38AH024-134
Commercial Air-Cooled
Condensing Units
With 40RM016-034
Air-Handling Units
20 to 130 Nominal Tons
Features/Benefits
Up to 4 compressors and 2
independent refrigerant circuits provide design flexibility; condensing unit can
supply one or 2 air handlers
Efficient 38AH Series units
save energy, providing condensing unit EERs up to 11.6
Variable air volume units
operate at as low as 8% of
nominal capacity without the
use of energy-inefficient hot
gas bypass
Constant volume units operate at as low as 16% of nominal capacity (standard) or
8% of nominal capacity (with
accessory unloader)
Weatherized steel cabinet
ensures corrosion protection
Protection against high discharge and low suction refrigerant pressure, and low
oil pressure ensure compressor reliability
Crankcase heaters prevent
oil dilution and ensure
compressor lubrication
Copyright 1995 Carrier Corporation
Form 38AH-4PD
Versatility
38AH Series condensing units feature
up to 4 compressors and 2 refrigerant circuits, and can be matched with
a wide variety of air-handling units.
All condensing unit circuits can supply
a single air handler or 2 separate air
handlers.
Standard units have constant volume control. A variable air volume
(VAV) option is available. VAV units
have electric unloaders on the compressors to closely match building
loads. The VAV option requires only a
simple connection to the Carrier
ModuPanel discharge air controller,
thereby saving installation time and
cost. (NOTE: Unit sizes 024-034
require field supplied and installed
accumulator.)
Durable construction
All 38AH units have weatherized cabinets constructed of heavy-duty galvanized steel prepainted with corrosionresistant baked enamel. Inside and
outside surfaces are protected to ensure long life and good looks. The
units exceed the requirements of the
Federal Test Method Standard
No. 141 (Method 6061) 500-hour salt
spray test.
The units coils have aluminum fins
mechanically bonded to copper tubes
for long-term reliability and improved
heat transfer. Copper fins on copper tubes are available for harsh
industrial or coastal conditions.
Reliability
The 38AH condensing units feature
time-proven, highly reliable 06D and
06E semi-hermetic compressors.
Unloading capability is a standard feature on the lead compressor of each
circuit. Each compressor has vibration
isolators to provide quiet operation
and reduced component stress.
Because 38AH units have 2 independent circuits, they provide inherent
backup capability. Each circuit is also
protected by the following safety
features:
Time Guardt anti-short-cycling
device
low oil pressure safety switch
low refrigerant pressure switch
(suction)
2
40RM016-034
Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Model Number Nomenclature 38AH024-034/40RM . . . . . . . . . . . . . . . 4,5
ARI Capacities 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options and Accessories 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options and Accessories 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Physical Data 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Physical Data 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12
Selection Procedure 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . 13
Performance Data 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . 14-20
Typical Piping and Wiring 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . 21,22
Electrical Data 38AH024-034/40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . 23,24
Controls 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Typical Control Wiring 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . 26,27
Application Data 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28,29
Application Data 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30,31
Model Number Nomenclature 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . 32
Ratings Summary 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Options and Accessories 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Physical Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34,35
Dimensions 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36-42
Condensing Unit Selection Procedure 38AH044-134 . . . . . . . . . . . . . . . . 43
System Selection Procedure 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . 43
Performance Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44-50
Typical Piping and Wiring 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . 51,52
Electrical Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-55
Controls 38AH044-084 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Controls 38AH094-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Typical Control Wiring 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . 58-60
Application Data 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61-67
Guide Specifications 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68,69
Guide Specifications 40RM016-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70,71
Guide Specifications 38AH044-134 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72-74
*Size 034 units use 10 Hp motor only; YC and WD option codes for
034 size designate standard motor and high-static drive.
024
028
034
INDOOR AIR
HANDLER
AIR HANDLER
AIRFLOW
(Cfm)
40RM016
40RM024
40RM028
40RM024
40RM028
40RM034
40RM028
40RM034
6,000
8,000
8,750
8,000
10,000
12,000
10,000
12,000
SYSTEM
Net Capacity
EER
(Btuh)
208,000**
9.3**
222,000**
9.2**
236,000**
9.8**
250,000
9.0
267,000
9.3
278,000
9.0
301,000
9.0
317,000
8.9
LEGEND
EER Energy Efficiency Ratio
IPLV Integrated Part Load Value
SST Saturated Suction Temperature
IPLV
9.5**
9.2**
9.9
9.2
9.2
9.2
9.1
9.1
11.6
13.0
290,000
11.2
12.9
344,000
11.1
12.9
NOTE: All systems with 38AH028 and 034 units are above the ARI 360-86
maximum certification capacity for 240,000 Btuh systems. These systems are tested and rated in accordance with the rating procedures for
ARI 360.
Field-installed accessories
Pressure-operated unloading allows compressors to be
unloaded in response to compressor suction pressure.
Electric unloader package includes hardware and solenoid valve to convert a pressure-operated unloader to electric unloading.
20 F low-ambient temperature kit (Motormastert
III) controls outdoor-fan motor operation to maintain the
correct head pressure at low outdoor ambient temperatures. Only one low ambient temperature kit is required per
unit.
Field-installed accessories
Discharge plenum directs the air discharge directly into
the occupied space; integral horizontal and vertical louvers
enable redirection of airflow. Accessory is available unpainted or painted.
Two-row hot water coils have 58-in. diameter copper
tubes mechanically bonded to aluminum plate fins. Coils
have non-ferrous headers.
One-row steam coil has 1-in. OD copper tube and aluminum fins. The Inner Distributing Tube (IDT) design provides uniform temperatures across the coil face. The steam
coil has a broad operating pressure range; up to 175 psig
at 400 F and up to 300 psig at 300 F. IDT steam coils are
especially suited to applications where sub-freezing air enters the unit.
Electric resistance heat coils have an open-wire design
and are mounted in a rigid frame. Safety cutouts for high
temperature conditions are standard.
024
Ckt 1
028
Ckt 2
Ckt 1
Ckt 1
Ckt 2
20
25
30
1760
1923
1820
1982
Reciprocating Semi-Hermetic
06DH328
06DA328
6
6
1750
1750
1880
2097
06DH824
6
1750
06DA824
6
1750
100
67
33**
100
76
58
3
20
2...30
1.0
16,700
2...19
39.20
37.7
06DH328
6
1750
100
100
100
67
67
33**
33**
Factory Installed
76
76
58
58
10
R-22
3
3
3
3
20
20
20
25
Propeller Type Direct Driven
2...30
1.0
16,700
1140
1550
Enhanced Copper Tubes, Lanced Aluminum Fins
2...19
39.20
37.7
426 6 7
320 6 20
27 6 3
44 6 5
Manual Reset
6.0
8.8
70 6 3
60 6 3
Fusible Plug
Liquid Line, Suction Line, Compressor
210
LEGEND
Diff Differential
FIOP Factory-Installed Option
VAV Variable Air Volume
*Rating conditions are 80 F db, 67 F wb at 95 F ambient temperature.
VAV FIOP double electrically actuated unloaders on compressor no. 1.
**Standard unit single suction pressure-actuated unloader on compressor no. 1.
With 25 ft of interconnecting piping.
\ Condenser 80% full of liquid R-22 at 120 F.
NOTE: Refer to Unloading Sequences table, page 28 for additional capacity step data.
034
Ckt 2
138
58
58
06DA537
6
1750
100
3
25
2...30
1.0
15,700
3...17
39.20
56.6
016
15
024
20
028
25
034
30
685
140
690
140
1020
180
1030
180
2...15
6000
4500-7500
2...15
8000
6000-10,000
2...18
10,000
7500-12,500
2...18
12,000
9000-15,000
3.7
3.0
5.0
5.0
7.5
7.5
10.0
10.0
1725
1725
1745
1745
1745
1755
1745
1755
2.5/2.5
3.5/3.5
4.5/4.5
5.0/5.0
R-22
17.67
2
12
3...15
29.83
2
18
3...15
175
13.33
1...10
13.33
1...10
13.33
2...8.5
13.33
2...8.5
2...118
2...118
15.0
1...10
15.0
1...10
15.0
2...12.5
15.0
2...12.5
150
2...138
2...138
2...58
2...212
2...212
2...2
2...2
1...114
Throwaway Factory Supplied
4...16 x 20 x 2
4...20 x 24 x 2
4...16 x 24 x 2
4...20 x 25 x 2
Either Side
LEGEND
TXV Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.
Dimensions 38AH024-034
NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all
sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space above unit.
3. C in the package number indicates copper coils.
4. Dimensions in [ ] are in millimeters.
5. The approximate operating weight of the unit is shown below.
6. Certified dimensional drawing is available on request.
024
024C
028
028C
034
034C
10
631.6
[286.5]
666.5
[302.3]
658.7
[298.8]
693.0
[314.3]
667.0
[302.5]
718.3
[325.8]
577.6
[262.0]
609.5
[276.5]
602.4
[273.3]
633.8
[287.5]
610.0
[276.7]
656.8
[297.9]
263.1
[119.3]
309.0
[140.2]
267.0
[121.1]
313.0
[142.0]
288.0
[130.7]
344.8
[156.4]
287.7
[130.5]
337.9
[153.3]
291.9
[132.4]
342.2
[155.2]
315.0
[142.9]
377.0
[171.0]
CENTER OF
GRAVITY
A Dim.
in.
[mm]
40.00
[1016]
43.00
[1092]
39.25
[997]
42.25
[1073]
41.00
[1041]
44.00
[1117]
B Dim.
in.
[mm]
32.75
[832]
TOTAL
UNIT WT
lb [kg]
1760
[798.3]
1923
[872.3]
1820
[825.6]
1982
[899.0]
1880
[853.0]
2097
[951.2]
Dimensions 40RM
40RM016,024
UNIT
40RM
016
024
UNIT WEIGHT
(lb)
685
690
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
Rear: 39
Front: 28-69
Right side: 28-69
Left Side: 28-69
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
11
UNIT
40RM
028
034
UNIT WEIGHT
(lb)
1020
1030
NOTES:
1. Dimensions in [ ] are in millimeters.
2.
Direction of airflow.
3. Recommended clearance:
Rear: 39
Front: 28-69
Right side: 28-69
Left Side: 28-69
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.
12
13
38AH034
SST
(F)
20
25
30
35
40
45
50
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
85
157
105
14.1
178
106
14.7
198
107
15.3
221
109
15.9
244
111
16.6
270
113
17.2
295
116
17.8
115
115
135
16.0
134
135
17.0
153
135
18.1
173
137
19.1
193
138
20.1
215
140
21.1
237
142
22.1
38AH028
SST
(F)
20
25
30
35
40
45
50
14
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
85
187
107
17.1
209
109
17.9
231
111
18.7
256
113
19.5
282
115
20.3
310
118
21.1
338
120
22.0
115
147
135
19.9
166
137
21.1
185
138
22.2
206
140
23.4
228
142
24.6
252
144
25.9
275
146
27.1
SST
(F)
20
25
30
35
40
45
50
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
TC
SDT
kW
85
223
107
21.2
249
109
22.2
276
110
23.1
307
112
24.2
336
115
25.3
369
117
26.3
402
120
27.4
Air Temp
95
206
117
22.5
232
118
23.6
258
119
24.7
287
121
25.9
314
123
27.1
346
126
28.3
378
128
29.6
Ent Condenser
100
105
199
190
122
127
23.1
23.7
224
215
123
128
24.2
24.9
249
241
124
129
25.4
26.2
277
267
126
130
26.7
27.6
305
294
128
132
28.0
28.9
335
324
136
135
29.3
30.3
366
354
133
137
30.6
31.7
LEGEND
kW Compressor Power
SDT Saturated Discharge Temperature
at Compressor (F)
SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)
115
175
137
24.8
209
137
26.2
222
138
27.6
248
140
29.0
274
141
30.5
302
144
32.0
330
146
33.6
115
58
135
8.01
67
135
8.52
77
135
9.03
87
137
9.54
97
138
10.0
108
140
10.6
119
142
11.1
115
71
135
10.2
81
135
10.8
92
135
11.3
104
137
11.8
116
138
12.4
128
140
12.9
141
142
13.5
115
74
135
9.97
83
137
10.5
93
138
11.1
103
140
11.7
114
142
12.3
126
144
12.9
138
146
13.5
115
104
138
14.6
117
139
15.4
130
140
16.3
144
142
17.2
158
144
18.1
174
147
19.1
189
149
20.1
LEGEND
kW Compressor Power
SDT Saturated Discharge Temperature
at Compressor (F)
SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)
*Circuits no. 1 and 2 on 38AH024 and 028 have identical capacities.
15
95
100
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
38AH024/40RM028
38AH024/40RM024
Temp (F)
Air Entering
Condenser
(Edb)
85
95
100
105
115
BF
Ewb
kW
SHC
TC
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Bypass Factor
Entering Wet-Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.
79
81
0.10
0.20
0.30
0.99
0.88
0.77
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
16
85
95
100
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
7500/0.04
72
278.4
149.6
17.39
265.2
144.8
19.01
259.8
142.8
19.86
252.5
140.1
20.66
239.5
135.4
22.21
67
254.6
191.9
16.85
242.4
187.0
18.35
237.0
184.8
19.10
230.2
182.1
19.79
217.6
177.0
21.22
38AH028/40RM024
BYPASS
FACTOR
Temp (F)
Air Entering
Condenser
(Edb)
Temp (F)
Air Entering
Condenser
(Edb)
85
95
100
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
6000/0.03
72
281.6
141.5
20.29
270.0
137.1
22.13
264.3
134.9
23.00
258.7
132.8
23.88
247.3
128.4
25.64
67
258.4
176.0
19.63
247.7
171.6
21.39
242.6
169.5
22.16
237.2
167.3
22.97
227.1
163.2
24.55
3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil
5. Combination ratings are based on a 2 F line loss. For a close-coupled system
(less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table
on page 29 are based on 2 F line loss. All combination ratings are based on
R-22.
95
100
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
38AH034/40RM028
38AH028/40RM034
Temp (F)
Air Entering
Condenser
(Edb)
85
95
100
105
115
BF
Ewb
kW
SHC
TC
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
LEGEND
Bypass Factor
Entering Wet-Bulb
Compressor Motor Power Input
Sensible Heating Capacity (1000 Btuh)
Total Capacity (1000 Btuh)
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The SHC is based on 80 F dry-bulb temperature of air entering evaporator coil.
Below 80 F dry-bulb, subtract (correction factor x cfm) from SHC.
Above 80 F dry bulb, add (correction factor x cfm) to SHC.
79
81
0.10
0.20
0.30
0.99
0.88
0.77
85
95
100
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
7500/0.04
72
338.9
171.9
25.39
325.5
167.0
27.53
319.5
164.7
28.63
312.6
162.2
29.77
281.0
150.6
32.40
67
312.7
215.4
24.59
299.5
210.0
26.56
294.4
208.0
27.54
287.4
205.2
28.59
257.3
193.0
31.04
38AH034/40RM034
BYPASS
FACTOR
Temp (F)
Air Entering
Condenser
(Edb)
Temp (F)
Air Entering
Condenser
(Edb)
85
95
100
105
115
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
TC
SHC
kW
9000/0.04
72
363.5
189.6
26.13
348.8
184.0
28.40
341.4
181.3
29.58
334.2
178.5
30.77
298.7
165.1
33.42
67
334.5
241.8
25.25
319.9
236.0
27.32
313.6
233.5
28.37
306.1
230.6
29.47
272.4
217.2
31.91
3. Gross capacities shown do not include a deduction for evaporator fan motor
heat.
