Introduction
The purpose of this page is to allow you to understand the basics of means of escape and not how to design a means of escape from fire. There are many considerations, not covered here, in planning means of escape, but it will give insight in how a means of escapes are designed. It is based on the old prescriptive concepts but understanding these principles will help in appling the modern risk based methods.
Time of evacuation Travel distances Number of Occupants Calculation of Exit Widths Calculation of Minimum Number of Exits
Time of evacuation
Time of evacuation is dependent on on the following factors;
Class A - complete noncombustible construction, i.e. elements of structure, floors, and walls. Supporting structure of brick or concrete; Class B - traditional construction, i.e. noncombustible walls with
combustible floors; Class C - combustible construction, i.e. timber floors and walls.
Based on these classes arbitrary evacuation times were decided upon and the times that are generally accepted as -;
Class 'A' construction - 3 minutes Class 'B' construction - 2.5 minutes Class 'C' construction - 2 minutes
These are not hard and fast times, and can be extended or reduced according to the particular circumstances
Number of Occupants
You must consider the people normally in the building, and the those who may use the building. Number of Occupants The number of occupants for an existing building with a reasonably fixed population may be ascertained by questioning the responsible person who owns or occupies the building. For buildings such as theatres or cinemas, the number of seats provided should be counted. Density Factor In an unoccupied premises, to calculate the maximum numbers of people permissible in any given occupancy you must refer to density factors. The density factor may be defined as "the available floor space per person". Design codes for new buildings lay down specific density factors, which will vary, dependent upon the intended use of the floor space, i.e. lounge, restaurant, etc, check out the following documents,
To ascertain the maximum numbers of people, you need to calculate the floor space, delete the area of permanent features, i.e. stairs, toilets, lifts, escalators, corridors and other circulation spaces. What is left is the usable floor space and this is divided by the density factor giving you the number of person able to occupy that area. Persons who may use the building Occasional visitors to the building must be considered and in the case of shops
and departmental stores these people will out number the people normally occupying the premises. In the case of retail premises density factors will usually give the numbers other situations a fair estimate must be made. Calculating the Number of Occupants Consider a retail premises consisting of a sales floor canteen and offices. As different parts of the building are put to a different uses therefore it is necessary to use different density factors. To calculate the number of people, it is necessary to divide the floor area by the floor space allowed per person. Number of People = area of room or storey / floor space per person If floor space factors for the above example are: 1. Shop floor (main sales) - 2 m2 per person; 2. Offices - 5 m2 per person; 3. Canteen - 1 m2 per person; and the relevant floor areas are: 1. Shop floor - 20 m x 30 m = 600 m2 2. Offices space - 8 m x 8 m = 64 m2 3. Canteen - 8 m x l0 m = 80 m2. This is the total floor area - not the usable floor area. It is therefore necessary now to deduct the floor area of the permanent features in the area where they are situated 1. W.C. In shop = 10 m2 2. Stairs in shop = 15 m2 x 2 = 30 m2 3. W.C. In canteen = 10 m2. 1. Shop floor - 600 m2 - 40 m2 = 560 m2 2. Offices space - 64 m2 - 8 m = 64 m2 3. Canteen - 80 m2 x l0 m2 = 70 m2. Therefore, the total number of people for which escape routes must be designed is, 1. Shop = 560/2 = 280 2. Offices open plan = 64/5 = 13 3. Canteen = 70/1 = 70 TOTAL = 363 people
Travel Distance
Travel distance is measured from any point in the building to a place of safety (i.e. relative or ultimate). Travel distance will depend on how quickly people will react and make their escape and how long it will be before the fire prevents that movement to the escape route. Research done after the second world war came up with findings that people in smoke, escaping to a place, clear of smoke traveled 40 feet per minute therefore with an escape times of 2 minutes a person could travel 80 feet, 2.5 minutes 100 feet and 3 minutes 120 feet. It also showed that if the exit allowed one person to Pass to 40 persons could escape in a minute. These figures were accepted for sometime until codes of practice appeared giving various travel distances for deferent occupancies however they do reflect the post war studies. If a room or compartment has two or more exits preferably diametrical opposed, (Escape in more than one direction) then a person escaping can turn their back on the fire. If there is only one exit then a person may have to travel towards the fire (Escape in one direction only) consequently the travel distance is reduced.
