2010 9th IEEE/IAS International Conference on Industry Applications - INDUSCON 2010 -

PSCAD/EMTDC c Model for Overvoltage and Common Mode Current Analysis in PWM Motor Drives
Camila C. Fl vio(1) , Vtor R. Diab(2) , Charles Bruno C. Assuncao(3) e Alessandro F. Moreira(4) a
Programa de P s-Graduacao em Engenharia El trica PPGEE o e Universidade Federal de Minas Gerais UFMG Belo Horizonte - MG - Brasil E-mail: (1) camilacan@yahoo.com.br, (2) vraydan@gmail.com, (3) charles.bca@gmail.com,

(4)

moreira@cpdee.ufmg.br

Abstract In this paper a high frequency model is developed in PSCAD/EMTDC c to investigate common mode and differential mode phenomena in PWM motor drive, that usually appears when long cables are used to connect the inverter to the motor. A unique model is presented to analyze not only the overvoltage and common mode current phenomena, but also the lter topologies which are utilized to mitigate their associated problems. Simulation analysis of a 3 HP PWM drive is presented. Both high frequency problems and performance of lter topologies are analyzed. Experimental results come along to validate the simulation model. Keywords Overvoltage and Common Mode Filters; Electrical Drive Systems Design and Applications; PSCAD/EMTDC Modeling.

I. I NTRODUCTION The use of Insulated Gate Bipolar Transistor IGBT in electrical drive systems has allowed an increase of the Pulse Width Modulation PWM carrier frequency and of the semiconductor switching time, improving the performance of the system in terms of current and torque control. However, such changes were accompanied by undesirable electromagnetic interference EMI problems, such as overvoltage at motor terminals and circulation of common mode currents. The occurrence of these problems also depends on the cable length that connects the inverter to the motor and the cable and motor characteristic impedances [1], [2], [3], [4], [5], [6]. The overvoltage phenomena and their associated problems have been studied in last decades, resulting in viable lter solutions [7], [8], [9], [10]. Among several possible methods for mitigation of overvoltage and circulation of common mode currents, a common point of study between these methods is to nd one topology that could solve the problems listed above together. Methodologies for mitigation of common mode currents departed of already existing dv/dt lters topologies, including appropriate modications [11], [12], [13], [14], [15]. The achievement of a simulation model, which represents with accuracy the characteristics of the system, the overvoltage and the circulation of common mode currents phenomena, is a critical point. Such a model enables the design, the perfor-

mance analysis and the optimization of dv/dt and common mode lters. Among the programs based on Electromagnetic Transients Program EMTP utilized to analyze electromagnetic transients in electrical systems, the PSCAD/EMTDC c program was chosen to develop the model of the PWM motor drive system. In this program, there are cable models appropriate for the electromagnetic transients study. In this program, a power cable model located on the ground with distributed parameters and frequency dependent parameters, was formulated and implemented for overvoltage and common mode current analysis in PWM motor drive systems with long cables [16]. The main contribution of this work is to develop a simulation model in the PSCD/EMTDC c program, representing all the drive system characteristics (inverter-cable-motor). The program has been utilized to investigate strategies that can mitigate overvoltage and common mode current problems. Simulation results of a low voltage 3hp drive system will be presented. Experimental results are also presented validating the simulation model developed. II. S IMULATION M ODEL OF THE PWM D RIVE S YSTEM The simulation model of the PWM motor drive system developed in PSCAD/EMTDC c includes the models for the inverter, the cable and the motor. Power supply system characteristics (PWM modulation), cable characteristics (size and electrical characteristics) and motor characteristics (low and high frequency parameters) are also included. The Fig.1 presents a schematic design of the model implemented in the program. Its important to point out that the PSCAD/EMTDC c program is simple to use by having a graphical interface that allows the schematic circuit construction and the simulation process analysis. The simulation results can be managed in an integrated environment. The characteristics and implementation details of drive system are described as follows. A. Inverter Considering that the common mode currents circulate through parasitic capacitances present between all elements of a drive system and their couplings with ground, its necessary

978-1-4244-8010-4/10/$26.00 2010 IEEE

Fig. 1. Drive system model implemented in PSCAD/EMTDC c program, including inverter (power module and switching circuit), cable and motor (low and high frequency) models [17].

to represent the capacitances present in the inverter. Therefore, in this model are represented the most important couplings:

Capacitances of each phase of the inverter to ground; Capacitance of the heat sink to ground; Capacitance of the DC link to ground.