4. Formulas:
sensible heat capacity (Btuh)
tldb = tedb
1.1 x cfm
tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evaporator coil (hlwb)
total capacity (Btuh)
hlwb = hewb
4.5 x cfm
where hewb = enthalpy of air entering evaporator coil
5. Combination ratings are based on a 2 F line loss. For a close-coupled system
(less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes table
on page 29 are based on 2 F line loss. All combination ratings are based on
R-22.
Interpolation is permissible.
Correction Factor = 1.1 x (1 BF) x (db 80).
17
016
024
028
034
AIRFLOW
(Cfm)
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000
0.0
Rpm
391
460
521
590
651
503
586
670
754
838
412
481
549
618
687
471
550
628
707
785
0.2
Bhp
0.51
0.80
1.13
1.60
2.10
1.07
1.64
2.37
3.28
4.39
1.15
1.76
2.55
3.52
4.71
1.78
2.72
3.93
5.44
7.27
Rpm
495
551
602
663
718
587
660
735
812
891
492
550
610
672
735
539
608
679
752
826
Bhp
0.75
1.08
1.43
1.93
2.45
1.37
1.98
2.74
3.69
4.83
1.53
2.17
2.99
4.00
5.22
2.17
3.15
4.40
5.94
7.81
EXTERNAL
0.4
Rpm
Bhp
581
1.00
629
1.35
675
1.73
730
2.26
779
2.81
661
1.67
726
2.31
795
3.12
867
4.09
941
5.27
568
2.00
616
2.66
669
3.50
725
4.53
783
5.78
604
2.63
665
3.64
730
4.92
797
6.49
867
8.39
LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure
Italics indicate special field-supplied drive required for use with standard motor.
Bold indicates standard drive and standard motor.
Plain type indicates medium-static drive and standard motor. For 40RM028
size only, plain type indicates medium-static drive and alternate motor.
indicates high-static drive and alternate motor. For 034 size
only, shading indicates high-static drive and standard motor.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pressure
drop.
3. Refer to fan motor and drives tables, pages 30 and 31 to complete
the selection.
4. Factory-supplied motor for 034 size is standard 10 Hp motor only;
alternate motor not available.
18
1.0
Rpm
787
823
858
901
941
846
898
954
1014
1077
776
802
836
876
922
788
827
874
928
986
1.2
Bhp
1.76
2.20
2.65
3.26
3.88
2.59
3.33
4.23
5.31
6.85
3.98
4.58
5.40
6.45
7.74
4.46
5.45
6.76
8.38
10.35
Rpm
845
878
911
951
990
900
948
1001
1059
1120
840
860
889
925
966
845
878
921
970
1024
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40
Bhp
2.02
2.48
2.96
3.60
4.24
2.90
3.67
4.61
5.72
7.02
4.83
5.38
6.17
7.21
8.49
5.22
6.18
7.47
9.10
11.07
016
024
028
034
AIRFLOW
(Cfm)
4,500
5,300
6,000
6,800
7,500
6,000
7,000
8,000
9,000
10,000
7,500
8,750
10,000
11,250
12,500
9,000
10,500
12,000
13,500
15,000
1.4
Rpm
899
930
961
999
1036
950
996
1047
1102
1160
903
917
941
972
1010
901
928
966
1011
1062
1.6
Bhp
2.29
2.78
3.28
3.94
4.60
3.21
4.02
4.99
6.13
7.46
5.79
6.26
7.01
8.02
9.29
6.07
6.98
8.24
9.86
11.84
Rpm
951
980
1009
1045
1080
999
1042
1091
1143
1200
963
972
991
1019
1053
955
978
1011
1052
Bhp
2.56
3.08
3.60
4.28
4.97
3.53
4.37
5.37
6.54
7.91
6.83
7.22
7.91
8.89
10.15
6.98
7.84
9.07
10.67
1021
7.98
1078
9.21
1078
9.38
1025
8.26
1040
8.89
1089
9.93
1064
9.83
1095
11.05
1008
7.98
1060
9.05
1026
8.76
1073
9.74
1055
9.95
1098
10.88
1092
11.52
LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure
Plain type indicates medium-static drive and standard motor. For 40RM028
size only, plain type indicates medium-static drive and alternate motor.
indicates high-static drive and alternate motor. For 034 size
only, shading indicates high-static drive and standard motor.
Italics indicate special field-supplied drive required for use with alternate
motor. For 034 size only, italics indicate special field-supplied drive required for use with standard motor.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See right for factory-supplied filter pressure
drop.
3. Refer to fan motor and drives tables, pages 30 and 31 to complete
the selection.
4. Factory-supplied motor for 034 size is standard 10 Hp motor only;
alternate motor not available.
2.2
Rpm
1091
1116
1141
1173
1131
1169
2.4
Bhp
3.41
3.99
4.57
5.33
4.50
5.43
Rpm
1133
1157
1181
1172
Bhp
3.70
4.30
4.91
4.83
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
PRESSURE DROP
(in. wg)
0.08
0.12
0.17
0.12
0.19
0.26
0.15
0.22
0.30
0.19
0.29
0.40
19
AIRFLOW
(Cfm)
016
024
028
034
6,000
8,000
10,000
12,000
Straight
50
60
76
85
VANE DEFLECTION
2212
43
51
65
72
45
31
37
47
52
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following multipliers to determine throw values for other terminal velocities.
TERMINAL VELOCITY
(Fpm)
50
100
150
THROW FACTOR
X
X
X
1.50
0.75
0.50
AIRFLOW
(Cfm)
DISCHARGE
PLENUM
RETURN AIR
GRILLE
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
0.10
0.16
0.23
0.16
0.26
0.37
0.15
0.24
0.34
0.20
0.32
0.46
0.01
0.02
0.03
0.02
0.04
0.06
0.02
0.03
0.05
0.03
0.05
0.07
016
024
028
034
016
024
028
034
AIRFLOW
(Cfm)
4,500
6,000
7,500
6,000
8,000
10,000
7,500
10,000
12,500
9,000
12,000
15,000
1-ROW
STEAM*
Cap.
402
458
479
458
487
499
511
575
626
560
621
670
Ldb
141
129
118
129
115
105
122
112
106
117
107
101
Cap.
412.0
471.0
529.0
506.0
584.0
652.0
649.0
752.0
842.0
735.0
850.0
950.0
2-ROW
HOT WATER
COIL
Ldb Gpm
145
41.2
133
47.1
125
52.9
138
50.6
128
58.4
120
65.2
140
64.9
130
75.2
122
84.2
136
73.5
126
85.0
119
95.0
HEATING COILS
Steam
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85
Electric
0.06
0.10
0.15
0.10
0.17
0.26
0.09
0.16
0.24
0.13
0.22
0.34
ECONOMIZER
0.06
0.09
0.15
0.09
0.17
0.28
0.06
0.09
0.14
0.08
0.14
0.21
PD
4.5
5.5
6.6
5.1
6.3
7.5
5.7
7.1
8.5
6.2
7.8
9.3
LEGEND
Cap. Capacity (Btuh in thousands)
Ldb Leaving-Air Dry-Bulb Temp (F)
PD
Pressure Drop (ft water)
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for steam heating coils:
175 psig at 400 F.
2. Maximum operating limit for hot water heating coils is 150 psig.
Capacity (Btuh)
3. Leaving db = ent db (F) +
1.1 x cfm
4. See Heating Correction Factors table.
20
Hot Water
0.15
0.23
0.33
0.23
0.37
0.53
0.28
0.44
0.63
0.37
0.59
0.85
Water Temp
Drop
(F)
10
20
30
HOT
Ent Water
Temp
(F)
140
160
180
200
220
140
160
180
200
220
140
160
180
200
220
Steam Pressure
(psig)
0
2
5
WATER COIL
Entering-Air Temp (F)
40
50
60
70
80
0.72
0.89
1.06
1.22
1.39
0.64
0.81
0.98
1.15
1.32
0.56
0.74
0.91
1.08
1.25
0.64
0.81
0.98
1.15
1.32
0.57
0.74
0.91
1.08
1.25
0.49
0.66
0.83
1.00
1.18
0.57
0.74
0.90
1.07
1.24
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.76
0.93
1.10
0.49
0.66
0.83
1.00
1.17
0.41
0.58
0.75
0.93
1.10
0.33
0.51
0.68
0.85
1.03
0.41
0.58
0.75
0.92
1.09
0.33
0.51
0.68
0.85
1.02
0.24
0.43
0.60
0.78
0.95
STEAM COIL
Entering-Air Temp (F)
40
50
60
70
1.06
0.98
0.91
0.85
1.09
1.02
0.95
0.89
1.13
1.06
1.00
0.93
80
0.78
0.82
0.87
LEGEND
LLSV Liquid Line Solenoid Valve
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Piping
Double Riser Piping (if required)
*Field supplied.
If double suction riser is required for piping system, size pipe diameter of 3 ft (maximum) riser
according to application data on page 29.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.
21
LEGEND
TXV Thermostatic Expansion Valve
Piping
*Field supplied.
22
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to
Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant migration to the compressor.
024
028
034
500
200
600
100
500
200
600
100
500
200
600
100
Volts
3 Ph, 60 Hz
208/230
380
460
575
208/230
380
460
575
208/230
380
460
575
UNIT
Supplied*
Min
Max
187
254
342
418
414
508
518
632
187
254
342
418
414
508
518
632
187
254
342
418
414
508
518
632
MCA
MOCP
(Fuse)
ICF
100.8
61.8
50.3
42.1
110.5
67.2
55.9
47.1
135.5
77.0
65.8
53.3
125
80
60
50
150
90
70
60
175
110
90
70
249.7
124.8
124.8
101.5
284.0
138.2
142.3
117.5
322.0
179.2
148.3
120.7
LEGEND
Canadian Standards Association
Full Load Amps
Maximum Instantaneous Current Flow during starting (the
point in the starting sequence where the sum of the LRA for
the starting compressor, plus the total RLA for all running
compressors, plus the total FLA for all running fan
motors is maximum).
LRA
Locked Rotor Amps
MCA Minimum Circuit Amps (complies with National Electrical Code
[NEC], Section 430-24)
MOCP Maximum Overcurrent Protection
RLA
Rated Load Amps
UL
Underwriters Laboratories
COMPRESSOR
RLA
LRA
Ckt 1
Ckt 2
Ckt 1
Ckt 2
39.3
39.3
198
198
24.0
24.0
93
93
19.6
19.6
99
99
15.7
15.7
79
79
43.6
43.6
228
228
26.4
26.4
104
104
22.1
22.1
114
114
19.7
19.7
91
91
43.6
63.6
228
266
26.4
34.3
104
145
22.1
30.0
114
120
17.9
22.9
91
96
FAN MOTORS
Qty
FLA
(ea)
Hp
6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4
6.2
3.9
3.1
3.4
*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum
limits.
All fans are protected by a single circuit breaker.
NOTE: The 208/230-v and 460-v base units are UL and CSA approved.
The 575-v base units are CSA approved.
CSA
FLA
ICF
016
024
028
034
FAN MOTOR
V*-PH-HZ
VOLTAGE
LIMITS
Hp
FLA
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
187-253
414-528
518-632
187-253
414-528
518-632
187-253
414-528
518-632
187-253
414-528
518-632
3.7
3.7
3.0
5.0
5.0
5.0
7.5
7.5
7.5
10.0
10.0
10.0
10.6
4.8
3.8
15.2/14.4
7.2
5.6
22.0/21.0
10.5
7.6
26.4/25.0
12.5
9.6
POWER SUPPLY
Minimum Circuit
MOCP
Amps
13.3
20
6.0
15
4.8
15
19.0/18.0
30/30
9.0
15
7.0
15
27.5/26.3
45/45
13.1
20
9.5
15
33.0/31.3
55/55
15.6
25
12.0
20
016
024
028
FAN MOTOR
V*-PH-HZ
VOLTAGE
LIMITS
Hp
FLA
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
187-253
414-528
518-632
187-253
414-528
518-632
187-253
414-528
518-632
5.0
5.0
5.0
7.5
7.5
7.5
10.0
10.0
10.0
15.2/14.4
7.2
5.6
22.0/21.0
10.5
7.6
26.4/25.0
12.5
9.6
POWER SUPPLY
Minimum Circuit
MOCP
Amps
19.9/18.0
30/30
9.0
15
7.0
15
27.5/26.3
45/45
13.1
20
9.5
15
33.0/31.3
55/55
15.6
25
12.0
20
LEGEND
FLA
Full Load Amps
Hp
Horsepower
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.
1095
23
016,024
028,034
HEATER
PART NO.
CAELHEAT016A00
CAELHEAT017A00
CAELHEAT018A00
CAELHEAT019A00
CAELHEAT020A00
CAELHEAT021A00
CAELHEAT022A00
CAELHEAT023A00
CAELHEAT024A00
CAELHEAT025A00
CAELHEAT026A00
CAELHEAT027A00
CAELHEAT028A00
CAELHEAT029A00
CAELHEAT030A00
CAELHEAT031A00
CAELHEAT032A00
CAELHEAT033A00
CAELHEAT034A00
CAELHEAT035A00
CAELHEAT036A00
CAELHEAT037A00
CAELHEAT038A00
CAELHEAT039A00
V-PH-HZ
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
240-3-60
480-3-60
575-3-60
LEGEND
ETL
Electrical Testing Laboratory
MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection (Amps)
*Sizes shown are for single-point connection of electric heat accessory
and air handler.
HEATER RATING
VOLTAGE
240
480
575
200
.694
208
.751
230
.918
.840 .918
1
24
HEATER
AMPS
24.1
12.0
10.0
47.9
24.1
20.1
71.9
36.1
30.1
120.0
60.1
50.2
47.9
24.1
20.1
95.7
48.1
40.2
120.0
60.1
50.2
167.9
84.0
70.3
NOMINAL kW
10
20
30
50
20
40
50
70
MCA*
MOCP*
52.1
25.5
20.2
82.1
40.6
32.7
112.2
55.6
45.3
172.4
85.7
70.4
86.5
42.6
34.7
146.7
72.6
59.8
176.8
87.7
72.4
236.9
117.8
97.5
60
30
25
110
50
45
150
80
70
250
125
100
110
60
45
200
100
80
250
125
100
350
175
150
NOTES:
1. MCA and MOCP values apply to both standard and alternate factorysupplied motors.
2. Electric heaters are tested and ETL approved at maximum total external static pressure of 1.9 in. wg.
3. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
determine heater capacity (kW) at unit nameplate voltage, multiply
240-v, 480-v, or 575-v capacity by multipliers found in table below.
