Product

Data

38AH024-134
Commercial Air-Cooled
Condensing Units
With 40RM016-034
Air-Handling Units
20 to 130 Nominal Tons

This catalog describes the full range


of versatile 38AH condensing units.
For 38AH sizes 024-034, this catalog
also describes matching Carrier
40RM air handlers, and gives combined ratings for these 38AH/40RM
systems. All 38AH condensing units
can also be matched to Carriers
39 Series air handlers. See the applicable product data catalogs or use
Carriers exclusive E-CAT II software
to select these matching indoor units.

Features/Benefits
Up to 4 compressors and 2
independent refrigerant circuits provide design flexibility; condensing unit can
supply one or 2 air handlers
Efficient 38AH Series units
save energy, providing condensing unit EERs up to 11.6
Variable air volume units
operate at as low as 8% of
nominal capacity without the
use of energy-inefficient hot
gas bypass
Constant volume units operate at as low as 16% of nominal capacity (standard) or
8% of nominal capacity (with
accessory unloader)
Weatherized steel cabinet
ensures corrosion protection
Protection against high discharge and low suction refrigerant pressure, and low
oil pressure ensure compressor reliability
Crankcase heaters prevent
oil dilution and ensure
compressor lubrication
Copyright 1995 Carrier Corporation

Form 38AH-4PD

The 38AH condensing unit offers the


utmost in system configuration and
control adaptability. Its premiumquality standard components ensure
durable, efficient operation.

Versatility
38AH Series condensing units feature
up to 4 compressors and 2 refrigerant circuits, and can be matched with
a wide variety of air-handling units.
All condensing unit circuits can supply
a single air handler or 2 separate air
handlers.
Standard units have constant volume control. A variable air volume
(VAV) option is available. VAV units
have electric unloaders on the compressors to closely match building
loads. The VAV option requires only a
simple connection to the Carrier
ModuPanel discharge air controller,
thereby saving installation time and
cost. (NOTE: Unit sizes 024-034
require field supplied and installed
accumulator.)
Durable construction
All 38AH units have weatherized cabinets constructed of heavy-duty galvanized steel prepainted with corrosionresistant baked enamel. Inside and
outside surfaces are protected to ensure long life and good looks. The
units exceed the requirements of the
Federal Test Method Standard
No. 141 (Method 6061) 500-hour salt
spray test.
The units coils have aluminum fins
mechanically bonded to copper tubes
for long-term reliability and improved
heat transfer. Copper fins on copper tubes are available for harsh
industrial or coastal conditions.
Reliability
The 38AH condensing units feature
time-proven, highly reliable 06D and
06E semi-hermetic compressors.
Unloading capability is a standard feature on the lead compressor of each
circuit. Each compressor has vibration
isolators to provide quiet operation
and reduced component stress.
Because 38AH units have 2 independent circuits, they provide inherent
backup capability. Each circuit is also
protected by the following safety
features:
Time Guardt anti-short-cycling
device
low oil pressure safety switch
low refrigerant pressure switch
(suction)
2

Quick installation is ensured by the


multipoise design. Units can be installed in either the horizontal or vertical configuration without modifications.
All units have drain-pan connections
Easier installation and service
on both sides, and pans can be
38AH units are equipped with hinged
pitched for right- or left-hand operacontrol-box access doors, liquid line
tion with a simple adjustment. Fan
shutoff valves, and service valves
motors and contactors are prewired
on the compressors.
and thermostatic expansion valves
Larger 38AH124 and 134 size
(TXVs) are factory-installed on all
units are shipped as 2 modules for
40RM models.
easier handling and rigging.
High efficiency, precision-balanced
fans minimize air turbulence, surgInnovative Carrier 40RM airing, and unbalanced operation, cutting
handling units in sizes 016operating expenses.
034: ideal matches for
The economizer accessory precisely
38AH024-034 condensing
controls the blend of outdoor air and
units
room air to achieve comfort levels.
The 40RM Series has excellent fan
performance, efficient direct-expansion When the outside air enthalpy is suitable, outside air dampers can fully
(DX) coils, a unique combination of
open to provide free cooling.
indoor air quality features, and easy
installation. Its versatility and state-ofRugged dependability
the-art features help to ensure that
40RM units are made to last. The dieyour split system provides economical
formed galvanized steel panels enperformance now and in the future.
sure structural integrity under all operaIndoor-air quality (IAQ) features ting conditions. Galvanized steel fan
housings are securely mounted to a
The unique combination of IAQ feadie-formed galvanized steel deck.
tures in the 40RM Series air hanMechanically bonded coil fins provide
dlers helps to make sure that only
improved heat transfer. Rugged
clean, fresh, conditioned air is delivpillow-block bearings are securely fasered to the occupied space.
tened to the solid steel fan shaft
Direct-expansion (DX) cooling coils
prevent the build-up of humidity in the with split collets and clamp locking
devices.
room, even during part-load conditions. The 016-034 sizes feature dual- Coil flexibility
circuit coils.
Model 40RM direct-expansion coils
Standard 2-in. disposable filters
have galvanized steel casings; inlet
remove dust and airborne particles
and outlet connections are on the
from the occupied space.
same end. The coils are designed for
Thermal insulation contains an
use with Refrigerant 22 and have
38-in. diameter copper tubes mechaniimmobilized anti-microbial agent to
inhibit the growth of bacteria and
cally bonded to aluminum sine-wave
fungi. The anti-microbial agent is regfins. The coils include matched,
istered with the U.S. Environmental
factory-installed TXVs with matching
Protection Agency (EPA).
distributor nozzles. Accessory hot
The pitched PVC drain pan can be
water and steam coils and electric heatadjusted for a right- or left-hand coners are also available.
nection to provide positive drainage
Easier installation and service
and to prevent standing condensate.
The multipoise design and component
The 40RM accessory economizer
layout help you to get the unit incan provide ventilation air to improve
stalled and running quickly. The DX
indoor-air quality. When used with
coils have factory-installed TXVs with
CO2 sensors, the economizer admits
matching distributor nozzles. Units can
fresh outdoor air to replace stale,
be converted from horizontal to vertirecirculated indoor air.
cal operation by simply repositionEconomy
ing the unit. Drain pan connections
The 40RM Series packaged air hanare duplicated on both sides of the
dlers have low initial costs, and they
unit. The filters, motor drive, TXVs,
continue to save money by providand coil connections are all easily
ing reduced installation expense and
accessed by removing a single side
energy-efficient performance.
panel.
high refrigerant pressure switch
(discharge)
calibrated circuit breakers for compressors and outdoor fans

40RM016-034

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Model Number Nomenclature 38AH024-034/40RM . . . . . . . . . . . . . . . 4,5
ARI Capacities 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options and Accessories 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options and Accessories 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Physical Data 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Physical Data 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
Selection Procedure 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . 13
Performance Data 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . 14-20
Typical Piping and Wiring 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . 21,22
Electrical Data 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . 23,24
Controls 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Typical Control Wiring 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . 26,27
Application Data 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28,29
Application Data 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30,31
Model Number Nomenclature 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . 32
Ratings Summary 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Options and Accessories 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Physical Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34,35
Dimensions 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-42
Condensing Unit Selection Procedure 38AH044-134 . . . . . . . . . . . . . . . . 43
System Selection Procedure 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . 43
Performance Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-50
Typical Piping and Wiring 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . 51,52
Electrical Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-55
Controls 38AH044-084 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Controls 38AH094-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Typical Control Wiring 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . 58-60
Application Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61-67
Guide Specifications 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68,69
Guide Specifications 40RM016-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70,71
Guide Specifications 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72-74

Model number nomenclature


38AH024-034/40RM

*Size 034 units use 10 Hp motor only; YC and WD option codes for
034 size designate standard motor and high-static drive.

ARI* capacities 38AH024-034/40RM


UNIT 38AH

024
028
034

INDOOR AIR
HANDLER

AIR HANDLER
AIRFLOW
(Cfm)

40RM016
40RM024
40RM028
40RM024
40RM028
40RM034
40RM028
40RM034

6,000
8,000
8,750
8,000
10,000
12,000
10,000
12,000

SYSTEM
Net Capacity
EER
(Btuh)
208,000**
9.3**
222,000**
9.2**
236,000**
9.8**
250,000
9.0
267,000
9.3
278,000
9.0
301,000
9.0
317,000
8.9

LEGEND
EER Energy Efficiency Ratio
IPLV Integrated Part Load Value
SST Saturated Suction Temperature

IPLV
9.5**
9.2**
9.9
9.2
9.2
9.2
9.1
9.1

CONDENSING UNIT ONLY


Net Capacity
EER
IPLV
(Btuh)
251,000

11.6

13.0

290,000

11.2

12.9

344,000

11.1

12.9

NOTE: All systems with 38AH028 and 034 units are above the ARI 360-86
maximum certification capacity for 240,000 Btuh systems. These systems are tested and rated in accordance with the rating procedures for
ARI 360.

*Air Conditioning and Refrigeration Institute.


ARI directory listed (ARI Standard 365-87). Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.
**ARI directory listed (ARI Standard 360-86).

Options and accessories 38AH024-034


Factory-installed options
VAV option provides unit with 2 electric unloaders and
control box modifications necessary to connect to a fieldinstalled ModuPanel control.

Field-installed accessories
Pressure-operated unloading allows compressors to be
unloaded in response to compressor suction pressure.
Electric unloader package includes hardware and solenoid valve to convert a pressure-operated unloader to electric unloading.
20 F low-ambient temperature kit (Motormastert
III) controls outdoor-fan motor operation to maintain the
correct head pressure at low outdoor ambient temperatures. Only one low ambient temperature kit is required per
unit.

Gage panel package provides a suction and a discharge


pressure gage for one refrigerant circuit.
ModuPanel control box allows 38AH system to operate
VAV system. Includes microprocessor satellite sequencer, 4
status lights, 5-hour bypass timer, and locked enclosure. Requires field-installed accumulator.
Carrier electronic programmable thermostats provide 2-stage heat and 2-stage cooling control with remote
communication ability.
Winter start package provides a timed bypass of lowpressure switch on start-up.

Options and accessories 40RM


Factory-installed options
Prepainted steel units are available from the factory for
applications that require painted units. Units are painted
with American Sterling Gray color.
Alternate fan motors and drives are available to provide the widest possible range of performance.

Field-installed accessories
Discharge plenum directs the air discharge directly into
the occupied space; integral horizontal and vertical louvers
enable redirection of airflow. Accessory is available unpainted or painted.
Two-row hot water coils have 58-in. diameter copper
tubes mechanically bonded to aluminum plate fins. Coils
have non-ferrous headers.
One-row steam coil has 1-in. OD copper tube and aluminum fins. The Inner Distributing Tube (IDT) design provides uniform temperatures across the coil face. The steam
coil has a broad operating pressure range; up to 175 psig
at 400 F and up to 300 psig at 300 F. IDT steam coils are
especially suited to applications where sub-freezing air enters the unit.
Electric resistance heat coils have an open-wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard.

Economizer (enthalpy controlled) provides ventilation


air and free cooling if outside ambient temperature and
humidity are suitable. Can also be used with CO2 sensors
to help meet indoor air quality requirements.
Return-air grille provides a protective barrier over the
return-air opening and gives a finished appearance to units
installed in the occupied space. Accessory is available unpainted or painted.
Subbase provides a stable, raised platform and room
for condensate drain connection for floor-mounted units.
Accessory is available unpainted or painted.
Overhead suspension package includes necessary brackets to support units in horizontal ceiling installations.
Carrier Comfort System electronic programmable
thermostats provide 2-stage cooling control and 2-stage
heat control with remote communication ability.
CO2 sensors can be used in conjunction with the economizer accessory to help meet indoor air quality requirements. The sensor signals the economizer to open when
the CO2 level in the space exceeds the set point. A Carrier
Comfort System programmable thermostat can also be used
to override the sensor if the outside air temperature is too
high or too low.

Physical data 38AH024-034


38AH024-034 UNITS
UNIT 38AH
NOMINAL CAPACITY (tons)*
OPERATING WEIGHT (lb)
With Aluminum-Fin Coil
With Copper-Fin Coil
COMPRESSOR
Type
Quantity Cylinders (ea)
Speed (rpm)
Capacity Steps
(FIOP or Acy) %
%
%
Unloader Setting (psig)
Load
Unload
OIL CHARGE PER CIRCUIT (Pt)
REFRIGERANT, TYPE
Shipping Charge (lb)
Operating Charge, Typical (lb)
CONDENSER FANS
Quantity...Dia (in.)
Nominal Hp
Nominal Airflow (cfm)
Speed (rpm)
Watts (ea)
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
Storage Cap. (lb) |
CONTROLS
Pressurestat (psig)
High Pressure
Cutout
Cut-in
Low Pressure
Cutout
Cut-in
Oil Pressure
Cutout (Diff)
Cut-in (Diff)
FAN CYCLING CONTROLS
No. 2 Fan:
Temp Close (F)
Temp Open (F)
PRESSURE RELIEF
Location
Temp (F)
CONNECTIONS (Sweat) (Ea ckt)
Suction in. OD
Liquid in. OD
Hot Gas Bypass in. OD

024
Ckt 1

028
Ckt 2

Ckt 1

Ckt 1

Ckt 2

20

25

30

1760
1923

1820
1982
Reciprocating Semi-Hermetic
06DH328
06DA328
6
6
1750
1750

1880
2097

06DH824
6
1750

06DA824
6
1750

100
67
33**

100

76
58

3
20
2...30
1.0
16,700

2...19
39.20
37.7

06DH328
6
1750

100
100
100
67

67
33**

33**
Factory Installed

76

76

58

58
10
R-22
3
3
3
3
20
20
20
25
Propeller Type Direct Driven
2...30
1.0
16,700
1140
1550
Enhanced Copper Tubes, Lanced Aluminum Fins
2...19
39.20
37.7

426 6 7
320 6 20
27 6 3
44 6 5
Manual Reset
6.0
8.8
70 6 3
60 6 3
Fusible Plug
Liquid Line, Suction Line, Compressor
210

LEGEND
Diff Differential
FIOP Factory-Installed Option
VAV Variable Air Volume
*Rating conditions are 80 F db, 67 F wb at 95 F ambient temperature.
VAV FIOP double electrically actuated unloaders on compressor no. 1.
**Standard unit single suction pressure-actuated unloader on compressor no. 1.
With 25 ft of interconnecting piping.
\ Condenser 80% full of liquid R-22 at 120 F.
NOTE: Refer to Unloading Sequences table, page 28 for additional capacity step data.

034
Ckt 2

138
58
58

06DA537
6
1750
100

3
25
2...30
1.0
15,700

3...17
39.20
56.6

Physical data 40RM


40RM016-034 UNITS
UNIT 40RM
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT (lb)
Base Unit with TXV
Plenum
FANS
Qty...Diam. (in.)
Nominal Airflow (cfm)
Airflow Range (cfm)
Nominal Motor Hp (Standard Motor)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
Motor Speed (rpm)
208/230-1-60
208/230-3-60 and 460-3-60
575-3-60
REFRIGERANT
Operating charge (lb)
(approx per circuit)*
DIRECT-EXPANSION COIL
Max Working Pressure (psig)
Face Area (sq ft)
No. of Splits
Split Type...Percentage
No. of Circuits per Split
Rows...Fins/in.
STEAM COIL
Max Working Pressure (psig at 400 F)
Total Face Area (sq ft)
Rows...Fins/in.
HOT WATER COIL
Max Working Pressure (psig)
Total Face Area (sq ft)
Rows...Fins/in.
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil Suction (ODF)
DX Coil Liquid Refrigerant (ODF)
Steam Coil, In (MPT)
Steam Coil, Out (MPT)
Hot Water Coil, In (MPT)
Hot Water Coil, Out (MPT)
Condensate (Male PVC)
FILTERS
Quantity...Size (in.)
Access Location

016
15

024
20

028
25

034
30

685
140

690
140

1020
180

1030
180

2...15
6000
4500-7500

2...15
8000
6000-10,000

2...18
10,000
7500-12,500

2...18
12,000
9000-15,000

3.7
3.0

5.0
5.0

7.5
7.5

10.0
10.0

1725
1725

1745
1745

1745
1755

1745
1755

2.5/2.5

3.5/3.5

4.5/4.5

5.0/5.0

R-22

17.67
2
12
3...15

Enhanced Copper Tubes; Aluminum Sine-Wave Fins


435
19.88
24.86
2
2
Face...50/50
13
15
3...17
3...15

29.83
2
18
3...15

175
13.33
1...10

13.33
1...10

13.33
2...8.5

13.33
2...8.5

2...118

2...118

15.0
1...10

15.0
1...10

15.0
2...12.5

15.0
2...12.5

150

2...138
2...138
2...58
2...212
2...212
2...2
2...2
1...114
Throwaway Factory Supplied
4...16 x 20 x 2
4...20 x 24 x 2
4...16 x 24 x 2
4...20 x 25 x 2
Either Side

LEGEND
TXV Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

Dimensions 38AH024-034

NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all
sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space above unit.
3. C in the package number indicates copper coils.
4. Dimensions in [ ] are in millimeters.
5. The approximate operating weight of the unit is shown below.
6. Certified dimensional drawing is available on request.

CORNER WEIGHT lbs [kg]


UNIT
38AH

024
024C
028
028C
034
034C

10

631.6
[286.5]
666.5
[302.3]
658.7
[298.8]
693.0
[314.3]
667.0
[302.5]
718.3
[325.8]

577.6
[262.0]
609.5
[276.5]
602.4
[273.3]
633.8
[287.5]
610.0
[276.7]
656.8
[297.9]

263.1
[119.3]
309.0
[140.2]
267.0
[121.1]
313.0
[142.0]
288.0
[130.7]
344.8
[156.4]

287.7
[130.5]
337.9
[153.3]
291.9
[132.4]
342.2
[155.2]
315.0
[142.9]
377.0
[171.0]

CENTER OF
GRAVITY
A Dim.
in.
[mm]
40.00
[1016]
43.00
[1092]
39.25
[997]
42.25
[1073]
41.00
[1041]
44.00
[1117]

B Dim.
in.
[mm]

32.75
[832]

TOTAL
UNIT WT
lb [kg]
1760
[798.3]
1923
[872.3]
1820
[825.6]
1982
[899.0]
1880
[853.0]
2097
[951.2]

Dimensions 40RM
40RM016,024

UNIT
40RM
016
024

UNIT WEIGHT
(lb)
685
690

NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
Rear: 39
Front: 28-69
Right side: 28-69
Left Side: 28-69
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

11

Dimensions 40RM (cont)


40RM028,034

UNIT
40RM
028
034

UNIT WEIGHT
(lb)
1020
1030

NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
Rear: 39
Front: 28-69
Right side: 28-69
Left Side: 28-69
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

12

Selection procedure 38AH024-034/40RM


NOTE: Pages 16 and 17 contain combination ratings for
38AH024-034 units and matching 40RM air handlers. If
the 38AH units are matched with 39L or 39NX air handlers, use the Carrier Electronic Catalog ACAPS software
package for combination ratings. If Totalinet P702 water
coolers are used, determine the performance by crossplotting the condensing unit performance found in this book
against the P702 performance in the P702 product data
book. If the 38AH condensing units are matched with 2 independent 40RM units, cross-plot for performance ratings
or contact Carrier Application Engineering for assistance.
I Determine cooling load, evaporator-air temperature and quantity.
Given:
Total Cooling Capacity
Required (TC) . . . . . . . . . . . . . . . . . . 235,000 Btuh
Sensible Heat Capacity
Required (SHC) . . . . . . . . . . . . . . . . . 185,000 Btuh
Temperature Air Entering
Condenser (Edb) . . . . . . . . . . . . . . . . . . . . . . . . 95 F
Temperature Air Entering
Evaporator (db/wb) . . . . . . . . . . . 80 F db, 67 F wb
Evaporator Air Quantity . . . . . . . . . . . . . . . 8000 cfm
External Static Pressure . . . . . . . . . . . . . . 0.80 in. wg
Length of Interconnecting
Refrigerant Piping . . . . . . . . . . . . . . . . 30 ft (Linear)

II Select condensing unit air-handler combination.


For this example, select a 38AH024 matched with a
40RM024. (See Combination Ratings table, page 16.)
This 38AH024/40RM024 condensing unit-air handler combination provides 237,200 Btuh of total cooling capacity and 188,600 Btuh of sensible capacity at
the given conditions. If other temperatures or airflow
values are required, interpolate the values from the combination ratings.
III Determine sizes of liquid and suction lines.
Enter the Refrigerant Pipe Sizes table (page 29). The
sizes shown are based on an equivalent length of pipe.
This equivalent length is equal to the linear length of
pipe indicated at the top of each sizing column, plus a
50% allowance for fitting losses. (For a more accurate
determination of actual equivalent length in place of
using the estimated 50% value, refer to Carrier System Design Manual.) For this example, note in the linear length column that the proper pipe size is 58 in.
for the liquid lines and 138 in. for the suction lines.
IV Determine fan rpm and bhp (brake horsepower).
At the Air Handler Fan Performance table (page 18),
enter the 40RM024 section at 8000 cfm and move to
the External Static Pressure (ESP) column. Note that
the conditions require 904 rpm at 3.86 bhp. Select
the standard motor and medium-static drive (option code
HC or FD).