BS 8300:2009. Design of buildings and their approaches to meet the needs of disabled people, gives guidance on means of escape for disabled people.
The result of this formula may well work out as a fraction, and if this fraction is greater than or equal to 0.75, it should be rounded up. Again, the + 1 in this formula is included to ensure that, in the event of the U/4 element being less than 0.75, then at least one exit would be provided to the room. In most codes of practice, however, it is the norm for 2 exits to be required situations in which rooms are occupied by more than 50 or 60 people, the reason being that the one exit required by the above formula could well - in the worst possible scenario - become blocked by the fire. Therefore, in addition to the formula, an additional exit equivalent to the largest size should be added; but where this is physically impracticable, the numbers permitted must be reduced. Example A traditionally constructed room has been designed to accommodate 710 people. How many units of exit are required, and what is the minimum number of exits. a) U = N / (40 x T) = 720 / (40 x 2.5) = 710 / 100 = 7.1 This fraction is less than 0.3 therefore it is rounded up to 7 units (b) E = U / 4 + 1 = 7 / 4 + 1 = 2.75 This fraction is equal to 0.75 therefore it is rounded up to 3 exits Therefore, the answer is that a minimum of 3 exits should be provided totaling 7 units, e.g. 2 x 2 units each + 1 x 3 units However, we must consider the possibility of one of these exits being obstructed by the fire, with the worst case being one of the largest being lost. In our example, this would leave us with 2 exits of 2 units each leaving just 4 units to discharge 710 people. Therefore, keeping the exits as they are, these remaining exits would need to be increased in size to accommodate our 710 people, and in this case we would need to increase each exit to be 4 units wide (i.e. 1950 mm each) in order to ensure the evacuation of our 710 people. Therefore, by now providing 3 exits of 4 units width each, we have allowed for one exit being blocked but still leave 8 units available for the evacuation, which is now a greater capacity than is required. A further adjustment could allow for one of the units to be a 3-unit exit that would leave us with 7 units for evacuation - which is satisfactory. We can transpose the formula for the number of units to N = U x 40 x T in order
to arrive at the maximum number of occupants allowed. The distribution of alternative exits is important so as to ensure that they can be effectively used in case one is blocked due to a fire nearby. This is achieved by ensuring that the alternatives are further apart than an angle of 45 from the farthest point in the room from the exit.
Time of evacuation Travel distances Number of Occupants Calculation of Exit Widths Calculation of Minimum Number of Exits
Whilst these factors are present in all cases, it is not so obvious that their importance will vary according to the circumstances. Sometimes one, sometimes another, will assume greater importance in your assessments and subsequent solution. For example, a precast concrete manufacturer housed in a single storey building constructed entirely of noncombustible materials. Because of the construction, your considerations will probably centre upon maximum travel distance to an exit within a reasonable period of time. Now consider a manufacturer using highly flammable materials, you would be looking for a rapid evacuation in a very short time and the fact that the building is completely noncombustible has little, effect. In new building, and the occupancy is unknown the differences required between the above two situations are considerable, and this can cause great difficulty in planning means of escape. In such cases, the means of escape must be designed to cater for the worst possible case. Having considered the factors that will influence escape, and having seen how these can be related to building type, it is important to look at the stages in the process of escape and the maximum distances people can be expected to travel. Escape is generally considered in four distinct 'Stages' as follows Stage 1 - escape from the room or area of fire origin
Stage 2 - escape from the compartment of origin via the circulation route to a protected stairway or an adjoining compartment offering refuge Stage 3 - escape from the floor of origin to the ground level Stage 4 - escape at ground level away from the building. You need to study each floor plan and consider each room or compartment, deciding if the travel distance from the furthest point of that room or compartment to a place of comparative or ultimate safety is less than the maximum travel distance. You need to then calculate the number of occupants and ascertain if the exits from the room or compartment to a place of comparative or ultimate safety is adequate