550
.915
575
600
1.089
Controls 38AH024-034
Sequence of operation
Single air handler, 2-stage cool thermostat At
start-up, the thermostat calls for first-stage cooling (TC1
closes) and with all safety devices satisfied, circuit no. 1 control relay (CR1) energizes, deenergizing the crankcase heater
at compressor no. 1. The indoor-fan motor starts immediately, and the liquid line solenoid valve (LLSV) for
solenoid drop refrigeration control on circuit no. 1 opens.
Outdoor-fan motor no. 1 and compressor no. 1 start after
one second. Fan no. 2 starts if the outdoor ambient temperature is above 70 F.
On standard units, compressor no. 1 operates either fully
loaded or at one step of unloading depending on the suction pressure, which in turn is dependent on the evaporator load conditions. As cooling demand increases, TC2 of
the 2-stage thermostat energizes control relay no. 2. CR2
deenergizes the crankcase heater at compressor no. 2 and
brings on compressor no. 2 after one second. The LLSV
for solenoid drop refrigerant control (circuit no. 2) opens as
soon as CR2 is energized. On standard units, compressor
no. 2 operates fully loaded.
As cooling demand is satisfied, thermostat contacts TC2
break and deenergize CR2, which then deenergizes compressor no. 2 and energizes its crankcase heater. The LLSV
on circuit no. 2 closes, preventing refrigerant migration back
to compressor no. 2 during the off cycle. If the space temperature continues to decrease, stage 1 thermostat contacts
TC1 break and deenergize CR1. Immediately after CR1 is
deenergized, compressor no. 1 shuts off and its crankcase
heater is energized. The LLSV on circuit no. 1 closes, preventing refrigerant migration back to compressor no. 1 during the off cycle. Outdoor-fan motors no. 1 and 2 deenergize as soon as CR1 is deenergized.
NOTE: If thermostat fan switch is in the auto position, the
indoor fan cycles on and off as the thermostat calls for
cooling (or heating). If the fan switch is in the continuous
position, the fan runs as long as the outdoor unit is powered up.
Two air handlers, two 2-stage cool thermostats (one
per air handler) At start-up of circuit no. 1, the
thermostat controlling circuit no. 1 calls for the first stage
of cooling when thermostat contact TC1 closes. If all safety
devices are satisfied, circuit no. 1 control relay CR1 energizes, which deenergizes the crankcase heater at compressor no. 1. The indoor-fan motor on the circuit no. 1
air handler starts immediately, and the main liquid line
solenoid valve (LLSV) for solenoid drop refrigerant control
on circuit no. 1 opens. Outdoor-fan motor no. 1 and compressor no. 1 start after one second. Fan no. 2 starts if the
outdoor ambient is above 70 F.
On standard units, compressor no. 1 operates either fully
loaded or at one step of unloading depending on the
suction pressure, which in turn is dependent on the evaporator load conditions. As cooling demand increases, TC2
of the 2-stage thermostat energizes the capacity control
LLSV resulting in full utilization of the evaporator surface.
The fully utilized evaporator surface raises the suction pressure until the pressure-operated capacity control valve
setting is exceeded, so that the compressor becomes fully
loaded.
The thermostat controlling circuit no. 2 calls for the first
stage of cooling when thermostat contact TC1 closes. Assuming all safety devices are satisfied, circuit no. 2 control
relay CR2 energizes, which deenergizes the crankcase heater
at compressor no. 2. The indoor-fan motor on circuit no. 2
air handler starts immediately, and the main LLSV for
solenoid drop refrigerant control on circuit no. 2 opens.
Compressor no. 2 starts after one second. The outdoor fans
are already running if circuit no. 1 is running. If circuit
no. 1 is not running when thermostat no. 2 calls for cooling, the outdoor fans are off. In this situation, outdoor-fan
motor no. 1 starts when compressor no. 2 starts. Outdoorfan motor no. 2 comes on if the outdoor ambient temperature is above 60 F.
IMPORTANT: Do not install CCS2 (capacity control
solenoid) unless accessory unloader is field-installed
on circuit no. 2 compressor. CCS2 is controlled from
TC2 contacts on thermostat that regulate circuit no.
2 air handler.
NOTE: Circuit no. 2 compressor does not have a factoryinstalled unloader; one must be field-installed if required.
As cooling demand is satisfied at thermostat no. 1 or 2
(whichever comes first), contacts TC2 break and the capacity control LLSV on that circuit is deenergized. This prevents refrigerant flow through the upper (circuit no. 1 or 2)
evaporator section, causing the suction pressure to drop
and the compressor on that circuit to unload.
As the space temperature drops further, thermostat
contacts TC1 open, which deenergizes control relay CR1
or CR2. Immediately after CR1 or CR2 is deenergized, the
compressor CR1 or CR2 control is shut off and its crankcase heater is energized. The LLSV on that circuit closes,
preventing refrigerant migration back to the compressor during the off cycle. Outdoor-fan motors no. 1 and 2 are deenergized only if the space thermostats for both circuits no. 1
and 2 are not calling for cooling.
NOTE: If the thermostat fan switch is in the auto position,
the indoor fan cycles on and off as the thermostat calls for
cooling (or heating). If the fan switch is in the continuous
position, the fan runs as long as the outdoor unit is powered up.
25
AUTO
C
CB
COM
GND
IFC
LLS
NEC
RV
TB
TC
LEGEND
Automatic Changeover
Contactor, Compressor
Circuit Breaker
Common
Ground
Indoor-Fan Contactor
Liquid Line Solenoid
National Electrical Code
Reversing Valve
Terminal Block
Thermostat, Cooling
Field Control Wiring
Factory Wiring
Field Power Wiring
Indicates Common Potential;
Does Not Indicate Wiring
26
208/230-3-60
460-3-60
575-3-60
380-3-60
UNIT (V-Ph-Hz)
**For a single air handler, LLS valve 1 is to be used on the lower (no. 1)
evaporator circuit. The LLS valve 2 is to be used on the upper (no. 2) evaporator circuit.
Only one indoor-fan contactor is required on single air-handler applications.
Use Carrier accessory part no. 40RR900181 for indoor-fan contactor.
230-1-60
115-1-60
NOTES:
1. CB4 protects TB3 circuit; CB5 protects TB2 circuits.
2. LLS1 and LLS2 are field supplied.
3. TB2 and TB3 are in 24-v circuits.
4. On the TSR-01 Relay Pack, the outside-air sensor, supply-air sensor, and direct expansion coil sensor are available as options.
27
AUTO
C
CB
CCS
COM
GND
IFC
LLS
NEC
RV
TB
TC
LEGEND
Automatic Changeover
Contactor, Compressor
Circuit Breaker
Capacity Control Solenoid
Common
Ground
Indoor-Fan Contactor
Liquid Line Solenoid
National Electrical Code
Reversing Valve
Terminal Block
Thermostat, Cooling
Field Control Wiring
Factory Wiring
Field Power Wiring
Indicates Common Potential;
Does Not Indicate Wiring
208/230-3-60
460-3-60
575-3-60
380-3-60
UNIT (V-Ph-Hz)
NOTES:
1. Capacity control solenoid (and liquid line solenoid drop refrigerant control)
valves are field supplied.
2. CB4 protects TB3 circuit, and CB5 protects TB2 circuit.
3. On the TSR-01 Relay Pack, the outside-air sensor, supply-air sensor, and
direct expansion coil sensor are available as options.
230-1-60
115-1-60
UNLOADING SEQUENCES
UNIT 38AH
024
028
034
CAPACITY/STAGE (%)
CV Units (Standard)*
VAV Units (Optional)
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 83, 50, 33
100, 83, 67, 50, 33, 17
100, 85, 43, 28
100, 85, 77, 43, 28, 14
LEGEND
CV Constant Volume
VAV Variable Air Volume
*Additional unloading available with field-installed accessory unloader.
NOTE: Capacities are based on 45 F saturated suction temperature and 95 F outdoor air temperature.
024
028
034
SYSTEM
CAPACITY (%)
100
83
67*
50
33
17*
100
83
67*
50
33
17*
100
81
62*
43
29
14*
28
115 F
See Minimum Outdoor-Air
Operating Temperature
table below.
55 F
95 F
20 to 50 F
275 F
60 F
UNIT 38AH
024 Ckt
Ckt
028 Ckt
Ckt
034 Ckt
Ckt
1
2
1
2
1
2
12
12
12
12
12
12
LEGEND
L Liquid Line
S Suction Line
*Double suction riser required if evaporator is below condensing unit and 2 unloaders are used on that
circuit.
Double suction riser required if evaporator is below condensing unit and compressor is equipped
with 2 unloaders. Note the only time circuit no. 2 may be equipped with 2 unloaders is if it is serving
its own air handler and the unit does not require low ambient operation (MotormasterT III control).
**Double suction riser required if evaporator is below condensing unit and compressor has one or more
unloader(s).
NOTES:
1. All line sizes are inches OD.
2. Standard unit comes with one pressure-operated unloader on circuit no. 1. If unit serves one air
handler, an additional unloader may be field installed on circuit no. 1 compressor only. If the unit
serves 2 separate air handlers and low ambient operation is required (Motormaster III control), each
circuits compressor may only be equipped with one unloader.
1
2
1
2
1
2
118
50-75
B
138
118
138
1 5 8
118
138
118
138
1 5 8
138
138
118
138
1 5 8
138
158
118
138
1 5 8
138
158
5
1
3
5
3
1 8
1 8
1 8
1 8
1 8
158
138
158
C
1 5 8
1 5 8
2 1 8
2 1 8
2 1 8
2 1 8
V-Ph-Hz
024-034
208-230/3/60
380-3-60
460-3-60
375-3-60
LEGEND
AWG American Wire Gage
kcmil Thousand Circular Mils
TB
Terminal Block
LEGEND
Suction Riser without Trap
Suction Riser with Trap
Suction Line to Condensing Unit
Pipe Diameter to be Same Size as Riser A
29
General
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit cycling,
and less part-load operation. Equipment should be selected
to perform at no less than 300 cfm/ton.
The air handler fan must always be operating when the
condensing unit is operating.
TXV
Qty...Part No.
DISTRIBUTOR
Qty...Part No.
016
024
028
034
2...XVE-8
2...XVE-10
2...EBSVE-11
2...SVE-15
2...1116
2...1116
2...1126
2...1126
FEEDER TUBES
PER DISTRIBUTOR
Qty...Size (in.)
12...14
13...14
15...14
18...14
NOZZLE
Qty...Part No.
2...E6
2...E8
2...C10
2...C12
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.
UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
016
1725
3.7
56Y
7 8
024
1745
5.0
S184T
118
028
1745
7.5
S213T
138
034
1745
10.0
S215T
138
LEGEND
NEMA National Electrical Manufacturers Association
UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
016
1725
3.0
56HZ
78
024
1745
5.0
184T
1 1 8
028
1750
10.0
S215T
138
575-3-60 MOTORS
028
1755
7.5
S213T
138
LEGEND
NEMA National Electrical Manufacturers Association
30
024
1745
7.5
S213T
138
LEGEND
NEMA National Electrical Manufacturers Association
575-3-60 MOTORS
UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
016
1745
5.0
S184T
1 1 8
034
1755
10.0
S215T
138
UNIT 40RM
Speed (rpm)
Hp
Frame (NEMA)
Shaft Dia (in.)
016
1745
5.0
184T
118
024
1755
7.5
S213T
1 3 8
LEGEND
NEMA National Electrical Manufacturers Association
028
1750
10.0
S215T
138
016
024
028
034
2.8-3.8
3.7-4.7
4.3-5.3
4.3-5.3
2.5
3.0
3.0
3.0
9.0
1716
1A
9.4
1716
2B
42.3
41.8
11.0
11516
2B*
(2) 42.8
or
(2) 43.8
11.0
11516
2B*
(2) 42.8
or
(2) 43.8
UNIT 40RM
MOTOR DRIVE
Motor Pulley Pitch
Diameter
Pulley Factory Setting
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.)
Pulley Bore (in.)
Belt No. Section
Belt Pitch (in.)
FAN SPEEDS (rpm)
Factory Setting
Range
Max Allowable Speed
Change per 12 Turn of
Moveable Motor Pulley
Flange
MAX FULL TURNS FROM
CLOSED POSITION
SHAFTS CENTER
DISTANCE (in.)
016
024
028
034
4.3-5.3
4.3-5.3
4.3-5.3
4.3-5.3
2.5
3.0
3.0
3.0
7.9
1716
1B
39.8
7.4
1716
2B
36.8
8.6
11516
2B
37.8
8.6
11516
2B
37.8
1060
9501171
1200
1118
10141200
1200
1024
8731075
1024
8731075
30.8
19.4
16.7
16.7
9.1610.99
8.1610.02
6.679.43
6.679.43
*Four belts shipped with unit. Use one set of 2 belts sized according to
the pulley setting.
016
024
028
034
3.7-4.7
4.3-5.3
4.3-5.3
4.3-5.3
3.0
3.0
3.0
3.0
8.6
1716
1B
9.4
1716
2B
41.8
41.8
9.4
11516
2B*
(2) 38.8
or
(2) 39.8
9.4
11516
2B*
(2) 38.8
or
(2) 39.8
31
*Export only.
CAPACITY
(Nominal Tons)
40
50
60
70
80
90
100
120
130
EER*
10.7
10.5
10.5
10.0
10.0
10.2
10.4
10.5
10.2
LEGEND
EER Energy Efficiency Ratio
*Rated in accordance with ARI (Air Conditioning & Refrigeration
Institute) standard 365-87.
NOTE: Ratings are based on 45 F suction temperature and 95 F outsideair temperature, and include suction line losses.
32
Field-installed accessories
Transformer relay package for remote-control (24-v)
thermostat. One 2-stage thermostat is required for use with
the relay package.
Additional electric unloader package includes hardware to add an additional step of unloading (coil not
included).
Additional pressure unloader package includes all unloader valves and hardware.
Gage panel package contains panel-mounted suction and
discharge pressure gages.
Hail guard package protects coils against damage from
hail and airborne debris.
ModuPanel control provides 10-step microprocessorbased control for VAV applications.
Motormastert III control maintains correct condensing
pressure at low ambient temperatures.
Sound-reduction kit provides a specially designed system
of fan propellers and stacks that lower noise without reducing unit performance; compatible with the Motormaster III
accessory.
Unloader conversion kit allows you to convert factoryinstalled pressure unloaders to electric unloading.
Compressor grille package protects the compressor area
after the unit is installed.
Condenser coil grille package protects the condenser
area after the unit is installed.
Electronic thermostats provide temperature control by
allowing programming of 2-stage heating/2-stage cooling
setbacks and set-ups with provision for weekends and
holidays.