13

Performance data 38AH024-034/40RM


CONDENSING UNIT RATINGS
38AH024

38AH034

SST
(F)
20
25
30
35
40
45
50

TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW

85
157
105
14.1
178
106
14.7
198
107
15.3
221
109
15.9
244
111
16.6
270
113
17.2
295
116
17.8

Air Temp Ent Condenser (F)


95
100
105
143
136
129
115
120
125
14.9
15.2
15.5
163
156
149
116
121
126
15.6
16.0
16.4
183
176
168
117
121
126
16.3
16.8
17.3
205
197
189
118
123
128
17.1
17.6
18.1
227
219
210
120
125
129
17.9
18.5
19.0
251
243
233
122
127
131
18.6
19.3
19.9
276
266
257
125
129
133
19.4
20.1
20.8

115
115
135
16.0
134
135
17.0
153
135
18.1
173
137
19.1
193
138
20.1
215
140
21.1
237
142
22.1

38AH028
SST
(F)
20
25
30
35
40
45
50

14

TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW

85
187
107
17.1
209
109
17.9
231
111
18.7
256
113
19.5
282
115
20.3
310
118
21.1
338
120
22.0

Air Temp Ent Condenser (F)


95
100
105
173
167
160
116
121
126
18.1
18.6
19.1
194
187
180
118
123
127
19.1
19.6
20.1
216
208
200
120
124
129
20.0
20.6
21.2
239
231
223
122
126
131
20.9
21.6
22.2
263
254
245
124
128
133
21.9
22.6
23.3
290
280
271
126
131
135
22.8
23.6
24.4
317
306
296
129
133
138
23.8
24.6
25.5

115
147
135
19.9
166
137
21.1
185
138
22.2
206
140
23.4
228
142
24.6
252
144
25.9
275
146
27.1

SST
(F)
20
25
30
35
40
45
50

TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW

85
223
107
21.2
249
109
22.2
276
110
23.1
307
112
24.2
336
115
25.3
369
117
26.3
402
120
27.4

Air Temp
95
206
117
22.5
232
118
23.6
258
119
24.7
287
121
25.9
314
123
27.1
346
126
28.3
378
128
29.6

Ent Condenser
100
105
199
190
122
127
23.1
23.7
224
215
123
128
24.2
24.9
249
241
124
129
25.4
26.2
277
267
126
130
26.7
27.6
305
294
128
132
28.0
28.9
335
324
136
135
29.3
30.3
366
354
133
137
30.6
31.7

LEGEND
kW Compressor Power
SDT Saturated Discharge Temperature
at Compressor (F)
SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)

115
175
137
24.8
209
137
26.2
222
138
27.6
248
140
29.0
274
141
30.5
302
144
32.0
330
146
33.6

CONDENSING UNIT RATINGS (cont)


38AH024 CIRCUIT NO. 1 OR 2*
Air Temp Ent Condenser (F)
SST
(F)
85
95
100
105
TC
78
71
68
65
20
SDT
105
115
120
125
kW
7.03
7.44
7.61
7.76
TC
89
82
78
74
25
SDT
106
116
121
126
kW
7.34
7.80
8.01
8.20
TC
99
92
88
84
30
SDT
107
117
121
126
kW
7.65
8.17
8.41
8.63
TC
111
103
99
95
35
SDT
109
118
123
128
kW
7.96
8.55
8.82
9.07
TC
122
114
109
105
40
SDT
111
120
125
129
kW
8.28
8.93
9.23
9.52
TC
135
126
121
117
45
SDT
113
122
127
131
kW
8.59
9.30
9.64
9.96
TC
148
138
133
128
50
SDT
116
125
129
133
kW
8.90
9.68
10.0
10.4
38AH028 CIRCUIT NO. 1 OR 2*
Air Temp Ent Condenser (F)
SST
(F)
85
95
100
105
TC
93
87
83
80
20
SDT
107
116
121
126
kW
8.55
9.07
9.31
9.54
TC
104
97
94
90
25
SDT
109
118
123
127
kW
8.95
9.53
9.80
10.1
TC
116
108
104
100
30
SDT
111
120
124
129
kW
9.35
9.99
10.3
10.6
TC
128
120
116
111
35
SDT
113
122
126
131
kW
9.76
10.5
10.8
11.1
TC
141
132
127
123
40
SDT
115
124
128
133
kW
10.2
10.9
11.3
11.6
TC
155
145
140
135
45
SDT
118
126
131
135
kW
10.6
11.4
11.8
12.2
TC
169
158
153
148
50
SDT
120
129
133
138
kW
11.0
11.9
12.3
12.7

115
58
135
8.01
67
135
8.52
77
135
9.03
87
137
9.54
97
138
10.0
108
140
10.6
119
142
11.1

38AH034 CIRCUIT NO. 1


Air Temp Ent Condenser (F)
SST
(F)
85
95
100
105
TC
93
85
82
78
20
SDT
105
115
120
125
kW
8.69
9.26
9.53
9.78
TC
105
97
93
89
25
SDT
106
116
121
125
kW
9.02
9.64
9.94
10.2
TC
117
109
105
101
30
SDT
107
116
121
126
kW
9.34
10.0
10.3
10.7
TC
131
122
117
113
35
SDT
109
118
123
127
kW
9.70
10.5
10.8
11.2
TC
144
134
130
125
40
SDT
111
120
124
129
kW
10.1
10.9
11.3
11.7
TC
159
148
143
138
45
SDT
113
122
127
131
kW
10.4
11.3
11.7
12.2
TC
174
163
157
152
50
SDT
116
124
129
133
kW
10.8
11.8
12.2
12.7

115
71
135
10.2
81
135
10.8
92
135
11.3
104
137
11.8
116
138
12.4
128
140
12.9
141
142
13.5

115
74
135
9.97
83
137
10.5
93
138
11.1
103
140
11.7
114
142
12.3
126
144
12.9
138
146
13.5

38AH034 CIRCUIT NO. 2


Air Temp Ent Condenser (F)
SST
(F)
85
95
100
105
TC
130
121
117
112
20
SDT
109
118
123
128
kW
12.5
13.2
13.6
13.9
TC
144
135
131
126
25
SDT
111
120
124
129
kW
13.2
14.0
14.3
14.7
TC
159
149
144
140
30
SDT
113
122
126
131
kW
13.8
14.7
15.1
15.5
TC
176
165
160
154
35
SDT
115
124
128
133
kW
14.5
15.4
15.9
16.4
TC
192
180
175
169
40
SDT
118
126
131
135
kW
15.2
16.2
16.7
17.2
TC
210
198
192
186
45
SDT
120
129
133
138
kW
15.9
17.0
17.6
18.1
TC
228
215
209
202
50
SDT
123
132
136
140
kW
16.6
17.8
18.4
19.0

115
104
138
14.6
117
139
15.4
130
140
16.3
144
142
17.2
158
144
18.1
174
147
19.1
189
149
20.1

LEGEND
kW Compressor Power
SDT Saturated Discharge Temperature
at Compressor (F)
SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)
*Circuits no. 1 and 2 on 38AH024 and 028 have identical capacities.

15

Performance data 38AH024-034/40RM (cont)


COMBINATION RATINGS
38AH024/40RM016
Temp (F)
Air Entering
Condenser
(Edb)
85

95

100

105

115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

38AH024/40RM028

Evaporator Air Cfm/BF


4500/0.03
6000/0.05
7500/0.08
Evaporator Air Ewb (F)
72
67
62
72
67
62
72
67
62
231.9 209.9 244.2 223.5 203.7 252.5 232.4 213.2
113.4 139.3 127.0 161.0 203.7 138.6 179.7 213.2
16.32 15.81 16.61 16.13 15.67 16.80 16.33 15.89
222.4 202.0 233.6 214.6 196.4 241.3 222.8 205.5
110.0 135.8 123.0 156.7 196.3 134.6 174.9 205.5
17.77 17.17 18.09 17.54 17.01 18.32 17.78 17.27
217.8 197.6 179.2 228.6 210.0 192.1 236.2 218.0 201.3
108.4 133.8 171.6 121.1 154.4 192.1 132.8 172.5 201.3
18.46 17.79 17.17 18.82 18.20 17.60 19.07 18.47 17.91
212.4 193.1 175.3 222.6 204.9 187.9 229.9 212.5 196.8
106.5 131.8 168.2 118.9 152.0 187.9 130.5 169.7 196.8
19.09 18.34 17.64 19.49 18.80 18.13 19.78 19.10 18.48
202.0 183.9 167.1 211.3 194.8 179.0 218.2 201.9 187.8
102.8 127.6 161.0 114.6 147.1 179.0 126.4 164.4 187.7
20.51 19.68 18.92 20.93 20.18 19.46 21.25 20.50 19.86

38AH024/40RM024
Temp (F)
Air Entering
Condenser
(Edb)
85

95

100

105

115

BF
Ewb
kW
SHC
TC

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

LEGEND
Bypass Factor
Entering Wet-Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.

79
81

0.10
0.20
0.30

0.99
0.88
0.77

ENTERING-AIR DRY-BULB TEMP (F)


78
77
76
75
under 75
82
83
84
85
over 85
Correction Factor
1.98
2.97
3.96
4.95
Use formula
1.76
2.64
3.52
4.40
shown at right.
1.54
2.31
3.08
3.85

Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).

16

85

95

100

105

115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Evaporator Air Cfm/BF


10,000/0.06
12,500/0.08
Evaporator Air Ewb (F)
62
72
67
62
72
67
62
235.5 289.1 265.4 250.7 294.9 274.8 263.5
232.0 170.2 223.7 250.7 190.0 252.2 263.5
16.40 17.64 17.09 16.75 17.77 17.31 17.05
225.7 275.0 252.3 240.3 279.9 261.3 252.5
223.0 165.2 218.3 240.3 185.0 246.4 252.2
17.86 19.30 18.64 18.29 19.44 18.90 18.64
220.9 269.4 246.7 235.6 274.2 255.7 247.8
218.6 163.2 216.0 235.6 183.1 243.9 247.8
18.56 20.18 19.42 19.05 20.34 19.72 19.46
215.4 261.6 239.5 229.7 266.1 248.3 241.6
213.5 160.5 213.1 229.7 180.4 240.7 241.6
19.21 21.02 20.15 19.77 21.19 20.50 20.24
204.7 248.0 226.4 218.8 251.8 235.0 230.3
203.7 155.7 207.7 218.7 175.6 234.9 230.3
20.63 22.60 21.62 21.27 22.77 22.01 21.80

7500/0.04
72
278.4
149.6
17.39
265.2
144.8
19.01
259.8
142.8
19.86
252.5
140.1
20.66
239.5
135.4
22.21

67
254.6
191.9
16.85
242.4
187.0
18.35
237.0
184.8
19.10
230.2
182.1
19.79
217.6
177.0
21.22

38AH028/40RM024

Evaporator Air Cfm/BF


6000/0.03
8000/0.06
10,000/0.07
Evaporator Air Ewb (F)
72
67
62
72
67
62
72
67
62
258.1 236.6 215.6 269.7 248.5 229.3 276.2 257.0 240.4
132.6 167.1 207.7 149.3 193.3 229.3 163.9 217.2 240.4
16.93 16.43 15.94 17.19 16.70 16.26 17.34 16.90 16.52
246.6 226.4 207.2 257.1 237.2 220.4 262.7 245.2 231.0
128.2 162.9 200.5 144.8 188.6 220.4 159.2 211.8 230.9
18.47 17.88 17.32 18.78 18.20 17.71 18.94 18.43 18.02
241.5 221.5 202.7 251.9 232.0 215.9 257.2 239.9 226.4
126.2 160.9 196.5 142.8 186.4 215.9 157.3 209.4 226.4
19.25 18.58 17.96 19.59 18.93 18.40 19.77 19.20 18.75
235.1 215.8 197.9 244.9 225.7 210.8 249.8 233.3 221.1
123.8 158.5 192.4 140.3 183.7 210.8 154.6 206.4 221.1
19.98 19.23 18.53 20.37 19.61 19.03 20.56 19.91 19.43
223.2 204.7 188.3 232.3 213.8 200.8 236.5 221.1 210.9
119.3 154.0 184.0 135.8 178.7 200.8 150.0 200.8 210.9
21.47 20.63 19.89 21.89 21.04 20.45 22.08 21.38 20.91

BYPASS
FACTOR

Temp (F)
Air Entering
Condenser
(Edb)

Temp (F)
Air Entering
Condenser
(Edb)
85

95

100

105

115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Evaporator Air Cfm/BF


8000/0.06
10,000/0.07
Evaporator Air Ewb (F)
62
72
67
62
72
67
62
294.8 272.1 248.7 302.9 281.2 260.2
158.4 203.3 248.7 173.3 228.3 260.2
20.66 20.02 19.35 20.90 20.28 19.68
225.1 282.4 260.5 239.2 289.7 269.3 250.5
216.1 153.9 198.4 239.2 168.7 222.8 250.5
20.64 22.55 21.82 21.11 22.79 22.11 21.48
221.0 276.1 254.8 234.7 283.0 263.4 245.8
212.5 151.6 196.0 234.7 166.3 220.1 245.8
21.33 23.45 22.63 21.86 23.71 22.96 22.28
216.1 270.4 249.1 229.9 276.9 257.6 240.9
208.2 149.5 193.6 229.8 164.2 217.5 240.9
22.08 24.37 23.47 22.66 24.65 23.83 23.13
207.8 257.8 237.8 220.9 263.4 245.8 231.5
201.0 145.0 188.8 220.9 159.4 212.1 231.5
23.50 26.21 25.13 24.22 26.52 25.57 24.79

6000/0.03
72
281.6
141.5
20.29
270.0
137.1
22.13
264.3
134.9
23.00
258.7
132.8
23.88
247.3
128.4
25.64

67
258.4
176.0
19.63
247.7
171.6
21.39
242.6
169.5
22.16
237.2
167.3
22.97
227.1
163.2
24.55

3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil
5. Combination ratings are based on a 2 F line loss. For a close-coupled system
(less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table
on page 29 are based on 2 F line loss. All combination ratings are based on
R-22.

COMBINATION RATINGS (cont)


38AH028/40RM028
Temp (F)
Air Entering
Condenser
(Edb)
85

95

100

105

115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

38AH034/40RM028

Evaporator Air Cfm/BF


7500/0.04
10,000/0.06
12,500/0.08
Evaporator Air Ewb (F)
72
67
62
72
67
62
72
67
62
304.2 279.9 256.5 316.4 291.8 272.1 323.5 301.5 285.4
159.1 202.1 251.2 179.8 234.5 272.1 199.5 263.9 285.4
20.93 20.24 19.57 21.28 20.58 20.02 21.48 20.86 20.40
291.5 267.4 246.2 303.0 278.7 261.6 309.3 288.3 274.6
154.4 197.1 241.7 175.0 229.2 261.6 194.8 258.2 274.6
22.85 22.05 21.34 23.23 22.42 21.85 23.44 22.74 22.29
284.9 261.3 241.3 295.9 272.2 256.4 301.9 281.6 269.2
152.0 194.6 237.3 172.6 226.5 256.4 192.3 255.2 269.2
23.79 22.88 22.11 24.21 23.30 22.69 24.44 23.66 23.18
279.0 255.3 236.1 289.8 266.0 251.3 295.6 275.4 264.0
149.9 192.2 232.5 170.4 224.0 251.3 190.2 252.5 264.0
27.74 23.74 22.92 25.20 24.19 23.57 25.44 24.59 24.11
265.8 243.1 226.3 275.7 253.0 240.9 280.7 262.0 253.1
145.0 187.3 223.5 165.4 218.6 240.9 185.2 246.7 253.1
26.65 25.42 24.51 27.18 25.95 25.30 27.45 26.44 25.96

38AH028/40RM034
Temp (F)
Air Entering
Condenser
(Edb)
85

95

100

105

115

BF
Ewb
kW
SHC
TC

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

LEGEND
Bypass Factor
Entering Wet-Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.

79
81

0.10
0.20
0.30

0.99
0.88
0.77

85

95

100

105

115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Evaporator Air Cfm/BF


10,000/0.06
12,500/0.08
Evaporator Air Ewb (F)
62
72
67
62
72
67
62
282.3 353.8 326.9 299.0 363.1 337.4 313.5
274.9 192.9 248.9 299.0 212.7 279.6 313.5
23.67 25.84 25.02 24.18 26.12 25.34 24.62
271.5 339.6 313.0 288.1 348.2 323.5 302.4
265.0 187.9 243.3 288.1 207.7 273.5 302.4
25.51 28.06 27.06 26.13 28.38 27.46 26.66
268.1 332.8 307.2 284.1 340.8 317.3 297.9
261.8 185.5 240.9 284.1 205.3 270.8 297.9
26.40 29.21 28.10 27.09 29.55 28.53 27.69
262.1 325.7 300.0 278.2 333.4 310.2 292.0
256.3 183.1 237.9 278.2 202.8 267.7 292.0
27.41 30.38 29.18 28.16 30.74 29.66 28.81
237.8 291.8 268.1 253.0 297.7 277.5 265.8
234.1 171.1 224.8 253.0 190.9 253.4 265.8
29.91 33.03 31.66 30.79 33.37 32.20 31.52

7500/0.04
72
338.9
171.9
25.39
325.5
167.0
27.53
319.5
164.7
28.63
312.6
162.2
29.77
281.0
150.6
32.40

67
312.7
215.4
24.59
299.5
210.0
26.56
294.4
208.0
27.54
287.4
205.2
28.59
257.3
193.0
31.04

38AH034/40RM034

Evaporator Air Cfm/BF


9000/0.04
12,000/0.06
15,000/0.08
Evaporator Air Ewb (F)
72
67
62
72
67
62
72
67
62
324.3 297.3 276.8 335.5 309.2 294.1 341.6 319.6 289.1
174.8 227.1 272.6 201.7 264.2 294.1 223.9 298.0 337.2
21.51 20.74 20.15 21.83 21.08 20.65 22.00 21.37 20.50
310.3 283.6 265.2 320.8 295.0 282.3 326.2 305.1 253.1
169.4 221.6 262.1 196.7 258.5 282.3 218.7 291.7 363.3
23.48 22.59 21.97 23.83 22.96 22.54 24.01 23.30 21.57
302.8 276.7 259.5 312.8 287.6 276.3 317.9 297.5 237.4
166.6 218.9 257.0 194.0 255.5 276.3 216.0 288.4 374.6
24.48 23.47 22.81 24.86 23.89 23.46 25.06 24.27 21.96
296.6 270.3 253.9 306.4 281.1 270.7 311.3 291.1 221.1
164.3 216.4 251.9 191.9 252.9 270.7 213.8 285.5 386.4
25.48 24.37 23.68 25.90 24.83 24.39 26.10 25.25 22.29
281.8 256.6 242.6 290.5 266.6 258.6 294.7 276.0 195.2
158.6 210.9 241.6 186.5 247.0 258.6 208.2 278.9 405.2
27.51 26.15 25.39 27.99 26.69 26.26 28.21 27.20 22.83

BYPASS
FACTOR

Temp (F)
Air Entering
Condenser
(Edb)

ENTERING-AIR DRY-BULB TEMP (F)


78
77
76
75
under 75
82
83
84
85
over 85
Correction Factor
1.98
2.97
3.96
4.95
Use formula
1.76
2.64
3.52
4.40
shown at right.
1.54
2.31
3.08
3.85

Temp (F)
Air Entering
Condenser
(Edb)
85

95

100

105

115

TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW

Evaporator Air Cfm/BF


12,000/0.06
15,000/0.08
Evaporator Air Ewb (F)
62
72
67
62
72
67
62
306.8 377.7 348.6 325.5 385.9 360.0 417.3
299.8 216.0 280.1 325.5 238.6 315.8 244.4
24.41 26.56 25.68 24.98 26.81 26.03 27.76
294.7 362.1 333.5 313.2 369.6 344.7 362.7
288.8 210.7 274.0 313.2 233.2 309.1 283.9
26.37 28.90 27.83 27.07 29.19 28.25 28.93
290.1 353.9 326.4 308.0 360.8 337.2 337.8
284.7 207.9 271.2 308.0 230.3 305.8 302.0
27.35 30.12 28.93 28.13 30.42 29.40 29.42
283.6 346.4 318.8 301.6 353.1 329.6 315.0
278.8 205.4 268.1 301.6 227.7 302.5 318.5
28.41 31.34 30.06 29.25 31.66 30.56 29.88
255.8 308.5 283.3 272.6 313.5 293.2 226.5
253.6 192.6 253.8 272.6 214.5 286.5 382.5
30.95 33.99 32.54 31.92 34.28 33.11 29.26

9000/0.04
72
363.5
189.6
26.13
348.8
184.0
28.40
341.4
181.3
29.58
334.2
178.5
30.77
298.7
165.1
33.42

67
334.5
241.8
25.25
319.9
236.0
27.32
313.6
233.5
28.37
306.1
230.6
29.47
272.4
217.2
31.91

3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil
5. Combination ratings are based on a 2 F line loss. For a close-coupled system
(less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table
on page 29 are based on 2 F line loss. All combination ratings are based on
R-22.

Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).

17

Performance data 38AH024-034/40RM (cont)


40RM FAN PERFORMANCE DATA 0.0-1.2 ESP
UNIT
40RM

016

024

028

034

AIRFLOW
(Cfm)
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000

0.0
Rpm
391
460
521
590
651
503
586
670
754
838
412
481
549
618
687
471
550
628
707
785

0.2
Bhp
0.51
0.80
1.13
1.60
2.10
1.07
1.64
2.37
3.28
4.39
1.15
1.76
2.55
3.52
4.71
1.78
2.72
3.93
5.44
7.27

Rpm
495
551
602
663
718
587
660
735
812
891
492
550
610
672
735
539
608
679
752
826

Bhp
0.75
1.08
1.43
1.93
2.45
1.37
1.98
2.74
3.69
4.83
1.53
2.17
2.99
4.00
5.22
2.17
3.15
4.40
5.94
7.81

EXTERNAL
0.4
Rpm
Bhp
581
1.00
629
1.35
675
1.73
730
2.26
779
2.81
661
1.67
726
2.31
795
3.12
867
4.09
941
5.27
568
2.00
616
2.66
669
3.50
725
4.53
783
5.78
604
2.63
665
3.64
730
4.92
797
6.49
867
8.39

LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure

Italics indicate special field-supplied drive required for use with standard motor.
Bold indicates standard drive and standard motor.
Plain type indicates medium-static drive and standard motor. For 40RM028
size only, plain type indicates medium-static drive and alternate motor.
indicates high-static drive and alternate motor. For 034 size
only, shading indicates high-static drive and standard motor.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pressure
drop.
3. Refer to fan motor and drives tables, pages 30 and 31 to complete
the selection.
4. Factory-supplied motor for 034 size is standard 10 Hp motor only;
alternate motor not available.

18

STATIC PRESSURE (in. wg)


0.6
0.8
Rpm
Bhp
Rpm
Bhp
657
1.25
725
1.50
700
1.63
764
1.91
741
2.04
801
2.34
791
2.59
847
2.92
837
3.16
890
3.52
727
1.97
789
2.28
787
2.65
844
2.99
851
3.49
904
3.86
918
4.50
967
4.90
988
5.70
1034
6.14
640
2.56
710
3.22
680
3.22
742
3.86
726
4.07
782
4.70
777
5.12
827
5.76
830
6.38
876
7.04
667
3.17
728
3.78
720
4.18
774
4.79
779
5.48
827
6.09
841
7.08
885
7.71
907
9.01
947
9.66

1.0
Rpm
787
823
858
901
941
846
898
954
1014
1077
776
802
836
876
922
788
827
874
928
986

1.2
Bhp
1.76
2.20
2.65
3.26
3.88
2.59
3.33
4.23
5.31
6.85
3.98
4.58
5.40
6.45
7.74
4.46
5.45
6.76
8.38
10.35

Rpm
845
878
911
951
990
900
948
1001
1059
1120
840
860
889
925
966
845
878
921
970
1024

FACTORY-SUPPLIED FILTER PRESSURE DROP


(in. wg)
UNIT
40RM
016
024
028
034

AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

Bhp
2.02
2.48
2.96
3.60
4.24
2.90
3.67
4.61
5.72
7.02
4.83
5.38
6.17
7.21
8.49
5.22
6.18
7.47
9.10
11.07

40RM, FAN PERFORMANCE DATA 1.4-2.4 ESP


UNIT
40RM

016

024

028

034

AIRFLOW
(Cfm)
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000

1.4
Rpm
899
930
961
999
1036
950
996
1047
1102
1160
903
917
941
972
1010
901
928
966
1011
1062

1.6
Bhp
2.29
2.78
3.28
3.94
4.60
3.21
4.02
4.99
6.13
7.46
5.79
6.26
7.01
8.02
9.29
6.07
6.98
8.24
9.86
11.84

Rpm
951
980
1009
1045
1080
999
1042
1091
1143
1200
963
972
991
1019
1053
955
978
1011
1052

Bhp
2.56
3.08
3.60
4.28
4.97
3.53
4.37
5.37
6.54
7.91
6.83
7.22
7.91
8.89
10.15
6.98
7.84
9.07
10.67

EXTERNAL STATIC PRESSURE (in. wg)


1.8
2.0
Rpm
Bhp
Rpm
Bhp
999
2.84
1046
3.12
1027
3.38
1072
3.68
1055
3.92
1098
4.24
1089
4.63
1132
4.98
1123
5.34
1164
5.71
1045
3.85
1089
4.17
1086
4.72
1129
5.07
1133
5.75
1173
6.13
1183
6.96

1021
7.98
1078
9.21
1078
9.38
1025
8.26
1040
8.89
1089
9.93
1064
9.83

1095
11.05

1008
7.98
1060
9.05
1026
8.76
1073
9.74
1055
9.95
1098
10.88
1092
11.52

LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure
Plain type indicates medium-static drive and standard motor. For 40RM028
size only, plain type indicates medium-static drive and alternate motor.
indicates high-static drive and alternate motor. For 034 size
only, shading indicates high-static drive and standard motor.
Italics indicate special field-supplied drive required for use with alternate
motor. For 034 size only, italics indicate special field-supplied drive required for use with standard motor.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pressure
drop.
3. Refer to fan motor and drives tables, pages 30 and 31 to complete
the selection.
4. Factory-supplied motor for 034 size is standard 10 Hp motor only;
alternate motor not available.

