14.2 19.14.3 19.15

Q=8.2L/s , H=16m primary pump Q=8L/s , H=16m secondary pressure pump 0.7 L\S h=30m Headers S&I 8" diameter headers at the pumps inlets & outlets as shown on drawings. The headers shall include all needed outlets (with 2" extra clogged outlets on each for future expansion), ball valves (Giacomini or equivalent), pressure gauges, thermometers, convexed end caps, 24kg/m3 fiberglass insulation, 0.7 galvanized metal steel sheet claddings, and steel supports.

No. No. No.

2 2 1

L.S

Carried To Section-19 Collection Mechanical 13/27

Section-19: Mechanical Bill of Quantities Item 19.16 Description Relocation of the Existing HVAC Equipment and Accessories to New Roof: The contractor shall, when pricing the rates of this bill, take into consideration including and allow for the cost expenses of all requirements stipulated in the preambles, drawings and technical specifications of the contract. Before the removal of the existing parts, the contractor shall submit a detailed report about the quantity of the parts, units and machines that have to be relocated on the future roof. The contractor afterwards shall examine and present a detailed report about the status and the conditions of all the parts, units, machines, and inform of any damaged existing part or machine, prior to disassembling the system. The contractor then has to submit his methodology for relocating all the existing units to the future roof, and should take into consideration that in all stages work shall be done in conjunction with the various work activities on site. This implies proper planning with UNDP and hospital authorized personal, to ensure smooth relocation of equipment and minimal HVAC interruption time inside the hospital building. When disassembling, the contractor has to maintain all the disassembled parts in good condition and take full responsibility for the intactness of all the disassembled parts. Damaged or broken parts on the existing system should be noted prior to disassembling the system and shall be paid for upon replacement according to the offered unit rate. Any damage done to the parts during the relocation shall be covered by the contractor. The price shall include Dismantling all existing electrical installations, panel boards and all accessories from existing mechanical A.C. room on the roof and reinstalling and reconnecting all electrical needs in the new mechanical room and changing all small cables and control wires if required, as well as, providing joints for any extension (by proper cable jointing method) for large cables. Main feeders (large size cables that are 19.16.1 Connecting all existing vent pipes and storm water pipes to the extended stand pipes in the concrete walls of the new structure, and relocating the existing vent caps on future roof , which shall include (but excluding the cost of pipes which shall be covered in the corresponding pipe supply and installation item) breaking and openings in concrete and all required labor, materials according to the instruction of the Engineer. No. 20 Unit Quantity Rate Amount

Carried To Section-19 Collection

Mechanical

14/27

Section-19: Mechanical Bill of Quantities Item 19.16.2 Description Relocating the existing AHUs on roof and re-installing them on on future roof as shown in drawings. The work shall include all piping from main riser to the units, pumps, valves, strainers, and galvanized ducts, openings in concrete for the existing slab, electrical panel and all required labor, materials, conduits and electrical wiring and fitting equipment according to the instruction of engineer. Price also includes the workmanship and know-how for the replacement of any of the following damaged parts or additional needed parts with new (same in size, capacity and quality) ones: Unit No. Quantity 1 Rate Amount

19.16.3.1 Insulated 2" Sch-40 black steel pipe as existing. 19.16.3.2 Butterfly valve 4" as existing. 19.16.3.3 Butterfly valve 3" as existing. 19.16.3.4 Butterfly valve 21/2" as existing. 19.16.3.5 Flow switch as existing. 19.16.3.6 Temperature gauge as existing. 19.16.3.7 Pressure gauge as existing. 19.16.3.8 4" flexible connection as existing. 19.16.3.9 3" flexible connection as existing. 19.16.3.10 4" non-return valve as existing. 19.16.3.11 3" non-return valve as existing. 19.16.3.12 Duct Works as existing. 19.16.3.13 Double Regulating valve 4" as existing. 19.16.3.14 Double Regulating valve 3" as existing. 19.16.3.15 Double Regulating valve 21/2" as existing. 19.16.4 Replacing all existing exhaust fans on roof and the re-installation on future roof as shown in drawings. The work shall include galvanized ducts, PVC piping, openings in concrete for the existing slab, connection to existing electrical panel and all required labor, conduits and electrical wiring, materials and lifting equipment all made according to the instruction of the engineer. Price also includes the workmanship and know-how needed for the replacement of any of the following damaged parts or additional needed parts with new (same in size, capacity and quality) ones:

LM No No No No No No No No No No M2 No No No No

10 1 1 1 1 1 1 1 1 1 1 10 1 1 1 3

19.16.4.1 Duct Works as existing.

M2

100

Carried To Section-19 Collection

Mechanical

15/27

Section-19: Mechanical Bill of Quantities Item 19.16.5 Description Relocating all existing chillers ont roof and the re-installation on future roof as shown on drawings. The relocation covers the piping connections, pumps, heat exchanger, valves, foundation isolation, all existing equipment, electrical connections and all required labor, conduits and electrical wiring, materials and lifting equipment, all must be made according to the instruction of the Engineer. Price also includes the workmanship and knowhow needed for the replacement of any of the following damaged or any needed additional parts with new (same in size, capacity and quality) ones: Unit No Quantity 2 Rate Amount

19.16.5.1 Insulated 4" Sch-40 black steel pipe as existing. 19.16.5.2 Insulated 3" Sch-40 black steel pipe as existing. 19.16.5.3 Insulated 21/2" Sch-40 black steel pipe as existing. 19.16.5.4 Insulated 2" Sch-40 black steel pipe as existing. 19.16.5.5 Butterfly valve 4" as existing. 19.16.5.6 Butterfly valve 3" as existing. 19.16.5.7 Butterfly valve 21/2" as existing. 19.16.5.8 4" flange as existing. 19.16.5.9 3" flange as existing. 19.16.5.10 21/2" flange as existing. 19.16.5.11 4" strainer as existing. 19.16.5.12 3" strainer as existing. 19.16.5.13 Flow switch as existing. 19.16.5.14 Temperature gauge as existing. 19.16.5.15 Pressure gauge as existing. 19.16.5.16 4" flexible connection as existing. 19.16.5.17 3" flexible connection as existing. 19.16.5.18 4" non-return valve as existing. 19.16.5.19 3" non-return valve as existing.

MR. MR. MR. MR. No No No No No No No No No No No No No No No

10 10 10 10 1 1 1 1 1 1 1 1 1 1 1 4 4 1 1 1

Carried To Section-19 Collection Total of Section-19: HVAC system carried to Summary sheet

Mechanical

16/27

Section-20: Mechanical Bill of Quantities Item 20 20.1 Medical Gases Medical gas copper piping as per ASTM / HTM02.01 Supply, install, connect, and testing of the following degreased medical oxygen compatible seam-less copper pipes type L. The pipes must be cleaned and treated for medical gas usage including capping the ends of each pipe to ensure that no foreign bodies or dusts or vapors affect the pipes. The copper pipes must meet the international standard of ASTM B-819 and to be cleaned for medical usage (degreased) in accordance with CE 0473. Each pipe must be pro-factory marked continuously with:_ OXY/MED ASTM B-819 Pipeline network must be welded and hanged according to the latest welding and hanging methods of healthcare technical memorandum HTM 02.01, ASTM B819 and G-01 Price includes proper isolation for piping under plastering and penetrations , hangers, brackets, fasteners, etc.., as well as various fittings and accessories needed to complete the works as shown on drawings and as per specifications. Price also includes proper flushing of the entire piping network using purified Nitrogen or Medical Compressed Air. 20.1.1 20.1.2 20.1.3 20.1.4 20.1.5 20.1.6 20.1.7 20.1.8 20.2 inch O.D. 5/8 inch O.D. 7/8 inch O.D. 1 3/8 inch O.D. 1 1/8 inch O.D. 1 5/8 inch O.D. 2 1/8 inch O.D. 2 5/8 inch O.D. Area Valves Control Boxes Supply, install, connect, and testing of the following recessed area valve control box for medical oxygen and vacuum, including 2 full-port 3-parts NIBCO shut off valves which controls the supply of gases or vacuum through the pipelines, and line pressure and vacuum gauges. The valves diameter varies between 15 up to 35 mm, as per drawings. The area valves control boxes should also include an emergency external supply port, equipped with disk and clutch mechanism for quick plug-in connection of the emergency external supply source. the front should be made of labeled transparent polycarbonate flexible unbreakable cover to ease access in emergency situation, all as per Dragger/Germany, Gregerson Germany, AIMCO/Canada, or EA. 20.2.2 20.2.3 20.2.4 Same as Item No.20. 2.1 but for medical oxygen, medical compressed air and vacuum. Same as Item No.20. 2.1 but for medical oxygen, nitrous-oxide, medical compressed air and vacuum. Same as Item No. 20.2.1 but for medical oxygen, nitrous oxide, high pressure compressed air, medical compressed air and vacuum Carried To Section-20 Collection Unit Unit Unit 1 2 1 M.R M.R M.R M.R M.R M.R M.R M.R 630 720 680 450 50 150 80 70 Description Unit Quantity Rate Amount