33
044
40
054
50
064
60
074
70
084
80
Cu-Al
Cu-Cu
3259
3547
3309
3597
3565
3998
3812
4229
4057
4735
Cu-Al
Cu-Cu
3250
3538
3290
3578
3780
4197
4000
4678
7
62
7
72
3530
3963
R-22
7
88
9
104
9
130
REFRIGERANT, TYPE
Shipping Charge (lb)
Operating Charge, Typical (lb)
DUAL-CKT UNIT
COMPRESSOR Type...Rpm
(Quantity) Cylinder Ckt*
Model No. 06E
Oil Charge (pt)
Capacity Control Steps (%)
Cu-Al
Cu-Cu
ODF
VAV
(4) A
(4) B
250
250
17
17
100
75
50
25
(4) A1 (4) A2
250
250
17
17
100
75
50
25
2
17
80.5
35
35
Reciprocating Semi-Hermetic...1750
(4) A
(6) B
(6) A
(6) B
(6) A
(6) B
250
265
265
275
275
299
17
21
21
21
21
19
100
100
100
79
84
86
58
69
71
42
48
43
21
32
29
16
14
(6) A
(6) B
299
299
19
19
100
83
67
50
33
17
Reciprocating Semi-Hermetic...1750
(6) A1 (4) A2 (6) A1 (6) A2 (6) A1 (6) A2
265
250
275
265
299
275
21
17
21
21
19
21
100
100
100
80
82
81
61
64
62
56
55
57
37
36
38
18
19
(6) A1 (6) A2
299
299
19
19
100
83
67
50
33
17
(4) 30
1.0
35,000
1140
6.2
2
17
80.5
35
35
LEGEND
Copper Tubes with Aluminum Fins
Copper Tubes with Copper Fins (Optional)
Outside Diameter, Female
Variable Air Volume
34
(6) 30
1.0
52,000
51,000
1140
9.3
3
17
80.5
55
2
19
116.7
55
218
7 8
5 8
55
3
17
116.7
55
80
80
UNIT 38AH
094
104
NOMINAL CAPACITY
(Tons)
OPERATING WEIGHT WITH
REFRIGERANT
(approx) - lb
Cu-Al
Cu-Cu
SHIPPING WEIGHT WITH
COIL PROTECTION
AND SKID
(approx) - lb
Cu-Al
Cu-Cu
REFRIGERANT, TYPE
Shipping Charge (lb)
Operating Charge,
Typical (lb)
Qty of Circuits
COMPRESSOR Type...Rpm
(Quantity Cylinder)
Compr
Model No. 06E
Oil Charge (pt)
Circuit Capacity - %
(approx)
Capacity Control Steps**
CONDENSER FANS
(4 Blade)
Quantity...Dia (in.)
Nominal Hp
Airflow (cfm)
Speed (rpm)
Total Power (kW)
CONDENSER COIL
Rows...Fins per in.
Face Area (sq ft)
Storage Capacity
(lb per ckt) at 120 F
CONNECTIONS
Suction, ODF (in.)
Liquid, ODF (in.)
Hot Gas Bypass,
ODF (in.)
90
124
134
124A
124B
134A
134B
100
60
60
60
70
5088
5813
5435
6160
3630*
4063*
3630*
4063*
3630*
4063*
3877*
4294*
5630
6355
5990
6715
3907*
4340*
3907*
4340*
4080*
4497*
10
148
10
135
3907*
4340*
R-22
7
88
7
88
7
88
9
104
(6)A1 (6)A2
275 265
21
21
45
4
(6)A1 (6)A2
299 275
19
21
55
4
4...30
1.0
35,000
1140
6.4
6...30
1.0
52,000
1140
9.2
3...17
80.5
110
2...19
116.7
110
(6)A1 (4)A2
275 250
21
17
55
6
(6)B1
299
19
45
6...30
1.0
52,000
1140
9.4
3...17
128.3
89
89
1
1
Reciprocating Semi-Hermetic...1750
(6)A1 (4)A2 (6)B1 (6)B2 (6)A1 (6)A2 (6)A1 (6)A2
265 250 265 265 275 265 275 265
21
17
21
21
21
21
21
21
47
53
50
50
6
4
4
6...30
4...30
4...30
1.0
1.0
1.0
52,000
35,000
35,000
1140
1140
1140
9.5
6.4
6.4
Enhanced Copper Tubes, Lanced Aluminum Fins
3...17
3...17
3...17
128.3
80.5
80.5
89
89
110
110
218
78
2 1 8
7 8
2 5 8
1 1 8
258
118
258
118
2 5 8
1 1 8
58
58
58
58
58
58
LEGEND
Cu-Al Copper Tubes with Aluminum Fins
Cu-Cu Copper Tubes with Copper Fins
ODF
Outside Diameter, Female
*Includes piping and trim kit.
Compressors are shipped with minimum oil charge.
**Capacity control steps listed are for constant volume units with no accessories. Refer to Unloading Sequence table, page 61, for additional
system capacity information.
NOTES:
1. Unit 38AH124 consists of one 124A module and one 124B module.
Unit 38AH134 consists of one 134A module and one 134B module.
2. Certified dimensional drawings available on request.
3. Lead and lag circuits and compressors are as follows:
UNIT 38AH
094
104
LEAD CIRCUIT
Compressor, Lead
Compressor, Lag
A
A1
A2
A
A1
A2
LAG CIRCUIT
Compressor, Lead
Compressor, Lag
B
B1
*
B
B1
B2
124
Module
124A
A1
A2
Module
124B
A1
A2
134
Module
134A
A1
A2
Module
134B
A1
A2
35
Dimensions 38AH044-134
UNITS 38AH044-064 (SEE PAGE 38 FOR CORNER WEIGHTS)
DIMENSIONS (ft-in.)
UNIT
38AH
044
044C
054
054C
064
064C
3-2
3-318
3-212
3-3
3-212
3-3316
4-12
4-916
4-316
4-38
4-12
4-58
34
VOLTAGE
208/230
208/230
460
575
380
DIA
(in.)
358
212
212
212
212
QTY
1
2
1
1
1
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH044 3259 lb
38AH064 3565 lb
38AH044C 3547 lb
38AH064C 3998 lb
38AH054 3309 lb
38AH054C 3597 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
4. Two 29 dia holes are recommended for parallel
conductors on 38AH044, 054 208/230-V units.
36
SUCTION
CONNECTION(S)
LIQUID
CONNECTION(S)
SUCTION C
LIQUID D
SUCTION
(CKT A)
SUCTION
(CKT B)
LIQUID
(CKT A)
LIQUID
(CKT B)
2189 dia
2589 dia
9 dia
1189 dia
28- 9
18-101169
18-105169
18-105169
18-713169
28-589
78
11 16
28-589
28-5349
28-11189
28-10589
5. One 3589 dia hole is recommended for singleentry power on 38AH064 (208/230-V) unit.
6. Circled numerals in Top View refer to condenser
fans; refer to Wiring Diagrams.
7. If spring isolators are used, a perimeter support
channel between the unit and the isolators is
recommended.
8. Except for liquid and suction connections, dimensions for the optional single-circuit units are
the same as those for dual-circuit units.
9. Certified dimension drawings are available on
request.
3-318
3-358
3-3
3-31116
4-81316
4-818
4-9
4-8
VOLTAGE
208/230
208/230
460
460
575
380
DIA
(in.)
212
358
212
358
212
358
QTY
2
2
1
1
1
1
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit
is:
38AH074 3812 lb
38AH074C 4229 lb
38AH084 4057 lb
38AH084C 4735 lb
2. Unit must have clearances for airflow as
follows:
Top Do not restrict in any way
Ends 5 ft
Sides 6 ft
SUCTION
CONNECTION(S)
LIQUID
CONNECTION(S)
SUCTION C
LIQUID D
SUCTION
(CKT A)
SUCTION
(CKT B)
LIQUID
(CKT A)
LIQUID
(CKT B)
DUAL CKT
SINGLE CKT
2189 dia
2589 dia
9 dia
1189 dia
28-11169
18-101169
18-105169
18-105169
18-713169
28-589
78
28-589
28-5 9
28-11189
28-10589
34
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting
unit to spring isolators.
4. Circled numerals in Top View refer to condenser fans;
refer to Wiring Diagrams.
5. If spring isolators are used, a perimeter support
channel between the unit and the isolators is
recommended.
6. Except for liquid and suction connections, dimensions for optional single-circuit units are the same
as those for dual-circuit units.
7. Certified dimension drawings available on request.
37
TOTAL
WEIGHT
044
044C
054
054C
064
064C
074
074C
084
084C
3259
3547
3309
3597
3565
3998
3812
4229
4057
4735
38
UNIT 38AH094
UNIT
38AH
094
094C
DIMENSIONS
(ft-in.)
X
Y
5-6
2-7
5-6
2-7
OPERATIONAL CORNER
WEIGHTS (lb)
A
B
C
D
1114
2192
1182
601
1273
2504
1350
686
VOLTAGE
208/230
460,575,380
DIAMETER
(in.)
358
358
QUANTITY
2
1
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH094 5088 lb
38AH094C 5813 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
4. Two 3589 dia holes are recommended for parallel conductors on 208/230-v units.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data
section, Fans table, page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the unit and
the isolators is recommended.
39
UNIT
38AH
104
104C
DIMENSIONS
(ft-in.)
X
Y
5-3
2-912
5-3
2-912
OPERATIONAL CORNER
WEIGHTS (lb)
A
B
C
D
1240
2138
1302
755
1405
2423
1476
856
40
VOLTAGE
208/230
460,575,380
DIAMETER
(in.)
358
358
QUANTITY
2
1
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH104 5435 lb
38AH104C 6160 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended
for mounting unit to spring isolators.
4. Two 3589 dia holes are recommended for parallel conductors on 208/230-v units.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section,
Fans table, page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended.
UNIT 38AH124
UNIT
38AH
MODULE
124A
124B
124A-C
124B-C
DIMENSIONS
OPERATIONAL CORNER
(ft-in.)
WEIGHTS (lb)
X
Y
K
L
A
B
C
D
4-158 3-218
1037
1030
779
785
4-158 3-218
4-158 3-278
4-158 3-278
VOLTAGE
124A
124B
208/230
460, 575, 380
DIA
(in.)
358
212
QTY
1
1
LEGEND
C
Copper Fin Coils
MTG Mounting
SAE Society of Automotive
Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH124 7260 lb
38AH124C 8126 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators.
4. One 3589 dia hole is recommended for single entry power into each module (124A
and 124B) on 208/230-v units.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section,
Fans table, page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the assembled unit
and the isolators is required. Do not support each module separately.
7. Each module must be rigged into position separately. The unit must not be rigged
after modules have been connected.
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.
41
134B
4-878 3-318
134A-C
4-158 3-278
134B-C
4-818 3-334
OPERATIONAL CORNER
WEIGHTS (lb)
A
B
C
D
1037 1030 779
785
1167
997 789
924
1144 1137 889
894
1293 1080 874 1047
134B
VOLTAGE
208/230
460, 575, 380
208/230
460, 575
380
DIA (in.)
358
212
212
212
358
QTY
1
1
2
1
1
LEGEND
C
Copper Fin Coils
MTG Mounting
of Automotive
SAE Society
Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH134 7507 lb
38AH134C 8357 lb
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends 5 ft
Sides 6 ft
3. Mounting holes may be used to mount unit to concrete pad. They
are not recommended for mounting unit to spring isolators.
42
4. One 3589 dia hole is recommended for single entry power into each module 134A on 208/230-v units.
Single entry power into Module 134B is not recommended.
5. Circled numerals in Top View refer to condenser fans; refer to Electrical Data section, Fans table,
page 54 and Wiring Diagram book.
6. If spring isolators are used, a perimeter support channel between the assembled unit and the isolators
is required. Do not support each module separately.
7. Each module must be rigged into position separately. The unit must not be rigged after modules have
been connected.
8. Suction and liquid connections can exit on either side of the unit.
9. Field power supply connections are required for each module.
43
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
38AH074
85
305.0
30.2
107.0
348.0
31.8
108.0
392.0
33.5
109.0
439.0
35.0
110.0
488.0
36.5
112.0
540.0
37.9
114.0
596.0
39.3
116.0
85
357.0
36.4
111.0
407.0
38.4
111.0
458.0
40.4
113.0
512.0
42.4
115.0
568.0
44.5
116.0
627.0
46.5
119.0
688.0
48.6
121.0
85
439.0
44.3
109.0
496.0
46.7
111.0
555.0
49.1
112.0
616.0
51.6
114.0
682.0
54.1
116.0
749.0
56.6
118.0
822.0
59.2
120.0
SST (F)
115
212.0
32.6
136.0
250.0
35.3
137.0
291.0
38.1
138.0
332.0
40.6
139.0
376.0
43.1
140.0
422.0
45.6
142.0
469.0
48.0
143.0
20
25
30
35
40
45
50
38AH054
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
20
25
30
35
40
45
50
44
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
115
430.0
61.0
137.0
489.0
65.4
138.0
548.0
69.7
139.0
611.0
74.2
141.0
677.0
78.3
143.0
745.0
83.5
145.0
817.0
88.2
147.0
115
494.0
72.0
142.0
560.0
76.8
142.0
629.0
81.8
143.0
703.0
86.8
144.0
780.0
92.0
145.0
860.0
97.4
147.0
944.0
102.9
149.0
38AH084
SST (F)
115
261.0
39.5
141.0
303.0
42.7
141.0
347.0
45.8
142.0
395.0
48.9
143.0
444.0
51.9
144.0
496.0
55.0
146.0
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
622.0
65.5
112.0
698.0
69.1
113.0
780.0
72.7
114.0
865.0
76.3
115.0
954.0
80.1
117.0
1047.0
84.1
119.0
1144.0
88.3
122.0
LEGEND
38AH064
SST (F)
85
549.0
55.6
108.0
614.0
58.6
110.0
683.0
61.9
111.0
754.0
65.0
113.0
829.0
68.3
115.0
910.0
71.7
118.0
994.0
75.1
120.0
115
331.0
48.7
139.0
380.0
52.2
139.0
431.0
55.9
141.0
485.0
59.5
142.0
541.0
63.1
144.0
600.0
66.9
146.0
662.0
70.6
148.0
kW
SDT
SST
TC
1095
Compressor Power
Saturated Discharge Temperature (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)
38AH104
SST (F)
20
25
30
35
40
45
50
kW
SCT
SCT(A)
SCT(B)
SDT
SDT(A)
SDT(B)
SST
TC
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
85
700
71.1
110
108
108
106
785
75.1
112
109
109
106
873
79.4
114
110
111
107
965
83.7
116
112
112
109
1062
88.1
119
114
114
110
1163
92.6
122
117
116
112
1269
97.3
125
119
118
114
115
535
77.3
139
137
138
136
612
83.1
140
138
139
137
691
88.9
141
139
140
137
772
94.9
143
140
141
138
857
100.9
145
142
143
140
946
107.1
148
144
145
141
1038
113.5
150
146
147
143
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
85
782
77.4
108
110
106
107
877
82.1
110
112
107
109
977
86.9
112
114
109
111
1082
91.7
114
117
110
112
1192
96.8
117
120
112
114
1308
101.9
119
123
114
117
1429
107.3
122
126
116
119
115
592
85.6
137
138
136
137
676
92.1
137
139
136
138
762
96.5
139
141
137
140
853
105.1
141
143
139
141
948
111.9
143
146
141
143
1047
118.9
145
148
143
145
1151
125.9
148
151
145
148
LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Condensing Temperature for Circuit A
Saturated Condensing Temperature for Circuit B
Saturated Discharge Temperature (F)
Saturated Discharge Temperature for Circuit A
Saturated Discharge Temperature for Circuit B
Saturated Suction Temperature Entering Condensing Unit (F)
Gross Cooling Capacity (1000 Btuh)
45
38AH134
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
(A) or (B)
Condenser Entering-Air
85
90
95
100
884
848
810
774
88.6
90.6
92.4
94.0
109
114
119
124
108
113
118
123
996
958
918
880
93.4
95.8
98.0
99.8
110
115
120
125
109
114
119
124
1114
1072 1030
990
98.2 101.0 103.6 106.0
112
117
121
126
110
115
120
125
1236 1192
1148
1104
103.2 106.4 109.4 112.0
114
118
123
128
112
117
121
126
1366 1320 1272 1226
108.4 111.8 115.2 118.2
116
120
125
130
114
118
123
128
1502 1452 1402 1352
113.6 117.4 121.0 124.6
118
123
127
132
116
120
125
130
1644 1590 1536 1484
118.8 123.0 127.0 131.0
121
125
130
134
118
122
127
132
Temperature (F)
105
110
115
738
702
668
95.2
96.4
97.4
129
134
138
128
133
138
842
804
766
101.6 103.2 104.4
130
134
139
129
134
139
948
908
868
108.0 110.0 111.6
131
136
140
130
135
139
1062 1018
974
114.6 116.8 119.0
132
137
142
131
136
141
1180
1132 1086
121.2 123.8 126.2
134
139
143
133
137
142
1302 1252 1204
127.8 131.0 133.8
136
141
145
135
139
144
1432 1380 1326
134.6 138.2 141.4
139
143
148
137
141
146
LEGEND
kW
Compressor Power
SCT
Saturated Condensing Temperature (F)
SCT(A) Saturated Condensing Temperature for Module 38AH124A
134A (F)
SCT(B) Saturated Condensing Temperature for Module 38AH124B
134B (F)
SDT
Saturated Discharge Temperature (F)
SDT(A) Saturated Discharge Temperature for Module 38AH124A
134A (F)
SDT(B) Saturated Discharge Temperature for Module 38AH124B
134B (F)
SST
Saturated Suction Temperature Entering Condensing Unit (F)
TC
Gross Cooling Capacity (1000 Btuh)
or
20
25
30
35
40
45
or
or
or
NOTE: Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of Modules 134A and 134B. Each module is one refrigeration circuit.