2.2
Rpm
1091
1116
1141
1173

1131
1169

2.4
Bhp
3.41
3.99
4.57
5.33

4.50
5.43

Rpm
1133
1157
1181

1172

Bhp
3.70
4.30
4.91

4.83

FACTORY-SUPPLIED FILTER PRESSURE DROP


(in. wg)
UNIT
40RM
016
024
028
034

AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40

19

Performance data 38AH024-034/40RM (cont)


40RM ACCESSORY PLENUM AIR THROW DATA
(ft)
UNIT
40RM

AIRFLOW
(Cfm)

016
024
028
034

6,000
8,000
10,000
12,000

Straight
50
60
76
85

VANE DEFLECTION
2212
43
51
65
72

45
31
37
47
52

NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150

THROW FACTOR
X
X
X

1.50
0.75
0.50

40RM ACCESSORY PRESSURE DROP


(in. wg)
UNIT
40RM

AIRFLOW
(Cfm)

DISCHARGE
PLENUM

RETURN AIR
GRILLE

4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46

0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07

016
024
028
034

40RM HYDRONIC HEATING CAPACITIES


UNIT
40RM

016
024
028
034

AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000

1-ROW
STEAM*
Cap.
402
458
479
458
487
499
511
575
626
560
621
670

Ldb
141
129
118
129
115
105
122
112
106
117
107
101

Cap.
412.0
471.0
529.0
506.0
584.0
652.0
649.0
752.0
842.0
735.0
850.0
950.0

2-ROW
HOT WATER
COIL
Ldb Gpm
145
41.2
133
47.1
125
52.9
138
50.6
128
58.4
120
65.2
140
64.9
130
75.2
122
84.2
136
73.5
126
85.0
119
95.0

HEATING COILS
Steam
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

Electric
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34

ECONOMIZER
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21

40RM HEATING CORRECTION FACTORS

PD
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5
6.2
7.8
9.3

LEGEND
Cap. Capacity (Btuh in thousands)
Ldb Leaving-Air Dry-Bulb Temp (F)
PD
Pressure Drop (ft water)
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for steam heating coils:
175 psig at 400 F.
2. Maximum operating limit for hot water heating coils is 150 psig.
Capacity (Btuh)
3. Leaving db = ent db (F) +
1.1 x cfm
4. See Heating Correction Factors table.

20

Hot Water
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85

Water Temp
Drop
(F)
10

20

30

HOT
Ent Water
Temp
(F)
140
160
180
200
220
140
160
180
200
220
140
160
180
200
220

Steam Pressure
(psig)
0
2
5

WATER COIL
Entering-Air Temp (F)
40

50

60

70

80

0.72
0.89
1.06
1.22
1.39
0.64
0.81
0.98
1.15
1.32
0.56
0.74
0.91
1.08
1.25

0.64
0.81
0.98
1.15
1.32
0.57
0.74
0.91
1.08
1.25
0.49
0.66
0.83
1.00
1.18

0.57
0.74
0.90
1.07
1.24
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.76
0.93
1.10

0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.75
0.93
1.10
0.33
0.51
0.68
0.85
1.03

0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95

STEAM COIL
Entering-Air Temp (F)
40
50
60
70
1.06
0.98
0.91
0.85
1.09
1.02
0.95
0.89
1.13
1.06
1.00
0.93

80
0.78
0.82
0.87

NOTE: Multiply capacity given in the Hydronic Heating Capacities table


by the correction factor for conditions at which unit is actually operating.
Correct leaving-air temperature using formula in Note 2 of Hydronic
Heating Capacities table.

Typical piping and wiring 38AH024-034


ROOFTOP INSTALLATION

LEGEND
LLSV Liquid Line Solenoid Valve
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Piping
Double Riser Piping (if required)
*Field supplied.
If double suction riser is required for piping system, size pipe diameter of 3 ft (maximum) riser
according to application data on page 29.

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

21

Typical piping and wiring


38AH024-034 (cont)
GROUND LEVEL INSTALLATION

LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.

22

NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to
Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.

Electrical data 38AH024-034/40RM


38AH UNITS
UNIT 38AH

024

028

034

500
200
600
100
500
200
600
100
500
200
600
100

Volts
3 Ph, 60 Hz
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575

UNIT
Supplied*
Min
Max
187
254
342
418
414
508
518
632
187
254
342
418
414
508
518
632
187
254
342
418
414
508
518
632

MCA

MOCP
(Fuse)

ICF

100.8
61.8
50.3
42.1
110.5
67.2
55.9
47.1
135.5
77.0
65.8
53.3

125
80
60
50
150
90
70
60
175
110
90
70

249.7
124.8
124.8
101.5
284.0
138.2
142.3
117.5
322.0
179.2
148.3
120.7

LEGEND
Canadian Standards Association
Full Load Amps
Maximum Instantaneous Current Flow during starting (the
point in the starting sequence where the sum of the LRA for
the starting compressor, plus the total RLA for all running
compressors, plus the total FLA for all running fan
motors is maximum).
LRA
Locked Rotor Amps
MCA Minimum Circuit Amps (complies with National Electrical Code
[NEC], Section 430-24)
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps
UL
Underwriters Laboratories

COMPRESSOR
RLA
LRA
Ckt 1
Ckt 2
Ckt 1
Ckt 2
39.3
39.3
198
198
24.0
24.0
93
93
19.6
19.6
99
99
15.7
15.7
79
79
43.6
43.6
228
228
26.4
26.4
104
104
22.1
22.1
114
114
19.7
19.7
91
91
43.6
63.6
228
266
26.4
34.3
104
145
22.1
30.0
114
120
17.9
22.9
91
96

FAN MOTORS
Qty

FLA
(ea)

Hp

6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4

*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum
limits.
All fans are protected by a single circuit breaker.
NOTE: The 208/230-v and 460-v base units are UL and CSA approved.
The 575-v base units are CSA approved.

CSA
FLA
ICF

40RM STANDARD MOTORS


UNIT 40RM

016
024
028
034

FAN MOTOR

V*-PH-HZ

VOLTAGE
LIMITS

Hp

FLA

208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60

187-253
414-528
518-632
187-253
414-528
518-632
187-253
414-528
518-632
187-253
414-528
518-632

3.7
3.7
3.0
5.0
5.0
5.0
7.5
7.5
7.5
10.0
10.0
10.0

10.6
4.8
3.8
15.2/14.4
7.2
5.6
22.0/21.0
10.5
7.6
26.4/25.0
12.5
9.6

POWER SUPPLY
Minimum Circuit
MOCP
Amps
13.3
20
6.0
15
4.8
15
19.0/18.0
30/30
9.0
15
7.0
15
27.5/26.3
45/45
13.1
20
9.5
15
33.0/31.3
55/55
15.6
25
12.0
20

40RM ALTERNATE MOTORS


UNIT 40RM

016
024
028

FAN MOTOR

V*-PH-HZ

VOLTAGE
LIMITS

Hp

FLA

208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60

187-253
414-528
518-632
187-253
414-528
518-632
187-253
414-528
518-632

5.0
5.0
5.0
7.5
7.5
7.5
10.0
10.0
10.0

15.2/14.4
7.2
5.6
22.0/21.0
10.5
7.6
26.4/25.0
12.5
9.6

POWER SUPPLY
Minimum Circuit
MOCP
Amps
19.9/18.0
30/30
9.0
15
7.0
15
27.5/26.3
45/45
13.1
20
9.5
15
33.0/31.3
55/55
15.6
25
12.0
20

LEGEND
FLA
Full Load Amps
Hp
Horsepower
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.

1095

23

Electrical data 38AH024-034/40RM (cont)


40RM ELECTRIC HEATER DATA
UNIT
40RM

016,024

028,034

HEATER
PART NO.
CAELHEAT016A00
CAELHEAT017A00
CAELHEAT018A00
CAELHEAT019A00
CAELHEAT020A00
CAELHEAT021A00
CAELHEAT022A00
CAELHEAT023A00
CAELHEAT024A00
CAELHEAT025A00
CAELHEAT026A00
CAELHEAT027A00
CAELHEAT028A00
CAELHEAT029A00
CAELHEAT030A00
CAELHEAT031A00
CAELHEAT032A00
CAELHEAT033A00
CAELHEAT034A00
CAELHEAT035A00
CAELHEAT036A00
CAELHEAT037A00
CAELHEAT038A00
CAELHEAT039A00

V-PH-HZ
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60

LEGEND
ETL
Electrical Testing Laboratory
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection (Amps)
*Sizes shown are for single-point connection of electric heat accessory
and air handler.

HEATER RATING
VOLTAGE
240
480
575

200
.694

208
.751

230
.918

ACTUAL HEATER VOLTAGE


240
440
460
480
1

.840 .918
1

NOTE: The following equation converts kW of heat energy to Btuh:


kW x 3,412 =Btuh.

24

HEATER
AMPS
24.1
12.0
10.0
47.9
24.1
20.1
71.9
36.1
30.1
120.0
60.1
50.2
47.9
24.1
20.1
95.7
48.1
40.2
120.0
60.1
50.2
167.9
84.0
70.3

NOMINAL kW
10

20

30

50

20

40

50

70

MCA*

MOCP*

52.1
25.5
20.2
82.1
40.6
32.7
112.2
55.6
45.3
172.4
85.7
70.4
86.5
42.6
34.7
146.7
72.6
59.8
176.8
87.7
72.4
236.9
117.8
97.5

60
30
25
110
50
45
150
80
70
250
125
100
110
60
45
200
100
80
250
125
100
350
175
150

NOTES:
1. MCA and MOCP values apply to both standard and alternate factorysupplied motors.
2. Electric heaters are tested and ETL approved at maximum total external static pressure of 1.9 in. wg.
3. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate voltage, multiply
240-v, 480-v, or 575-v capacity by multipliers found in table below.

550

.915

575

600

1.089

Controls 38AH024-034
Sequence of operation
Single air handler, 2-stage cool thermostat At
start-up, the thermostat calls for first-stage cooling (TC1
closes) and with all safety devices satisfied, circuit no. 1 control relay (CR1) energizes, deenergizing the crankcase heater
at compressor no. 1. The indoor-fan motor starts immediately, and the liquid line solenoid valve (LLSV) for
solenoid drop refrigeration control on circuit no. 1 opens.
Outdoor-fan motor no. 1 and compressor no. 1 start after
one second. Fan no. 2 starts if the outdoor ambient temperature is above 70 F.
On standard units, compressor no. 1 operates either fully
loaded or at one step of unloading depending on the suction pressure, which in turn is dependent on the evaporator load conditions. As cooling demand increases, TC2 of
the 2-stage thermostat energizes control relay no. 2. CR2
deenergizes the crankcase heater at compressor no. 2 and
brings on compressor no. 2 after one second. The LLSV
for solenoid drop refrigerant control (circuit no. 2) opens as
soon as CR2 is energized. On standard units, compressor
no. 2 operates fully loaded.
As cooling demand is satisfied, thermostat contacts TC2
break and deenergize CR2, which then deenergizes compressor no. 2 and energizes its crankcase heater. The LLSV
on circuit no. 2 closes, preventing refrigerant migration back
to compressor no. 2 during the off cycle. If the space temperature continues to decrease, stage 1 thermostat contacts
TC1 break and deenergize CR1. Immediately after CR1 is
deenergized, compressor no. 1 shuts off and its crankcase
heater is energized. The LLSV on circuit no. 1 closes, preventing refrigerant migration back to compressor no. 1 during the off cycle. Outdoor-fan motors no. 1 and 2 deenergize as soon as CR1 is deenergized.
NOTE: If thermostat fan switch is in the auto position, the
indoor fan cycles on and off as the thermostat calls for
cooling (or heating). If the fan switch is in the continuous
position, the fan runs as long as the outdoor unit is powered up.
Two air handlers, two 2-stage cool thermostats (one
per air handler) At start-up of circuit no. 1, the
thermostat controlling circuit no. 1 calls for the first stage
of cooling when thermostat contact TC1 closes. If all safety
devices are satisfied, circuit no. 1 control relay CR1 energizes, which deenergizes the crankcase heater at compressor no. 1. The indoor-fan motor on the circuit no. 1
air handler starts immediately, and the main liquid line
solenoid valve (LLSV) for solenoid drop refrigerant control
on circuit no. 1 opens. Outdoor-fan motor no. 1 and compressor no. 1 start after one second. Fan no. 2 starts if the
outdoor ambient is above 70 F.
On standard units, compressor no. 1 operates either fully
loaded or at one step of unloading depending on the

suction pressure, which in turn is dependent on the evaporator load conditions. As cooling demand increases, TC2
of the 2-stage thermostat energizes the capacity control
LLSV resulting in full utilization of the evaporator surface.
The fully utilized evaporator surface raises the suction pressure until the pressure-operated capacity control valve
setting is exceeded, so that the compressor becomes fully
loaded.
The thermostat controlling circuit no. 2 calls for the first
stage of cooling when thermostat contact TC1 closes. Assuming all safety devices are satisfied, circuit no. 2 control
relay CR2 energizes, which deenergizes the crankcase heater
at compressor no. 2. The indoor-fan motor on circuit no. 2
air handler starts immediately, and the main LLSV for
solenoid drop refrigerant control on circuit no. 2 opens.
Compressor no. 2 starts after one second. The outdoor fans
are already running if circuit no. 1 is running. If circuit
no. 1 is not running when thermostat no. 2 calls for cooling, the outdoor fans are off. In this situation, outdoor-fan
motor no. 1 starts when compressor no. 2 starts. Outdoorfan motor no. 2 comes on if the outdoor ambient temperature is above 60 F.
IMPORTANT: Do not install CCS2 (capacity control
solenoid) unless accessory unloader is field-installed
on circuit no. 2 compressor. CCS2 is controlled from
TC2 contacts on thermostat that regulate circuit no.
2 air handler.
NOTE: Circuit no. 2 compressor does not have a factoryinstalled unloader; one must be field-installed if required.
As cooling demand is satisfied at thermostat no. 1 or 2
(whichever comes first), contacts TC2 break and the capacity control LLSV on that circuit is deenergized. This prevents refrigerant flow through the upper (circuit no. 1 or 2)
evaporator section, causing the suction pressure to drop
and the compressor on that circuit to unload.
As the space temperature drops further, thermostat
contacts TC1 open, which deenergizes control relay CR1
or CR2. Immediately after CR1 or CR2 is deenergized, the
compressor CR1 or CR2 control is shut off and its crankcase heater is energized. The LLSV on that circuit closes,
preventing refrigerant migration back to the compressor during the off cycle. Outdoor-fan motors no. 1 and 2 are deenergized only if the space thermostats for both circuits no. 1
and 2 are not calling for cooling.
NOTE: If the thermostat fan switch is in the auto position,
the indoor fan cycles on and off as the thermostat calls for
cooling (or heating). If the fan switch is in the continuous
position, the fan runs as long as the outdoor unit is powered up.

25

AUTO
C
CB
COM
GND
IFC
LLS
NEC
RV
TB
TC

LEGEND
Automatic Changeover
Contactor, Compressor
Circuit Breaker
Common
Ground
Indoor-Fan Contactor
Liquid Line Solenoid
National Electrical Code
Reversing Valve
Terminal Block
Thermostat, Cooling
Field Control Wiring
Factory Wiring
Field Power Wiring
Indicates Common Potential;
Does Not Indicate Wiring

26
208/230-3-60
460-3-60
575-3-60
380-3-60

UNIT (V-Ph-Hz)

**For a single air handler, LLS valve 1 is to be used on the lower (no. 1)
evaporator circuit. The LLS valve 2 is to be used on the upper (no. 2) evaporator circuit.
Only one indoor-fan contactor is required on single air-handler applications.
Use Carrier accessory part no. 40RR900181 for indoor-fan contactor.

230-1-60

115-1-60

CONTROL CIRCUIT PROTECTED AT:


(V-Ph-Hz)

*Use thermostat wiring shown here for single air-handler applications.


CB3 protects control circuit at the following unit voltages:

38AH024-034 UNITS WITH SINGLE AIR HANDLER

NOTES:
1. CB4 protects TB3 circuit; CB5 protects TB2 circuits.
2. LLS1 and LLS2 are field supplied.
3. TB2 and TB3 are in 24-v circuits.
4. On the TSR-01 Relay Pack, the outside-air sensor, supply-air sensor, and direct expansion coil sensor are available as options.

Typical control wiring 38AH024-034

27

AUTO
C
CB
CCS
COM
GND
IFC
LLS
NEC
RV
TB
TC

LEGEND
Automatic Changeover
Contactor, Compressor
Circuit Breaker
Capacity Control Solenoid
Common
Ground
Indoor-Fan Contactor
Liquid Line Solenoid
National Electrical Code
Reversing Valve
Terminal Block
Thermostat, Cooling
Field Control Wiring
Factory Wiring
Field Power Wiring
Indicates Common Potential;
Does Not Indicate Wiring
208/230-3-60
460-3-60
575-3-60
380-3-60

UNIT (V-Ph-Hz)

NOTES:
1. Capacity control solenoid (and liquid line solenoid drop refrigerant control)
valves are field supplied.
2. CB4 protects TB3 circuit, and CB5 protects TB2 circuit.
3. On the TSR-01 Relay Pack, the outside-air sensor, supply-air sensor, and
direct expansion coil sensor are available as options.

Use Carrier accessory part no. 40RR900181 for indoor-fan contactor.


**Install LLS valve no. 1 in the liquid line of the air handler controlled by the
38AH circuit no. 1 thermostat. Install LLS valve no. 2 in the liquid line of the
air handler controlled by the 38AH circuit no. 2 thermostat.
Do not install CCS2 unless accessory unloader is field-installed on circuit
no. 2 compressor.

230-1-60

115-1-60

CONTROL CIRCUIT PROTECTED AT:


(V-Ph-Hz)

*CB3 protects control circuit as follows:

38AH024-034 UNITS WITH 2 AIR HANDLERS

Application data 38AH024-034


Installation
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation.
When selecting vapor line sizes, oil return must be evaluated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor
unit is operating.
IMPORTANT: When application is in a VAV (variable
air volume) system, total building load is not the sum
of the individual peak loads. If individual peak loads
are summed, the equipment tends to be oversized for
the load.
To minimize return-air temperature extremes, use the
equipment room as a return-air plenum when applying
VVT systems with supply-to-return air recycle as used with
Carrier VVT control systems.
Ductwork should be sized according to unit size, not
building load.

To minimize the possibility of air recirculation, avoid the


use of concentric supply/return grilles.
Indoor equipment should be selected at no less than
300 cfm/ton.
Condensing units applied in VVT or VAV systems must
have field-supplied and installed accumulators. Order part
number --KH--73LZ-001 from Service Parts.
OPERATING LIMITS
Maximum Outdoor Ambient
Minimum Outdoor Ambient
Minimum Return-Air
Temperature
Maximum Return-Air
Temperature
Normal Acceptable
Saturation Suction
Temperature Range
Maximum Discharge
Temperature
Minimum Discharge
Superheat

UNLOADING SEQUENCES
UNIT 38AH
024
028
034

CAPACITY/STAGE (%)
CV Units (Standard)*
VAV Units (Optional)
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 85, 43, 28
100, 85, 77, 43, 28, 14

LEGEND
CV Constant Volume
VAV Variable Air Volume
*Additional unloading available with field-installed accessory unloader.
NOTE: Capacities are based on 45 F saturated suction temperature and 95 F outdoor air temperature.

MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE


AND LOADING SEQUENCES
UNIT 38AH

024

028

034

SYSTEM
CAPACITY (%)
100
83
67*
50
33
17*
100
83
67*
50
33
17*
100
81
62*
43
29
14*

MINIMUM OUTDOOR-AIR TEMP (F)


Standard Unit
Low Ambient Control
20
20
20
53
20
20
20
20
20
20
50
20
20
20
20
20
20
49
20
20
20

*VAV or accessory unloader on Circuit 1.


MotormasterT III cannot be used with 2 unloaders when unit is connected to 2 separate air handlers.
NOTE: Minimum outdoor-air operating temperature is based on 90 F saturated condensing
temperature and 100% capacity.

28

115 F
See Minimum Outdoor-Air
Operating Temperature
table below.
55 F
95 F
20 to 50 F
275 F
60 F

REFRIGERANT PIPE SIZES


SINGLE SUCTION RISERS

UNIT 38AH
024 Ckt
Ckt
028 Ckt
Ckt
034 Ckt
Ckt

1
2
1
2
1
2

12
12
12
12
12
12

LENGTH OF INTERCONNECTING PIPING,


0-25
25-50
50-75
S
L
S
L
S
5 8
5 8
1 1 8
138
138
5 8
5 8
1 1 8
138
138
5 8
5 8
1 1 8
138
138
5 8
5 8
1 1 8
138
138
5 8
5 8
1 1 8
138
158*
5 8
7 8
1 3 8
158
158

FOR EACH CIRCUIT (Ft)


75-100
100-200
L
S
L
S
7 8
5 8
158*
158*
7 8
5 8
158
158
7 8
7 8
158*
218**
7 8
7 8
158
218**
7 8
7 8
158*
218**
7 8
7 8
158
218

LEGEND
L Liquid Line
S Suction Line
*Double suction riser required if evaporator is below condensing unit and 2 unloaders are used on that
circuit.
Double suction riser required if evaporator is below condensing unit and compressor is equipped
with 2 unloaders. Note the only time circuit no. 2 may be equipped with 2 unloaders is if it is serving
its own air handler and the unit does not require low ambient operation (MotormasterT III control).
**Double suction riser required if evaporator is below condensing unit and compressor has one or more
unloader(s).
NOTES:
1. All line sizes are inches OD.
2. Standard unit comes with one pressure-operated unloader on circuit no. 1. If unit serves one air
handler, an additional unloader may be field installed on circuit no. 1 compressor only. If the unit
serves 2 separate air handlers and low ambient operation is required (Motormaster III control), each
circuits compressor may only be equipped with one unloader.

DOUBLE SUCTION RISERS


UNIT 38AH
024 Ckt
Ckt
028 Ckt
Ckt
034 Ckt
Ckt

1
2
1
2
1
2

118

50-75
B

138

LENGTH OF INTERCONNECTING PIPING (Ft)


75-100
100-200
C
A
B
C
A
B

118
138
1 5 8
118
138

118
138
1 5 8
138
138

118
138
1 5 8
138
158

118
138
1 5 8
138
158
5
1
3
5
3
1 8
1 8
1 8
1 8
1 8
158

138
158

C
1 5 8
1 5 8
2 1 8
2 1 8
2 1 8
2 1 8

NOTE: Refer to figure for A, B, and C dimensions.

MAXIMUM LIQUID LIFT


UNIT 38AH
024
028
034

MAXIMUM LIQUID LIFT


PER CIRCUIT
(Ft)
76
73
100

WIRE SIZES FOR FIELD POWER SUPPLY


UNIT 38AH

V-Ph-Hz

024-034

208-230/3/60
380-3-60
460-3-60
375-3-60

LEGEND
AWG American Wire Gage
kcmil Thousand Circular Mils
TB
Terminal Block

FIELD POWER WIRE SIZE


TB1 WILL ACCEPT
350 kcmil
2/0 AWG

LEGEND
Suction Riser without Trap
Suction Riser with Trap
Suction Line to Condensing Unit
Pipe Diameter to be Same Size as Riser A

29

Application data 40RM


Operating limits
Maximum fan speed 40RM016-024 . . . . . . 1200 rpm
Maximum fan speed 40RM028,034 . . . . . . 1100 rpm

General
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation. Equipment should be selected
to perform at no less than 300 cfm/ton.
The air handler fan must always be operating when the
condensing unit is operating.

Ductwork should be sized according to unit size, not


building load. For larger units with two fans, a split duct
transition is recommended at the fan outlets, but a plenum
can be used with slight reduction in external static pressure
capability.
For variable air volume (VAV) systems with supply-toreturn air recycling, use the equipment room as a return air
plenum.

FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA


UNIT 40RM

TXV
Qty...Part No.

DISTRIBUTOR
Qty...Part No.

016
024
028
034

2...XVE-8
2...XVE-10
2...EBSVE-11
2...SVE-15

2...1116
2...1116
2...1126
2...1126

FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...14
13...14
15...14
18...14

NOZZLE
Qty...Part No.
2...E6
2...E8
2...C10
2...C12

NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.

STANDARD FAN MOTOR DATA

ALTERNATE FAN MOTOR DATA

208/230-3-60 AND 460-3-60 MOTORS

208/230-3-60 AND 460-3-60 MOTORS

UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

016
1725
3.7
56Y
7 8

024
1745
5.0
S184T
118

028
1745
7.5
S213T
138

034
1745
10.0
S215T
138

LEGEND
NEMA National Electrical Manufacturers Association

UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

016
1725
3.0
56HZ
78

024
1745
5.0
184T
1 1 8

028
1750
10.0
S215T
138

575-3-60 MOTORS
028
1755
7.5
S213T
138

LEGEND
NEMA National Electrical Manufacturers Association

30

024
1745
7.5
S213T
138

LEGEND
NEMA National Electrical Manufacturers Association

575-3-60 MOTORS
UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

016
1745
5.0
S184T
1 1 8

034
1755
10.0
S215T
138

UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)

016
1745
5.0
184T
118

024
1755
7.5
S213T
1 3 8

LEGEND
NEMA National Electrical Manufacturers Association

028
1750
10.0
S215T
138

STANDARD DRIVE DATA


UNIT 40RM
MOTOR DRIVE
Motor Pulley Pitch
Diameter
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)

HIGH-STATIC DRIVE DATA

016

024

028

034

2.8-3.8

3.7-4.7

4.3-5.3

4.3-5.3

2.5

3.0

3.0

3.0

9.0
1716
1A

9.4
1716
2B

42.3

41.8

11.0
11516
2B*
(2) 42.8
or
(2) 43.8

11.0
11516
2B*
(2) 42.8
or
(2) 43.8

FAN SPEEDS (rpm)


Factory Setting
632
771
752
752
Range
537-728 679-863 682-841 674-831
Max Allowable Speed
1200
1200
1100
1100
Change per 12 Turn of
Moveable Motor Pulley
19.1
15.3
13.1
13.1
Flange
MAX FULL TURNS FROM
5
6
6
6
CLOSED POSITION
SHAFTS CENTER
10.449.126.676.67DISTANCE (in.)
12.32
10.99
9.43
9.43

UNIT 40RM
MOTOR DRIVE
Motor Pulley Pitch
Diameter
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed
Change per 12 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER
DISTANCE (in.)

016

024

028

034

4.3-5.3

4.3-5.3

4.3-5.3

4.3-5.3

2.5

3.0

3.0

3.0

7.9
1716
1B
39.8

7.4
1716
2B
36.8

8.6
11516
2B
37.8

8.6
11516
2B
37.8

1060
9501171
1200

1118
10141200
1200

1024
8731075

1024
8731075

30.8

19.4

16.7

16.7

9.1610.99

8.1610.02

6.679.43

6.679.43

*Four belts shipped with unit. Use one set of 2 belts sized according to
the pulley setting.

MEDIUM-STATIC DRIVE DATA


UNIT 40RM
MOTOR DRIVE
Motor Pulley Pitch
Diameter
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)

016

024

028

034

3.7-4.7

4.3-5.3

4.3-5.3

4.3-5.3

3.0

3.0

3.0

3.0

8.6
1716
1B

9.4
1716
2B

41.8

41.8

9.4
11516
2B*
(2) 38.8
or
(2) 39.8

9.4
11516
2B*
(2) 38.8
or
(2) 39.8

FAN SPEEDS (rpm)


Factory Setting
842
881
881
881
Range
742-943 798-984 798-984 798-984
Max Allowable Speed
1200
1200
1100
1100
Change per 12 Turn of
Moveable Motor Pulley
16.7
15.3
15.3
15.3
Flange
MAX FULL TURNS FROM
6
6
6
6
CLOSED POSITION
SHAFTS CENTER
10.449.166.676.67DISTANCE (in.)
12.32
10.99
9.43
9.43
*Four belts shipped with unit. Use one set of 2 belts sized according to
the pulley setting.

31

Model number nomenclature


38AH044-134

*Export only.

Ratings summary 38AH044-134


UNIT SIZE
044
054
064
074
084
094
104
124
134

CAPACITY
(Nominal Tons)
40
50
60
70
80
90
100
120
130

EER*
10.7
10.5
10.5
10.0
10.0
10.2
10.4
10.5
10.2

LEGEND
EER Energy Efficiency Ratio
*Rated in accordance with ARI (Air Conditioning & Refrigeration
Institute) standard 365-87.
NOTE: Ratings are based on 45 F suction temperature and 95 F outsideair temperature, and include suction line losses.

32

Options and accessories 38AH044-134


Factory-installed options
VAV (variable air volume) control box modification
makes the condensing unit compatible with the ModuPanel
VAV controller. Includes factory-installed accumulator. Also
includes electric unloaders on compressors as follows:
1 38AH044
2 38AH054-084,104
3 38AH094
4 38AH124,134 (2 per module)
Single-circuit modification (sizes 38AH044-084 only)
includes factory-installed accumulator and all piping and wiring modifications required to make the unit single circuit.
Single-circuit modification with VAV (sizes 38AH044084 only) includes piping, wiring, and electric unloaders
on compressors (one on 38AH044 and 2 on 38AH054084) to make the unit single circuit, VAV-ready. Also includes factory-installed accumulator.

Field-installed accessories
Transformer relay package for remote-control (24-v)
thermostat. One 2-stage thermostat is required for use with
the relay package.
Additional electric unloader package includes hardware to add an additional step of unloading (coil not
included).

Additional pressure unloader package includes all unloader valves and hardware.
Gage panel package contains panel-mounted suction and
discharge pressure gages.
Hail guard package protects coils against damage from
hail and airborne debris.
ModuPanel control provides 10-step microprocessorbased control for VAV applications.
Motormastert III control maintains correct condensing
pressure at low ambient temperatures.
Sound-reduction kit provides a specially designed system
of fan propellers and stacks that lower noise without reducing unit performance; compatible with the Motormaster III
accessory.
Unloader conversion kit allows you to convert factoryinstalled pressure unloaders to electric unloading.
Compressor grille package protects the compressor area
after the unit is installed.
Condenser coil grille package protects the condenser
area after the unit is installed.
Electronic thermostats provide temperature control by
allowing programming of 2-stage heating/2-stage cooling
setbacks and set-ups with provision for weekends and
holidays.

33

Physical data 38AH044-134


UNIT 38AH
NOMINAL CAPACITY (Tons)
OPERATING WEIGHT WITH
REFRIGERANT (lb) (approx)
SHIPPING WEIGHT WITH
COIL PROTECTION ONLY (lb) (approx)

044
40

054
50

064
60

074
70

084
80

Cu-Al
Cu-Cu

3259
3547

3309
3597

3565
3998

3812
4229

4057
4735

Cu-Al
Cu-Cu

3250
3538

3290
3578

3780
4197

4000
4678

7
62

7
72

3530
3963
R-22
7
88

9
104

9
130

REFRIGERANT, TYPE
Shipping Charge (lb)
Operating Charge, Typical (lb)
DUAL-CKT UNIT
COMPRESSOR Type...Rpm
(Quantity) Cylinder Ckt*
Model No. 06E
Oil Charge (pt)
Capacity Control Steps (%)

OPTIONAL SINGLE-CKT UNIT


COMPRESSOR Type...Rpm
(Quantity) Cylinder Ckt**
Model No. 06E
Oil Charge (pt)
Capacity Control Steps (%)

CONDENSER FANS (4 Blade)


(Quantity) Dia (in.)
Nominal Hp
Airflow (cfm)
Speed (rpm)
Total Power (kW)
CONDENSER COIL Rows
Fins per in.
2
Face Area (ft )
Storage Capacity (lb per circuit) at 120 F
CONNECTIONS
Suction, ODF (in.)
Liquid, ODF (in.)
Hot Gas Bypass, ODF (in.)

Cu-Al
Cu-Cu
ODF
VAV

(4) A
(4) B
250
250
17
17
100
75
50
25

(4) A1 (4) A2
250
250
17
17
100
75
50
25

2
17
80.5
35

35

Reciprocating Semi-Hermetic...1750
(4) A
(6) B
(6) A
(6) B
(6) A
(6) B
250
265
265
275
275
299
17
21
21
21
21
19
100
100
100
79
84
86
58
69
71
42
48
43
21
32
29
16
14

(6) A
(6) B
299
299
19
19
100
83
67
50
33
17

Reciprocating Semi-Hermetic...1750
(6) A1 (4) A2 (6) A1 (6) A2 (6) A1 (6) A2
265
250
275
265
299
275
21
17
21
21
19
21
100
100
100
80
82
81
61
64
62
56
55
57
37
36
38
18
19

(6) A1 (6) A2
299
299
19
19
100
83
67
50
33
17

(4) 30
1.0
35,000
1140
6.2
2
17
80.5
35
35

LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Variable Air Volume

*Circuit A compressor is lead.


Unloading steps available only on units ordered with the VAV factory-installed option or on
constant-volume units with additional field-installed accessory unloader.
**Circuit A compressor is lead on standard units; circuit B compressor is lead on optional singlecircuit units.
For optional single-circuit units, suction ODF is 258 in. and liquid ODF is 118 inches. Singlecircuit units have a factory-installed manifold; no field modification is required.
NOTES:
1. Certified dimensional drawings available on request.
2. Refer to Unloading Sequences table, page 61 for additional system capacity step data.

34

(6) 30
1.0
52,000

51,000
1140
9.3

3
17
80.5
55

2
19
116.7
55

218
7 8
5 8

55

3
17
116.7
55

80

80

UNIT 38AH

094

104

NOMINAL CAPACITY
(Tons)
OPERATING WEIGHT WITH
REFRIGERANT
(approx) - lb
Cu-Al
Cu-Cu
SHIPPING WEIGHT WITH
COIL PROTECTION
AND SKID
(approx) - lb
Cu-Al
Cu-Cu
REFRIGERANT, TYPE
Shipping Charge (lb)
Operating Charge,
Typical (lb)
Qty of Circuits
COMPRESSOR Type...Rpm
(Quantity Cylinder)
Compr
Model No. 06E
Oil Charge (pt)
Circuit Capacity - %
(approx)
Capacity Control Steps**
CONDENSER FANS
(4 Blade)
Quantity...Dia (in.)
Nominal Hp
Airflow (cfm)
Speed (rpm)
Total Power (kW)
CONDENSER COIL
Rows...Fins per in.
Face Area (sq ft)
Storage Capacity
(lb per ckt) at 120 F
CONNECTIONS
Suction, ODF (in.)
Liquid, ODF (in.)
Hot Gas Bypass,
ODF (in.)

90

124

134

124A

124B

134A

134B

100

60

60

60

70

5088
5813

5435
6160

3630*
4063*

3630*
4063*

3630*
4063*

3877*
4294*

5630
6355

5990
6715

3907*
4340*

3907*
4340*

4080*
4497*

10
148

10
135

3907*
4340*
R-22
7
88

7
88

7
88

9
104

(6)A1 (6)A2
275 265
21
21
45
4

(6)A1 (6)A2
299 275
19
21
55
4

4...30
1.0
35,000
1140
6.4

6...30
1.0
52,000
1140
9.2

3...17
80.5
110

2...19
116.7
110

(6)A1 (4)A2
275 250
21
17
55
6

(6)B1
299
19
45

6...30
1.0
52,000
1140
9.4
3...17
128.3
89

89

1
1
Reciprocating Semi-Hermetic...1750
(6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2
265 250 265 265 275 265 275 265
21
17
21
21
21
21
21
21
47
53
50
50
6
4
4
6...30
4...30
4...30
1.0
1.0
1.0
52,000
35,000
35,000
1140
1140
1140
9.5
6.4
6.4
Enhanced Copper Tubes, Lanced Aluminum Fins
3...17
3...17
3...17
128.3
80.5
80.5
89
89
110
110

218
78

2 1 8
7 8

2 5 8
1 1 8

258
118

258
118

2 5 8
1 1 8

58

58

58

58

58

58

LEGEND
Cu-Al Copper Tubes with Aluminum Fins
Cu-Cu Copper Tubes with Copper Fins
ODF
Outside Diameter, Female
*Includes piping and trim kit.
Compressors are shipped with minimum oil charge.
**Capacity control steps listed are for constant volume units with no accessories. Refer to Unloading Sequence table, page 61, for additional
system capacity information.

NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module.
Unit 38AH134 consists of one 134A module and one 134B module.
2. Certified dimensional drawings available on request.
3. Lead and lag circuits and compressors are as follows:
UNIT 38AH

094

104

LEAD CIRCUIT
Compressor, Lead
Compressor, Lag

A
A1
A2

A
A1
A2

LAG CIRCUIT
Compressor, Lead
Compressor, Lag

B
B1
*

B
B1
B2

124
Module
124A
A1
A2
Module
124B
A1
A2

134
Module
134A
A1
A2
Module
134B
A1
A2

*Circuit has only one compressor.

35

Dimensions 38AH044-134
UNITS 38AH044-064 (SEE PAGE 38 FOR CORNER WEIGHTS)
DIMENSIONS (ft-in.)
UNIT
38AH
044
044C
054
054C
064
064C

3-2
3-318
3-212
3-3
3-212
3-3316

4-12
4-916
4-316
4-38
4-12
4-58

34

CHART 1, FIELD POWER SUPPLY


CONNECTIONS
UNIT
38AH
044,054
064
044,054,064
044,054,064
044,054,064

VOLTAGE
208/230
208/230
460
575
380

DIA
(in.)
358
212
212
212
212

DUAL CKT SINGLE CKT

QTY
1
2
1
1
1

LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH044 3259 lb
38AH064 3565 lb
38AH044C 3547 lb
38AH064C 3998 lb
38AH054 3309 lb
38AH054C 3597 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
4. Two 29 dia holes are recommended for parallel
conductors on 38AH044, 054 208/230-V units.

36

SUCTION
CONNECTION(S)
LIQUID
CONNECTION(S)
SUCTION C
LIQUID D
SUCTION
(CKT A)
SUCTION
(CKT B)
LIQUID
(CKT A)
LIQUID
(CKT B)

2189 dia

2589 dia

9 dia

1189 dia

28- 9
18-101169

18-105169
18-105169

18-713169

28-589

78

11 16

28-589

28-5349

28-11189

28-10589

5. One 3589 dia hole is recommended for singleentry power on 38AH064 (208/230-V) unit.
6. Circled numerals in Top View refer to condenser
fans; refer to Wiring Diagrams.
7. If spring isolators are used, a perimeter support
channel between the unit and the isolators is
recommended.
8. Except for liquid and suction connections, dimensions for the optional single-circuit units are
the same as those for dual-circuit units.
9. Certified dimension drawings are available on
request.

UNITS 38AH074,084 (SEE PAGE 38 FOR CORNER WEIGHTS)


DIMENSIONS
(ft-in.)
UNIT
38AH
074
074C
084
084C

3-318
3-358
3-3
3-31116

4-81316
4-818
4-9
4-8

CHART 1, FIELD POWER SUPPLY


CONNECTIONS
UNIT
38AH
074
084
074
084
074,084
074,084

VOLTAGE
208/230
208/230
460
460
575
380

DIA
(in.)
212
358
212
358
212
358

QTY
2
2
1
1
1
1

LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit
is:
38AH074 3812 lb
38AH074C 4229 lb
38AH084 4057 lb
38AH084C 4735 lb
2. Unit must have clearances for airflow as
follows:
Top Do not restrict in any way
Ends 5 ft
Sides 6 ft

SUCTION
CONNECTION(S)
LIQUID
CONNECTION(S)
SUCTION C
LIQUID D
SUCTION
(CKT A)
SUCTION
(CKT B)
LIQUID
(CKT A)
LIQUID
(CKT B)

DUAL CKT

SINGLE CKT

2189 dia

2589 dia

9 dia

1189 dia

28-11169
18-101169

18-105169
18-105169

18-713169

28-589

78

28-589

28-5 9

28-11189

28-10589

34

3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting
unit to spring isolators.
4. Circled numerals in Top View refer to condenser fans;
refer to Wiring Diagrams.
5. If spring isolators are used, a perimeter support
channel between the unit and the isolators is
recommended.
6. Except for liquid and suction connections, dimensions for optional single-circuit units are the same
as those for dual-circuit units.
7. Certified dimension drawings available on request.

37

Dimensions 38AH044-134 (cont)


UNITS 38AH044-084; OPERATIONAL CORNER WEIGHTS WITH
REFRIGERANT CHARGE (APPROXIMATE) Lb
UNIT 38AH

TOTAL
WEIGHT

044
044C
054
054C
064
064C
074
074C
084
084C

3259
3547
3309
3597
3565
3998
3812
4229
4057
4735

C Copper Fin Coils

38

OPERATIONAL CORNER WEIGHT


A
B
C
D
939
893
695
732
1013
967
765
802
964
905
697
742
1034
978
771
814
1018
1011
765
771
1125
1117
874
879
1146
986
777
903
1272
1059
862
1035
1220
1049
827
961
1425
1186
965
1159

UNIT 38AH094

UNIT
38AH
094
094C

DIMENSIONS
(ft-in.)
X
Y
5-6
2-7
5-6
2-7

OPERATIONAL CORNER
WEIGHTS (lb)
A
B
C
D
1114
2192
1182
601
1273
2504
1350
686

CHART 1, FIELD POWER SUPPLY


CONNECTIONS
UNIT
38AH
094
094

VOLTAGE
208/230
460,575,380

DIAMETER
(in.)
358
358

QUANTITY
2
1

LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers

NOTES:
1. The approximate operating weight of the unit is:
38AH094 5088 lb
38AH094C 5813 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
4. Two 3589 dia holes are recommended for parallel conductors on 208/230-v units.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data
section, Fans table, page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the unit and
the isolators is recommended.

39

Dimensions 38AH044-134 (cont)


UNIT 38AH104

UNIT
38AH
104
104C

DIMENSIONS
(ft-in.)
X
Y
5-3
2-912
5-3
2-912

OPERATIONAL CORNER
WEIGHTS (lb)
A
B
C
D
1240
2138
1302
755
1405
2423
1476
856

CHART 1, FIELD POWER SUPPLY CONNECTIONS


UNIT
38AH
104
104

40

VOLTAGE
208/230
460,575,380

DIAMETER
(in.)
358
358

QUANTITY
2
1

LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers

NOTES:
1. The approximate operating weight of the unit is:
38AH104 5435 lb
38AH104C 6160 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended
for mounting unit to spring isolators.
4. Two 3589 dia holes are recommended for parallel conductors on 208/230-v units.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section,
Fans table, page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended.

UNIT 38AH124
UNIT
38AH
MODULE
124A
124B
124A-C
124B-C

DIMENSIONS
OPERATIONAL CORNER
(ft-in.)
WEIGHTS (lb)
X
Y
K
L
A
B
C
D
4-158 3-218

1037
1030
779
785

4-158 3-218
4-158 3-278

1144 1137 889 894

4-158 3-278

CHART 1, FIELD POWER SUPPLY


CONNECTIONS
UNIT 38AH
MODULE

VOLTAGE

124A
124B

208/230
460, 575, 380

DIA
(in.)
358
212

QTY
1
1

LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers

NOTES:
1. The approximate operating weight of the unit is:
38AH124 7260 lb
38AH124C 8126 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
4. One 3589 dia hole is recommended for single entry power into each module (124A
and 124B) on 208/230-v units.

5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section,
Fans table, page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the assembled unit
and the isolators is required. Do not support each module separately.
7. Each module must be rigged into position separately. The unit must not be rigged
after modules have been connected.
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.

41

Dimensions 38AH044-134 (cont)


UNIT 38AH134
DIMENSIONS
UNIT
(ft-in.)
38AH
MODULE
X
Y
K
L
134A
4-158 3-218

134B

4-878 3-318
134A-C
4-158 3-278

134B-C

4-818 3-334

OPERATIONAL CORNER
WEIGHTS (lb)
A
B
C
D
1037 1030 779
785
1167
997 789
924
1144 1137 889
894
1293 1080 874 1047

CHART 1, FIELD POWER SUPPLY CONNECTIONS


UNIT 38AH MODULE
134A

134B

VOLTAGE
208/230
460, 575, 380
208/230
460, 575
380

DIA (in.)
358
212
212
212
358

QTY
1
1
2
1
1

LEGEND

C
Copper Fin Coils
MTG Mounting
of Automotive
SAE Society
Engineers

NOTES:
1. The approximate operating weight of the unit is:
38AH134 7507 lb
38AH134C 8357 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They
are not recommended for mounting unit to spring isolators.

42

4. One 3589 dia hole is recommended for single entry power into each module 134A on 208/230-v units.
Single entry power into Module 134B is not recommended.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table,
page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the assembled unit and the isolators
is required. Do not support each module separately.
7. Each module must be rigged into position separately. The unit must not be rigged after modules have
been connected.
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.

Condensing unit selection procedure


38AH044-134
I Determine required capacity, saturated suction
temperature (SST) at the compressors, and the
temperature of the air entering the condensing
unit.
Given:
Cooling Load . . . . . . . . . . . . . . . . . . . . . 625,000 Btuh
Saturated suction temperature . . . . . . . . . . . . . . . 40 F
Entering-air temperature . . . . . . . . . . . . . . . . . . . 95 F

II Enter the Condensing Unit Ratings table at the


given saturated suction temperature and enteringair temperature for the required cooling
capacity.
The 38AH064 unit has a cooling capacity of
634,000 Btuh at 40 F SST and 95 F entering-air temperature; the unit meets requirements according to the
given conditions.

System selection procedure 38AH044-134


System requirements can often be met by combining 38AH
condensing units with one or two air handlers.
For systems with one air handler:
Use a personal computer and Carriers ACAPS (Applied
Coil and Air Handler Performance and Selection) software
to select a model 39L or 39NX air handler with directexpansion (DX) coils. Enter the software program and input your job requirements. From the list presented, select a
38AH condensing unit that you estimate will meet capacity
requirements. For sizes 044-084, you can select either a
standard dual-circuit unit (designated D) or an optional singlecircuit manifolded unit (designated S). All other sizes have
dual circuits only.
After you have selected a 38AH unit, you can check its
performance with one or several DX coils. From the DX
coil list presented on the screen, match the 38AH with any
coil or all coils. The program calculates the combined performance of the condensing unit and each DX coil and
presents the resulting system capacities and operating temperatures. Matching thermostatic expansion valves and
nozzles for the DX coils are automatically selected and
displayed.

For systems with two air handlers:


Use a personal computer and Carriers ACAPS software to
select a model 39L or 39NX air handler with direct-expansion
(DX) coils.
For the first air handler, enter the ACAPS program and
input the job requirements. To choose a condensing unit,
select the Specify Your Own option. The program asks
you for condensing unit capacities at 30 F and 50 F SST.
See the Condensing Unit Circuit and Module Ratings tables
on pages 47-50 in this book, and enter the capacities from
condenser circuit A or B (remember to use the correct Air
Temperature Entering Condenser column when locating the
circuit capacities).
For the second air handler, repeat the procedure to select the second DX coil for the condenser circuit (A or B)
not used in the first selection.