Both rectier and inverter are modeled through semiconductor switches (diodes and IGBT) available in the library of the program. The rectier is uncontrolled three-phase bridge. The inverter is implemented by a three-phase system using as semiconductor device the IGBT. The sinusoidal PWM modulation is used. The rms value of the input voltage is 220 V and the value of the DC bus capacitance is 2000 F. In this model its possible to implement other forms of the PWM modulation, which is a subject for further analysis. B. Cables The cable model is a key point to analyze overvoltage and common mode current circulation phenomena [18]. It is a mandatory requisite that this representation takes into account the distributed nature of the cable and the variation of its parameters with frequency, fully achievable in the PSCAD/EMTDC c program. The cable model utilized in the system takes into account some fundamental characteristics such as:

Frequency dependent parameters: calculated for a wide range of frequencies, with higher capacity representation of the physical phenomenon of propagation. Phase domain models: determine the dynamic system behavior directly in the phase domain, which are more accurate models.

To implement the cable model, one must determine its physical and electrical characteristics. When choosing the model in phase domain it is necessary to specify the frequency band to be held for the synthesis of rational functions polynomial and the approximate number of poles and residues to be used for determining the characteristic admittance and propagation constant. With respect to physical characteristics, the amount and size of layers of the cable should be dened, and its locations in relation to the ground. The cable was represented by a tetrapolar cable (three phases and a earth wire). It is important to emphasize the importance of correctly setting the cable electric parameters (permittivity and permeability) in the program, since these parameters are intrinsically related to the propagation characteristics of the voltage pulse. C. Motor The model of the motor utilized in the simulation is very accurate to represent the overvoltage and common mode current phenomena. In this model, both high and low frequency phenomena are well represented. The low frequency behaviour of the motor is obtained using a DQ (Park transformation) dynamic model. The high frequency behaviour is obtained

Distributed parameters: takes into account the principle of wave propagation, including attenuation and time delay of the PWM voltage pulse.

using a high frequency model, which parameters are described as follows [17], [19]: Rt , Lt e Ct : network responsible for representing the high frequency phenomena in the turn-to-turn motor wiring; Cg : represents the turn-to-ground capacitance; Rg : represents the turn-to-ground resistance; Re : responsible for accounting losses in the motor frame. Table I shows the motor parameters used in the model implemented in the simulation program. It can be observed that the motor impedance to ground at high frequency is very low, since the capacitive coupling is very low. If the motor frame is grounded, there will be circulation of high frequency currents through these couplings, creating electromagnetic interference problems.
TABLE I L OW AND H IGH F REQUENCY PARAMETERS OF THE S IMULATION S YSTEM .
Motor Nameplate Data 3hp - 230/460V - 3 - 60Hz - 9/4.5A - 1755rpm Filter Low Freq. High Freq. Inverter R 50 Rs 0,42 Cg 313,6 pF Fase A 100 L 23 H Rr 0.28 Rg 35,5 Fase B 100 C 138 F Lls 2,7 mH Re 5,6 k Fase C 100 Lc 100 H Llr 2,7 mH Ct 31,4 pF Dissipador 300 Lm 34,8 mH Lt 2,7 mH Rt 1,15 k

Fig. 3.

RLC lter connected at the inverter output and coupled to DC bus.

Fig. 4. RLC lter connected at the inverter output, including common mode inductor, coupled to DC bus.

pF pF pF pF

III. F ILTERS T OPOLOGIES TO M ITIGATE OVERVOLTAGE AND C OMMON M ODE C URRENTS Some topologies are suggested in the literature to mitigate, at the same time, overvoltage and common mode current problems and the most important are presented in this work. The lters implemented are basically passive networks associated with certain forms of connection to the inverter DC bus, including common mode inductors. The following topologies are analyzed in the simulation program: RLC lter connected at the inverter output (Fig.2) [7], [10]. RLC lter connected at the inverter output and coupled to DC bus (Fig.3) [11]. RLC lter connected at the inverter output, coupled to bus DC and including common mode inductor, (Fig.4) [13], [14], [15].

increasing the rise time of voltage pulse, the dv/dt rate reduces at the motor terminals and, consequently, the common mode current amplitudes are reduced. Such topologies can reduce about 50% the peak value of the common mode currents. If further reduction of the the common mode current amplitude is desired, it is proposed to use the RLC lter networks and certain manner of connection to the inverter DC bus. The lter connected to the DC bus is able to reduce both differential mode and common mode currents. The lter consists of an RLC network connected at the inverter output with the lter neutral point connected to the midpoint of DC bus. Herein, it is possible to reduce common mode at the motor terminals as long as it diverts common mode current to the DC bus. The instantaneous and steady state values of common mode current can be reduced by employing appropriate values for the lter components. The inclusion of the common mode inductor aims to add a high impedance to common mode, which reduces even more the common mode current amplitudes. The common mode inductor creates a magnetic eld that displays a high impedance for common mode signals but low impedance for differential mode signals. IV. S IMULATIONS R ESULTS This section presents simulations results for the 3 hp motor drive system, using a 20 meters length power cable. Figs. 5 and 6 presents the results for the simulation system without lters. It can be observed that there are transient overvoltages in every switching, with voltage peak arriving at twice as the value of the DC bus voltage, normally expected for this system conguration [4]. Examining the system operation with other cable lengths, it is observed that the oscillations frequency of the voltage transient is reduced as cable length increases. This happens due to the fact that the frequency of transient voltage uctuations is inversely proportional to the length of the cable. This frequency depends not only on cable length, but other system characteristics such as propagation

Fig. 2.