46
SST (F)
50
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
TC
kW
SDT(A)
SDT(B)
SCT(A)
SCT(B)
85
992
99.8
109
108
108
104
1113
105.3
110
109
109
106
1240
110.9
112
111
110
107
1373
116.6
114
113
112
109
1514
122.5
116
115
114
110
1662
128.4
118
117
116
113
1817
134.4
121
120
118
115
115
765
109.7
138
137
138
134
872
117.5
139
138
139
134
983
125.5
140
139
139
136
1099
133.7
142
141
141
137
1220
141.8
142
142
142
139
1348
150.3
145
145
144
141
1481
158.9
148
147
146
142
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
153.0
15.0
105.0
174.0
15.8
107.0
195.0
16.7
108.0
218.0
17.5
110.0
241.0
18.3
112.0
266.0
19.1
114.0
293.0
19.9
117.0
38AH044 CIRCUIT B
Air Temperature
90
95
146.0
138.0
15.4
15.7
110.0
115.0
166.0
158.0
16.3
16.7
111.0
116.0
187.0
179.0
17.2
17.6
113.0
117.0
209.0
201.0
18.0
18.6
115.0
119.0
233.0
224.0
18.9
19.5
117.0
121.0
257.0
248.0
19.8
20.5
119.0
123.0
283.0
273.0
20.6
21.4
121.0
126.0
Entering
100
130.0
15.9
120.0
150.0
17.0
121.0
171.0
18.0
122.0
192.0
19.1
124.0
215.0
20.1
126.0
238.0
21.1
128.0
263.0
22.1
130.0
Condenser (F)
105
110
123.0
115.0
16.1
16.2
124.0
129.0
142.0
134.0
17.3
17.5
125.0
130.0
162.0
154.0
18.4
18.7
127.0
131.0
183.0
175.0
19.5
19.9
128.0
133.0
205.0
196.0
20.6
21.1
130.0
135.0
228.0
219.0
21.7
22.3
132.0
137.0
252.0
242.0
22.8
23.4
135.0
139.0
Air Temperature
90
95
145.0
137.0
15.7
16.0
115.0
120.0
167.0
159.0
16.6
17.0
115.0
120.0
190.0
182.0
17.4
17.9
116.0
121.0
215.0
206.0
18.2
18.8
116.0
121.0
240.0
231.0
19.0
19.6
118.0
122.0
266.0
256.0
19.8
20.5
119.0
124.0
293.0
283.0
20.6
21.4
121.0
126.0
Entering
100
129.0
16.1
125.0
150.0
17.3
125.0
173.0
18.3
125.0
197.0
19.3
126.0
221.0
20.2
127.0
246.0
21.2
128.0
273.0
22.1
130.0
Condenser (F)
105
110
121.0
113.0
16.2
16.3
130.0
135.0
142.0
134.0
17.5
17.6
130.0
135.0
164.0
155.0
18.6
18.9
130.0
135.0
188.0
178.0
19.7
20.1
131.0
136.0
212.0
202.0
20.8
21.3
132.0
137.0
237.0
227.0
21.8
22.4
133.0
138.0
262.0
252.0
22.8
23.5
135.0
139.0
Air Temperature
90
95
198.0
190.0
21.3
21.7
114.0
119.0
224.0
215.0
22.5
23.0
115.0
120.0
252.0
242.0
23.8
24.4
117.0
122.0
281.0
270.0
25.1
25.8
119.0
123.0
311.0
299.0
26.4
27.2
121.0
126.0
343.0
330.0
27.8
28.6
123.0
128.0
376.0
363.0
29.1
30.1
126.0
130.0
Entering
100
181.0
22.2
124.0
206.0
23.5
125.0
232.0
25.0
126.0
259.0
26.4
128.0
288.0
27.9
130.0
318.0
29.5
132.0
350.0
31.0
135.0
Condenser (F)
105
110
173.0
165.0
22.5
22.9
129.0
134.0
197.0
188.0
24.0
24.4
130.0
135.0
222.0
212.0
25.5
26.0
131.0
136.0
249.0
238.0
27.0
27.6
133.0
137.0
277.0
265.0
28.6
29.3
135.0
139.0
306.0
294.0
30.2
31.0
137.0
141.0
337.0
324.0
31.9
32.7
139.0
144.0
115
107.0
16.3
134.0
126.0
17.6
135.0
146.0
19.0
136.0
166.0
20.2
138.0
187.0
21.5
139.0
209.0
22.8
141.0
232.0
24.0
143.0
38AH054 CIRCUIT A
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
152.0
15.4
110.0
175.0
16.2
110.0
199.0
16.9
111.0
223.0
17.6
112.0
249.0
18.4
113.0
275.0
19.1
115.0
303.0
19.8
117.0
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
207.0
20.8
109.0
234.0
21.9
111.0
262.0
23.1
112.0
291.0
24.3
114.0
323.0
25.6
116.0
355.0
26.8
119.0
390.0
28.1
121.0
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TG
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
85
152.0
15.2
108.0
174.0
16.0
109.0
197.0
16.8
109.0
221.0
17.5
110.0
247.0
18.2
112.0
274.0
18.8
113.0
303.0
19.4
115.0
Air Temperature
90
95
144.0
136.0
15.6
15.9
113.0
118.0
166.0
158.0
16.4
16.8
113.0
118.0
188.0
180.0
17.3
17.8
114.0
119.0
212.0
203.0
18.1
18.6
115.0
120.0
237.0
228.0
18.9
19.5
116.0
121.0
264.0
254.0
19.6
20.3
118.0
123.0
292.0
281.0
20.3
21.1
119.0
124.0
Entering
100
128.0
16.1
123.0
149.0
17.1
123.0
171.0
18.2
124.0
194.0
19.2
125.0
218.0
20.1
126.0
244.0
21.0
127.0
270.0
21.9
129.0
Condenser (F)
105
110
121.0
113.0
16.2
16.3
128.0
133.0
141.0
133.0
17.4
17.6
128.0
133.0
162.0
154.0
18.5
18.8
129.0
134.0
185.0
176.0
19.6
20.0
130.0
135.0
209.0
199.0
20.7
21.2
131.0
136.0
233.0
223.0
21.7
22.3
132.0
137.0
259.0
248.0
22.7
23.4
134.0
139.0
115
105.0
16.3
138.0
124.0
17.7
138.0
145.0
19.1
139.0
166.0
20.4
139.0
189.0
21.6
140.0
213.0
22.8
142.0
237.0
24.0
143.0
Air Temperature
90
95
197.0
188.0
21.5
22.0
117.0
122.0
222.0
213.0
22.8
23.3
118.0
123.0
249.0
240.0
24.1
24.7
120.0
124.0
278.0
267.0
25.5
26.2
121.0
126.0
308.0
296.0
26.9
27.6
124.0
128.0
339.0
327.0
28.3
29.1
126.0
130.0
372.0
359.0
29.7
30.7
129.0
133.0
Entering
100
180.0
22.4
126.0
204.0
23.8
128.0
230.0
25.3
129.0
257.0
26.8
131.0
285.0
28.3
133.0
315.0
29.9
135.0
346.0
31.5
137.0
Condenser (F)
105
110
172.0
164.0
22.7
22.3
131.0
136.0
195.0
186.0
24.2
24.6
132.0
137.0
220.0
211.0
25.8
26.3
134.0
138.0
246.0
236.0
27.4
27.9
135.0
140.0
274.0
263.0
29.0
29.6
137.0
142.0
303.0
291.0
30.7
31.4
140.0
144.0
333.0
321.0
32.4
33.2
142.0
146.0
115
156.0
23.3
141.0
178.0
25.0
142.0
201.0
26.7
143.0
226.0
28.5
145.0
252.0
30.2
147.0
279.0
32.1
149.0
Air Temperature
90
95
223.0
213.0
24.0
24.4
114.0
119.0
252.0
242.0
25.4
25.9
115.0
120.0
282.0
272.0
26.7
27.4
116.0
121.0
314.0
303.0
28.1
28.9
118.0
122.0
347.0
335.0
29.5
30.3
120.0
124.0
382.0
369.0
30.8
31.8
122.0
126.0
418.0
405.0
32.2
33.4
124.0
129.0
Entering
100
203.0
24.8
124.0
231.0
26.4
124.0
261.0
28.0
126.0
291.0
29.6
127.0
323.0
31.2
129.0
356.0
32.8
131.0
391.0
34.4
133.0
Condenser (F)
105
110
194.0
184.0
25.1
25.3
128.0
133.0
221.0
211.0
26.8
27.2
129.0
134.0
250.0
239.0
28.5
29.0
130.0
135.0
280.0
268.0
30.2
30.8
132.0
137.0
311.0
299.0
31.9
32.6
134.0
138.0
344.0
331.0
33.6
34.4
135.0
140.0
378.0
364.0
35.4
36.3
138.0
142.0
115
174.0
25.5
138.0
201.0
27.4
139.0
228.0
29.4
140.0
257.0
31.3
141.0
287.0
33.2
143.0
318.0
35.2
145.0
351.0
37.1
147.0
38AH054 CIRCUIT B
115
105.0
16.2
140.0
125.0
17.7
140.0
146.0
19.1
140.0
169.0
20.4
141.0
192.0
21.7
141.0
217.0
22.9
142.0
38AH064 CIRCUIT A
SST (F)
SST (F)
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
STD
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
85
205.0
21.0
112.0
232.0
22.2
113.0
259.0
23.5
115.0
289.0
24.8
117.0
319.0
26.1
119.0
352.0
27.4
122.0
385.0
28.8
124.0
38AH064 CIRCUIT B
115
157.0
23.2
139.0
179.0
24.8
139.0
203.0
26.5
141.0
228.0
28.2
142.0
254.0
29.9
144.0
282.0
31.7
146.0
311.0
33.5
148.0
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
STD
TC
kW
STD
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
232.0
23.5
109.0
262.0
24.8
110.0
293.0
26.0
111.0
325.0
27.3
113.0
359.0
28.5
115.0
394.0
29.8
117.0
432.0
31.1
119.0
47
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
85
236.0
23.4
108.0
265.0
24.6
109.0
296.0
25.9
110.0
328.0
27.1
112.0
361.0
28.4
114.0
397.0
29.7
117.0
434.0
31.0
119.0
38AH074 CIRCUIT B
Air Temperature
90
95
227.0
217.0
23.9
24.3
113.0
118.0
256.0
246.0
25.2
25.8
114.0
118.0
286.0
275.0
26.6
27.2
115.0
120.0
317.0
306.0
28.0
28.7
117.0
121.0
350.0
338.0
29.3
30.2
119.0
123.0
385.0
372.0
30.7
31.7
121.0
126.0
421.0
408.0
32.1
33.2
123.0
128.0
Entering
100
208.0
24.7
122.0
236.0
26.3
123.0
265.0
27.8
124.0
295.0
29.4
126.0
327.0
31.0
128.0
360.0
32.6
130.0
395.0
34.2
132.0
Condenser (F)
105
110
198.0
188.0
25.0
25.3
127.0
132.0
226.0
216.0
26.7
27.1
128.0
133.0
255.0
244.0
28.4
28.8
129.0
134.0
284.0
273.0
30.1
30.6
131.0
135.0
315.0
303.0
31.7
32.4
132.0
137.0
348.0
335.0
33.5
34.2
135.0
139.0
382.0
368.0
35.2
36.1
137.0
141.0
Air Temperature
90
95
299.0
288.0
33.5
34.1
118.0
123.0
336.0
325.0
35.4
36.1
118.0
123.0
376.0
364.0
37.3
38.2
119.0
124.0
418.0
405.0
39.3
40.3
120.0
125.0
462.0
448.0
41.3
42.4
122.0
127.0
508.0
492.0
43.5
44.6
124.0
128.0
556.0
539.0
45.7
47.0
126.0
131.0
Entering
100
277.0
34.7
128.0
313.0
36.8
128.0
351.0
39.0
129.0
391.0
41.2
130.0
433.0
43.4
131.0
477.0
45.8
133.0
522.0
48.2
135.0
Condenser (F)
105
110
267.0
256.0
35.2
35.7
133.0
138.0
301.0
290.0
37.4
38.0
133.0
138.0
339.0
326.0
39.7
40.4
134.0
139.0
378.0
364.0
42.0
42.8
135.0
140.0
419.0
404.0
44.4
45.3
136.0
141.0
461.0
446.0
46.8
47.8
138.0
142.0
506.0
489.0
49.4
50.5
140.0
144.0
115
178.0
25.5
137.0
206.0
27.4
138.0
233.0
29.2
138.0
262.0
31.1
140.0
292.0
33.1
142.0
323.0
35.0
144.0
355.0
36.9
146.0
38AH084 CIRCUIT A
SST (F)
20
25
30
35
40
45
50
kW
SDT
SST
TC
48
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
310.0
32.9
113.0
348.0
34.7
114.0
389.0
36.5
114.0
432.0
38.3
115.0
477.0
40.2
117.0
524.0
42.2
119.0
573.0
44.3
122.0
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
85
313.0
32.2
108.0
349.0
34.0
110.0
387.0
36.0
112.0
426.0
37.9
114.0
468.0
39.9
116.0
513.0
42.0
118.0
560.0
44.1
121.0
Air Temperature
90
95
303.0
293.0
32.8
33.5
113.0
118.0
338.0
326.0
34.8
35.5
114.0
119.0
374.0
362.0
36.8
37.7
116.0
121.0
413.0
400.0
38.9
39.9
118.0
123.0
454.0
440.0
41.1
42.1
121.0
125.0
498.0
482.0
43.2
44.4
123.0
127.0
543.0
527.0
45.5
46.8
125.0
130.0
Entering
100
282.0
34.0
122.0
315.0
36.2
124.0
350.0
38.4
126.0
387.0
40.7
128.0
426.0
43.1
130.0
467.0
45.5
132.0
510.0
48.0
134.0
Condenser (F)
105
110
272.0
262.0
34.6
35.1
127.0
132.0
304.0
294.0
36.8
37.4
129.0
133.0
338.0
327.0
39.2
39.8
130.0
135.0
374.0
361.0
41.6
42.3
132.0
137.0
412.0
398.0
44.0
44.9
134.0
139.0
452.0
437.0
46.6
47.5
137.0
141.0
494.0
478.0