43

Performance data 38AH044-134


CONDENSING UNIT RATINGS
38AH044
SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

38AH074
85
305.0
30.2
107.0
348.0
31.8
108.0
392.0
33.5
109.0
439.0
35.0
110.0
488.0
36.5
112.0
540.0
37.9
114.0
596.0
39.3
116.0

Condenser Entering-Air Temperature (F)


90
95
100
105
110
290.0
274.0
258.0
244.0
228.0
31.0
31.6
32.0
32.3
32.5
112.0
117.0
122.0
126.0
131.0
332.0
316.0
299.0
283.0
267.0
32.7
33.5
34.1
34.7
35.1
112.0
117.0
122.0
127.0
132.0
375.0
359.0
342.0
324.0
308.0
34.5
35.4
36.2
36.9
37.5
114.0
118.0
123.0
128.0
133.0
421.0
404.0
386.0
368.0
351.0
36.1
37.2
38.3
39.1
39.9
115.0
120.0
125.0
129.0
134.0
470.0
452.0
433.0
414.0
395.0
37.8
39.0
40.2
41.3
42.3
117.0
121.0
126.0
131.0
136.0
521.0
502.0
482.0
461.0
442.0
39.4
40.8
42.1
43.4
44.6
119.0
123.0
128.0
132.0
137.0
575.0
554.0
533.0
511.0
490.0
40.9
42.5
44.0
45.5
46.8
120.0
125.0
130.0
135.0
139.0

85
357.0
36.4
111.0
407.0
38.4
111.0
458.0
40.4
113.0
512.0
42.4
115.0
568.0
44.5
116.0
627.0
46.5
119.0
688.0
48.6
121.0

Condenser Entering-Air Temperature (F)


90
95
100
105
110
342.0
325.0
309.0
293.0
277.0
37.2
38.0
38.5
38.9
39.3
116.0
121.0
126.0
131.0
136.0
389.0
372.0
354.0
337.0
320.0
39.4
40.3
41.1
41.7
42.2
117.0
122.0
127.0
131.0
136.0
439.0
422.0
403.0
384.0
366.0
41.5
42.6
43.6
44.4
45.2
118.0
123.0
127.0
132.0
137.0
493.0
473.0
454.0
434.0
414.0
43.7
45.0
46.1
47.1
48.0
119.0
124.0
129.0
133.0
138.0
548.0
527.0
506.0
486.0
465.0
45.9
47.2
48.5
49.8
50.9
121.0
125.0
130.0
135.0
140.0
605.0
583.0
561.0
540.0
518.0
48.1
49.6
51.1
52.5
53.8
123.0
127.0
132.0
137.0
140.0
665.0
642.0
619.0
595.0
573.0
50.3
52.1
53.6
55.2
56.7
125.0
130.0
134.0
139.0
143.0

85
439.0
44.3
109.0
496.0
46.7
111.0
555.0
49.1
112.0
616.0
51.6
114.0
682.0
54.1
116.0
749.0
56.6
118.0
822.0
59.2
120.0

Condenser Entering-Air Temperature (F)


90
95
100
105
110
421.0
403.0
384.0
367.0
349.0
45.3
46.1
47.0
47.6
48.2
114.0
119.0
124.0
129.0
134.0
476.0
457.0
437.0
418.0
399.0
47.9
48.9
49.9
50.8
51.6
115.0
120.0
125.0
130.0
135.0
534.0
514.0
493.0
472.0
451.0
50.5
51.8
53.0
54.0
55.0
117.0
122.0
126.0
131.0
136.0
595.0
573.0
550.0
529.0
506.0
53.2
54.7
56.0
57.2
58.4
119.0
123.0
128.0
133.0
137.0
658.0
634.0
611.0
588.0
564.0
55.9
57.5
59.1
60.5
61.9
121.0
125.0
130.0
135.0
139.0
725.0
699.0
674.0
650.0
625.0
58.6
60.4
62.3
63.8
65.4
123.0
127.0
132.0
136.0
141.0
794.0
768.0
741.0
715.0
688.0
61.3
63.5
65.4
67.3
69.0
125.0
130.0
134.0
139.0
143.0

SST (F)

115
212.0
32.6
136.0
250.0
35.3
137.0
291.0
38.1
138.0
332.0
40.6
139.0
376.0
43.1
140.0
422.0
45.6
142.0
469.0
48.0
143.0

20

25

30

35

40

45

50

38AH054
SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

20

25

30

35

40

45

50

44

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

Condenser Entering-Air Temperature (F)


90
95
100
105
110
530.0
510.0
490.0
470.0
450.0
56.7
57.8
58.7
59.6
60.4
113.0
118.0
122.0
127.0
132.0
594.0
572.0
551.0
530.0
510.0
60.0
61.3
62.5
63.5
64.5
114.0
119.0
124.0
129.0
133.0
660.0
637.0
615.0
593.0
571.0
63.4
64.9
66.2
67.6
68.6
116.0
121.0
125.0
130.0
135.0
730.0
706.0
682.0
658.0
634.0
66.9
68.6
70.1
71.7
72.9
118.0
122.0
127.0
132.0
136.0
804.0
778.0
753.0
727.0
701.0
70.4
72.3
74.1
75.7
77.3
120.0
124.0
129.0
133.0
138.0
883.0
854.0
827.0
800.0
772.0
73.9
76.1
78.1
80.1
81.7
122.0
127.0
131.0
136.0
140.0
964.0
935.0
905.0
876.0
846.0
77.6
80.0
82.2
84.3
86.4
124.0
129.0
133.0
138.0
142.0

115
430.0
61.0
137.0
489.0
65.4
138.0
548.0
69.7
139.0
611.0
74.2
141.0
677.0
78.3
143.0
745.0
83.5
145.0
817.0
88.2
147.0

Condenser Entering-Air Temperature (F)


90
95
100
105
110
600.0
578.0
556.0
536.0 514.0
66.8
68.0
69.2
70.2
71.2
117.0
122.0
127.0
132.0 137.0
674.0
652.0
628.0
604.0 582.0
70.5
72.0
73.4
74.6
75.8
118.0
123.0
128.0
132.0 138.0
754.0
729.0
704.0
679.0 654.0
74.4
76.1
77.7
79.1
80.5
119.0
123.0
128.0
133.0 138.0
837.0
811.0
783.0
757.0 729.0
78.3
80.3
82.1
83.7
85.3
120.0
125.0
129.0
134.0 139.0
924.0
896.0
866.0
838.0 809.0
82.4
84.5
86.6
88.5
90.3
122.0
126.0
131.0
136.0 140.0
1015.0
984.0
953.0
922.0 892.0
86.7
89.0
91.3
93.4
95.4
124.0
128.0
133.0
138.0 142.0
1111.0 1077.0 1044.0 1011.0 977.0
91.1
93.7
96.1
98.5 100.7
126.0
131.0
135.0
140.0 144.0

115
494.0
72.0
142.0
560.0
76.8
142.0
629.0
81.8
143.0
703.0
86.8
144.0
780.0
92.0
145.0
860.0
97.4
147.0
944.0
102.9
149.0

38AH084
SST (F)

115
261.0
39.5
141.0
303.0
42.7
141.0
347.0
45.8
142.0
395.0
48.9
143.0
444.0
51.9
144.0
496.0
55.0
146.0

20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
622.0
65.5
112.0
698.0
69.1
113.0
780.0
72.7
114.0
865.0
76.3
115.0
954.0
80.1
117.0
1047.0
84.1
119.0
1144.0
88.3
122.0

LEGEND

38AH064
SST (F)

85
549.0
55.6
108.0
614.0
58.6
110.0
683.0
61.9
111.0
754.0
65.0
113.0
829.0
68.3
115.0
910.0
71.7
118.0
994.0
75.1
120.0

115
331.0
48.7
139.0
380.0
52.2
139.0
431.0
55.9
141.0
485.0
59.5
142.0
541.0
63.1
144.0
600.0
66.9
146.0
662.0
70.6
148.0

kW
SDT
SST
TC

1095

Compressor Power
Saturated Discharge Temperature (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)

CONDENSING UNIT RATINGS (cont)


38AH094

38AH104

SST (F)

20

25

30

35

40

45

50

kW
SCT
SCT(A)
SCT(B)
SDT
SDT(A)
SDT(B)
SST
TC

TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)

85
700
71.1
110
108
108
106
785
75.1
112
109
109
106
873
79.4
114
110
111
107
965
83.7
116
112
112
109
1062
88.1
119
114
114
110
1163
92.6
122
117
116
112
1269
97.3
125
119
118
114

Condenser Entering-Air Temperature (F)


90
95
100
105
110
672
646
618
591
562
72.6
73.8
74.9
76.0
76.7
115
119
124
129
134
112
117
122
127
132
113
118
123
128
133
111
116
121
126
131
757
727
699
670
641
76.8
78.5
79.9
81.1
82.3
116
121
126
130
135
113
118
123
128
133
114
119
124
129
134
111
116
121
126
132
843
812
782
752
722
81.4
83.1
84.8
86.4
87.8
118
123
127
132
136
115
120
124
129
134
115
120
125
130
135
112
117
122
127
132
934
901
869
837
805
85.9
88.0
89.9
91.8
93.4
121
125
130
134
138
117
121
126
131
135
117
122
127
132
136
114
119
124
128
133
1028
994
960
926
891
90.6
93.0
95.2
97.3
99.2
123
128
132
136
141
119
123
128
133
137
119
124
129
133
138
115
120
125
130
135
1127
1091
1055
1018
982
95.4
98.0
100.6
102.9
105.2
126
130
135
139
143
121
126
130
135
139
121
126
131
136
140
117
122
127
132
136
1231
1192
1154
1115
1077
100.3
103.2
106.1
108.7
111.2
129
133
138
142
146
124
128
133
137
142
123
128
133
138
142
119
124
129
133
138

115
535
77.3
139
137
138
136
612
83.1
140
138
139
137
691
88.9
141
139
140
137
772
94.9
143
140
141
138
857
100.9
145
142
143
140
946
107.1
148
144
145
141
1038
113.5
150
146
147
143

SST (F)

20

25

30

35

40

45

50

TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)

85
782
77.4
108
110
106
107
877
82.1
110
112
107
109
977
86.9
112
114
109
111
1082
91.7
114
117
110
112
1192
96.8
117
120
112
114
1308
101.9
119
123
114
117
1429
107.3
122
126
116
119

Condenser Entering-Air Temperature (F)


90
95
100
105
110
749
718
686
654
624
79.2
80.9
82.3
83.6
84.7
113
117
122
127
132
115
119
124
129
133
111
116
121
126
131
112
117
122
127
132
843
809
775
742
709
84.2
86.1
87.7
89.3
90.8
114
119
123
128
133
116
121
126
130
135
112
117
122
127
131
114
119
124
128
133
941
904
869
833
798
89.1
91.4
93.4
95.3
96.9
116
121
125
130
134
119
123
128
132
137
113
118
123
128
133
115
120
125
130
135
1043
1004
967
929
891
94.4
96.8
99.1
101.3
103.2
118
123
127
132
136
121
126
130
134
139
115
120
125
129
134
117
122
127
132
137
1151
1109
1069
1028
988
99.6
102.5
105
107.4
109.7
121
125
130
134
138
124
128
133
137
141
117
122
127
131
136
119
124
129
134
139
1264
1220
1176
1132
1090
105.2
108.2
111.1
113.8
116.4
124
128
132
136
141
127
131
135
140
144
119
124
128
133
138
122
126
131
136
141
1382
1335
1289
1243
1197
110.8
114.1
117.3
120.3
123.2
126
131
135
139
143
130
134
138
143
147
121
126
131
135
140
124
129
133
138
143

115
592
85.6
137
138
136
137
676
92.1
137
139
136
138
762
96.5
139
141
137
140
853
105.1
141
143
139
141
948
111.9
143
146
141
143
1047
118.9
145
148
143
145
1151
125.9
148
151
145
148

LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Condensing Temperature for Circuit A
Saturated Condensing Temperature for Circuit B
Saturated Discharge Temperature (F)
Saturated Discharge Temperature for Circuit A
Saturated Discharge Temperature for Circuit B
Saturated Suction Temperature Entering Condensing Unit (F)
Gross Cooling Capacity (1000 Btuh)

NOTE: Units 38AH094 and 104 consist of circuits A and B.

45

Performance data 38AH044-134 (cont)


CONDENSING UNIT RATINGS (cont)
38AH124

38AH134

SST (F)

20

25

30

35

40

45

50

TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT

(A) or (B)
(A) or (B)

(A) or (B)
(A) or (B)

(A) or (B)
(A) or (B)

(A) or (B)
(A) or (B)

(A) or (B)
(A) or (B)

(A) or (B)
(A) or (B)

(A) or (B)
(A) or (B)

Condenser Entering-Air
85
90
95
100
884
848
810
774
88.6
90.6
92.4
94.0
109
114
119
124
108
113
118
123
996
958
918
880
93.4
95.8
98.0
99.8
110
115
120
125
109
114
119
124
1114
1072 1030
990
98.2 101.0 103.6 106.0
112
117
121
126
110
115
120
125
1236 1192
1148
1104
103.2 106.4 109.4 112.0
114
118
123
128
112
117
121
126
1366 1320 1272 1226
108.4 111.8 115.2 118.2
116
120
125
130
114
118
123
128
1502 1452 1402 1352
113.6 117.4 121.0 124.6
118
123
127
132
116
120
125
130
1644 1590 1536 1484
118.8 123.0 127.0 131.0
121
125
130
134
118
122
127
132

Temperature (F)
105
110
115
738
702
668
95.2
96.4
97.4
129
134
138
128
133
138
842
804
766
101.6 103.2 104.4
130
134
139
129
134
139
948
908
868
108.0 110.0 111.6
131
136
140
130
135
139
1062 1018
974
114.6 116.8 119.0
132
137
142
131
136
141
1180
1132 1086
121.2 123.8 126.2
134
139
143
133
137
142
1302 1252 1204
127.8 131.0 133.8
136
141
145
135
139
144
1432 1380 1326
134.6 138.2 141.4
139
143
148
137
141
146

LEGEND
kW
Compressor Power
SCT
Saturated Condensing Temperature (F)
SCT(A) Saturated Condensing Temperature for Module 38AH124A
134A (F)
SCT(B) Saturated Condensing Temperature for Module 38AH124B
134B (F)
SDT
Saturated Discharge Temperature (F)
SDT(A) Saturated Discharge Temperature for Module 38AH124A
134A (F)
SDT(B) Saturated Discharge Temperature for Module 38AH124B
134B (F)
SST
Saturated Suction Temperature Entering Condensing Unit (F)
TC
Gross Cooling Capacity (1000 Btuh)

or

20

25

30

35

40

45

or
or
or

NOTE: Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of Modules 134A and 134B. Each module is one refrigeration circuit.

46

SST (F)

50

TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)

85
992
99.8
109
108
108
104
1113
105.3
110
109
109
106
1240
110.9
112
111
110
107
1373
116.6
114
113
112
109
1514
122.5
116
115
114
110
1662
128.4
118
117
116
113
1817
134.4
121
120
118
115

Condenser Entering-Air Temperature (F)


90
95
100
105
110
955
916
878
840
802
102.0
104.0
105.7
107.2
108.6
114
119
124
129
134
113
117
122
127
132
113
118
123
128
133
109
114
119
124
129
1073
1032
992
952
912
107.9
110.3
112.3
114.3
116.0
115
120
125
130
134
114
119
123
128
133
114
119
124
129
134
111
115
120
125
130
1197
1154
1111
1068
1025
113.9
116.7
119.2
121.5
123.6
117
121
126
131
136
116
120
125
130
134
115
120
125
130
135
112
117
122
126
131
1327
1281
1235
1190
1145
120.0
123.2
126.1
128.9
131.3
118
123
128
132
137
118
122
127
131
136
117
121
126
131
136
114
119
123
128
133
1465
1415
1367
1318
1269
126.2
129.8
133.1
136.3
139.2
120
124
129
133
138
120
124
129
133
138
118
123
128
133
137
116
120
125
130
134
1609
1557
1504
1452
1399
132.6
136.5
140.3
143.8
147.2
123
127
132
136
141
122
126
131
136
140
120
125
130
135
139
117
122
127
131
136
1761
1704
1649
1593
1537
139.0
143.4
147.6
151.5
155.4
125
130
134
139
143
124
129
133
138
142
122
127
132
137
141
119
124
129
133
138

115
765
109.7
138
137
138
134
872
117.5
139
138
139
134
983
125.5
140
139
139
136
1099
133.7
142
141
141
137
1220
141.8
142
142
142
139
1348
150.3
145
145
144
141
1481
158.9
148
147
146
142

CONDENSING UNIT CIRCUIT AND MODULE RATINGS


38AH044 CIRCUIT A
SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
153.0
15.0
105.0
174.0
15.8
107.0
195.0
16.7
108.0
218.0
17.5
110.0
241.0
18.3
112.0
266.0
19.1
114.0
293.0
19.9
117.0

38AH044 CIRCUIT B
Air Temperature
90
95
146.0
138.0
15.4
15.7
110.0
115.0
166.0
158.0
16.3
16.7
111.0
116.0
187.0
179.0
17.2
17.6
113.0
117.0
209.0
201.0
18.0
18.6
115.0
119.0
233.0
224.0
18.9
19.5
117.0
121.0
257.0
248.0
19.8
20.5
119.0
123.0
283.0
273.0
20.6
21.4
121.0
126.0

Entering
100
130.0
15.9
120.0
150.0
17.0
121.0
171.0
18.0
122.0
192.0
19.1
124.0
215.0
20.1
126.0
238.0
21.1
128.0
263.0
22.1
130.0

Condenser (F)
105
110
123.0
115.0
16.1
16.2
124.0
129.0
142.0
134.0
17.3
17.5
125.0
130.0
162.0
154.0
18.4
18.7
127.0
131.0
183.0
175.0
19.5
19.9
128.0
133.0
205.0
196.0
20.6
21.1
130.0
135.0
228.0
219.0
21.7
22.3
132.0
137.0
252.0
242.0
22.8
23.4
135.0
139.0

Air Temperature
90
95
145.0
137.0
15.7
16.0
115.0
120.0
167.0
159.0
16.6
17.0
115.0
120.0
190.0
182.0
17.4
17.9
116.0
121.0
215.0
206.0
18.2
18.8
116.0
121.0
240.0
231.0
19.0
19.6
118.0
122.0
266.0
256.0
19.8
20.5
119.0
124.0
293.0
283.0
20.6
21.4
121.0
126.0

Entering
100
129.0
16.1
125.0
150.0
17.3
125.0
173.0
18.3
125.0
197.0
19.3
126.0
221.0
20.2
127.0
246.0
21.2
128.0
273.0
22.1
130.0

Condenser (F)
105
110
121.0
113.0
16.2
16.3
130.0
135.0
142.0
134.0
17.5
17.6
130.0
135.0
164.0
155.0
18.6
18.9
130.0
135.0
188.0
178.0
19.7
20.1
131.0
136.0
212.0
202.0
20.8
21.3
132.0
137.0
237.0
227.0
21.8
22.4
133.0
138.0
262.0
252.0
22.8
23.5
135.0
139.0

Air Temperature
90
95
198.0
190.0
21.3
21.7
114.0
119.0
224.0
215.0
22.5
23.0
115.0
120.0
252.0
242.0
23.8
24.4
117.0
122.0
281.0
270.0
25.1
25.8
119.0
123.0
311.0
299.0
26.4
27.2
121.0
126.0
343.0
330.0
27.8
28.6
123.0
128.0
376.0
363.0
29.1
30.1
126.0
130.0

Entering
100
181.0
22.2
124.0
206.0
23.5
125.0
232.0
25.0
126.0
259.0
26.4
128.0
288.0
27.9
130.0
318.0
29.5
132.0
350.0
31.0
135.0

Condenser (F)
105
110
173.0
165.0
22.5
22.9
129.0
134.0
197.0
188.0
24.0
24.4
130.0
135.0
222.0
212.0
25.5
26.0
131.0
136.0
249.0
238.0
27.0
27.6
133.0
137.0
277.0
265.0
28.6
29.3
135.0
139.0
306.0
294.0
30.2
31.0
137.0
141.0
337.0
324.0
31.9
32.7
139.0
144.0

115
107.0
16.3
134.0
126.0
17.6
135.0
146.0
19.0
136.0
166.0
20.2
138.0
187.0
21.5
139.0
209.0
22.8
141.0
232.0
24.0
143.0

38AH054 CIRCUIT A
SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
152.0
15.4
110.0
175.0
16.2
110.0
199.0
16.9
111.0
223.0
17.6
112.0
249.0
18.4
113.0
275.0
19.1
115.0
303.0
19.8
117.0

20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
207.0
20.8
109.0
234.0
21.9
111.0
262.0
23.1
112.0
291.0
24.3
114.0
323.0
25.6
116.0
355.0
26.8
119.0
390.0
28.1
121.0

20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TG
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT

85
152.0
15.2
108.0
174.0
16.0
109.0
197.0
16.8
109.0
221.0
17.5
110.0
247.0
18.2
112.0
274.0
18.8
113.0
303.0
19.4
115.0

Air Temperature
90
95
144.0
136.0
15.6
15.9
113.0
118.0
166.0
158.0
16.4
16.8
113.0
118.0
188.0
180.0
17.3
17.8
114.0
119.0
212.0
203.0
18.1
18.6
115.0
120.0
237.0
228.0
18.9
19.5
116.0
121.0
264.0
254.0
19.6
20.3
118.0
123.0
292.0
281.0
20.3
21.1
119.0
124.0

Entering
100
128.0
16.1
123.0
149.0
17.1
123.0
171.0
18.2
124.0
194.0
19.2
125.0
218.0
20.1
126.0
244.0
21.0
127.0
270.0
21.9
129.0

Condenser (F)
105
110
121.0
113.0
16.2
16.3
128.0
133.0
141.0
133.0
17.4
17.6
128.0
133.0
162.0
154.0
18.5
18.8
129.0
134.0
185.0
176.0
19.6
20.0
130.0
135.0
209.0
199.0
20.7
21.2
131.0
136.0
233.0
223.0
21.7
22.3
132.0
137.0
259.0
248.0
22.7
23.4
134.0
139.0

115
105.0
16.3
138.0
124.0
17.7
138.0
145.0
19.1
139.0
166.0
20.4
139.0
189.0
21.6
140.0
213.0
22.8
142.0
237.0
24.0
143.0

Air Temperature
90
95
197.0
188.0
21.5
22.0
117.0
122.0
222.0
213.0
22.8
23.3
118.0
123.0
249.0
240.0
24.1
24.7
120.0
124.0
278.0
267.0
25.5
26.2
121.0
126.0
308.0
296.0
26.9
27.6
124.0
128.0
339.0
327.0
28.3
29.1
126.0
130.0
372.0
359.0
29.7
30.7
129.0
133.0

Entering
100
180.0
22.4
126.0
204.0
23.8
128.0
230.0
25.3
129.0
257.0
26.8
131.0
285.0
28.3
133.0
315.0
29.9
135.0
346.0
31.5
137.0

Condenser (F)
105
110
172.0
164.0
22.7
22.3
131.0
136.0
195.0
186.0
24.2
24.6
132.0
137.0
220.0
211.0
25.8
26.3
134.0
138.0
246.0
236.0
27.4
27.9
135.0
140.0
274.0
263.0
29.0
29.6
137.0
142.0
303.0
291.0
30.7
31.4
140.0
144.0
333.0
321.0
32.4
33.2
142.0
146.0

115
156.0
23.3
141.0
178.0
25.0
142.0
201.0
26.7
143.0
226.0
28.5
145.0
252.0
30.2
147.0
279.0
32.1
149.0

Air Temperature
90
95
223.0
213.0
24.0
24.4
114.0
119.0
252.0
242.0
25.4
25.9
115.0
120.0
282.0
272.0
26.7
27.4
116.0
121.0
314.0
303.0
28.1
28.9
118.0
122.0
347.0
335.0
29.5
30.3
120.0
124.0
382.0
369.0
30.8
31.8
122.0
126.0
418.0
405.0
32.2
33.4
124.0
129.0

Entering
100
203.0
24.8
124.0
231.0
26.4
124.0
261.0
28.0
126.0
291.0
29.6
127.0
323.0
31.2
129.0
356.0
32.8
131.0
391.0
34.4
133.0

Condenser (F)
105
110
194.0
184.0
25.1
25.3
128.0
133.0
221.0
211.0
26.8
27.2
129.0
134.0
250.0
239.0
28.5
29.0
130.0
135.0
280.0
268.0
30.2
30.8
132.0
137.0
311.0
299.0
31.9
32.6
134.0
138.0
344.0
331.0
33.6
34.4
135.0
140.0
378.0
364.0
35.4
36.3
138.0
142.0

115
174.0
25.5
138.0
201.0
27.4
139.0
228.0
29.4
140.0
257.0
31.3
141.0
287.0
33.2
143.0
318.0
35.2
145.0
351.0
37.1
147.0

38AH054 CIRCUIT B
115
105.0
16.2
140.0
125.0
17.7
140.0
146.0
19.1
140.0
169.0
20.4
141.0
192.0
21.7
141.0
217.0
22.9
142.0

38AH064 CIRCUIT A
SST (F)

SST (F)

SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
STD
TC
kW
STD
TC
kW
SDT
TC
kW
SDT

85
205.0
21.0
112.0
232.0
22.2
113.0
259.0
23.5
115.0
289.0
24.8
117.0
319.0
26.1
119.0
352.0
27.4
122.0
385.0
28.8
124.0

38AH064 CIRCUIT B
115
157.0
23.2
139.0
179.0
24.8
139.0
203.0
26.5
141.0
228.0
28.2
142.0
254.0
29.9
144.0
282.0
31.7
146.0
311.0
33.5
148.0

SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
STD
TC
kW
STD
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
232.0
23.5
109.0
262.0
24.8
110.0
293.0
26.0
111.0
325.0
27.3
113.0
359.0
28.5
115.0
394.0
29.8
117.0
432.0
31.1
119.0

(See Legend, page 48.)