20.2.1

Unit

Mechanical

17/27

Section-20: Mechanical Bill of Quantities Item 20.3 20.3.1 Description Digital Local Area Pressure and Vacuum Alarm Panel Supply, install, connect, and testing of digital local alarm panel for one compressed gas and one vacuum service, the alarm panel shall be capable of accommodating pressure and vacuum services as special application, the sensor shall be capable of local or remote mounting, each sensor and electronic panel shall be gas specific to avoid cross-connecting of the sensor with its digital display panel, each digital display panel must be equipped with three decimal seven-segment digits, each service shall have a LED display indicating the on-line measured pressure - up to 250 PSI (400 PSI for Nitrogen), each service shall have trend bar for showing the pressure direction (Green-Normal, yellowcaution, Red-High/Low) in the case of alarm the red light will flash and the alarm will sound, cancelling the alarm by the "CILENCE" bottom will stop the audible alarm but the red light will continue to flash until failure is fixed. TEST & CILENCE bottoms shall be easily accessed for operating and testing the unit. it shall be field programmable push buttons for adjusting the high and low set points (+/-20% of Normal Pressure), selecting the pressure/vacuum units and configuring the alarm repeat intervals. Input Power shall be 90 VAC to 230 VAC, 50-60Hz, for real-time monitoring of medical oxygen and vacuum, all as per Dragger/Germany, Gregerson/Germany, Amico/Canada, or EA.. Unit 9 Unit Quantity Rate Amount

20.3.2

Same as .Item No. 20.3.1 but for medical oxygen, medical compressed air and vacuum. Same as Item No. 20.3.1 but for medical oxygen, nitrous-oxide, medical compressed air and vacuum. Same as Item No. 20.3.1 but for medical oxygen, nitrous oxide, high pressure compressed air, medical compressed air and vacuum

Unit

20.3.3

Unit

20.3.4

Unit

Carried To Section-20 Collection

Mechanical

18/27

Section-20: Mechanical Bill of Quantities Item Description Unit Quantity Rate Amount

20.5

AGSS Outlets Supply, install, connect, and testing of anesthesia gas scavenging system with on-off switching indicator, to remove surplus anesthetic gas and explosive gas mixtures from operating theatres and anesthesia rooms, recessed type, with 22 mm. evacuation port according to DIN standards, all shall be as per Dragger/Germany, Gregerson/Germany, or Amico/Canada. Unit 2

20.6

Diamond Service Wall Outlets for Oxygen and Vacuum. Two gases wall outlet

20.6.1

Supply, install, connect, and testing of recessed type, chrome plated, color and pin coded die-cast front assembly, primary check inlet/outlet valve with decorative frame for two different codes of Oxygen and Vacuum, a hanging slide for 2 liters vacuum collecting bottle must be included, all shall be as per Dragger/Germany, Gregerson/Germany, or Amico/Canada. Four gases wall outlet Same as Item No. 6.1 but for Oxygen, Nitrous Oxide, Compressed Air and Vacuum.