49.1
50.3
139.0
143.0
115
252.0
35.5
137.0
283.0
38.0
138.0
315.0
40.5
140.0
349.0
43.1
141.0
385.0
45.7
143.0
422.0
48.5
146.0
462.0
51.3
148.0
Air Temperature
90
95
301.0
290.0
33.3
33.9
116.0
121.0
338.0
327.0
35.1
35.9
117.0
122.0
378.0
365.0
37.1
37.9
118.0
122.0
419.0
406.0
39.0
40.0
119.0
124.0
462.0
448.0
41.1
42.1
121.0
125.0
507.0
492.0
43.2
44.4
123.0
127.0
555.0
538.0
45.4
46.7
125.0
130.0
Entering
100
279.0
34.5
126.0
315.0
36.6
127.0
353.0
38.7
127.0
392.0
40.9
128.0
433.0
43.2
130.0
476.0
45.5
132.0
522.0
47.9
134.0
Condenser (F)
105
110
269.0
258.0
35.0
35.5
131.0
136.0
303.0
292.0
37.2
27.8
131.0
137.0
340.0
328.0
39.4
40.1
132.0
137.0
379.0
365.0
41.7
42.5
133.0
138.0
419.0
405.0
44.1
45.0
135.0
139.0
461.0
446.0
46.6
47.6
137.0
141.0
505.0
488.0
49.1
50.2
139.0
143.0
115
248.0
35.9
141.0
281.0
38.3
141.0
315.0
40.8
142.0
352.0
43.3
143.0
390.0
45.9
144.0
430.0
48.6
146.0
472.0
51.3
148.0
38AH084 CIRCUIT B
LEGEND
Compressor Power
Saturated Temperature Leaving Compressor (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)
115
246.0
36.1
143.0
279.0
38.5
143.0
314.0
41.0
144.0
351.0
43.5
145.0
390.0
46.1
146.0
430.0
48.8
147.0
472.0
51.6
149.0
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
SDT
TC
kW
STD
TC
kW
SDT
TC
kW
SDT
85
312.0
32.6
111.0
350.0
34.4
112.0
391.0
36.2
113.0
433.0
38.0
114.0
477.0
39.9
116.0
523.0
41.9
118.0
571.0
44.0
121.0
20
25
30
35
40
45
50
85
385
39.0
110
108
433
41.3
112
109
482
43.7
114
111
533
46.1
116
112
587
48.6
119
114
643
51.1
122
116
702
53.7
125
118
38AH094 CIRCUIT B
Air Temperature
90
95
368
352
39.8
40.4
115
119
113
118
416
398
42.2
43.1
116
121
114
119
464
446
44.8
45.7
118
123
115
120
515
496
47.3
48.5
121
125
117
122
568
548
50.0
51.3
123
128
119
124
623
602
52.6
54.1
126
130
121
126
680
658
55.4
57.0
129
133
123
128
Entering
100
335
40.9
124
123
381
43.8
126
124
428
46.6
127
125
477
49.5
130
127
528
52.5
132
129
581
55.5
135
131
636
58.6
138
133
Condenser (F)
105
110
318
300
41.4
41.6
129
134
128
133
363
346
44.4
44.9
130
135
129
134
410
392
47.4
48.1
132
136
130
135
458
439
50.5
51.3
134
138
132
136
508
487
53.6
54.6
136
141
133
138
559
538
56.8
58.0
139
143
136
140
613
591
60.0
61.4
142
146
138
142
Air Temperature
90
95
349
334
36.6
37.4
113
117
111
116
394
378
38.9
39.8
114
119
112
117
441
423
41.1
42.2
116
121
113
118
490
471
43.5
44.6
118
123
115
120
541
521
45.8
47.2
121
125
117
122
595
574
48.3
49.7
124
128
119
124
651
629
50.8
52.4
126
131
121
126
Entering
100
318
38.0
122
121
361
40.5
123
122
406
43.1
125
123
453
45.7
127
125
502
48.4
130
127
553
51.1
132
128
607
53.9
135
131
Condenser (F)
105
110
302
287
38.6
39.0
127
132
126
131
345
329
41.2
41.9
128
133
127
131
389
372
44.0
44.7
130
134
128
133
435
416
46.7
47.6
132
136
129
134
482
463
49.5
50.6
134
138
131
136
532
512
52.4
53.6
136
141
133
138
585
563
55.3
56.7
139
143
135
140
115
283
41.7
139
138
328
45.2
140
139
373
48.6
141
140
419
52.0
143
141
467
55.5
145
143
517
59.0
148
145
568
62.6
150
147
38AH104 CIRCUIT A
SST (F)
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
20
25
30
35
40
45
50
kW
SDT
SST
TC
85
365
35.8
108
106
411
37.9
110
107
458
40.1
112
109
508
42.2
114
110
561
44.5
117
112
616
46.7
119
114
673
49.1
122
116
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
85
315
32.1
108
106
352
33.8
109
106
391
35.7
110
107
432
37.6
112
109
475
39.5
114
110
520
41.5
117
112
567
43.6
119
114
Air Temperature
90
95
304
294
32.8
33.4
112
117
111
116
341
329
34.6
35.4
113
118
111
116
379
366
36.6
37.4
115
120
112
117
419
405
38.6
39.5
117
121
114
119
460
446
40.6
41.7
119
123
115
120
504
489
42.8
43.9
121
126
117
122
551
534
44.9
46.2
124
128
119
124
Entering
100
283
34.0
122
121
318
36.1
123
121
354
38.2
124
122
392
40.4
126
124
432
42.7
128
125
474
45.1
130
127
518
47.5
133
129
Condenser (F)
105
110
273
262
34.6
35.1
127
132
126
131
307
295
36.7
37.4
128
133
126
132
342
330
39.0
39.7
129
134
127
132
379
366
41.3
42.1
131
135
128
133
418
404
43.7
44.6
133
137
130
135
459
444
46.1
47.2
135
139
132
136
502
486
48.7
49.8
137
142
133
138
115
252
35.6
137
136
284
37.9
138
137
318
40.3
139
137
353
42.9
140
138
390
45.4
142
140
429
48.1
144
141
470
50.9
146
143
Air Temperature
90
95
400
384
42.6
43.5
115
119
112
117
449
431
45.3
46.3
116
121
114
119
500
481
48.0
49.2
119
123
115
120
553
533
50.9
52.2
121
126
117
122
610
588
53.8
55.3
124
128
119
124
669
646
56.9
58.5
127
131
122
126
731
706
60.0
61.7
130
134
124
129
Entering
100
368
44.3
124
122
414
47.2
126
124
463
50.3
128
125
514
53.4
130
127
567
56.6
133
129
623
60.0
135
131
682
63.4
138
133
Condenser (F)
105
110
352
337
45.0
45.7
129
133
127
132
397
380
48.1
48.9
130
135
128
133
444
426
51.3
52.2
132
137
130
135
494
475
54.6
55.6
134
139
132
137
546
525
57.9
59.1
137
141
134
139
600
578
61.4
62.8
140
144
136
141
658
634
65.0
66.5
143
147
138
143
115
321
46.3
138
137
364
49.7
139
138
408
53.1
141
140
455
56.6
143
141
504
60.3
146
143
556
64.1
148
145
610
67.9
151
148
38AH104 CIRCUIT B
115
271
39.3
137
136
312
42.4
137
136
354
45.4
139
137
398
48.5
141
139
444
51.6
143
141
491
54.8
145
143
541
58.0
148
145
SST (F)
20
25
30
35
40
45
50
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
TC
kW
SDT
SCT
85
417
41.6
110
107
466
44.2
112
109
519
46.8
114
111
574
49.5
117
112
631
52.3
120
114
692
55.2
123
117
756
58.2
126
119
LEGEND
Compressor Power
Saturated Temperature Leaving Compressor (F)
Saturated Temperature Entering Compressor (F)
Gross Cooling Capacity (1000 Btuh)
49
kW
SCT
SDT
SST
TC
115
334
48.7
138
138
383
52.2
139
139
434
55.8
140
139
487
59.5
142
141
543
63.1
143
142
602
66.9
145
144
663
70.7
148
146
LEGEND
Compressor Power
Saturated Condensing Temperature (F)
Saturated Discharge Temperature (F)
Saturated Suction Temperature Entering Condensing Unit (F)
Gross Cooling Capacity (1000 Btuh)
NOTE: Unit 38AH124 consists of Modules 124A and 124B. Unit 38AH134 consists of Modules 134A and 134B. Each module is one circuit.
50
Entering
100
491
58.7
122
119
552
62.4
123
120
616
66.2
125
122
683
70.1
127
123
754
74.0
129
125
828
78.0
131
127
907
82.1
133
129
Condenser (F)
105
110
471
451
59.6
60.4
127
132
124
129
531
510
63.5
64.4
128
133
125
130
594
571
67.5
68.6
130
134
126
131
659
636
71.6
72.9
131
136
128
133
728
703
75.7
77.3
133
138
130
134
801
773
79.9
81.7
136
140
131
136
877
847
84.2
86.3
138
142
133
138
115
431
61.0
137
134
489
65.3
138
134
549
69.7
139
136
612
74.2
141
137
677
78.7
142
139
746
83.4
145
141
818
88.2
147
142
LEGEND
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Line Voltage
Piping
Double Riser Piping
(If Required)
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific
installation. Face-split connection shown; row-split connection also possible.
4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the compressor.
51
LEGEND
NEC National Electrical Code
TXV Thermostatic Expansion Valve
Line Voltage
Piping
*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for, or to include all details for, a specific
installation. Face-split connection shown; row-split connection also possible.
4. Liquid line solenoid valve (solenoid drop control) is required to minimize refrigerant migration to the compressor.
52
VOLTAGE
DESIGNATION
COMPRESSOR
MODEL (A/B)
500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200
044
054
064
074
084
SUPPLY VOLTAGE*
NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
06E-250/250
06E-250/265
06E-265/275
06E-275/299
06E-299/299
POWER SUPPLY
COMPRESSOR
Min
Max
MCA
MOCP
ICF
187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342
254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418
174.6
88.9
78.4
93.5
201.8
100.1
88.0
107.1
244.0
113.1
100.6
126.9
322.3
145.0
132.2
174.5
363.3
163.6
148.9
200.7
225
110
90
125
250
125
125
150
350
150
125
175
450
200
175
250
500
225
200
250
434.7
218.6
162.4
241.2
535.7
268.6
206.4
297.2
617.5
307.6
226.1
341.1
829.0
408.2
336.8
458.0
870.0
426.8
353.5
484.2
A
RLA
67.9
34.6
28.8
34.6
67.9
34.5
28.8
34.6
89.7
43.6
36.5
45.5
106.4
46.8
40.4
52.6
147.4
65.4
57.1
78.8
B
LRA
345
173
120
191
345
173
120
191
446
223
164
247
506
253
176
280
690
345
276
382
RLA
67.9
34.6
28.8
34.6
89.7
43.6
36.5
45.5
106.4
46.8
40.4
52.6
147.4
65.4
57.1
78.8
147.4
65.4
57.1
78.8
LRA
345
173
120
191
446
223
164
247
506
253
176
280
690
345
276
382
690
345
276
382
VOLTAGE
DESIGNATION
094
104
500
600
100
200
500
600
100
200
COMPRESSOR
A1/A2/B1/B2
MODEL NO.
06E-275/
250/299/-
06E-265/250/
265/265
NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
SUPPLY
VOLTAGE*
Min
187
414
518
342
187
414
518
342
Max
254
508
632
418
254
508
632
418
POWER SUPPLY
MCA
MOCP
ICF
391.3
179.5
160.9
209.1
392.2
192.7
168.0
205.9
500
225
200
250
450
225
200
250
754.2
369.4
282.3
416.8
725.9
361.2
286.2
396.0
COMPRESSOR
A2
B1
RLA LRA
RLA
LRA
67.9
345
147.7
690
34.6
173
65.4
345
28.8
120
57.1
276
34.6
191
78.8
382
67.9
345
89.7
446
34.6
173
43.6
223
28.8
120
36.5
164
34.6
191
45.5
247
A1
RLA
106.4
46.8
40.4
52.6
89.7
43.6
36.5
45.5
LRA
506
253
176
280
446
223
164
247
B2
RLA
89.7
43.6
36.5
45.5
LRA
446
223
164
247
134B
VOLTAGE
DESIGNATION
500
600
100
200
500
600
100
200
COMPRESSOR
A1/A2
MODEL NO.