47

Performance data 38AH044-134 (cont)


CONDENSING UNIT CIRCUIT AND MODULE RATINGS (cont)
38AH074 CIRCUIT A
SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT

85
236.0
23.4
108.0
265.0
24.6
109.0
296.0
25.9
110.0
328.0
27.1
112.0
361.0
28.4
114.0
397.0
29.7
117.0
434.0
31.0
119.0

38AH074 CIRCUIT B
Air Temperature
90
95
227.0
217.0
23.9
24.3
113.0
118.0
256.0
246.0
25.2
25.8
114.0
118.0
286.0
275.0
26.6
27.2
115.0
120.0
317.0
306.0
28.0
28.7
117.0
121.0
350.0
338.0
29.3
30.2
119.0
123.0
385.0
372.0
30.7
31.7
121.0
126.0
421.0
408.0
32.1
33.2
123.0
128.0

Entering
100
208.0
24.7
122.0
236.0
26.3
123.0
265.0
27.8
124.0
295.0
29.4
126.0
327.0
31.0
128.0
360.0
32.6
130.0
395.0
34.2
132.0

Condenser (F)
105
110
198.0
188.0
25.0
25.3
127.0
132.0
226.0
216.0
26.7
27.1
128.0
133.0
255.0
244.0
28.4
28.8
129.0
134.0
284.0
273.0
30.1
30.6
131.0
135.0
315.0
303.0
31.7
32.4
132.0
137.0
348.0
335.0
33.5
34.2
135.0
139.0
382.0
368.0
35.2
36.1
137.0
141.0

Air Temperature
90
95
299.0
288.0
33.5
34.1
118.0
123.0
336.0
325.0
35.4
36.1
118.0
123.0
376.0
364.0
37.3
38.2
119.0
124.0
418.0
405.0
39.3
40.3
120.0
125.0
462.0
448.0
41.3
42.4
122.0
127.0
508.0
492.0
43.5
44.6
124.0
128.0
556.0
539.0
45.7
47.0
126.0
131.0

Entering
100
277.0
34.7
128.0
313.0
36.8
128.0
351.0
39.0
129.0
391.0
41.2
130.0
433.0
43.4
131.0
477.0
45.8
133.0
522.0
48.2
135.0

Condenser (F)
105
110
267.0
256.0
35.2
35.7
133.0
138.0
301.0
290.0
37.4
38.0
133.0
138.0
339.0
326.0
39.7
40.4
134.0
139.0
378.0
364.0
42.0
42.8
135.0
140.0
419.0
404.0
44.4
45.3
136.0
141.0
461.0
446.0
46.8
47.8
138.0
142.0
506.0
489.0
49.4
50.5
140.0
144.0

115
178.0
25.5
137.0
206.0
27.4
138.0
233.0
29.2
138.0
262.0
31.1
140.0
292.0
33.1
142.0
323.0
35.0
144.0
355.0
36.9
146.0

38AH084 CIRCUIT A
SST (F)
20

25

30

35

40

45

50

kW
SDT
SST
TC

48

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
310.0
32.9
113.0
348.0
34.7
114.0
389.0
36.5
114.0
432.0
38.3
115.0
477.0
40.2
117.0
524.0
42.2
119.0
573.0
44.3
122.0

SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT

85
313.0
32.2
108.0
349.0
34.0
110.0
387.0
36.0
112.0
426.0
37.9
114.0
468.0
39.9
116.0
513.0
42.0
118.0
560.0
44.1
121.0

Air Temperature
90
95
303.0
293.0
32.8
33.5
113.0
118.0
338.0
326.0
34.8
35.5
114.0
119.0
374.0
362.0
36.8
37.7
116.0
121.0
413.0
400.0
38.9
39.9
118.0
123.0
454.0
440.0
41.1
42.1
121.0
125.0
498.0
482.0
43.2
44.4
123.0
127.0
543.0
527.0
45.5
46.8
125.0
130.0

Entering
100
282.0
34.0
122.0
315.0
36.2
124.0
350.0
38.4
126.0
387.0
40.7
128.0
426.0
43.1
130.0
467.0
45.5
132.0
510.0
48.0
134.0

Condenser (F)
105
110
272.0
262.0
34.6
35.1
127.0
132.0
304.0
294.0
36.8
37.4
129.0
133.0
338.0
327.0
39.2
39.8
130.0
135.0
374.0
361.0
41.6
42.3
132.0
137.0
412.0
398.0
44.0
44.9
134.0
139.0
452.0
437.0
46.6
47.5
137.0
141.0
494.0
478.0
49.1
50.3
139.0
143.0

115
252.0
35.5
137.0
283.0
38.0
138.0
315.0
40.5
140.0
349.0
43.1
141.0
385.0
45.7
143.0
422.0
48.5
146.0
462.0
51.3
148.0

Air Temperature
90
95
301.0
290.0
33.3
33.9
116.0
121.0
338.0
327.0
35.1
35.9
117.0
122.0
378.0
365.0
37.1
37.9
118.0
122.0
419.0
406.0
39.0
40.0
119.0
124.0
462.0
448.0
41.1
42.1
121.0
125.0
507.0
492.0
43.2
44.4
123.0
127.0
555.0
538.0
45.4
46.7
125.0
130.0

Entering
100
279.0
34.5
126.0
315.0
36.6
127.0
353.0
38.7
127.0
392.0
40.9
128.0
433.0
43.2
130.0
476.0
45.5
132.0
522.0
47.9
134.0

Condenser (F)
105
110
269.0
258.0
35.0
35.5
131.0
136.0
303.0
292.0
37.2
27.8
131.0
137.0
340.0
328.0
39.4
40.1
132.0
137.0
379.0
365.0
41.7
42.5
133.0
138.0
419.0
405.0
44.1
45.0
135.0
139.0
461.0
446.0
46.6
47.6
137.0
141.0
505.0
488.0
49.1
50.2
139.0
143.0

115
248.0
35.9
141.0
281.0
38.3
141.0
315.0
40.8
142.0
352.0
43.3
143.0
390.0
45.9
144.0
430.0
48.6
146.0
472.0
51.3
148.0

38AH084 CIRCUIT B

LEGEND
Compressor Power
Saturated Temperature Leaving Compressor (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)

115
246.0
36.1
143.0
279.0
38.5
143.0
314.0
41.0
144.0
351.0
43.5
145.0
390.0
46.1
146.0
430.0
48.8
147.0
472.0
51.6
149.0

SST (F)
20

25

30

35

40

45

50

TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT

85
312.0
32.6
111.0
350.0
34.4
112.0
391.0
36.2
113.0
433.0
38.0
114.0
477.0
39.9
116.0
523.0
41.9
118.0
571.0
44.0
121.0

CONDENSING UNIT CIRCUIT AND MODULE RATINGS (cont)


38AH094 CIRCUIT A
SST (F)
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT

20

25

30

35

40

45

50

85
385
39.0
110
108
433
41.3
112
109
482
43.7
114
111
533
46.1
116
112
587
48.6
119
114
643
51.1
122
116
702
53.7
125
118

38AH094 CIRCUIT B
Air Temperature
90
95
368
352
39.8
40.4
115
119
113
118
416
398
42.2
43.1
116
121
114
119
464
446
44.8
45.7
118
123
115
120
515
496
47.3
48.5
121
125
117
122
568
548
50.0
51.3
123
128
119
124
623
602
52.6
54.1
126
130
121
126
680
658
55.4
57.0
129
133
123
128

Entering
100
335
40.9
124
123
381
43.8
126
124
428
46.6
127
125
477
49.5
130
127
528
52.5
132
129
581
55.5
135
131
636
58.6
138
133

Condenser (F)
105
110
318
300
41.4
41.6
129
134
128
133
363
346
44.4
44.9
130
135
129
134
410
392
47.4
48.1
132
136
130
135
458
439
50.5
51.3
134
138
132
136
508
487
53.6
54.6
136
141
133
138
559
538
56.8
58.0
139
143
136
140
613
591
60.0
61.4
142
146
138
142

Air Temperature
90
95
349
334
36.6
37.4
113
117
111
116
394
378
38.9
39.8
114
119
112
117
441
423
41.1
42.2
116
121
113
118
490
471
43.5
44.6
118
123
115
120
541
521
45.8
47.2
121
125
117
122
595
574
48.3
49.7
124
128
119
124
651
629
50.8
52.4
126
131
121
126

Entering
100
318
38.0
122
121
361
40.5
123
122
406
43.1
125
123
453
45.7
127
125
502
48.4
130
127
553
51.1
132
128
607
53.9
135
131

Condenser (F)
105
110
302
287
38.6
39.0
127
132
126
131
345
329
41.2
41.9
128
133
127
131
389
372
44.0
44.7
130
134
128
133
435
416
46.7
47.6
132
136
129
134
482
463
49.5
50.6
134
138
131
136
532
512
52.4
53.6
136
141
133
138
585
563
55.3
56.7
139
143
135
140

115
283
41.7
139
138
328
45.2
140
139
373
48.6
141
140
419
52.0
143
141
467
55.5
145
143
517
59.0
148
145
568
62.6
150
147

38AH104 CIRCUIT A
SST (F)
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT

20

25

30

35

40

45

50

kW
SDT
SST
TC

85
365
35.8
108
106
411
37.9
110
107
458
40.1
112
109
508
42.2
114
110
561
44.5
117
112
616
46.7
119
114
673
49.1
122
116

SST (F)

20

25

30

35

40

45

50

TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT

85
315
32.1
108
106
352
33.8
109
106
391
35.7
110
107
432
37.6
112
109
475
39.5
114
110
520
41.5
117
112
567
43.6
119
114

Air Temperature
90
95
304
294
32.8
33.4
112
117
111
116
341
329
34.6
35.4
113
118
111
116
379
366
36.6
37.4
115
120
112
117
419
405
38.6
39.5
117
121
114
119
460
446
40.6
41.7
119
123
115
120
504
489
42.8
43.9
121
126
117
122
551
534
44.9
46.2
124
128
119
124

Entering
100
283
34.0
122
121
318
36.1
123
121
354
38.2
124
122
392
40.4
126
124
432
42.7
128
125
474
45.1
130
127
518
47.5
133
129

Condenser (F)
105
110
273
262
34.6
35.1
127
132
126
131
307
295
36.7
37.4
128
133
126
132
342
330
39.0
39.7
129
134
127
132
379
366
41.3
42.1
131
135
128
133
418
404
43.7
44.6
133
137
130
135
459
444
46.1
47.2
135
139
132
136
502
486
48.7
49.8
137
142
133
138

115
252
35.6
137
136
284
37.9
138
137
318
40.3
139
137
353
42.9
140
138
390
45.4
142
140
429
48.1
144
141
470
50.9
146
143

Air Temperature
90
95
400
384
42.6
43.5
115
119
112
117
449
431
45.3
46.3
116
121
114
119
500
481
48.0
49.2
119
123
115
120
553
533
50.9
52.2
121
126
117
122
610
588
53.8
55.3
124
128
119
124
669
646
56.9
58.5
127
131
122
126
731
706
60.0
61.7
130
134
124
129

Entering
100
368
44.3
124
122
414
47.2
126
124
463
50.3
128
125
514
53.4
130
127
567
56.6
133
129
623
60.0
135
131
682
63.4
138
133

Condenser (F)
105
110
352
337
45.0
45.7
129
133
127
132
397
380
48.1
48.9
130
135
128
133
444
426
51.3
52.2
132
137
130
135
494
475
54.6
55.6
134
139
132
137
546
525
57.9
59.1
137
141
134
139
600
578
61.4
62.8
140
144
136
141
658
634
65.0
66.5
143
147
138
143

115
321
46.3
138
137
364
49.7
139
138
408
53.1
141
140
455
56.6
143
141
504
60.3
146
143
556
64.1
148
145
610
67.9
151
148

38AH104 CIRCUIT B
115
271
39.3
137
136
312
42.4
137
136
354
45.4
139
137
398
48.5
141
139
444
51.6
143
141
491
54.8
145
143
541
58.0
148
145

SST (F)

20

25

30

35

40

45

50

TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT

85
417
41.6
110
107
466
44.2
112
109
519
46.8
114
111
574
49.5
117
112
631
52.3
120
114
692
55.2
123
117
756
58.2
126
119

LEGEND
Compressor Power
Saturated Temperature Leaving Compressor (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)

49

Performance data 38AH044-134 (cont)


CONDENSING UNIT CIRCUIT AND MODULE RATINGS (cont)
38AH124 MODULES 124A OR 124B; 38AH134 MODULE 134A
Air Temperature Entering Condenser (F)
SST (F)
85
90
95
100
105
110
TC
442
424
405
387
369
351
kW
44.3
45.3
46.2
47.0
47.6
48.2
20
SDT
109
114
119
124
129
134
SCT
108
113
118
123
128
133
TC
498
479
459
440
421
402
kW
46.7
47.9
49.0
49.9
50.8
51.6
25
SDT
110
115
120
125
130
134
SCT
109
114
119
124
129
134
TC
557
536
515
495
474
454
kW
49.1
50.5
51.8
53.0
54.0
55.0
30
SDT
112
117
121
126
131
136
SCT
110
115
120
125
130
135
TC
618
596
574
552
531
509
kW
51.6
53.2
54.7
56.0
57.3
58.4
35
SDT
114
118
123
128
132
137
SCT
112
117
121
126
131
136
TC
683
660
636
613
590
566
kW
54.2
55.9
57.6
59.1
60.6
61.9
40
SDT
116
120
125
130
134
139
SCT
114
118
123
128
133
137
TC
751
726
701
676
651
626
kW
56.8
58.7
60.5
62.3
63.9
65.5
45
SDT
118
123
127
132
136
141
SCT
116
120
125
130
135
139
TC
822
795
768
742
716
690
kW
59.4
61.5
63.5
65.5
67.3
69.1
50
SDT
121
125
130
134
139
143
SCT
118
122
127
132
137
141

kW
SCT
SDT
SST
TC

115
334
48.7
138
138
383
52.2
139
139
434
55.8
140
139
487
59.5
142
141
543
63.1
143
142
602
66.9
145
144
663
70.7
148
146

LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (F)
Saturated Suction Temperature Entering Condensing Unit (F)
Gross Cooling Capacity (1000 Btuh)

NOTE: Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of Modules 134A and 134B. Each module is one circuit.

50

38AH134 MODULE 134B


Air Temperature
SST (F)
85
90
95
TC
550
531
511
kW
55.5
56.7
57.8
20
SDT
108
113
117
SCT
104
109
114
TC
615
594
573
kW
58.6
60.0
61.3
25
SDT
109
114
119
SCT
106
111
115
TC
683
661
639
kW
61.8
63.4
64.9
30
SDT
111
116
120
SCT
107
112
117
TC
755
731
707
kW
65.0
66.8
68.5
35
SDT
113
118
122
SCT
109
114
119
TC
831
805
779
kW
68.3
70.3
72.2
40
SDT
115
120
124
SCT
111
116
120
TC
911
883
856
kW
71.6
73.9
76.0
45
SDT
117
122
126
SCT
113
117
122
TC
995
966
936
kW
75.0
77.5
79.9
50
SDT
120
124
129
SCT
115
119
124

Entering
100
491
58.7
122
119
552
62.4
123
120
616
66.2
125
122
683
70.1
127
123
754
74.0
129
125
828
78.0
131
127
907
82.1
133
129

Condenser (F)
105
110
471
451
59.6
60.4
127
132
124
129
531
510
63.5
64.4
128
133
125
130
594
571
67.5
68.6
130
134
126
131
659
636
71.6
72.9
131
136
128
133
728
703
75.7
77.3
133
138
130
134
801
773
79.9
81.7
136
140
131
136
877
847
84.2
86.3
138
142
133
138

115
431
61.0
137
134
489
65.3
138
134
549
69.7
139
136
612
74.2
141
137
677
78.7
142
139
746
83.4
145
141
818
88.2
147
142

Typical piping and wiring 38AH044-134


ROOFTOP INSTALLATION UNIT 38AH104 WITH SINGLE AIR HANDLER SHOWN

LEGEND
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Line Voltage
Piping
Double Riser Piping
(If Required)

*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific
installation. Face-split connection shown; row-split connection also possible.
4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the compressor.

51

Typical piping and wiring


38AH044-134 (cont)
GROUND-LEVEL INSTALLATION UNIT 38AH104 WITH SINGLE AIR HANDLER SHOWN

LEGEND
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Line Voltage
Piping

*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific
installation. Face-split connection shown; row-split connection also possible.
4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the compressor.

52

Electrical data 38AH044-134


38AH044-084 DUAL-CIRCUIT CONDENSING UNITS
UNIT
38AH

VOLTAGE
DESIGNATION

COMPRESSOR
MODEL (A/B)

500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200

044

054

064

074

084

SUPPLY VOLTAGE*

NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60

06E-250/250

06E-250/265

06E-265/275

06E-275/299

06E-299/299

POWER SUPPLY

COMPRESSOR

Min

Max

MCA

MOCP

ICF

187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342

254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418

174.6
88.9
78.4
93.5
201.8
100.1
88.0
107.1
244.0
113.1
100.6
126.9
322.3
145.0
132.2
174.5
363.3
163.6
148.9
200.7

225
110
90
125
250
125
125
150
350
150
125
175
450
200
175
250
500
225
200
250

434.7
218.6
162.4
241.2
535.7
268.6
206.4
297.2
617.5
307.6
226.1
341.1
829.0
408.2
336.8
458.0
870.0
426.8
353.5
484.2

A
RLA
67.9
34.6
28.8
34.6
67.9
34.5
28.8
34.6
89.7
43.6
36.5
45.5
106.4
46.8
40.4
52.6
147.4
65.4
57.1
78.8

B
LRA
345
173
120
191
345
173
120
191
446
223
164
247
506
253
176
280
690
345
276
382

RLA
67.9
34.6
28.8
34.6
89.7
43.6
36.5
45.5
106.4
46.8
40.4
52.6
147.4
65.4
57.1
78.8
147.4
65.4
57.1
78.8

LRA
345
173
120
191
446
223
164
247
506
253
176
280
690
345
276
382
690
345
276
382

38AH094,104 DUAL-CIRCUIT CONDENSING UNITS


UNIT
38AH

VOLTAGE
DESIGNATION

094

104

500
600
100
200
500
600
100
200

COMPRESSOR
A1/A2/B1/B2
MODEL NO.
06E-275/
250/299/-

06E-265/250/
265/265

NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60

SUPPLY
VOLTAGE*
Min
187
414
518
342
187
414
518
342

Max
254
508
632
418
254
508
632
418

POWER SUPPLY
MCA

MOCP

ICF

391.3
179.5
160.9
209.1
392.2
192.7
168.0
205.9

500
225
200
250
450
225
200
250

754.2
369.4
282.3
416.8
725.9
361.2
286.2
396.0

COMPRESSOR
A2
B1
RLA LRA
RLA
LRA
67.9
345
147.7
690
34.6
173
65.4
345
28.8
120
57.1
276
34.6
191
78.8
382
67.9
345
89.7
446
34.6
173
43.6
223
28.8
120
36.5
164
34.6
191
45.5
247

A1
RLA
106.4
46.8
40.4
52.6
89.7
43.6
36.5
45.5

LRA
506
253
176
280
446
223
164
247

B2
RLA

89.7
43.6
36.5
45.5

LRA

446
223
164
247

38AH124,134 DUAL-CIRCUIT CONDENSING UNITS


UNIT
38AH
MODULE
124A
124B
134A

134B

VOLTAGE
DESIGNATION
500
600
100
200
500
600
100
200

COMPRESSOR
A1/A2
MODEL NO.
06E-275/
265

06E-299/
275

NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60

SUPPLY
VOLTAGE*
Min
187
414
518
342
187
414
518
342

Max
254
508
632
418
254
508
632
418

POWER SUPPLY**
MCA

MOCP

ICF

244.0
113.1
100.6
126.9
322.3
145.0
132.2
174.5

350
150
125
175
450
200
175
250

573.8
280.8
218.0
315.2
685.6
334.8
253.5
382.2

COMPRESSOR
A1
RLA
106.4
46.8
40.4
52.6
147.4
65.4
57.1
78.8

A2
LRA
506
253
176
280
690
345
276
382

RLA
89.7
43.6
36.5
45.5
106.4
46.8
40.4
52.6

LRA
446
223
164
247
506
253
176
280

See Legend on page 55.