RLC lter connected at the inverter output.

The RLC lter connected at the inverter output operates with the principle of increasing the rise time of the PWM voltage pulse, ltering out the high frequency components. By

speed of the voltage pulse and motor parasitic capacitances. However, these characteristics loose their importance when the cable is long. Fig. 6 also shows the waveforms of the common mode voltage at the motor terminals and the common mode current that ows through the connection to ground. One can check the high common mode current peaks.

Fig. 5. Simulation results for the drive without lter. Cable length: 20m. Phase-to-phase voltage waveforms.

Fig. 8. Simulation results for the drive with RLC lter connected to the output of the inverter. Cable length: 20m. Common mode voltage at the motor and Common mode current waveforms.

mode voltage and decreasing in the common mode current peak. Greater attenuation of common mode currents can be obtained when common mode inductors are included in the RLC network, as shown in Figs. 11 and 12.

Fig. 6. Simulation results for the drive without lter. Cable length: 20m. Common mode voltage at the motor and Common mode current waveforms. Fig. 9. Simulation results for the drive with RLC lter connected at the inverter output and coupled to the DC bus. Cable length: 20m. Phase-to-phase voltage waveforms.

V. E XPERIMENTAL R ESULTS A setup of a 3 hp drive system was realized in laboratory in order to validate the simulation results obtained with the PSCAD/EMTDC c program. Figs. 13 and 14 present the experimental results without the use of lters. One can check the overvoltage at the motor terminals and the common mode current waveforms. Figs. 15 and 16 present the experimental results with the use of the RLC lter connected at the output of the inverter. One can check the voltage attenuation and the reduction of common mode currents. It can be veried a good correlation between the experimental and the simulation results, validating the simulation model developed in PSCAD/EMTDC c . VI. C ONCLUSIONS This paper has presented a simulation model of a induction motor drive system developed in the PSCAD/EMTDC c program. The simulation models includes inverter, cable and

Fig. 7. Simulation results for the drive with RLC lter connected to the output of the inverter. Cable length: 20m. Phase-to-phase voltage waveforms.

Figs. 7 and 8 presents the simulation results obtained when a RLC lter is connected to the output of the inverter. One can observe a signicant reduction of the overvoltage at the motor terminals. For the common mode, it can be seen a reduction in frequency of oscillation of voltage and current. The common mode current peak was also reduced to about 50% of the nominal value. Figs. 9 and 10 presents the results when a RLC lter is connected to the inverter output with a coupling to the inverter DC bus. It can be observed, in this case, the signicant reduction of oscillations in the common

Fig. 10. Simulation results for the drive with RLC lter connected at the inverter output and coupled to the DC bus. Cable length: 20m. Common mode voltage at the motor and Common mode current waveforms.

Fig. 12. Simulation results for the drive with RLC lter connected at the inverter output and coupled to the DC bus, including common mode inductors. Cable length: 20m. Common mode voltage at the motor and Common mode current waveforms.

Fig. 11. Simulation results for the drive with RLC lter connected at the inverter output and coupled to the DC bus, including common mode inductors. Cable length: 20m. Phase-to-phase voltage waveforms.

motor representations. This model allows one to analyze the overvoltage phenomena at the motor terminals and the circulation of common mode currents. The model has made possible the analysis of lter topologies which are utilized to mitigate such phenomena. Simulation results were presented for a low voltage drive system. Filter topologies were also analyzed, demonstrating their capability to mitigate the overvoltage and circulation of common mode currents. Experimental results were also presented validating the simulation model developed showing good agreement. It can be concluded that the simulation model developed is viable to analyze the high frequency phenomena. Filter topologies that can mitigate, at the same time, overvoltage an common mode current phenomena were also analyzed in simulation and proved to be very effective way to reduce the common mode currents. These topologies are being developed in laboratory. Experimental results of these topologies will be presented in a future work. ACKNOWLEDGMENTS Acknowledgments should be made to the Laborat rio de o Aplicacoes Industriais - LAI, of the Department of Electrical Engineering, of the Universidade Federal de Minas Gerais UFMG, where the experimental results are being developed. Thanks also to the CNPq Agency for the nancial support.

Fig. 13. Experimental results for the drive system, 20m cable, without lter. Phase-to-phase voltage waveforms at the the output of the inverter and at the motor terminals.