06E-275/
265
06E-299/
275
NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
SUPPLY
VOLTAGE*
Min
187
414
518
342
187
414
518
342
Max
254
508
632
418
254
508
632
418
POWER SUPPLY**
MCA
MOCP
ICF
244.0
113.1
100.6
126.9
322.3
145.0
132.2
174.5
350
150
125
175
450
200
175
250
573.8
280.8
218.0
315.2
685.6
334.8
253.5
382.2
COMPRESSOR
A1
RLA
106.4
46.8
40.4
52.6
147.4
65.4
57.1
78.8
A2
LRA
506
253
176
280
690
345
276
382
RLA
89.7
43.6
36.5
45.5
106.4
46.8
40.4
52.6
LRA
446
223
164
247
506
253
176
280
53
VOLTAGE
DESIGNATION
500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200
500
600
100
200
044
054
064
074
084
COMPRESSOR
MODEL
(A1/A2)
06E-250/250
06E-265/250
06E-275/265
06E-299/275
06E-299/299
NAMEPLATE
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
SUPPLY VOLTAGE*
Min
Max
MCA
MOCP
ICF
187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342
187
414
518
342
254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418
254
508
632
418
174.6
88.9
78.4
93.5
201.8
100.1
88.0
107.1
244.0
113.1
100.6
126.9
322.3
145.0
132.2
174.5
363.3
163.6
148.9
200.7
225
110
90
125
250
125
125
150
350
150
125
175
450
200
175
250
500
225
200
250
434.7
218.6
162.4
241.2
456.5
227.6
170.1
252.1
573.8
280.8
218.0
315.2
685.6
334.8
253.5
382.2
870.0
426.8
353.5
484.2
FANS
UNIT
38AH
044
054
064
074
084
094
104
Modules 124A,
124B,134A
Module 134B
54
Nameplate
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
208/230-3-60
460-3-60
575-3-60
380-3-60
POWER SUPPLY
COMPRESSOR
A1
A2
RLA
LRA
RLA
67.9
345
67.9
34.6
173
34.6
28.8
120
28.8
34.6
191
34.6
89.7
446
67.9
43.6
223
34.6
36.5
164
28.8
45.5
247
34.6
106.4
506
89.7
46.8
253
43.6
40.4
176
36.5
52.6
280
45.5
147.4
690
106.4
65.4
345
46.8
57.1
276
40.4
78.8
382
52.6
147.4
690
147.4
65.4
345
65.4
57.1
276
57.1
78.8
382
78.8
LRA
345
173
120
191
345
173
120
191
446
223
164
247
506
253
176
280
690
345
276
382
CONTROL CIRCUIT
38AH
044-134
500
600
100
200
UNIT POWER
V-Ph-Hz
208/230-3-60
460-3-60
575-3-60
380-3-60
CONTROL POWER
V-Ph-Hz
Min
Max
115-1-60
103
127
115-1-60
103
127
115-1-60
103
127
230-1-60
207
253
AMPS
4.1
4.1
4.1
2.0
*Units are suitable for use on electrical systems where voltage supplied to unit
terminals is within listed minimum to maximum limits.
All compressors are across-the-line start only.
**38AH124 and 134 units require a separate power supply for each unit module.
AWG
CSA
FLA
ICF
IFC
kcmil
LLS
LRA
MCA
MOCP
PW
RLA
UL
NOTES:
1. Maximum allowable phase imbalance:
Voltage 2%
Amps 10%
2. Maximum incoming wire size for terminal block is 500 kcmil.
3. Wiring for field power supply must be rated 75 C minimum. Use copper, copperclad aluminum, or aluminum conductors. Maximum incoming wire size for each
terminal block is 500 kcmil.
4. Terminal blocks TB3 and TB4 are for external field control connections. Control connections are to be class 1 wiring.
VA
(Each Stage)
AMPS
VAC
044-084
300
094
275
104
325
124
134
300
300
2.5
1.3
2.29
1.15
2.70
1.35
2.50
2.50
120
240
120
240
120
240
120
120
38AH
LENGTH
(ft)
Up to 50
50-75
More Than 75
55
Controls 38AH044-084
Sequence of operation
Circuits A1 and B1 are controlled by independent circuitry.
It is therefore possible to maintain partial cooling capability
even if one compressor is inoperable.
NOTE: Single-circuit units do not have independent control circuitry.
On a call for cooling, the first-stage cooling thermostat
TC1 closes, energizing the first stage of the condenser fans
and timer motor TM-A (TM for single-circuit units). After
12 seconds, the timer energizes lead compressor contactor
C-A1 and the lead compressor starts. (Circuit A compressor is the lead on dual-circuit units, and compressor A1 is
the lead on single-circuit units.) At the same time, solenoid
drop relay SDR2 energizes and closes its contacts, which
energizes and opens liquid line solenoid valve LLS-A (LLS-A1
for single-circuit units). Circuit A (compressor A1 for singlecircuit units) is now operational.
A set of bypass contacts in timer TM-A allows the
circuit A compressor (compressor A1 for single-circuit units)
40 seconds to build sufficient oil pressure. If the oil pressure is insufficient after 40 seconds, circuit A (compressor
A1 for single-circuit units) shuts down and must be reset
manually.
A second set of bypass contacts in timer TM-A (TM for
single-circuit units) allows the refrigerant circuit 212 minutes
to build sufficient low-side pressure. This time delay is a
start-up feature for low ambient conditions; no accessory is
required. If refrigerant circuit pressure is insufficient to close
the low-pressure switch after 212 minutes, the circuit A compressor (compressor A1 for single-circuit units) shuts down
for 512 minutes and then automatically attempts to restart.
No manual reset is required.
56
For dual-circuit units: If circuit A is insufficient for the cooling requirements, second-stage thermostat TC2 closes to
bring circuit B on line. Circuit B follows the same sequence
of operation as circuit A, except a relay delays circuit B
compressor start-up for 40 seconds after a call for cooling.
Because circuit A has a 12-second delay after TC1 closes,
and circuit B has a 40-second delay after TC2 closes, the
two compressors cannot start at the same time.
For optional single-circuit units: If compressor A1 is insufficient for the cooling requirements, second-stage thermostat TC2 closes, which opens liquid line solenoid valve
LLS-A2. Compressor A2 starts only after the D-D2 contacts in timer TM close (approximately 212 minutes after
compressor A1 is energized) and the suction pressure is sufficient to close capacity control pressure switches CCPS1
and CCPS2.
NOTE: Liquid line solenoid valves must be field-supplied
and installed at the evaporator for both dual- and optional
single-circuit units.
Indoor-fan operation: When the fan switch on the thermostat is set for automatic operation (AUTO), the fieldsupplied indoor-fan contactor (IFC) is cycled with the lead
compressor. If the fan switch is set at the continuous position (CONT), the IFC is energized as long as the unit power
is on.
Controls 38AH094-134
Sequence of operation
Units are controlled with electromechanical components.
Each refrigeration circuit is operated by an independent timer
motor which controls the operation sequence of each circuit. It is possible to maintain partial cooling capability even
if one circuit is inoperable.
On a call for cooling, first stage cooling thermostat
TC1 closes. Condenser fans and timer motor (TM) are energized. After approximately 7 seconds, timer contacts E-E1
close. Approximately 12 seconds after TC1 closes, normally open timer contacts B-B1 close for 1 second. This
energizes compressor A1 contacts CA1 and starts the compressor. At the same time, solenoid drop relays (SDRs) and
liquid line solenoid valve no. 1 (LLS-A1) open, and timer
relay no. 1 (TR1) is energized. Normally open TR1 contacts close completing a circuit around B-B1 and through
compressor A1 contactors to maintain compressor operation when B-B1 contacts open. Contacts E-E1 remain closed
for approximately 40 seconds to bypass the oil pressure
switch. If oil pressure is insufficient when contacts E-E1 open,
the compressor stops, the timer cycles off, and the control
circuit locks out. At start-up, timer motor contacts D-D1 are
closed, bypassing low-pressure relay contacts LPR-A for 212
minutes. This provides a winter start-up feature.
Approximately 212 minutes after TC1 closes, timer
contacts D-D1 open and D-D2 close. If pressure is insufficient to close the low-pressure switch, the low-pressure switch
relay remains open, the compressor shuts down, and the
Time Guardt control is initiated. Time Guard control prevents compressor from restarting for 5 minutes after the
demand for cooling is satisfied.
Units 38AH094 and 104 If circuit A operation is insufficient for the cooling requirements, the thermostat second stage TC2 closes to bring circuit B on-line for cooling.
This circuit follows the same sequence of operation as the
lead circuit, except a 60-second time-delay relay (TDR) delays compressor start-up for 60 seconds after the call for
cooling.
Modules 124A, 124B, 134A, and 134B If compressor A1 is insufficient for the cooling requirements, the
thermostat second stage closes, which opens the liquid line
solenoid valve LLS-A2. Compressor A2 starts only after
D-D2 contacts in the timer close and the suction pressure is
sufficient to close the capacity control switches.
All units When the fan switch is set for automatic (AUTO)
operation, the indoor-fan contactor (IFC) is cycled with the
lead compressor. If the fan switch is set for continuous
(CONT), the IFC is energized as long as the unit power
is on.
Restart after stoppage by safety control The highpressure switch and the oil pressure switch must be reset
manually by breaking the control power supply at any of
the following points: Control circuit fuse, fan motor circuit
breaker, or thermostat. Restart follows the Time Guard control 5-minute delay. Stoppage by low-pressure switch results in Time Guard control 5-minute delay, then unit attempts to restart.
The compressor motor overcurrent protectors are manualreset circuit breakers. Reset of control circuit may also be
necessary.
57
58
AWG
C
CR
HD
IFC
IFR
kcmil
LLS
NEC
R
RV
SDR
TB
TR
LEGEND
American Wire Gage
Compressor Contactor
Control Relay
Heating Device
Indoor Fan Contactor
Indoor-Fan Relay
Thousand Circular Mils
Liquid Line Solenoid
National Electrical Code
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Solenoid Drop Relay
Terminal Block
Timer Relay
Factory Wiring
Field Wiring
C
CCPS
CR
HD
IFC
IFR
LLS
NEC
R
RV
SDR
TB
TR
LEGEND
Compressor Contactor
Capacity Control Pressure Switch
Control Relay
Heating Device
Indoor Fan Contactor
Indoor-Fan Relay
Liquid Line Solenoid
National Electrical Code
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Solenoid Drop Relay
Terminal Block
Timer Relay
Factory Wiring
Field Wiring
59
60
C
CCPS
CR
IFC
IFR
LLS
NEC
R
RV
SDR
TB
TR
LEGEND
Compressor Contactor
Capacity Control Pressure Switch
Control Relay
Indoor Fan Contactor
Indoor-Fan Relay
Liquid Line Solenoid
National Electrical Code
Heating Relay (fieldsupplied 24-v sealed coil,
10 va maximum rating)
Reversing Valve
Solenoid Drop Relay
Terminal Block
Timer Relay
Factory Wiring
Field Wiring
6. For VAV systems, the total building load is NOT the sum
of the individual peak loads. Equipment selected for the
sum of the individual peak loads will be oversized.
7. For VAV systems with supply-to-return air recycling, use
the equipment room as a return-air plenum.
8. To minimize air recirculation, do not use concentric supply and return grilles.
9. Standard units applied in VVT systems must have fieldsupplied and installed accumulators on each circuit.
Order part number 38AK-500-410 from Service Parts.
LIQUID LINE DATA
UNIT 38AH
MAXIMUM
ALLOWABLE
LIQUID LIFT
(ft)
044
054
064
074
084
094
104
124
134
69
75
75
45
75
55
50
75
45
LIQUID LINE
Max Allowable
Max Allowable
Pressure Drop
Temp Loss
(psi)
(F)
CAPACITY/STAGE (%)
Standard Units
Optional Single-Circuit Units
100, 75, 50, 25
100, 75, 50, 25
100, 79, 42, 21
100, 80, 56, 37
100, 84, 48, 32
100, 82, 55, 36
100, 86, 43, 29
100, 81, 57, 38
100, 83, 50, 33
100, 83, 50, 33
100, 85, 55, 44, 33, 22
CAPACITY/STAGE (%)
Standard Dual-Circuit Units
Optional Single-Circuit Units
100, 75, 50, 25
100, 75, 50, 25
100, 79, 58, 42, 21
100, 80, 61, 56, 37
100, 84, 69, 48, 32, 16
100, 82, 64, 55, 36, 18
100, 86, 71, 43, 29, 14
100, 81, 62, 57, 38, 19
100, 83, 67, 50, 33, 17
100, 83, 67, 50, 33, 17
100, 85, 70, 55, 44, 33, 22
100, 91, 82, 77, 68, 50, 41, 32, 27, 18, 9
100, 90, 79, 76, 66, 45, 37, 28, 25, 16, 8
NOTES:
1. Capacities are based on 45 F saturated suction temperature and 95 F outdoor-air temperature.
2. Single-circuit option available for sizes 044-084 only.
61
044
054
064
074
084
QUANTITY OF LOADED
COMPRESSOR CYLINDERS
Ckt A
Ckt B
Total
4
4
8
2
4
6
4
0
4
2
0
2
4
6
10
2
6
8
2
4
6*
4
0
4
2
0
2
6
6
12
4
6
10
2
6
8*
6
0
6
4
0
4
2
0
2*
6
6
12
4
6
10
2
6
8*
6
0
6
4
0
4
2
0
2*
6
6
12
4
6
10
2
6
8*
6
0
6
4
0
4
2
0
2*
SYSTEM
CAPACITY
(%)
50
20
48
20
39
20
31
20
20
20
100
75
50
25
100
79
58*
42
21
100
84
69*
48
32
16*
100
86
71*
43
29
14*
100
83
67*
50
33
17*
044
054
064
074
084
QUANTITY OF LOADED
CYLINDERS
8
6
4
2
10
8
6*
6
4
12
10
8*
6
4
2*
12
10
8*
6
4
2*
12
10
8*
6
4
2*
SYSTEM
CAPACITY
(%)
100
75
50
25
100
80
61*
56
37
100
82
64*
55
36
18*
100
81
62*
57
38
19*
100
83
67*
50
33
17*
62
47
20
41
20
38
20
22
20
20
20
094
104
124
134
Ckt B
6
4
2*
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0
12
10
8
6
4
2
0
0
0
0
0
0
Total
16
14
12
10
8
6
4
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2
24
22
20
18
16
14
12
10
8
6
4
2
SYSTEM
CAPACITY
(%)
100
85
70*
55
44
33
22
100
91
82
74
65
56
47
38
26
17
9
100
91
82*
77
68
59
50
41
32*
27
18
9*
100
90
79*
76
66
56
45
37
28*
25
16
8*
25
20
14
20
38
38
20
38
22
20
*Requires VAV (variable air volume) unit or accessory unloader(s) field installed on circuit lead compressor. Lead compressor is identified in Physical Data section, page 35.
Requires field-installed accessory unloader on circuit lead compressor. Lead compressor is identified in Physical Data section, page 35.
NOTES:
1. Temperatures calculated with the minimum number of fans operating per circuit.
2. For 38AH124 and 134 units, circuit A is Module 38AH124A or 134A. Circuit B is
Module 38AH124B or 134B.
3. Minimum outdoor-air operating temperature is based on 90 F saturated condensing
temperature and 100% capacity.