Unit

20.6.2

Unit

Carried To Section-20 Collection

Mechanical

19/27

Item

Section-20: Mechanical Bill of Quantities Description

Unit

Quantity

Rate

Amount

20.7

Factory-Preassembled Bed head unit for one bed, according to CE-0473, EN-46001, ISO 9001 Intermediate Care Bed Head Units Supply, install, connect, and testing of encompassing extruded and smooth rounded edges aluminum duct system, with four cavities, three of which are directly accessed using snap-on covers. Supplying electrical and lighting service, as well as medical gas service. The gas outlets should be installed in a separate compartment. The number of electrical circuits, apart of the low voltage circuit, should be three: main line power circuit, UPS power circuit, and lighting circuit provided by others, each connected to the corresponding terminals at the electrical connection in the bed-head unit. The piping connections to the BHU shall be made directly without any interface facility, and including wall hung rail for secondary equipment. BHU shall be as per Dragger/Germany, Medicop/Austria, AHC/USA, Gregerson/Germany, or Medaes/England, or E.A The bed head unit is equipped with the following services : One oxygen outlet One compressed air outlet One vacuum outlet 2 electrical sockets, Main line 2 electrical sockets, coded-UPS line one potential grounding socket indirect light (36W Fl. lamp), class A3 electronic CG. direct light (18W PL BIAX lamp), class A3 electronic CG. cut-off switch for direct / indirect lights one telephone socket preparation for nurse call socket The Price shall include complete interior wiring, cabling, piping, insulating etc , for complete installation. The contractor must provide detailed drawing (supported with all required standard conformities) prior to supply for approval. Intensive Care bed Head Units Bed head unit for one bed Supply, install, connect, and testing of double 100/140 mm. profile Encompassing extruded aluminum duct system, with preparation of integrated upper & lower hanging rail assembly, Supplying electrical and lighting service, as well as medical gas service, including the following preparations for each patient bed: Two oxygen outlet One compressed air outlet One vacuum outlet 4 electrical sockets, Main line 2 electrical sockets, UPS line 2 potential grounding socket Day Light (full spectrum) light Color magnifying examination light Cut-off switch for magnifying examination light One telephone socket Preparation for nurse call socket All in accordance with EN-737 6, ISO 13485, 2003 and G-01 and as per Dragger/Germany, Medicop/Austria, Amico/Canada, Gregerson/Germany, or Medaes/England. Unit 91

20.7.1

20.7.2

Unit

20.7.3 20.7.4

Same as Item No. 7.2 but for four beds to serve four pre-matured Unit incubators. Same as Item No. 7.2 but for six beds to serve six pre-matured Unit Incubators Carried To Section-20 Collection Mechanical

2 2

20/27

Section-20: Mechanical Bill of Quantities Item 20.8 Description Vital Life Support Column for one Emergency bed, according to EN-793 and EN-60601-1-2 Supply, install, connect, and testing of vertical column surface made of medical high pressure laminate decorative Trespa, electro-polished anodized 2000 mm x 600 mm x 250 mm. Aluminum. structure Horizontal hanging rail and vertical anodized Aluminum tracks provides three-dimensional hanging of various type of equipment, complete with two medical oxygen outlets, two medical compressed air outlets, two vacuum outlets, four essential electrical sockets and four UPS coded sockets, each socket is equipped with built-in normal-power on LED indication connected to independent electrical circuit and marked terminals for each socket, with two potential equalization grounding sockets connected to main grounding line by two separate grounding bridges. Columns shall be as per Drager/Germany, Medicop/Austria, Amico/Canada, Gregerson/Germany, or Medaes/England. Integrated Combinational Ceiling-suspended System for Operating Theatre Supply, install, connect, and testing of central Ceiling-suspended system for the OR, comprising prismatic cool operating light, with 130,000 lux light intensity at 1m distance, with full spectrum daylight color temperature of 4,300 K, with automatic switch-over standby lamp, electronic intensity and focus control, with power module and emergency relay, and tandem ceiling pendant with double boom arms, drop tube, modular service head, and medical rail with pneumatic control, including : two medical oxygen outlets, two medical compressed air outlets, two nitrousoxide outlets, two vacuum outlets, one AGSS outlet, one air motor outlet, with four electrical sockets for main power wired to two separate electrical circuits, with two electrical sockets for UPS power wired to a separate electrical circuit, and two potential equalization sockets, both suspended from central ceiling flange, interface plate, and ceiling canopy, all in accordance with 93/42/EEC conformity. The OR system shall be as per Herus/Germany, Dragger/Germany, Trumph/Switzerland, or EA. Delivery, Labor, Preparation Room Lights Supply, install, connect, and testing of ceiling-mounted Labor, Preparation, and Examination Rooms Lights, examination light for ceiling mounting, of 300 mm diameter with 40,000. lux intensity at 1m distance, complies with Protection class I according to IEC The hermetically sealed aluminum light housing is dust- and fracture-proof. The light should be plastic-coated for fast and easy cleaning. The powerful halogen lighting system ensures the optimum illumination of the operating field. Special filter components guarantee cool, white light free from any deep shadows. The high-quality reflector technology ensures a uniform light field and first-rate color rendering properties. The light exit surface consists of hardened safety glass that is highly resistant to mechanical and chemical influences, with spring regulated arm for easy height adjustment. The examination light shall be as per Herus/Germany, Dragger/Germany, Trumph/Switzerland, or EA. Carried To Section-20 Collection Unit Quantity Rate Amount