53

Electrical data 38AH044-134 (cont)


38AH044-084 OPTIONAL SINGLE-CIRCUIT CONDENSING UNITS
38AH

VOLTAGE
DESIGNATION
500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200

044

054

064

074

084

COMPRESSOR
MODEL
(A1/A2)
06E-250/250

06E-265/250

06E-275/265

06E-299/275

06E-299/299

NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60

SUPPLY VOLTAGE*
Min

Max

MCA

MOCP

ICF

187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342

254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418

174.6
88.9
78.4
93.5
201.8
100.1
88.0
107.1
244.0
113.1
100.6
126.9
322.3
145.0
132.2
174.5
363.3
163.6
148.9
200.7

225
110
90
125
250
125
125
150
350
150
125
175
450
200
175
250
500
225
200
250

434.7
218.6
162.4
241.2
456.5
227.6
170.1
252.1
573.8
280.8
218.0
315.2
685.6
334.8
253.5
382.2
870.0
426.8
353.5
484.2

FANS
UNIT
38AH

044

054

064

074

084

094

104

Modules 124A,
124B,134A

Module 134B

54

Nameplate
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60

POWER SUPPLY

CONDENSER FAN MOTORS


Total
Qty
Hp
(No.) FLA Each
kW
(1,2) 5.5 (3,4) 5.4
(1,2) 2.8 (3,4) 2.7
4
1
6.2
(1-4) 3.4
(1-4) 3.9
(1,2) 5.5 (3,4) 5.4
(1,2) 2.8 (3,4) 2.7
4
1
6.2
(1-4) 3.4
(1-4) 3.9
(1,2) 5.5 (3,4) 5.4
(1,2) 2.8 (3,4) 2.7
4
1
6.2
(1-4) 3.4
(1-4) 3.9
(1,2) 5.5 (3-6) 5.4
(1,2) 2.8 (3-6) 2.7
6
1
9.3
(1-6) 3.4
(1-6) 3.9
(1,2) 5.5 (3-6) 5.4
(1,2) 2.8 (3-6) 2.7
6
1
9.3
(1-6) 3.4
(1-6) 3.9
(1,2) 5.5 (3-6) 5.4
(1,2) 2.8 (3-6) 2.7
6
1
9.4
(1-6) 3.4
(1-6) 3.9
(1,2) 5.5 (3-6) 5.4
(1,2) 2.8 (3-6) 2.7
6
1
9.5
(1-6) 3.4
(1-6) 3.9
(1,2) 5.5 (3,4) 5.4
(1,2) 2.8 (3,4) 2.7
4
1
6.4
(1-4) 3.4
(1-4) 3.9
(1,2) 5.5 (3-6) 5.4
(1,2) 2.8 (3-6) 2.7
6
1
9.2
(1-6) 3.4
(1-6) 3.9

COMPRESSOR
A1
A2
RLA
LRA
RLA
67.9
345
67.9
34.6
173
34.6
28.8
120
28.8
34.6
191
34.6
89.7
446
67.9
43.6
223
34.6
36.5
164
28.8
45.5
247
34.6
106.4
506
89.7
46.8
253
43.6
40.4
176
36.5
52.6
280
45.5
147.4
690
106.4
65.4
345
46.8
57.1
276
40.4
78.8
382
52.6
147.4
690
147.4
65.4
345
65.4
57.1
276
57.1
78.8
382
78.8

LRA
345
173
120
191
345
173
120
191
446
223
164
247
506
253
176
280
690
345
276
382

CONTROL CIRCUIT
38AH
044-134
500
600
100
200

UNIT POWER
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60

See Legend on page 55.

CONTROL POWER
V-Ph-Hz
Min
Max
115-1-60
103
127
115-1-60
103
127
115-1-60
103
127
230-1-60
207
253

AMPS
4.1
4.1
4.1
2.0

LEGEND and NOTES


(for pages 53 and 54)
American Wire Gage
Canadian Standards Association
Full Load Amps
Maximum Instantaneous Current Flow During Starting. (The point in
the starting sequence where the sum of the LRA for the starting compressors, plus the total RLA for all running compressors plus the FLA
for all running fan motors is maximum.)
Indoor-Fan Contactor
Thousand Circular Mils
Liquid Line Solenoid
Locked Rotor Amps
Minimum Circuit Amps (used for sizing; complies with National Electrical Code [NEC] section 430-24.)
Maximum Overcurrent Protection (used for sizing disconnect; complies with NEC Article 440-22.)
Part Wind
Rated Load Amps
Underwriters Laboratories

5. Field-supplied components (IFC, LLS-A, and LLS-B) must have a maximum


sealed coil rating of 30 va each (0.25 amp at 120 vac and 0.13 amp at
230 vac). Thermostats must have a minimum pilot duty rating as follows:

*Units are suitable for use on electrical systems where voltage supplied to unit
terminals is within listed minimum to maximum limits.
All compressors are across-the-line start only.
**38AH124 and 134 units require a separate power supply for each unit module.

6. Units have the following va of power available for field-installed accessories:


38AH044-084 175 va
38AH094 140 va
38AH104 130 va
38AH124,134 175 va each module
7. To minimize voltage drop, the following wire sizes are recommended:

AWG
CSA
FLA
ICF

IFC
kcmil
LLS
LRA
MCA

MOCP
PW
RLA
UL

NOTES:
1. Maximum allowable phase imbalance:
Voltage 2%
Amps 10%
2. Maximum incoming wire size for terminal block is 500 kcmil.
3. Wiring for field power supply must be rated 75 C minimum. Use copper, copperclad aluminum, or aluminum conductors. Maximum incoming wire size for each
terminal block is 500 kcmil.
4. Terminal blocks TB3 and TB4 are for external field control connections. Control connections are to be class 1 wiring.

VA
(Each Stage)

AMPS

VAC

044-084

300

094

275

104

325

124
134

300
300

2.5
1.3
2.29
1.15
2.70
1.35
2.50
2.50

120
240
120
240
120
240
120
120

38AH

LENGTH
(ft)
Up to 50
50-75
More Than 75

INSULATED WIRE AWG


(35 C Minimum)
No. 18
No. 16
No. 14

8. The 575-v base units are CSA approved.


9. The 208/230-v and 460-v base units are UL and CSA approved.
10. Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of
Modules 134A and 134B. Each module has a control box.
11. All fans are protected by a single circuit breaker.

55

Controls 38AH044-084
Sequence of operation
Circuits A1 and B1 are controlled by independent circuitry.
It is therefore possible to maintain partial cooling capability
even if one compressor is inoperable.
NOTE: Single-circuit units do not have independent control circuitry.
On a call for cooling, the first-stage cooling thermostat
TC1 closes, energizing the first stage of the condenser fans
and timer motor TM-A (TM for single-circuit units). After
12 seconds, the timer energizes lead compressor contactor
C-A1 and the lead compressor starts. (Circuit A compressor is the lead on dual-circuit units, and compressor A1 is
the lead on single-circuit units.) At the same time, solenoid
drop relay SDR2 energizes and closes its contacts, which
energizes and opens liquid line solenoid valve LLS-A (LLS-A1
for single-circuit units). Circuit A (compressor A1 for singlecircuit units) is now operational.
A set of bypass contacts in timer TM-A allows the
circuit A compressor (compressor A1 for single-circuit units)
40 seconds to build sufficient oil pressure. If the oil pressure is insufficient after 40 seconds, circuit A (compressor
A1 for single-circuit units) shuts down and must be reset
manually.
A second set of bypass contacts in timer TM-A (TM for
single-circuit units) allows the refrigerant circuit 212 minutes
to build sufficient low-side pressure. This time delay is a
start-up feature for low ambient conditions; no accessory is
required. If refrigerant circuit pressure is insufficient to close
the low-pressure switch after 212 minutes, the circuit A compressor (compressor A1 for single-circuit units) shuts down
for 512 minutes and then automatically attempts to restart.
No manual reset is required.

56

For dual-circuit units: If circuit A is insufficient for the cooling requirements, second-stage thermostat TC2 closes to
bring circuit B on line. Circuit B follows the same sequence
of operation as circuit A, except a relay delays circuit B
compressor start-up for 40 seconds after a call for cooling.
Because circuit A has a 12-second delay after TC1 closes,
and circuit B has a 40-second delay after TC2 closes, the
two compressors cannot start at the same time.
For optional single-circuit units: If compressor A1 is insufficient for the cooling requirements, second-stage thermostat TC2 closes, which opens liquid line solenoid valve
LLS-A2. Compressor A2 starts only after the D-D2 contacts in timer TM close (approximately 212 minutes after
compressor A1 is energized) and the suction pressure is sufficient to close capacity control pressure switches CCPS1
and CCPS2.
NOTE: Liquid line solenoid valves must be field-supplied
and installed at the evaporator for both dual- and optional
single-circuit units.
Indoor-fan operation: When the fan switch on the thermostat is set for automatic operation (AUTO), the fieldsupplied indoor-fan contactor (IFC) is cycled with the lead
compressor. If the fan switch is set at the continuous position (CONT), the IFC is energized as long as the unit power
is on.

Controls 38AH094-134
Sequence of operation
Units are controlled with electromechanical components.
Each refrigeration circuit is operated by an independent timer
motor which controls the operation sequence of each circuit. It is possible to maintain partial cooling capability even
if one circuit is inoperable.
On a call for cooling, first stage cooling thermostat
TC1 closes. Condenser fans and timer motor (TM) are energized. After approximately 7 seconds, timer contacts E-E1
close. Approximately 12 seconds after TC1 closes, normally open timer contacts B-B1 close for 1 second. This
energizes compressor A1 contacts CA1 and starts the compressor. At the same time, solenoid drop relays (SDRs) and
liquid line solenoid valve no. 1 (LLS-A1) open, and timer
relay no. 1 (TR1) is energized. Normally open TR1 contacts close completing a circuit around B-B1 and through
compressor A1 contactors to maintain compressor operation when B-B1 contacts open. Contacts E-E1 remain closed
for approximately 40 seconds to bypass the oil pressure
switch. If oil pressure is insufficient when contacts E-E1 open,
the compressor stops, the timer cycles off, and the control
circuit locks out. At start-up, timer motor contacts D-D1 are
closed, bypassing low-pressure relay contacts LPR-A for 212
minutes. This provides a winter start-up feature.
Approximately 212 minutes after TC1 closes, timer
contacts D-D1 open and D-D2 close. If pressure is insufficient to close the low-pressure switch, the low-pressure switch
relay remains open, the compressor shuts down, and the
Time Guardt control is initiated. Time Guard control prevents compressor from restarting for 5 minutes after the
demand for cooling is satisfied.

Units 38AH094 and 104 If circuit A operation is insufficient for the cooling requirements, the thermostat second stage TC2 closes to bring circuit B on-line for cooling.
This circuit follows the same sequence of operation as the
lead circuit, except a 60-second time-delay relay (TDR) delays compressor start-up for 60 seconds after the call for
cooling.
Modules 124A, 124B, 134A, and 134B If compressor A1 is insufficient for the cooling requirements, the
thermostat second stage closes, which opens the liquid line
solenoid valve LLS-A2. Compressor A2 starts only after
D-D2 contacts in the timer close and the suction pressure is
sufficient to close the capacity control switches.
All units When the fan switch is set for automatic (AUTO)
operation, the indoor-fan contactor (IFC) is cycled with the
lead compressor. If the fan switch is set for continuous
(CONT), the IFC is energized as long as the unit power
is on.
Restart after stoppage by safety control The highpressure switch and the oil pressure switch must be reset
manually by breaking the control power supply at any of
the following points: Control circuit fuse, fan motor circuit
breaker, or thermostat. Restart follows the Time Guard control 5-minute delay. Stoppage by low-pressure switch results in Time Guard control 5-minute delay, then unit attempts to restart.
The compressor motor overcurrent protectors are manualreset circuit breakers. Reset of control circuit may also be
necessary.

57

Typical control wiring 38AH044-134


24-V THERMOSTAT CONTROL WIRING DUAL-CIRCUIT UNITS 38AH044-084

58

AWG
C
CR
HD
IFC
IFR
kcmil
LLS
NEC
R

RV
SDR
TB
TR

LEGEND
American Wire Gage
Compressor Contactor
Control Relay
Heating Device
Indoor Fan Contactor
Indoor-Fan Relay
Thousand Circular Mils
Liquid Line Solenoid
National Electrical Code
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Solenoid Drop Relay
Terminal Block
Timer Relay
Factory Wiring
Field Wiring

*Jumper removed only when separate 24-v transformer power source


is used to power the TSR-01 relay pack.
To control heating device and provide automatic indoor-fan operation
on heating.
NOTE: Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.

Internal TSR-01 relay contacts are rated for 1 amp/24 vac.

24-V THERMOSTAT CONTROL WIRING UNITS 38AH094 AND 104

C
CCPS
CR
HD
IFC
IFR
LLS
NEC
R

RV
SDR
TB
TR

LEGEND
Compressor Contactor
Capacity Control Pressure Switch
Control Relay
Heating Device
Indoor Fan Contactor
Indoor-Fan Relay
Liquid Line Solenoid
National Electrical Code
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Solenoid Drop Relay
Terminal Block
Timer Relay
Factory Wiring
Field Wiring

*Jumper removed only when separate 24-v transformer power source


is used to power the TSR-01 relay pack.
To control heating device and provide automatic indoor-fan operation
on heating.
NOTE: Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.

Internal TSR-01 relay contacts are rated for 1 amp/24 vac.

59

Typical control wiring 38AH044-134 (cont)


24-V THERMOSTAT CONTROL WIRING UNITS 38AH124 AND 134

60

C
CCPS
CR
IFC
IFR
LLS
NEC
R

RV
SDR
TB
TR

LEGEND
Compressor Contactor
Capacity Control Pressure Switch
Control Relay
Indoor Fan Contactor
Indoor-Fan Relay
Liquid Line Solenoid
National Electrical Code
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Solenoid Drop Relay
Terminal Block
Timer Relay
Factory Wiring
Field Wiring

*Jumper removed only when separate 24-v transformer power source


is used to power the TSR-01 relay pack.
To control heating device and provide automatic indoor-fan operation
on heating.
NOTES:
1. Field-supplied liquid line solenoid valves installed at the evaporator
are required on all units.
2. Disconnect black wire from CR2 terminal 6; cap loose end and secure. Connect new field-supplied wire from CR2 terminal 6 to TB3
terminal 1 on module 124B or 134B.

Internal TSR-01 relay contacts are rated for 1 amp/24 vac.

Application data 38AH044-134


Operating limits
Maximum outdoor ambient . . . . . . . . . . . . . . . . . . . . 115 F
Minimum outdoor ambient . . . . . . . . . Refer to Minimum
Outdoor-Air Operating Temperature
table, page 62.
Minimum return-air temperature . . . . . . . . . . . . . . . . 55 F
Maximum return-air temperature . . . . . . . . . . . . . . . 95 F
Range of acceptable saturation
suction temperature . . . . . . . . . . . . . . . . . . . . . . 20 to 50 F
Maximum discharge temperature . . . . . . . . . . . . . . . 275 F
Minimum discharge superheat . . . . . . . . . . . . . . . . . 60 F
NOTES:
1. Select indoor equipment at no less than 300 cfm/ton
(nominal condensing unit capacity).
2. Total combined draw of the 2 field-supplied liquid line
solenoid valves and one air handler fan contactor must
not exceed 90 va. If the specified va must be exceeded,
use a remote relay to control the load.
3. Select equipment to match or to be slightly less than
peak load.
4. Evaluate oil return when selecting vapor line sizes, especially for partial load conditions.
5. Indoor fan must operate when outdoor unit is operating.

6. For VAV systems, the total building load is NOT the sum
of the individual peak loads. Equipment selected for the
sum of the individual peak loads will be oversized.
7. For VAV systems with supply-to-return air recycling, use
the equipment room as a return-air plenum.
8. To minimize air recirculation, do not use concentric supply and return grilles.
9. Standard units applied in VVT systems must have fieldsupplied and installed accumulators on each circuit.
Order part number 38AK-500-410 from Service Parts.
LIQUID LINE DATA

UNIT 38AH

MAXIMUM
ALLOWABLE
LIQUID LIFT
(ft)

044
054
064
074
084
094
104
124
134

69
75
75
45
75
55
50
75
45

LIQUID LINE
Max Allowable
Max Allowable
Pressure Drop
Temp Loss
(psi)
(F)

NOTE: Values shown are for units operating at 45 F saturated suction


at condensing unit and 95 F entering outdoor air.

UNLOADING SEQUENCES STANDARD CONSTANT VOLUME


(CV) UNITS*
UNIT 38AH
044
054
064
074
084
094
104
124
134

CAPACITY/STAGE (%)
Standard Units
Optional Single-Circuit Units
100, 75, 50, 25
100, 75, 50, 25
100, 79, 42, 21
100, 80, 56, 37
100, 84, 48, 32
100, 82, 55, 36
100, 86, 43, 29
100, 81, 57, 38
100, 83, 50, 33
100, 83, 50, 33
100, 85, 55, 44, 33, 22

100, 91, 74, 65, 47, 38, 26, 17

100, 91, 77, 68, 50, 41, 27, 18

100, 90, 76, 66, 45, 37, 25, 16

*Additional unloading available with field-installed accessory unloader.


NOTES:
1. Capacities are based on 45 F saturated suction temperature and 95 F outdoor-air temperature.
2. Single-circuit option available for sizes 044-084 only.

UNLOADING SEQUENCES OPTIONAL VARIABLE AIR VOLUME


(VAV) UNITS
UNIT 38AH
044
054
064
074
084
094
104
124
134

CAPACITY/STAGE (%)
Standard Dual-Circuit Units
Optional Single-Circuit Units
100, 75, 50, 25
100, 75, 50, 25
100, 79, 58, 42, 21
100, 80, 61, 56, 37
100, 84, 69, 48, 32, 16
100, 82, 64, 55, 36, 18
100, 86, 71, 43, 29, 14
100, 81, 62, 57, 38, 19
100, 83, 67, 50, 33, 17
100, 83, 67, 50, 33, 17
100, 85, 70, 55, 44, 33, 22

100, 91, 74, 65, 47, 38, 26, 17

100, 91, 82, 77, 68, 50, 41, 32, 27, 18, 9

100, 90, 79, 76, 66, 45, 37, 28, 25, 16, 8

NOTES:
1. Capacities are based on 45 F saturated suction temperature and 95 F outdoor-air temperature.
2. Single-circuit option available for sizes 044-084 only.

61

Application data 38AH044-134 (cont)


MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE AND LOADING SEQUENCES
38AH044-084 DUAL-CIRCUIT UNITS
UNIT 38AH

044

054

064

074

084

QUANTITY OF LOADED
COMPRESSOR CYLINDERS
Ckt A
Ckt B
Total
4
4
8
2
4
6
4
0
4
2
0
2
4
6
10
2
6
8
2
4
6*
4
0
4
2
0
2
6
6
12
4
6
10
2
6
8*
6
0
6
4
0
4
2
0
2*
6
6
12
4
6
10
2
6
8*
6
0
6
4
0
4
2
0
2*
6
6
12
4
6
10
2
6
8*
6
0
6
4
0
4
2
0
2*

SYSTEM
CAPACITY
(%)

MINIMUM OUTDOOR OPERATING TEMP (F)


w/Std Fans

w/MotormasterT III Control

50

20

48

20

39

20

31

20

20

20

100
75
50
25
100
79
58*
42
21
100
84
69*
48
32
16*
100
86
71*
43
29
14*
100
83
67*
50
33
17*

*Requires units with VAV (variable air volume) factory-supplied option.


NOTES:
1. Units have 2 independent refrigeration circuits. Circuit A is lead
circuit.

2. Minimum operating temperature is the higher outdoor temperature of


the 2 circuits.
3. Minimum outdoor-air operating temperature is based on 90 F saturated condensing temperature and 100% capacity.

MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE AND LOADING SEQUENCES


38AH044-084 SINGLE-CIRCUIT UNITS
UNIT 38AH

044

054

064

074

084

QUANTITY OF LOADED
CYLINDERS
8
6
4
2
10
8
6*
6
4
12
10
8*
6
4
2*
12
10
8*
6
4
2*
12
10
8*
6
4
2*

SYSTEM
CAPACITY
(%)
100
75
50
25
100
80
61*
56
37
100
82
64*
55
36
18*
100
81
62*
57
38
19*
100
83
67*
50
33
17*

*Requires VAV (variable air volume) factory-supplied option or


accessory unloader.

62

MINIMUM OUTDOOR OPERATING TEMP (F)


w/Std Fans

w/MotormasterT III Control

47

20

41

20

38

20

22

20

20

20

NOTE: Minimum outdoor-air operating temperature is based on 90 F


saturated condensing temperature and 100% capacity.

MINIMUM OUTDOOR-AIR OPERATING TEMPERATURE AND LOADING SEQUENCES


38AH094-134 DUAL CIRCUIT UNITS
UNIT 38AH

094

104

124

134

QUANTITY OF LOADED COMPRESSOR


CYLINDERS
Ckt A
10
10
10
10
8
6
4
10
10
10
10
10
10
10
8
6
4
2
12
12
12
12
12
12
12
10
8
6
4
2*
12
12
12
12
12
12
12
10
8
6
4
2*

Ckt B
6
4
2*
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0

Total
16
14
12
10
8
6
4
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2

SYSTEM
CAPACITY
(%)
100
85
70*
55
44
33
22
100
91
82
74
65
56
47
38
26
17
9
100
91
82*
77
68
59
50
41
32*
27
18
9*
100
90
79*
76
66
56
45
37
28*
25
16
8*

MINIMUM OUTDOOR OPERATING TEMP (F)


W/Std Fans
w/MotormasterT III
Control
Ckt A
Ckt B

25

20

14

20

38

38

20

38

22

20

*Requires VAV (variable air volume) unit or accessory unloader(s) field installed on circuit lead compressor. Lead compressor is identified in Physical Data section, page 35.
Requires field-installed accessory unloader on circuit lead compressor. Lead compressor is identified in Physical Data section, page 35.
NOTES:
1. Temperatures calculated with the minimum number of fans operating per circuit.
2. For 38AH124 and 134 units, circuit A is Module 38AH124A or 134A. Circuit B is
Module 38AH124B or 134B.
3. Minimum outdoor-air operating temperature is based on 90 F saturated condensing
temperature and 100% capacity.

63

Application data 38AH044-134 (cont)


REFRIGERANT PIPING REQUIREMENTS
38AH044-084 DUAL-CIRCUIT UNITS
UNIT 38AH
044
054
064
074
084

CV
L
S
VAV

Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B

15-25
L
58
58
58
78
78
78
78
78
78
78

S
158
158
158
158
158
218
218
218
218
218

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE FT


25-50
50-75
75-100
100-150
L
S
L
S
L
S
L
S
7 8
7 8
7 8
78
158
218
2 1 8
2 1 8
7 8
7 8
7 8
78
158
218
2 1 8
2 1 8
7 8
7 8
7 8
78
158
218
2 1 8
2 1 8
7 8
7 8
218
218
118
2 1 8
1 1 8
2 1 8
1
1
1
1
7 8
7
7
2 8
8
2 8
8
2 8
1 8
2 1 8
7 8
7 8
218
218
118
2 1 8
1 1 8
258
7 8
218
118
218
118
2 1 8
1 1 8
258*
118
218
118
218
118
258
138
258
118
218
118
218
118
258*
1 3 8
258*
118
218
118
218
118
258
138
258

LEGEND
Constant Volume
Liquid Line
Suction Line
Variable Air Volume

*Units with factory-installed VAV option or field-installed accessory


unloader 2 unloaders on circuit A, and 1 unloader on circuit B;
double suction riser required.
Units with 2 field-installed unloaders on circuit A and 2 on circuit B;
double suction riser required.
NOTE: It is possible to install 2 unloaders on circuit B, but not
recommended.

150-200
L
S
7 8
2 1 8
7 8
2 1 8
7 8
2 1 8
1 1 8
258*
1
1 8
258*
118
258
118
258*
138
258
138
258*
138
258

NOTES:
1. Double risers may be required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F pressure drop at nominal rating
conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.

38AH044-084 DUAL-CIRCUIT UNITS,


DOUBLE SUCTION RISER
UNIT 38AH
044
054
064
074
084

Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B

138
1 3 8

50-75
B

158
158

218
218

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE FT


75-100
100-150
A
B
C
A
B
C
A

1 3 8
158
218
1 3 8
158
218
1 5 8
1 3 8
158
218
1 3 8
158
218
1 5 8

158
218
258
1 5 8
5
1
5

1 8
2 8
2 8
1 5 8
1 5 8
218
258
1 5 8
218
258
1 5 8
158
218
258
1 5 8
218
258
1 5 8
1 5 8
218
258
1 5 8
218
258
1 5 8

LEGEND

Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.

64

150-200
B

218
218
218
218
218
218
218

258
258
258
258
258
258
258

3. Suction line sizing is based on 2 F pressure drop at nominal rating


conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.