63
CV
L
S
VAV
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
15-25
L
58
58
58
78
78
78
78
78
78
78
S
158
158
158
158
158
218
218
218
218
218
LEGEND
Constant Volume
Liquid Line
Suction Line
Variable Air Volume
150-200
L
S
7 8
2 1 8
7 8
2 1 8
7 8
2 1 8
1 1 8
258*
1
1 8
258*
118
258
118
258*
138
258
138
258*
138
258
NOTES:
1. Double risers may be required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F pressure drop at nominal rating
conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
Ckt A
Ckt B
138
1 3 8
50-75
B
158
158
218
218
1 3 8
158
218
1 3 8
158
218
1 5 8
1 3 8
158
218
1 3 8
158
218
1 5 8
158
218
258
1 5 8
5
1
5
1 8
2 8
2 8
1 5 8
1 5 8
218
258
1 5 8
218
258
1 5 8
158
218
258
1 5 8
218
258
1 5 8
1 5 8
218
258
1 5 8
218
258
1 5 8
LEGEND
Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
64
150-200
B
218
218
218
218
218
218
218
258
258
258
258
258
258
258
15-20
L
138
138
150-200
S
318***
318***
318***
138
318***
138
318***
158
358***
158
358***
158
358***
L
78
78
S
2 1 8
2 1 8
L
7 8
1 1 8
118
2 1 8
1 1 8
258***
118
258***
138
318***
138
118
2 1 8
1 1 8
258***
138
318***
138
318***
118
258**
118
258**
138
318**
138
318**
LEGEND
CV Constant Volume
L
Liquid Line
S
Suction Line
VAV Variable Air Volume
*Standard CV unit with 1 unloader on circuit A and 1 unloader on
circuit B; double suction riser required.
Units with factory-installed VAV option or field-installed accessory
unloader 2 unloaders on circuit A, and 1 unloader on circuit B;
double suction riser required.
**Units with 2 field-installed unloaders on circuit A and 2 on circuit B;
double suction riser required.
NOTE: It is possible to install 2 unloaders on circuit B, but not
recommended.
NOTES:
1. Double risers may be required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F pressure drop at nominal rating
conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.
2 5 8
A
158
158
150-200
B
258
258
C
318
318
2 1 8
2 5 8
1 5 8
2 1 8
2 5 8
1 5 8
2 5 8
318
158
258
318
158
258
318
158
2 1 8
2 5 8
1 5 8
2 5 8
3 1 8
1 5 8
2 5 8
318
158
258
318
218
318
358
358
UNIT 38AH
044
054
064
Modules 124A,
124B,134A
074;
Module 134B
084
1 5 8
15-50
B
2 1 8
1 5 8
58
18
58
58
58
18
LEGEND
Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
58
58
18
18
18
58
18
18
65
15-25
(4.6-7.6)
L
S
150-200
(45.7-61.0)
L
S
78
218
118
218
118
258**
118
258**
138
258**
138
318***
78
218
78
218
118
218**
118
258**
118
258**
138
258**
78
218
78
218
118
258
118
258
118
258
138
318***
218
118
218
118
258**
118
258**
138
318***
138
318***
78
LEGEND
CV Constant Volume
L
Liquid Line
S
Suction Line
VAV Variable Air Volume
*Standard CV unit with 1 unloader on circuit A and 1 unloader on
circuit B; double suction riser required.
Units with factory-installed VAV option or field-installed accessory
unloader 2 unloaders on circuit A, and 1 unloader on circuit B;
double suction riser required.
**Units with 2 field-installed unloaders on circuit A and 2 on circuit B;
double suction riser required.
NOTE: It is possible to install 2 unloaders on circuit B, but not
recommended.
NOTES:
1. Double risers may be required if condensing unit is elevated above
evaporator. See footnotes and double suction riser table below.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
3. Suction line sizing is based on 2 F pressure drop at nominal rating
conditions. Liquid line sizing is based on 2 F pressure drop. Higher
design pressure drop criteria may allow selection of smaller pipe sizes
but at a penalty of decreased system capacity and efficiency.
4. Suction line riser selections are based on using maximum possible
unloaders.
5. Refer to Carrier System Design Manual or to E20-II design programs
for further information on selecting pipe sizes for split systems.
6. All pipe sizes are OD inches.
UNIT 38AH
094
Ckt A
094
Ckt B
104
Ckt A
104
Ckt B
25-50
(6.1-15.2)
A
B
C
150-200
(45.7-61.0)
B
158
218
258
158
218
258
1 5 8
2 1 8
2 5 8
1 5 8
258
318
138
158
218
158
218
258
1 5 8
2 1 8
2 5 8
1 5 8
218
258
138
218
258
138
218
258
1 3 8
2 1 8
2 5 8
1 5 8
258
318
138
218
258
138
218
258
1 3 8
2 5 8
3 1 8
1 5 8
258
318
LEGEND
Not Required
Pipe A Suction Riser Without Trap
Pipe B Suction Riser With Trap
Pipe C Suction Line to Condensing Unit
NOTES:
1. See Refrigerant Piping Requirements table at top of page to determine need for double suction risers.
2. Pipe sizes are based on the total linear length, shown for each column, plus a 50% allowance for fittings.
66
A
B
C
D
RED.
STR
LEGEND
Pipe A, Suction Riser, Lower Trap
Pipe B, Suction Riser with Trap
Suction Line to Condensing Unit
Pipe D, Suction Riser Short Lift
Reducer
Street
NOTE: Short riser, pipe D, is used when routing suction line to condensing unit connection. See table below:
UNIT 38AH
044
054
064
074
084
094
104
124A,B
134A,B
PIPE D DIAMETER*
Dual Circuit
Single Circuit
A
B
1 5 8
218
1 5 8
1 5 8
1 5 8
218
5
1
1 8
2 8
218
1
1
2 8
2 8
218
2 1 8
2 1 8
258
2 1 8
2 1 8
218
2 1 8
1
1
2 8
2 8
1
1
2 8
2 8
67
68
C. Fans:
1. Condenser fans shall be direct-driven propeller type,
discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type with
class B insulation and permanently lubricated
bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be a product of the unit
manufacturer.
2. Compressors shall be serviceable, reciprocating,
semi-hermetic type.
3. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge, suction and discharge shutoff valves, and an inserttype, factory-installed crankcase heater to control
oil dilution.
4. Compressor shall be mounted on spring vibration
isolators with an isolation efficiency of no less than
95%.
5. Compressor speed shall not exceed 1750 rpm.
6. Lead compressor shall unload using pressureoperated suction cutoff unloading (electrical solenoid unloading shall be available as an accessory).
E. Condenser Coil:
1. Condenser coil shall be air cooled, circuited for
integral subcooler.
2. Coil shall be constructed of aluminum fins (copper fins optional) mechanically bonded to internally grooved, seamless copper tubes which are
then cleaned, dehydrated, and sealed.
3. Coil shall be protected by a sheet metal casing to
eliminate the need for wind baffles for low ambient temperature operation.
4. Coil shall be protected to avoid damage due to the
elements and vandalism.
F. Refrigeration Components:
Refrigeration circuit components shall include hot gas
mufflers, hot gas bypass stub tubes, high-side pressure relief devices, liquid line shut-off valves, suction
and discharge shutoff valves, holding charge, and compressor oil.
J. Special Features:
1. Solid-State Head Pressure Control:
Control shall regulate fan motor speed in response
to the saturated condensing temperature of the
unit. The control shall be capable of maintaining
a condensing temperature of 100 F 10 F with
outdoor temperatures at 20 F.
2. Electric Solenoid Unloader:
Unloader valve piston, coil, and hardware shall
be supplied to convert any pressure-operated compressor unloader to 115-v electric unloading.
Accessory ModuPanel or field-supplied step controller shall be provided for control of electrical
unloading.
3. Gage Panel:
A gage panel package shall be provided which includes a suction and discharge pressure gage. One
is required for each refrigerant circuit.
4. ModuPanel Control Box:
Control box shall be provided to allow system to
operate as a VAV (variable air volume) system.
5. Thermostats, 24 v (including Carrier Programmable Temp-System MS[T]01ES):
Thermostat shall provide 2-stage cooling control
of unit.
6. Pressure-Operated Unloader:
Unloader shall be available to allow compressors
to be unloaded in response to compressor suction
pressure.
7. Winter Start Package:
Winter start control to prevent nuisance tripouts
at low ambient temperatures.
8. VAV Option:
A factory-installed variable air volume option shall
be supplied to provide unit with 2 electric unloaders and control box modifications necessary
to connect to a field-installed ModuPanel control
box. (Field supplied accumulators required for each
circuit.)
69
70
A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
2. Cabinet panels shall be fully insulated with 12-in.
fire-retardant material. Insulation shall contain an
EPA-registered immobilized antimicrobial agent to
effectively resist the growth of bacteria and fungi
as proven by tests in accordance with ASTM standards G21 and 22.
3. Unit shall contain condensate drain pans for both
vertical and horizontal applications. Drain pans shall
have connections on right and left sides of unit to
facilitate field connection. Drain pans shall have
the ability to be sloped toward the right or left side
of the unit to prevent standing water from accumulating in pans.
4. Unit shall have factory-supplied 2-in. throwawaytype filters installed upstream from the cooling coil.
Filter access shall be from either the right or left
side of the unit.
B. Coils:
Coils shall consist of 3 rows of 38-in. copper tubes
with sine-wave aluminum fins bonded to the tubes by
mechanical expansion. Coil tubing shall be internally
rifled to maximize heat transfer. Suction and liquid
line connections shall be made on the same side of
the coil. Direct-expansion coils shall feature factoryinstalled thermostatic expansion valves (TXVs) for
refrigerant control. The TXVs shall be capable of external adjustment.
C. Operating Characteristics:
cfm airUnit shall be capable of providing
flow at an external static pressure of
in wg.
D. Motor:
Fan motor of the size and electrical characteristics
specified on the equipment schedule shall be factory
supplied and installed.
E. Factory-Installed Options:
1. Alternate Motor and Drive:
An alternate motor and medium- or high-static drive
shall be available to meet the airflow and external
static pressure requirements specified on the equipment schedule.
2. External Paint:
Where conditions require, units shall be painted
with an American Sterling Gray finish.
F. Field-Installed Accessories:
1. Hot Water Coil:
Coil shall be 2-row, U-bend coil with copper tubes
and aluminum plate fins bonded to the tubes by
mechanical expansion. Coil shall be mounted in
a galvanized steel housing that shall be fastened
to the units fan deck for blow-thru heating operation. Coil shall have maximum working pressure of 150 psig.
2. Steam Distributing Coil:
Coil shall consist of one row of copper tubes with
aluminum plate fins, and shall have inner steam
distributing tubes. Coil shall be mounted in a galvanized steel housing and shall be fastened to the
units fan deck for blow-thru heating operation.
Coil shall have maximum working pressure of
175 psig at 400 F.
3. Electric Heaters:
Heaters for nominal 240, 480, or 575-volt,
3-phase, 60 Hz power supply shall be factorysupplied for field installation as shown on the
equipment drawings. Electric heat assembly shall
be ETL agency approved, and shall have singlepoint power wiring. Heater assembly shall include contactors with 24-v coils, power wiring,
24-v control wiring terminal blocks, and a hinged
access panel.
4. Air Discharge Plenum:
Plenum shall be factory supplied to provide freeblow air distribution for vertical floor-mounted
units. A grille with moveable vanes for horizontal or vertical airflow adjustment shall be included.
Plenum housing shall be field-installed on the
units fan deck for blow-thru air distribution.
5. Return-Air Grille:
Grille shall be factory supplied for field installation on the units return air opening.
6. Unit Subbase:
Subbase assembly shall be factory supplied for
field installation. Subbase shall elevate floormounted vertical units to provide access for correct condensate drain connection.
7. Economizer:
Economizer for ventilation or free cooling shall
be factory provided for field installation. For free
cooling applications, economizer shall be compatible with factory-supplied thermostat; economizer dampers shall open when outdoor air enthalpy is suitable for free cooling. Economizer shall
be compatible with factory-supplied CO2 sensor;
economizer dampers shall open when indoor CO2
level rises above predetermined set point.
8. Communicating Electronic Thermostat:
Electronic programmable thermostat assemblies
shall provide 2-stage heating and 2-stage cooling control with remote communication ability
and shall be factory-supplied for field installation.
9. Overhead Suspension Package:
Package shall include necessary brackets to support units in a horizontal ceiling installation.
10. CO2 Sensor:
Sensor shall provide the ability to signal the economizer to open when the space CO2 level exceeds
the predetermined set point.
71
72
C. Fans:
1. Condenser fans shall be direct-drive propeller type,
discharging air vertically upward.
2. Condenser fan motors shall be 3-phase type
with class B insulation and permanently lubricated
bearings. Motors shall be drip proof with sealed
bearings.
3. Shafts shall have inherent corrosion resistance.
4. Fan blades shall be statically and dynamically
balanced.
5. Condenser-fan openings shall be equipped with
PVC-coated steel wire safety guards.
D. Compressors:
1. Compressors shall be serviceable, reciprocating,
semi-hermetic type.
2. Compressors shall be equipped with an automatically reversible oil pump, operating oil charge,
suction and discharge shutoff valves, and an inserttype factory-sized crankcase heater to control oil
dilution.
3. Compressors shall be mounted on spring vibration isolators with an isolation efficiency of no less
than 95%.
4. Compressor speed shall not exceed 1750 rpm.
5. Lead compressors on each circuit shall unload using suction cutoff unloading (electric solenoid unloading shall be available as an accessory).
E. Condenser Coils:
1. Condenser coils shall be air cooled and circuited
for integral subcooler.
2. Coil shall be constructed of aluminum fins mechanically bonded to internally grooved, seamless
copper tubes which are then cleaned, dehydrated,
and sealed. Copper fins shall be available as an
option.
F. Refrigeration Components:
Refrigeration circuit components shall include hot
gas muffler, hot gas bypass stub tubes, high-side pressure relief device, liquid line shutoff valve, suction
and discharge shutoff valves, holding charge of refrigerant R-22, and compressor oil. 38AH094-134
and all 38AH044-084 single-circuit units shall have
suction line accumulators. VAV units shall also have
suction line accumulators.
I. Electrical Requirements:
1. Nominal unit electrical characteristics shall be
v, 3-ph, 60 Hz. The unit shall be capable
of satisfactory operation within voltage limits of
v to
v.
2. Unit or module electrical power shall be singlepoint connection.
3. Unit control circuit shall be 115 v (or 230 v for
380-3-60 unit).
J. Special Features:
1. Unloader Conversion Kit:
Unloader valve, piston, and hardware shall be
supplied to convert any pressure-operated compressor unloader to 115-v (or 230-v) electrical
unloading. Accessory ModuPanel control or
field-supplied step controller shall be required for
electrical unloading.
2. Gage Panel:
A gage panel package shall be provided which
includes a suction and discharge pressure gage
for each refrigerant circuit.
3. Accessory Transformer Relay Package:
Relay shall be provided for use with a remotecontrol 24-v thermostat.
4. Electric Unloader Package:
Electric unloader shall provide an additional step
of electric unloading.
5. Pressure Unloader Package:
Pressure unloader shall provide an additional step
of pressure unloading.
6. ModuPanel Control:
Control shall provide up to 10-steps of
microprocessor-based control for variable air volume (VAV) applications.
7. Motormastert III Control:
Control shall maintain correct condensing pressure at low ambient temperatures.
8. Compressor Grille Package:
Grilles shall protect the compressor area after unit
installation.
9. Condenser Coil Grille Package:
Grilles shall protect the condenser area after unit
installation.
10. Sound-Reduction Kit:
Kit shall contain specially designed fan propellers and stacks to lower sound emitted from the
unit, and shall be compatible with the Motormaster III control.
73
74
1095
5-95
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2
Tab 3a 1a
Page 76
Printed in U.S.A.
1095