Unit

20.9

Unit

20.10

Unit

Mechanical

21/27

Section-20: Mechanical Bill of Quantities Item 20.11 Description Baby Bath Tubs Supply, install, connect, and testing of baby bath tubs as per Lido Baby/ 01 or equal, each set consisting of: Acrylic Ceramic bath tub & washing sink Hand shower Electronic water tab Thermostatic water mixer Transformer Electronic hand washing scrub sinks Supply, install, connect, and testing of stainless steel suspended electronic hand washing units with channel type tank and paneling under basin, two electronic taps, one electronic soap dispenser and thermostatic mixer. Made of AISI 316 stainless steel , size 120x55x110 cm. overflowproof tank (35 cm deep) with rounded inner edges and inclined front part to prevent water from spraying outside, which shall be as per Steris/USA or EA. 20.13 Supply and installation of Ceiling Column, rigid, according to EN 737, 793, 12218 Supply, install, connect, and testing of ceiling column surface as made of Trespa, polished anodized or painted Aluminum. Horizontal hanging rail and vertical anodized Aluminum tracks provided for hanging various type of equipment, complete with two medical oxygen outlets, two medical compressed air outlets, two nitrous-oxide outlets, two vacuum outlets, one AGSS outlets, one air motor outlet, four electrical sockets for mains power, connected in two separate electrical circuits, and two electrical sockets for UPS power, connected in a separate electrical circuit, with two potential equalization sockets, all as per Dragger/Germany, Gregerson/Germany, or EA.. Unit 1 Unit Quantity Rate Amount

Unit

20.12

Unit

20.14 20.14.1

Extra Incorporated Additional items Secondary equipment hanging rail assembly including one meter long rail Panel mounted gas outlet Panel mounted electrical socket Panel mounted potential grounding socket Panel mounted RJ-45 data socket Panel mounted telephone socket Panel mounted pressure gauge unit 1

20.14.2 20.14.3 20.14.4 20.14.5 20.14.6 20.14.7

Unit Unit Unit Unit Unit Unit

1 1 1 1 1 1

Carried To Section-20 Collection Total of Section-20: Medical Gases carried to Summary sheet

Mechanical

22/27

Section-21: Laboratory Works(provisional works) Item 21 21.1 21.1.1 Description Laboratory working benches Clinical pathology & bacteriology lab benches Middle bench Island bench Structure: A doubled 60x30x2 mm-thick hot galvanized steel profile structure, H structure consists of vertical stands and horizontal brackets, supported by horizontal rectangular structures and vertical rectangular structures to carry the work top surfaces and the modular lower storing cabinets, the structure is protected by three layers of epoxy oven paint, color as selected by customer, all as made by PV Lab, or EA. Unit 2 Unit Quantity Rate Amount