38AH044-084 OPTIONAL SINGLE-CIRCUIT UNITS; 38AH124,134


MODULAR UNITS (DUAL-CIRCUIT)
UNIT 38AH
044
054
064;
Modules 124A,
124B,134A
074;
Module 134B
084

15-20

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE FT


20-50
50-75
75-100
100-150
S
L
S
L
S
L
S
218
118
258***
118
258***
138
258***
258***
118
258***
118
258***
138
318***

L
138
138

150-200
S
318***
318***

318***

138

318***

138

318***

158

358***

158

358***

158

358***

L
78
78

S
2 1 8
2 1 8

L
7 8
1 1 8

118

2 1 8

1 1 8

258***

118

258***

138

318***

138

118

2 1 8

1 1 8

258***

138

318***

138

318***

118

258**

118

258**

138

318**

138

318**

LEGEND
CV Constant Volume
L
Liquid Line
S
Suction Line
VAV Variable Air Volume
*Standard CV unit with 1 unloader on circuit A and 1 unloader on
circuit B; double suction riser required.
Units with factory-installed VAV option or field-installed accessory
unloader 2 unloaders on circuit A, and 1 unloader on circuit B;
double suction riser required.
**Units with 2 field-installed unloaders on circuit A and 2 on circuit B;
double suction riser required.
NOTE: It is possible to install 2 unloaders on circuit B, but not
recommended.

NOTES:
1. Double risers may be required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F pressure drop at nominal rating
conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.

38AH044-084 OPTIONAL SINGLE-CIRCUIT UNITS;


38AH124,134 MODULAR UNITS (DUAL-CIRCUIT)
DOUBLE SUCTION RISER

2 5 8

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE FT


50-75
75-100
100-150
A
B
C
A
B
C
A
B
C
1 5 8
2 1 8
2 5 8
1 5 8
2 1 8
258
158
218
258
1 5 8
2 1 8
2 5 8
1 5 8
2 1 8
258
158
258
318

A
158
158

150-200
B
258
258

C
318
318

2 1 8

2 5 8

1 5 8

2 1 8

2 5 8

1 5 8

2 5 8

318

158

258

318

158

258

318

158

2 1 8

2 5 8

1 5 8

2 5 8

3 1 8

1 5 8

2 5 8

318

158

258

318

218

318

358

358

UNIT 38AH
044
054
064
Modules 124A,
124B,134A
074;
Module 134B
084

1 5 8

15-50
B

2 1 8

1 5 8

58

18

58

58

58

18

LEGEND

Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.

58

58

18

18

18

58

18

18

3. Suction line sizing is based on 2 F pressure drop at nominal rating


conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.

65

Application data 38AH044-134 (cont)


REFRIGERANT PIPING REQUIREMENTS
38AH094-104 DUAL-CIRCUIT UNITS
UNIT
38AH
094
Ckt A
094
Ckt B
104
Ckt A
104
Ckt B

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE - FT (M)


25-50
50-75
75-100
100-150
(7.6-15.2)
(15.2-22.9)
(22.9-30.5)
(30.5-45.7)
L
S
L
S
L
S
L
S

15-25
(4.6-7.6)
L
S

150-200
(45.7-61.0)
L
S

78

218

118

218

118

258**

118

258**

138

258**

138

318***

78

218

78

218

118

218**

118

258**

118

258**

138

258**

78

218

78

218

118

258

118

258

118

258

138

318***

218

118

218

118

258**

118

258**

138

318***

138

318***

78

LEGEND
CV Constant Volume
L
Liquid Line
S
Suction Line
VAV Variable Air Volume
*Standard CV unit with 1 unloader on circuit A and 1 unloader on
circuit B; double suction riser required.
Units with factory-installed VAV option or field-installed accessory
unloader 2 unloaders on circuit A, and 1 unloader on circuit B;
double suction riser required.
**Units with 2 field-installed unloaders on circuit A and 2 on circuit B;
double suction riser required.
NOTE: It is possible to install 2 unloaders on circuit B, but not
recommended.

NOTES:
1. Double risers may be required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F pressure drop at nominal rating
conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.

38AH094-104 DUAL-CIRCUIT UNITS,


DOUBLE SUCTION RISER

UNIT 38AH
094
Ckt A
094
Ckt B
104
Ckt A
104
Ckt B

25-50
(6.1-15.2)
A
B
C

TOTAL LINEAR LENGTH OF INTERCONNECTING PIPE - FT (M)


50-75
75-100
100-150
(15.2-22.9)
(22.9-30.5)
(30.5-45.7)
B
C
A
B
C
A
B
C

150-200
(45.7-61.0)
B

158

218

258

158

218

258

1 5 8

2 1 8

2 5 8

1 5 8

258

318

138

158

218

158

218

258

1 5 8

2 1 8

2 5 8

1 5 8

218

258

138

218

258

138

218

258

1 3 8

2 1 8

2 5 8

1 5 8

258

318

138

218

258

138

218

258

1 3 8

2 5 8

3 1 8

1 5 8

258

318

LEGEND

Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.

66

3. Suction line sizing is based on 2 F pressure drop at nominal rating


conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.

REFRIGERANT PIPING REQUIREMENTS


DOUBLE SUCTION RISER CONSTRUCTION

A
B
C
D
RED.
STR

LEGEND
Pipe A, Suction Riser, Lower Trap
Pipe B, Suction Riser with Trap
Suction Line to Condensing Unit
Pipe D, Suction Riser Short Lift
Reducer
Street

NOTE: Short riser, pipe D, is used when routing suction line to condensing unit connection. See table below:

UNIT 38AH
044
054
064
074
084
094
104
124A,B
134A,B

PIPE D DIAMETER*
Dual Circuit
Single Circuit
A
B
1 5 8
218
1 5 8
1 5 8
1 5 8
218
5
1
1 8
2 8
218
1
1
2 8
2 8
218
2 1 8
2 1 8
258
2 1 8
2 1 8

218
2 1 8

1
1
2 8
2 8

1
1
2 8
2 8

*Maximum length of riser is 3 ft (914 mm).

67

Guide specifications 38AH024-034


Commercial Air-Cooled
Condensing Units
HVAC Guide Specifications Section 15675
Size Range: 20 to 30 Tons, Nominal
Carrier Model Number: 38AH
Part 1 General
1.01 SYSTEM DESCRIPTION
A. Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit
shall have 2 independent refrigerant circuits. Unit shall
consist of semi-hermetic reciprocating compressors,
an air-cooled coil, propeller-type condenser fans, and
a control box. Unit shall discharge condenser air upward as shown on contract drawings.
B. Unit shall be used in a refrigeration circuit to match
up to Packaged Air Handler Unit(s), Section 15859.
1.02 QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standard
365-87, latest edition.
B. Systems up to 20 tons shall be certified and listed in
the latest ARI directory.
C. Unit construction shall comply with latest edition of
ASHRAE and with NEC.
D. Unit shall be constructed in accordance with UL standards and shall carry the UL label of approval. Unit
shall have CSA approval.
E. Unit cabinet shall be capable of withstanding Federal Test Method Standard No. 141 (Method 6061)
500-hour salt spray test.
F. Air-cooled condenser coils shall be leak tested at
150 psig and pressure tested at 480 psig.
1.03 DELIVERY, STORAGE AND HANDLING
A. Unit shall be shipped as single package only, and shall
be stored and handled per unit manufacturers
recommendations.
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING
ENGINEER)
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory-assembled, single-piece, air-cooled condensing unit. Contained within the unit enclosure shall be
all factory wiring, piping, controls, compressors, holding charge, and special features required prior to field
start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted, baked
enamel finish.
2. Unit access panels shall be hinged for control box
service access.
3. Lifting holes shall be provided to facilitate rigging.

68

C. Fans:
1. Condenser fans shall be direct-driven propeller type,
discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type with
class B insulation and permanently lubricated
bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be a product of the unit
manufacturer.
2. Compressors shall be serviceable, reciprocating,
semi-hermetic type.
3. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge, suction and discharge shutoff valves, and an inserttype, factory-installed crankcase heater to control
oil dilution.
4. Compressor shall be mounted on spring vibration
isolators with an isolation efficiency of no less than
95%.
5. Compressor speed shall not exceed 1750 rpm.
6. Lead compressor shall unload using pressureoperated suction cutoff unloading (electrical solenoid unloading shall be available as an accessory).
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins (copper fins optional) mechanically bonded to internally grooved, seamless copper tubes which are
then cleaned, dehydrated, and sealed.
3. Coil shall be protected by a sheet metal casing to
eliminate the need for wind baffles for low ambient temperature operation.
4. Coil shall be protected to avoid damage due to the
elements and vandalism.
F. Refrigeration Components:
Refrigeration circuit components shall include hot gas
mufflers, hot gas bypass stub tubes, high-side pressure relief devices, liquid line shut-off valves, suction
and discharge shutoff valves, holding charge, and compressor oil.

G. Controls and Safeties:


1. Minimum control functions shall include:
a. Power and control terminal blocks.
b. Five-minute time delay protection to prevent
compressor short-cycling.
c. Lockout on auto-reset safety until reset from
thermostat.
d. Capacity control on the lead compressor
shall be by suction cutoff unloaders in response to compressor suction pressure. Electric solenoid unloading shall be available as
an accessory.
e. Head pressure control to 50 F by fan cycling.
One condenser fan shall be cycled by ambient temperature to maintain proper head
pressure.
2. Minimum safety devices shall include:
a. Compressor oil pressure switches
b. High discharge-pressure cutout.
c. Compressor overtemperature cutout.
d. Low suction-pressure cutout.
e. Condenser-fan motors to be protected against
overload or single-phase condition by internal overloads.
f. Electrical overload protection through the use
of definite-purpose contactors and calibrated,
ambient-compensated, magnetic trip circuit
breakers. Circuit breakers shall open all 3
phases in the event of an overload in any one
of the phases or a single-phase condition.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
Btuh at a suction temperature of
exceed
F. The power consumption at full load shall
not exceed
kW.
2. The combination of the condensing unit and the
evaporator or fan coil unit shall have a total net
Btuh or greater at concooling capacity of
ditions of:
cfm entering-air temperature at
the evaporator at
F wet bulb and
F
dry bulb, and air entering the condensing unit at
F.
Btuh/
3. The system shall have an EER of
Watt or greater at standard ARI conditions.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 60 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit electrical power shall be single-point
connection.
3. Unit control circuit shall contain a 24-v transformer for unit control, with capacity to operate
an indoor- fan interlock.

J. Special Features:
1. Solid-State Head Pressure Control:
Control shall regulate fan motor speed in response
to the saturated condensing temperature of the
unit. The control shall be capable of maintaining
a condensing temperature of 100 F 10 F with
outdoor temperatures at 20 F.
2. Electric Solenoid Unloader:
Unloader valve piston, coil, and hardware shall
be supplied to convert any pressure-operated compressor unloader to 115-v electric unloading.
Accessory ModuPanel or field-supplied step controller shall be provided for control of electrical
unloading.
3. Gage Panel:
A gage panel package shall be provided which includes a suction and discharge pressure gage. One
is required for each refrigerant circuit.
4. ModuPanel Control Box:
Control box shall be provided to allow system to
operate as a VAV (variable air volume) system.
5. Thermostats, 24 v (including Carrier Programmable Temp-System MS[T]01ES):
Thermostat shall provide 2-stage cooling control
of unit.
6. Pressure-Operated Unloader:
Unloader shall be available to allow compressors
to be unloaded in response to compressor suction
pressure.
7. Winter Start Package:
Winter start control to prevent nuisance tripouts
at low ambient temperatures.
8. VAV Option:
A factory-installed variable air volume option shall
be supplied to provide unit with 2 electric unloaders and control box modifications necessary
to connect to a field-installed ModuPanel control
box. (Field supplied accumulators required for each
circuit.)

69

Guide specifications 40RM016-034


Commercial Packaged Air-Handling Unit
HVAC Guide Specifications Section 15859
Size Range: 2,400 to 12,000 Cfm, Nominal Airflow
6 to 30 Tons, Nominal Cooling
Carrier Model Number: 40RM (Direct-Expansion Coil)
Part 1 GENERAL
1.01 SYSTEM DESCRIPTION
A. Indoor, packaged air-handling unit for use in commercial split systems. Unit shall have a multipoise design
and shall be capable of horizontal or vertical installation on a floor or in a ceiling, with or without ductwork. (Only vertical units are to be applied without
ductwork.)
B. Unit shall have a direct-expansion coil and shall be
used in a refrigerant circuit with a matching air-cooled
condensing unit.
1.02 QUALITY ASSURANCE
A. Coils shall be designed and tested in accordance with
ASHRAE 15 Safety Code for Mechanical Refrigeration, latest edition.
B. Unit shall be constructed in accordance with ETL and
ETLC standards and shall carry the ETL and ETLC
labels.
C. Unit insulation and adhesive shall comply with
NFPA-90A requirements for flame spread and smoke
generation. Insulation shall contain an EPA-registered
immobilized antimicrobial agent to effectively resist
the growth of bacteria and fungi as proven by tests in
accordance with ASTM standards G21 and 22.
D. Unit shall be manufactured in a facility registered to
the ISO 9002 manufacturing quality standard.
E. Direct-expansion coils shall be burst tested at 435 psi
and leak tested at 150 psi.
1.03 DELIVERY AND STORAGE
Units shall be stored and handled per manufacturers
recommendations.
Part 2 Products
2.01 EQUIPMENT
Indoor mounted, draw-thru, packaged air-handling
unit that can be used in a suspended horizontal configuration or a vertical configuration. Unit shall consist of forward-curved belt-driven centrifugal fan(s),
motor and drive assembly, prewired fan motor contactor, factory-installed refrigerant metering devices,
cooling coil, 2-in. disposable air filters, and condensate drain pans for vertical or horizontal configurations.

70

A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 12-in.
fire-retardant material. Insulation shall contain an
EPA-registered immobilized antimicrobial agent to
effectively resist the growth of bacteria and fungi
as proven by tests in accordance with ASTM standards G21 and 22.
3. Unit shall contain condensate drain pans for both
vertical and horizontal applications. Drain pans shall
have connections on right and left sides of unit to
facilitate field connection. Drain pans shall have
the ability to be sloped toward the right or left side
of the unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 2-in. throwawaytype filters installed upstream from the cooling coil.
Filter access shall be from either the right or left
side of the unit.
B. Coils:
Coils shall consist of 3 rows of 38-in. copper tubes
with sine-wave aluminum fins bonded to the tubes by
mechanical expansion. Coil tubing shall be internally
rifled to maximize heat transfer. Suction and liquid
line connections shall be made on the same side of
the coil. Direct-expansion coils shall feature factoryinstalled thermostatic expansion valves (TXVs) for
refrigerant control. The TXVs shall be capable of external adjustment.
C. Operating Characteristics:
cfm airUnit shall be capable of providing
flow at an external static pressure of
in wg.
D. Motor:
Fan motor of the size and electrical characteristics
specified on the equipment schedule shall be factory
supplied and installed.
E. Factory-Installed Options:
1. Alternate Motor and Drive:
An alternate motor and medium- or high-static drive
shall be available to meet the airflow and external
static pressure requirements specified on the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted
with an American Sterling Gray finish.

F. Field-Installed Accessories:
1. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes
and aluminum plate fins bonded to the tubes by
mechanical expansion. Coil shall be mounted in
a galvanized steel housing that shall be fastened
to the units fan deck for blow-thru heating operation. Coil shall have maximum working pressure of 150 psig.
2. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with
aluminum plate fins, and shall have inner steam
distributing tubes. Coil shall be mounted in a galvanized steel housing and shall be fastened to the
units fan deck for blow-thru heating operation.
Coil shall have maximum working pressure of
175 psig at 400 F.
3. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt,
3-phase, 60 Hz power supply shall be factorysupplied for field installation as shown on the
equipment drawings. Electric heat assembly shall
be ETL agency approved, and shall have singlepoint power wiring. Heater assembly shall include contactors with 24-v coils, power wiring,
24-v control wiring terminal blocks, and a hinged
access panel.
4. Air Discharge Plenum:
Plenum shall be factory supplied to provide freeblow air distribution for vertical floor-mounted
units. A grille with moveable vanes for horizontal or vertical airflow adjustment shall be included.
Plenum housing shall be field-installed on the
units fan deck for blow-thru air distribution.

5. Return-Air Grille:
Grille shall be factory supplied for field installation on the units return air opening.
6. Unit Subbase:
Subbase assembly shall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for correct condensate drain connection.
7. Economizer:
Economizer for ventilation or free cooling shall
be factory provided for field installation. For free
cooling applications, economizer shall be compatible with factory-supplied thermostat; economizer dampers shall open when outdoor air enthalpy is suitable for free cooling. Economizer shall
be compatible with factory-supplied CO2 sensor;
economizer dampers shall open when indoor CO2
level rises above predetermined set point.
8. Communicating Electronic Thermostat:
Electronic programmable thermostat assemblies
shall provide 2-stage heating and 2-stage cooling control with remote communication ability
and shall be factory-supplied for field installation.
9. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
10. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds
the predetermined set point.

71

Guide specifications 38AH044-134


Commercial Air-Cooled Condensing Units
HVAC Guide Specifications
Size Range: 40 to 130 Tons, Nominal
Carrier Model Number: 38AH
Part 1 General
1.01 SYSTEM DESCRIPTION
Outdoor-mounted, air-cooled condensing unit suitable for on-the-ground or rooftop installation. Unit
shall have 2 independent refrigeration circuits and shall
consist of 2, 3, or 4 semi-hermetic reciprocating compressors, air-cooled coils, propeller-type condenser
fans, and a control box. Unit shall discharge condenser air upward as shown on contract drawings.
Unit shall be used in refrigeration circuit matched with
a central station air-handling unit or direct-expansion
coils.
1.02 QUALITY ASSURANCE
A. Unit performance shall be rated in accordance with
ARI Standard 365, latest edition.
B. Unit construction shall comply with latest edition of
ASHRAE and with NEC.
C. Base unit shall be constructed in accordance with UL
standards and shall carry the UL label of approval.
Unit shall have CSA approval.
D. Unit cabinet shall be capable of withstanding Federal Test Method Standard No. 141 (Method 6061)
500-hour salt-spray test.
E. Air-cooled condenser coils shall be leak tested at
150 psig and pressure tested at 450 psig.
1.03 DELIVERY, STORAGE, AND HANDLING
Unit shall be shipped as single package or 2-container
package, and shall be stored and handled per unit
manufacturers recommendations.
1.04 WARRANTY
For inclusion by specifying engineer.
Part 2 Products
2.01 EQUIPMENT
A. General:
Factory assembled, single-piece or 2-piece, air-cooled
condensing unit. Contained within the unit enclosure
shall be all factory wiring, piping, controls, compressors, holding charge (R-22), and special features required prior to field start-up.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of galvanized steel,
bonderized, and coated with a prepainted, baked
enamel finish.
2. Unit access panels shall be hinged for control box
service access.
3. Lifting holes shall be provided to facilitate rigging.

72

C. Fans:
1. Condenser fans shall be direct-drive propeller type,
discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type
with class B insulation and permanently lubricated
bearings. Motors shall be drip proof with sealed
bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser-fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be serviceable, reciprocating,
semi-hermetic type.
2. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an inserttype factory-sized crankcase heater to control oil
dilution.
3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no less
than 95%.
4. Compressor speed shall not exceed 1750 rpm.
5. Lead compressors on each circuit shall unload using suction cutoff unloading (electric solenoid unloading shall be available as an accessory).
E. Condenser Coils:
1. Condenser coils shall be air cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins mechanically bonded to internally grooved, seamless
copper tubes which are then cleaned, dehydrated,
and sealed. Copper fins shall be available as an
option.
F. Refrigeration Components:
Refrigeration circuit components shall include hot
gas muffler, hot gas bypass stub tubes, high-side pressure relief device, liquid line shutoff valve, suction
and discharge shutoff valves, holding charge of refrigerant R-22, and compressor oil. 38AH094-134
and all 38AH044-084 single-circuit units shall have
suction line accumulators. VAV units shall also have
suction line accumulators.

G. Controls and Safeties:


1. Minimum control functions shall include:
a. Five-minute Time Guardt protection to prevent compressor short-cycling.
b. Lockout on auto-reset safety until reset from
thermostat.
c. Capacity control on the lead compressor shall
be by suction cutoff unloaders in response
to compressor suction pressure. Electric
solenoid unloading shall be available as an accessory.
d. Head pressure control for mild ambient temperature operation through fan cycling. Condenser fans (except fans 1 and 2) shall be
cycled by discharge pressure to maintain proper
head pressure.
e. Winter start control to prevent nuisance tripouts at low ambient temperatures.
2. Minimum safety devices shall include:
Automatic reset (after resetting first at
thermostat)
a. Low suction pressure cutout.
b. Condenser-fan motors protected against overloads or single-phase condition by internal
overloads.
c. Low oil pressure cutout.
Manual reset at the unit
a. Electrical overload protection through the use
of definite-purpose contactors and calibrated,
ambient compensated, magnetic trip circuit
breakers. Circuit breakers shall open all 3
phases in the event of an overload in any one
of the phases or a single-phase condition.
b. High discharge-pressure cutout.
H. Operating Characteristics:
1. The capacity of the condensing unit shall meet or
Btuh at a suction temperature of
exceed
F. The power consumption at full load shall
not exceed
kW.
2. The combination of the condensing unit and the
evaporator or air handling unit shall have a total
net cooling capacity of
Btuh or greater at
cfm entering-air temperaconditions of
ture at the evaporator at
F wet bulb and
F dry bulb, and air entering the condensing unit at
F.
3. The system shall have an Energy Efficiency Ratio
(EER) of
Btuh/watt or greater at standard
ARI conditions.

I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 60 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit or module electrical power shall be singlepoint connection.
3. Unit control circuit shall be 115 v (or 230 v for
380-3-60 unit).
J. Special Features:
1. Unloader Conversion Kit:
Unloader valve, piston, and hardware shall be
supplied to convert any pressure-operated compressor unloader to 115-v (or 230-v) electrical
unloading. Accessory ModuPanel control or
field-supplied step controller shall be required for
electrical unloading.
2. Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for each refrigerant circuit.
3. Accessory Transformer Relay Package:
Relay shall be provided for use with a remotecontrol 24-v thermostat.
4. Electric Unloader Package:
Electric unloader shall provide an additional step
of electric unloading.
5. Pressure Unloader Package:
Pressure unloader shall provide an additional step
of pressure unloading.
6. ModuPanel Control:
Control shall provide up to 10-steps of
microprocessor-based control for variable air volume (VAV) applications.
7. Motormastert III Control:
Control shall maintain correct condensing pressure at low ambient temperatures.
8. Compressor Grille Package:
Grilles shall protect the compressor area after unit
installation.
9. Condenser Coil Grille Package:
Grilles shall protect the condenser area after unit
installation.
10. Sound-Reduction Kit:
Kit shall contain specially designed fan propellers and stacks to lower sound emitted from the
unit, and shall be compatible with the Motormaster III control.

73

Guide specifications 38AH044-134 (cont)


11. Hail Guard Package:
Guard shall protect coils from airborne debris.
12. Electronic Thermostats (including Carrier
Communicating Temp Monitor Thermostat
MS[T]01ES):
Thermostat shall provide temperature control by
allowing programming of 2-stage heating/2-stage
cooling set-ups and setbacks.
13. VAV Control Box:
Modification shall include electric unloaders on
compressors (1 for 38AH044; 2 for 38AH054084 and 104; 3 for 38AH094; and 4 for
38AH124,134) to make condensing unit compatible with ModuPanel VAV controller. Unit shall
include factory-installed accumulator.

74

14. Single-Circuit Modification (sizes 044-084 only)


Modification shall include all piping and wiring
to make unit single circuit. Unit shall include
factory-installed accumulator.
15. Single-Circuit Modification with VAV:
Modification shall include piping, wiring, and electric unloaders on compressors (one on 38AH044
and 2 on 38AH054-084) to make unit single circuit, VAV ready.

Carrier Corporation Syracuse, New York 13221

1095

5-95

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2
Tab 3a 1a

Page 76

Catalog No. 523-869

Printed in U.S.A.

1095

PC 111

Form 38AH-4PD
Replaces: 38AH-3PD

76