Fig. 14. Experimental results for the drive system, 20m cable, without lter. Common mode voltage and common mode current waveforms. Current scale: 2 A / division.

Fig. 15. Experimental results for the drive system with 20m cable and RLC lter connected at the output of the inverter. Phase-to-phase voltage waveforms at the output of the inverter and motor terminals.

Fig. 16. Experimental results for the drive system with 20m cable and RLC lter connected at the output of the inverter. Common mode voltage and common mode current waveforms. Scale Current: 1 A / division

R EFERENCES
[1] E. Persson, Transient effects in application of pwm inverters to induction motors, IEEE Transactions on Industry Applications, vol. 28, no. 5, pp. 10951101, September/October 1992. [2] A. Bonnet, Analysis of the impact of pulse width modulated inverter voltage waveforms on ac induction motors, IEEE Transactions on Industry Applications, vol. 32, no. 2, pp. 386392, March/April 1996.

[3] G. Skibinski, J. Pankau, R. Sladky, and J. Campbell, Generation, control and reglation of emi from ac drives, IEEE Industry Application Society, pp. 15711583, October 1997. [4] G. L. Skibinski, R. J. Kerkman, and D. Schlegel, Emi emissions of modern pwm ac drives, IEEE Industry Applications Magazine, vol. 5, no. 6, pp. 4781, November/December 1999. [5] D. Busse, J. Erdman, R. J. Kerkman, D. Schlegel, and G. Skibinski, Characteristics of shaft voltage and bearing currents, IEEE Industry Applications Magazine, pp. 2132, November/December 1997. [6] S. Ogasawara and H. Akagi, Modeling and damping of high frequency leakage currents in pwm inverter-fed ac motor drive systems, IEEE, pp. 29 36, 1995. [7] A. von Jouanne, P. Enjeti, and W. Gray, Filtering techniques to minimize the effect of long motor leads on pwm inverter-fed ac motor drive systems, IEEE Transactions Industry Applications, vol. 32, no. 2, pp. 386392, March/April 1996. [8] G. L. Skibinski, Design methodology of a cable terminator to reduce reected voltage on ac motors, in IEEE Industry Application Society Annual Meeting, San Diego, CA, USA, October 1996. [9] L. Palma and P. Enjeti, An inverter output lter to mitigate dv/dt effects in pwm drive system, IEEE 17th APEC, pp. 550556, 2002. [10] A. F. Moreira, P. M. Santos, T. A. Lipo, and G. Venkataramanan, Filter networks for long cable drives and theirs inuence on motor voltage distribution and common-mode currents, IEEE Transactions on Industrial Electronics, vol. 52, no. 2, pp. 515522, April 2005. [11] D. Rendusara and P. Enjeti, New inverter output lter conguration reduces common mode and diferencial mode dv/dt at the motor terminals in pwm drive systems, Power Electronics Specialists Conference, pp. 12691275, 1997. [12] J. Yanshu, X. Diango, and C. Xiyou, A novel inverter output dv/dt supression lter, Industrial Electronics Society, pp. 29012905, 2003. [13] H. Akagi, H. Hasegawa, and T. Doumoto, Design and performance of a passive emi lter for use with a voltage-source pwm inverter having sinusoidal output voltage and zero common-mode voltage, IEEE Transactions on Power Electronics, vol. 19, no. 4, pp. 10691076, July 2004. [14] H. Akagi and T. Duomoto, An approach to eliminating high-frequency shaft voltage and leakage current from a inverter-driven motor, IEEE Transactions on Industry Applications, vol. 40, no. 4, pp. 1162 1169, July/August 2004. [15] , A passive emi lter for preventing high-frequency leakage current from owing through the grounded inverter heat sink of an adjustablespeed motor drive system, IEEE Transactions on Industry Applycations, vol. 41, no. 5, pp. 12121223, September/October 2005. [16] T. F. L. Milagres, A. F. Moreira, W. C. Boaventura, and H. de Paula, Implementation of distributed-parameter model of power cable in pscad/emtdc software, COBEP 2007 - IX Congresso Brasileiro em Eletr nica de Pot ncia, set/out 2007. o e [17] A. F. Moreira, T. A. Lipo, G. Venkataramanan, and S. Bernet, Highfrequency modeling for cable and induction motor overvoltage studies in long cable drives, IEEE Transactions on Industry Applications, vol. 38, no. 5, pp. 12971306, September/October 2002. [18] H. de Paula, M. L. R. Chaves, D. A. Andrade, M. A. A. Freitas, and J. L. Domingos, A simple and accurate cable modeling suitable for high-frequency phenomena analysis in pwm motor drives, IEEE, pp. 680687, 2005. [19] A. Boglietti and E. Carpaneto, Induction motor high frequency model, IEEE - IAS, pp. 15511558, Oct 1999.