Dimensions: length: 2,800 mm. Width: 1,400 mm. Height: 900 mm. working surface, 1,600 mm upper shelve Working surface: All made of 20 mm-thick rigid polypropylene TOP LAB TRESPA, both heat and chemical resistance, manufactured by HOESCHT/Germany, or EA.. Central service board: 20 cm. Width, made by laminated wood sandwich and coated with 3 mm-thick TRESPA, Prepared to carry lab fittings and cup sinks and water faucetsetc. Double upper shelve: Two upper shelves installed on the center of the working surface, 50 cm width, 30 mm-thick post-forming covered by Formica

Electricity energy carrier: 45 degrees panel aluminum profile contains 12 power sockets from each side and installed in the center of the working surface at the lower shelve bottom with possibility to add any low tension sockets or telephone sockets or potential sockets

21.1.2

Central Bench washing Stand Dimensions: 1400x700x900 mm. Structure: All made of 17 mm-thick laminated wood, covered by Formica from inside and back, PVC layer from outside. Test tubes drying rack A 1400x660H mm. drying rack made of laminated wood and covered by PVC layer, equipped by 3 lines of different diameters test tube hangers Washing sink: A 600x400x200H mm. ceramic sink installed in the center of the washing stand working surface including drain valve and siphon valve and all required connections Working surface: made by 20 mm-thick TRESPA or Ceramic Tiles, all as per PV Lab make, or EA. Carried To Section-21 Collection Mechanical

Unit

23/27

Section-21: Mechanical Bill of Quantities Item 21.1.3.a Side Working Bench Structure: A 60x30x2 mm-thick hot galvanized steel profile structure, C structure consists of vertical stands and horizontal brackets, supported by horizontal rectangular structures and vertical rectangular structures to carry the work top surfaces and the modular lower storing cabinets, the structure is protected by three layers of epoxy oven paint, color as selected by customer, all as made by PV Lab, or EA. Dimensions: 700W x 900H mm. Working surface: 20 mm-thick TOP LAB TRESPA 21.1.3.b 21.1.4 Modular lower cabinet or drawer set (600x400x488) mm Fume Hoods Dimensions: Width: 1200 mm. Depth: 750 mm. Height:2620 mm. Structure: 18 mm laminated wood sandwich with 63 mm-thick edges. External coating: Tap Formica, color as selected by customer. Internal coating: 3 mm-thick. TOPLAB TRESPA, all as made by PV Lab, or EA. Unit Unit 15 2 Description Unit MR Quantity 40 Rate Amount

Working surface: CERAMIC TILES. with a front 30 mm elevated threshold and tapering edge which provides a 10 mm elevation above the worktop, including preparing bores for valves and sink and water faucet etc. the unit is equipped by 4 power sockets type GEWISS and cut-off switch to operate the blower and the lighting Back of the hood: There will be a double back, allowing routing and regulating the air flow from the upper and the lower parts of the hood by means of upper and lower flues, the hood back is made of 6 mm-thick TRESPA, a polypropylene lattice will be mounted at the outlet of the air suction inlet to prevent foreign bodies from entering the blower. Status indication: An electrical mechanism for indicating the operation status of the air suction blower by means of red lamp and green lamp mounted on the front panel of the hood Vertical window: Made of 6 mm-thick safety glass and stainless-steel frame slides on polypropylene rails and balanced by means of ball bearing wheels, balancing bar and counter weight. Electrical accessories and wiring: A Thermo magnet drive for driving the blower motor, 2 single phase power sockets, a lighting switch, a safety fuse and control lamp. All mounted on the hoods front panel. A 2 x 20 watts fluorescent lamps will be mounted on the upper cover outside hood, with a sealed transparent window to ensure that no gases enters the lamp area. A CL terminal box and marked terminal connections to the mains and to the blower will be mounted on the hidden upper part of the hood. Carried To Section-21 Collection

Mechanical

24/27

Section-21: Mechanical Bill of Quantities Item Suction blower: Rigid PVC, UV resistance centrifugal polypropylene booster made by COLASIT, Swiss made, or EA. Motor: 3-phase, Completely tight, TEFC, F isolation grade, 1400 r/pm. hp. Manufactured by SIEMENS, Germany or equal approved. Direct drive, model RN-250 protected by a safety switch. 21.2 21.2.1 Lab fitting for burning gas A bench fitting with 2 valves (180) and lift/turn safety handles Metals: Brass DIN 17660-CuZn39Pb3 and nickel Sealing: Nitrile. Lubricant: approved for burning gases, all as per Broen or EA. Lab fitting for burning gas A bench fitting with single valve (90) and lift/turn safety handles Metals: Brass DIN 17660-CuZn39Pb3 and nickel Sealing: Nitrile. Lubricant: approved for burning gases, all as per Broen or EA. 21.2.3 Lab fitting for burning gas A bench fitting with 2 valves (90) and lift/turn safety handles Metals: Brass DIN 17660-CuZn39Pb3 and nickel Sealing: Nitrile. Lubricant: approved for burning gases, all as per Broen or EA. Lab fittings for non-burning gases A bench fitting with single valve (90) and coded turn lift safety handles Metals: Brass DIN 17660-CuZn39Pb3 and nickel Sealing: Nitrile. Lubricant: approved for non-burning gases, all as per Broen or EA. Lab fittings for water Bench fitting with built-in BALLOFIX shut-off valve, ceramic head work, on site adjustable spout and detachable nozzle, all as per Broen 15279009, or EA. Lab fittings for water Bench mounted one hole mixer with swivel spout, ceramic head works and detachable nozzle, al as per Broen 15274009, or EA. Unit 6 Unit 6 Description Unit Quantity Rate Amount

21.2.2

21.2.4

Unit

21.2.5

Unit

21.2.6

Unit

Carried To Section-21 Collection

Mechanical

25/27

Section-21: Mechanical Bill of Quantities Item 21.3 Description Combined emergency eye wash and body shower Combined Body and eye shower, wall mounted in brass with chemical resistant Poly-coat with self-draining shower head. Water inlet at the top or bottom. Eye shower has built-in FLOWFIX (6.7 g/pm). Eye shower, combined wall mounted with two heads in brass with chemical resistant Poly-coat. Water is regulated with a builtin FLOWFIX (6.7 g/pm). Body shower 3/4 NPT male inlet. In brass with chemical resistant Poly-coat, all as Broen 17455909, or EA Unit Unit Quantity 1 Rate Amount

21.4 21.4.1

Poly-propylene sinks for side working benches A 600x400x200H mm. polypropylene sink installed in the center of the washing stand working surface including drain valve and siphon valve and all required connections as per Polysink PS0503S, or EA

Unit

21.4.2

Poly-propylene cup sinks for central console working benches A 300x150x200H mm. ellipse polypropylene cup sink installed in the center of the washing stand working surface including drain valve and all required connections, as per Polysink PS3015, or EA

Unit

Carried To Section-21 Collection Total of Section-21: Laboratory Works(provisional) carried to Summary sheet Mechanical 26/27

Item 22.1

Section-22: Lift Works Description


Supply and install one set of micro lift, capacity 100Kg, 0.3m/s speed, by-parting doors, cabin walls and doors are stainless steel 304, 2 stops in-line, 3 floors, all as per BKG /Germany or EA.Cabin . - cant off system finish with hair line stainless steel , adjustment guides shoes on both sides and removable shelf . - compensation device on suspension ropes / chains . Doors Finish *Door made of hair line stainless steel . *Frames are made with hair line stainless steel . Controller : B.K.G / Germany production which has all the functions as the suggested specifications . 1- call and send control with 24 v safety . 2- pre wired with pluas . 3- adjustable and time limited dispatch device . 4- acoustic arrival signal . 5- position indicator on each entrance . 6- thermal motor protection as main switch on control panel .

Unit
Complete

Quantity
1

Rate

Amount

7- machine room light with socket and hand lamp . Counter weight : Galvanized frame construction with iron infills . Drive unit : - Drive unit with slandered motor IPS4 . DISC brake and handwhell , 3*400V , 50 HZ , according to IEC Machine room door : - single hinged door with sash lock , both hinging sides available- with side frames made of STAINLESS STEEL . Structure : - steel structure , made of cold rolled galvanized special profiles, pre installed with T guides T45X5 + plastic trunking in ZM segments . Conduct the necessary maintenance and repair to the existing three "Thyssen" passenger elevators and one " LG" lift, including providing the necessary parts and material for satisfactory operation of the lifts. The repair work shall include the supply and installation of the following parts:

22.2a 22.2b 22.2c 22.2d 22.2e 22.2f 22.2g 22.2h 22.2i 22.2j 22.2k 22.2l 22.2k 22.2l 22.2m 22.2n 22.2o 22.2p 22.2q 22.2r 22.2s 22.2t 22.2v 22.2w

A- Thyssen lifts - parts: Door Spring No Top roller No Landing Door Contact No Alarm bell 12 V No Rechargeable lamp No Thyssen Push Button- Crystal No Door Lock "Thyssen" No Indicator with Arrow in the head No Inductor Posi-detector No Tall Photo Cell No Door Cam (Right + Left) No Landing Door Hanger1000mm No B- LG lifts -parts: Landing Door Shoe No Complete Lamp up the Car No Rechargeable lamp No Alarm bell 12 V No P.V.C Luck strong for car Floor M2 Rotary Encoder No IPM 100A No Condenser 6800F No Resistance 56Ohm No Rectifier Bridge 100A No Inverter Cables No DPP PCB No Total of Section-22: Lift Works carried to Summary sheet Mechanical

3 1 7 3 3 10 10 10 3 1 4 10 4 1 1 1 3.5 1 1 2 2 1 4 1

27/27

Project: Jenin Hospital Civil works Summary ( Bill 1)

Sec. 1 1) Total of Preliminary Works

Description

Amount

2) Total of Concrete Works

3) Total of Stone Works

4) Total of Block Works

5) Total of Plastering Works

6) Total of Flooring and Covering Works

7) Total of Water Proofing Works

8) Total of Carpentry Works

9) Total of Suspended Ceiling Works

10

10) Total of Painting Works

11

11) Total of Metal Works

12

12) Total of Other Works

Total of the Civil Works..carried to main summary

Summary - Civil

Jenin Hospital Electrical Summary Sheet Electrical Works Summary Sheet (Bill 2) Sec. 13.1 Total for Sec.13.1) Points 13.2 Total for Sec.13.2) Conduit, piping, and excavations 13.3 Total for Sec.13.3) Cables 13.4 Total for Sec.13.4) Structural elelement cabinet 13.5 Total for Sec.13.5) Grounding 13.6 Total for Sec.13.6) Electrical Switchboards 13.7 Total for Sec.13.7 ) Lumenaire supply and Installation. 13.8 Total for Sec.13.8) Nurse call System 13.9 Total for Sec.13.9) Fire alarm system. 13.10 Total for Sec.13.10) Intercome system. 13.11 Total for Sec.13.11) Public adress system 13.12 Total for Sec.13.12 ) Telephone system 13.13 Total for Sec.13.13 ) LV Boxes 13.14 Total for Sec.13.14 ) UPS System 13.15 Total for Sec.13.15 ) Patch Panels (PP) Description Amount

Bill 3

Total for Electrical Works ..carried to main summary

Summary -Electrical

Project: Jenin Hospital

Mechanical works Summary( Bill 3)

Sec.

Description

Amount

14

Total of waste and drainage works:

15

Total of roof drain works:

16

Total of Sanitary fixtures and their accessories works:

17

Total of Domestic Cold and Hot Water system works:

18

Total of Fire Fighting system works:

19

Total of HVAC System works:

20

Total of Medical Systems works:

21

Total of Laboratory works(provisional)

22

Tota of Lift works Total of the Mechanical works, including sec 21 provisional works, carried to main summary

Summary - Mechanical

Over All Summary

Project: Jenin Hospital

Main Summary

Bill No.

Description

Total

Bill # 1

Civil Works Summary

Bill # 2

Electrical Works Summary

Bill # 3

Mechanical Works Summary

Total of All Works including Provesional Items

Percentage % discount or addition Amount of discount or addition Net Grand Total

The sum of ________________________________________

Contractor:

Signature: Date: