DATA SHEET - 245KV GIS DOC. NO.

SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

GUARANTEED TECHNICAL & OTHER PARTICULARS OF 245kV GIS Sr. No.

Description of Technical Particulars : : : : : : : : : : : : : : : :

Requirement As per vendor list Bidder to furnish Bidder to furnish 220 kV 50 Hz 245 kV 2000 Amp. 2000 Amp. 2000 Amp. 40 kA 40 kA 1050 kV (peak) 1200 kV (peak) Bidder to furnish

Vendors Data Hyundai Korea 300SR 220 kV 50 Hz 245 kV 2000 Amp. 2000 Amp. 2000 Amp. 50 kA 50 kA 1050 kV (peak) 1200 kV (peak) N/A N/A N/A

220 kV GIS General Name of manufacture 1 Place of manufacture, inspection & testing 2 Manufacturer's type / designation 3 Rated voltage 4 System frequency 5 Maximum(continuous)service rated voltage 6 Normal current rating 7 - Generator Transformer feeder circuit - Line feeder circuit - Bus coupler circuit Short time current rating 8 - 1 second rms. - 3 second rms. Rated Lightning impulse withstand voltage 9 - Phase to earth - Across open contacts Rated Switching surge withstand voltage 10 - Phase To earth - Phase to phase - Across open contacts Rated one minute power frequency 11 withstand voltage - Phase to earth - Across open contacts Maximum temperature rise over ambient of 12 35.5 deg. C. rating of current carrying parts at 220 Thermal 13 kV for the rated symmetrical short circuit current 14 15 16 17 Altitude upto which the switchgear shall operate satisfactorily Ambient conditions of the operation of the GIS Earthing details of enclosure Density and pressure of filling gas in various compartments of the enclosure at 200 C (i) Compartments in kPa (ii) Circuit Breakers in kPA Features adopted for preventing burn through in the various enclosures of SF6 GIS Time in m sec to withstand an internal flashover without burn through Guaranteed life of the GIS

: : : :

460 kV (rms) 530 kV (rms) As per IEC 694 /40 Deg C 1 Sec

460 kV (rms) 530 kV (rms) As per IEC60694 Table 3 3 Sec

: :

2000 m

2000m -10~50 Solidly earthed

- 10 Deg C to 50 Deg C Solidly earthed : Bidder to furnish

: : : : :

18

500 - 750 Kpa 500 - 750 Kpa through release of pressure relief device / rupture disc As per IEC 30 years

500kPa 700kPa Rupture disc

300ms 30 years

19

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No.

Description of Technical Particulars a) Guaranteed number of loaded/unloaded operations of various equipments of SF6 GIS i.e. circuit breakers, disconnectors, grounding switches (please mention item wise).

Requirement CB - 2000 ( M1) :

Vendors Data CB: 10000(M2)

20

: b) Max. number of interruptions at rated S.C current with associated recovery voltage the : Circuit Breaker is capable to withstand without requiring change of any parts. a) Guaranteed Average leakage of SF6 gas from the equipment and percentage per year. (i) From complete GIS/ year (ii) From compartments /year b) Quantity of SF6 gas required to completely charge the 3-pole equipment including any tank storage system c) Quantity of SF6 gas required for largest gas compartment d) Operating pressure - Circuit breaker - Others Details of the features existing in the equipment to carry out P.D. measurements at works/site Details of the control wiring used in the Equipment The extent of field welding required for site assembly, if any along with the procedure to be adopted by the firm at site Details of the documents, drawings & operating principles of the major components of the equipment, presenting a clear picture of the fundamental principle, general arrangements and operating mechanism photographs enclosed showing the basic drgs. Enclosed Details of the flow diagram/ showing all valves and pressures involved, for the hydraulic and gas system. Details of the test data enclosed including test data of the parts indicating the ability of the equipment (including high speed grounding switches) The values of resistors inserted in the line circuit breaker during closing operations, if any, along with the length of time the resistors are left in the circuit. Methods adopted to limit switching surges for breaker and disconnectors Values of maximum switching surges generated : : : : : : : : :

*DS/ES/H-ES 1000 / 2000 10 to 21 Nos.

DS/ES/HSES: 2000 20 @40kA

21

less than or equal to 1% less than or equal to 2% Bidder to furnish

0.5 0.5 Approx. 204kg/bay (without GIB) 84kg/3-phae

Bidder to furnish Bidder to furnish 6-7 bar 6-7 bar UHF/ Acoustic

700kPa 500kPa UHF sensor

22 23 24

2.5 sq.mm, 750V Bidder to furnish

2.5 sq.mm, 750V N/A

Bidder to furnish :

Yes

25

Bidder to furnish : Bidder to furnish : Bidder to furnish : Bidder to furnish <2.6 PU

Yes

26

Yes

27

N/A

28

29 30

: :

N/A <2.6 PU

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 31 32 33

Description of Technical Particulars Heat generated in K.W. when the complete switchgear is operating at its rated capacity :

Requirement Bidder to furnish

Vendors Data 14.4

34

35

Noise level of Circuit Breaker at a distance of 80 dB : 5m from it. Material used in fabrication (Copper, Aluminum, Silver, Stainless Steel etc) a) Breaker main contact surfaces. Copper with silver : plated b) Disconnecting switch contact surfaces. Copper with silver : plated c) Grounding switch contact surfaces. Copper with silver : plated d) Internal bus. Aliminum : e) Internal bus contact surfaces. Aluminum with silver : plated f) Bus enclosure. Aliminum : g) Terminal pads. Tinned copper : Terminal pad contact surface. Tinned copper : Bellows or compensating units Stainless steel : Operating Mechanism - Breaker Hydraulic / spring : - Disconnecting switch Motor : - High speed fault making grounding switch Motor/spring : charged -Safety grounding switch Motor : Time required to recharge the operating Hydraulic - 5 min system to a fully charged condition after four Spring - 15 Sec : successive operations (without pumping action) Details of provisions made for movement of maintenance personnel on the equipment : Bidder to furnish

80

Copper with silver plated Copper with silver plated Copper with silver plated Aluminum Aluminum with silver plated Aluminum Tinned copper Tinned copper Stainless steel Motor spring Motor Motor spring Motor 15 Sec

36

Platform (The location of platform will be provided at the detail design stage) 60 pico farads/mtre Below 100V 0.25A 80

37

a) Capacitance per meter of the enclosed bus b) Max. potential rise of enclosure at 50kA (ref voltage of low freq) in volts c) Bus charging current in amps Surge impedance in ohms of the enclosed bus (The bidder should furnish the method used for the calculations of surge impedance and capacitance of insulated bus). a) Electric resistance at 20 deg C in micro ohms/metre. - Bus enclosure - Internal bus b) Data used for calculation of electric resistance in (a) - Cross sectional area of bus conductor - Cross sectional area of bus enclosure. -Conductivity of material of bus conductor - Conductivity of material of bus enclosure. -Current density in bus conductor.

: : : :

50 pico farads/ metre Bidder to furnish Bidder to furnish 80 Ohm

38

39

: :

8.3 11.1

3.8 12.7

: : : : :

3043 sqmm 8999 sqmm 0.03 Ohm sq m /mtr 0.05 Ohm sq m /mtr 2 A/mm2

2607 7891 51% 40% 1A/mm2

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No.

Description of Technical Particulars Maximum Guaranteed power losses in the bus bar per single phase meter at rated voltage and current at 40C ambient temp in a) Enclosure b) Conductor Dimensions a) Bus enclosure outside diameter b) Bus enclosure wall thickness c) Internal bus, outside diameter d) Internal bus thickness Weight (The weight of each assembled bay to be indicated separately) a) Generator Transformer Bay b) 220 kV XLPE cable feeder Bay c) 220 kV Bus coupler Bay d) Bus Bars : : : : : : :

Requirement

Vendors Data

40

41

25 W 50 W Bidder to furnish

16 W 50 W 322mm 8mm 93mm 10mm

42

Bidder to furnish : : : : Approx.10,000kg Approx.8,000kg Approx. 5,000kg Approx. 3,000kg

II Equipment included in GIS A. Circuit Breake r* (The following particulars for each type of breaker shall be furnished) Name plate data 1 - Manufacturer's name As per vendor list : - Type / designation Bidder to furnish : - Rated frequency 50 Hz : - Rated voltage 220 kV : - Rated interrupting current 40 kA : - Number of poles 3 : - Class (indoors) Indoor : - Number of interrupting chambers per pole 1 : - Maximum Operating Voltage Breaking 245 kV Capacity : Making & Breaking a) Breaking Capacity - Rated breaking current 40 kA(rms) : - Rated breaking MVA (Symmetrical) 40 kA(rms) : - Breaking time 60 ms. (approx) : b) Making Capacity - Rated making current 100 kA : - Rated making MVA symmetri cal 100 kA : - making time 100 ms (approx) : c) Max operating time at full rated 60 ms. (approx) : interrupted capacity from the instant of trip coil energizing d) Operating pressure kg/cm2 - Components - Circuit Breaker e) Amount of gas (SF6) required for largest compartment f) Amount of gas required to completely change the 8-poles equipment including any tank storage system g) Total length of break per phase : : : Bidder to furnish : : 100-200 mm 6-7 bar 6-7 bar Bidder to furnish

Hyundai 300SR 50 Hz 220 kV 50 kA 3 Indoor 1 245 kV

50 kA(rms) 50 kA(rms) 60 ms 125 kA 125 kA 75 ms 60 ms

500 kPa 700 kPa 84 kg/3-phase 28kg/1-pole

123mm

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 2

Description of Technical Particulars Operating voltages of closing/opening coil - Maximum Operating voltage - Minimum Operating voltage - Range factor Current ratings - Rated continuous current at 400C ambient temp. - Rated interrupting current for 1s, - Rated symmetrical interrupting current - Rated asymmetrical interrupting current - Percentage D.C. component - Rated short circuit making current Rated Insulation level a) Dry one minute power frequency withstand voltage - To earth - Across open contacts b) 1.2/50 microsecond full wave lightning impulse withstands voltage. i) To ground ii) Across the open contacts c) 250/2,500 microsecond switching impulse withstands voltage. d) Line to ground power frequency withstand voltage at gas pressure equivalent to atmospheric pressure e) Minimum allowable moisture content in interrupting medium f) Total breaking time i) At 10% rated interrupting capacity ii) At 60% rated interrupting capacity iii) At 100%rated interrupting capacity Maximum temperature rise above ambient at rated load and voltage for - contacts - Hottest part - Enclosure Operating data - Rated Operating duty cycle Line Breakers, Generator Transformers , Shunt Reactor & Bus Coupler Breakers - Reclosing duty cycle (Line Breakers) - Permissible tripping delay - Maximum arc duration at a) 10% rated breaking current b) 30% -- do-c) 60% -- do-d) 100% -- do-- Closing time : : : : : : : : : :

Requirement 242 V 154 V Bidder to furnish 2000 A : : : : : : 40 kA 40 kA 40 kA 40-70% (approx) 100 kA (peak)

Vendors Data 242 V 154 V 85-110% 2000/3150 A 50 kA 50 kA 50 kA 70 % at 40kA 125 kA (peak)

: :

460 kV(rms) 530 kV(rms)

460 kV(rms) 530 kV(rms)

: : :

1050 kV(peak) 1200kV(peak) Not Applicable 245 /3 kV

1050 kV(peak) 1200 kV(peak) N/A 245 /3 kV

: 300 ppm / vol. : : : : < 50 ms < 50 ms < 55 ms As per IEC < 65 deg C < 75deg C < 40deg C O-0.3s-CO-1min-CO < 50 ms < 50 ms < 55 ms 300 ppm / vol.

: : : :

< 65 < 75 < 40 O-0.3s-CO-1min-CO

O-3min-CO-3min- CO As per IEC < < < < < 20 ms 20 ms 20 ms 20 ms 100 ms

O-3min-CO-3min- CO As per IEC < 20 ms < 20 ms < 20 ms < 20 ms < 100 ms

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No.

Description of Technical Particulars - Total breaking time at 10% rated breaking current 30% -- do-60% -- do-100% -- do-Arc duration from separation of arc at contact to instant of arc extinction for full rated interrupting capacity. - Length of arc at 10% rated breaking current 30% -- do-60% -- do-100% -- do-Max. length of arc at lowest fault current - Longest time To interrupt 'current' less than 25% of rated symmetrical short circuit current from energizing trip circuit - Minimum time from arc extinction To Contact remake for auto reclosing. - Minimum dead time for a) 3 phase reclosing b) 1 phase reclosing - Maximum difference of time at opening of series contacts within one pole Maximum difference of time at opening between phases Maximum difference of time at Closing between phases Details of the curve enclosed for maximum opening time vs. 3 phase fault current of interruptions before Number scheduled maintenance is required Number of mechanical operations before scheduled maintenance is required Number of interruptions at Rated S.C.current with associated TRV without changing any parts. Description and frequency of scheduled maintenance required Time interval between the issue of trip command and the instance of opening of breaker contact - Recovery voltage rate of rise at a) Rated symmetrical interrupting current b) 60 percent of rated symmetrical interrupting curr ent c) 30 percent of rated symmetrical interrupting current d) 10 percent of rated symmetrical interrupting curr ent - Amplitude factor - Phase factor : : : : < < < < <

Requirement 60 60 60 60 25 ms ms ms ms ms

Vendors Data < 60 ms < 60 ms < 60 ms < 60 ms < 25 ms

a) b) c) d)

e) a) b) c) d) e)

: : : : : :

Bidder to furnish mm mm mm mm mm < 50 ms

19.2 19.1 11.5 18.7 18.7(L90) < 50 ms

: 350 ms : : : 300 ms 300 ms Not Applicable < 5 ms : < 5 ms : Bidder to furnish 36 single pole @ 40 kA 2000 N/A 20/ each single phase @40kA 10000 5 ms 300 ms 300 ms N/A 3.3 ms 350 ms

: :

36 single pole operations : Bidder to furnish :

20/ each single phase @40kA 30 years

: :

2 kV/ms 3 kV/ms 5 kV/ms

2 kV/ms 3 kV/ms 5 kV/ms 7 kV/ms 1.4 1.3

: 7 kV/ms : : : 1.4 1.3

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No.

Description of Technical Particulars - Natural frequency - Devices used for controlling RRRV - Devices used for uniform voltage distribution - distribution of voltage Across breaks - Details of Switching resistors required Preinsertion (on closing) Preinsertion time Tripping Recovery voltage distribution between breaks in percent of rated voltage a) Single line to ground fault b) Interruption of short lines c)Switching off an unloaded transformer Details of the operating mechanism - Tripping coil - Closing coil - Number of Closing coils : : : : : : :

Requirement 50 Hz *Bidder *Bidder *Bidder *Bidder to to to to furnish furnish furnish furnish

Vendors Data 50 Hz N/A N/A N/A N/A

*Bidder to furnish : : : : : : Hydraulic / spring Hydraulic / spring 1/More shall be finalied during details engg. 2 Bidder to furnish N/A N/A N/A Motor spring Motor spring 1

- Number of Tripping coils Hydraulic fluid supply system for mechanical operation - Pump, motor, hp, voltage/Phase and quantity of motors - Storage compartment pressure Kg/cm sq - Minimum oil pressure required for successful i nterruption, breaker rating, Kg/cm sq - No of stored ' close-open operation' - Quantity of oil required for one without pumps operation close-open operation SF6 gas system - Normal Operating pressure - Normal Operating density - Weight of gas per breaker - Lockout pressure - Alarm pressure - Whether breakers work at single pressure or dual pressure - Type of SF6 gas flow(axial or radial) - Type of nozzles (single flow or double flow) - Compression ratio for puffer action - Quantity of compressed gas for puffer action - Total volume of SF6 gas required per circuit breaker at operating pressure. - arc monitoring pressure - Fill pressure -Loss of Dielectric

: :

2 N/A N/A

: : : : : : : : : : : : : : : : : : : : 4.0 A : 6-7.5 bar 45 - 55 gm/lit during detail engg 5.6-6.7 bar 5.8-7.0 bar single axial single puffer Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish

N/A N/A

N/A N/A

7 bar 52.51g/cc 28 kg/1-phase 620 kPa 620 kPa Single Axial Single Puffer 28.2kg 0.22kg at open position Max. P 50 kPa 0.05MPa Rated 700kPa 20% loss of dielectric during the short circuit current breaking 7.5 A

10

Control power requirement - Tripping(3poles)current at rated supply voltage

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No.

Description of Technical Particulars - Tripping(3poles)current at 70% of rated supply voltage 220 VDC - Closing(3 poles) current at rated supply voltage 220 VDC - Closing (3 poles) current at 85% of supply voltage 220 VDC - Tripping voltage Range percent - Closing voltage range percent Heaters - Continuously current rating - Thermostat power rating Noise performance (circuit breaker operation) - Measurement standard - Noise level - Distance Interrupters - Type of main contacts, arcing contacts & Aux. Contact - Material of main contacts/arcing contacts, silver coated or not :

Requirement 2.7 A 3.8 A : 3.2 A : : : : : : : : NEMA 80 dB 5 mtr multi finger / penetrating / others Yes : : : : : : : : : : : : : Bidder to furnish 1 125 - 200 mm 100 - 200 mm 8-11 m/s 2.5-5 m/s Bidder to furnish 1.3 Trip Free electrical trip free 125A Bidder to furnish Bidder to furnish 70-110 85-110 Bidder to furnish

Vendors Data 5.3 A 8.1 A 6.9 A 70-110 85-110 0.8 A 100 W NEMA 80 5 Multi finger Yes N/A 1 123mm 161mm 5.8~6.0 m/s 4.0 m/s 18.7ms 1.3 Trip free electrical trip free 125 A 250 A 20 A

11

12

13

14 15 16 17 18 19 20 21 22 23 24 25

- Contact pressure Kg/sq mm - Number of Interrupters per pole - Break Length of an interrupter - Length of Contact travel - rate of Contact travel at Tripping - rate of Contact travel at Closing - Arcing withstand time First pole to clear factor Whether fixed trip or trip frees Details of anti pumping device Rated line-charging breaking current Rated small capacitive breaking current Rated small inductive breaking current Generator transformer, Line & Bus coupler breakers, Shunt Reactor : breaker Rated characteristics for short line fault : a) Rated transient recovery voltage for terminal faults : b) Parameters as per IEC : Rated value of phase making current : Max. interrupting capacity under phase opposition conditions : Capacity for interrupting in-rush current of transformer : Max. over voltage factor of the circuit breaker when switching off a) Unloaded transformer b) Loaded transformer c) Open circuited lines d) Synchronous system Details of operation counter : : : : :

Bidder to furnish Bidder to furnish Bidder to furnish As per IEC 12.5 kA Bidder to furnish

L90, L75 364 4 parameter 125 kA 12.5 kA 20A

26

< 2.5 < 2.5 < 2.5 < 2.5 Bidder to furnish

< 2.5 < 2.5 < 2.5 < 2.5 9999

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 27

Description of Technical Particulars No. of auxiliary contacts, their continuous rating and breaking capacities, including those used for circuit breaker operation and interlocking i) Those closed when breaker is closed ii) Those open when breaker is open iii) Those adjustable w.r.t. the position of main contacts Partial discharge level at 1.2Un/ 3 Radio interference level at 266 kV (rms) Corona extinction voltage Maximum impact loading on foundation during breaker opening and closing operations under fault conditions. Seismic withstand value (horizontal and vertical) Tests to be conducted by the supplier at works (All details to be given) a) Type tests b) Routine tests Tests to be conducted at site Overall dimensions (LxBxH), : : : :

Requirement

Vendors Data

: : : : : : :

6 (convertible type) 6 (convertible type) 6NO + 6NC < 5 Pico-coulombs As per IEC 156 kV(rms) 8000kg (approx)

6(adjustable type) 6(adjustable type) 6NO + 6NC < 5 Pico-coulombs As per IEC 156 kV(rms) 4200 kg

28 29 30 31 32

: : :

0.35g (H) 0.25g (V) As per IEC

0.5g (H) 0.5g (V)

33

34 35

Bidder to furnish Bidder to furnish

Yes(with extra cost) Yes Yes 17745mm(L) x 6300mm(W) x 4159mm(H)

36

Weight of breaker complete with operating mechanism, bushing, frame work, a) with SF6 gas b) without SF6 gas Descriptive bulletins and drawings of the circuit breakers giving general details of construction. Out of phase switching capability of the circuit breaker Comments regarding the suitability of the circuit breaker for restrike free operation of power transformer carrying full load current. Guaranteed time difference between the first pole and last pole operation timing. Details of the standard accessories to be supplied along with the breaker No. of the enclosed drg. showing the control scheme of circuit breaker Details of the provision to be made on GIS to reduce H.V. transients to acceptable values. Guaranteed degraded values of B.I.L. switching surges and 50 Hz rated values during the life of equipment. (Test data to support this guarantee to be enclosed by the bidder). : :

Bidder to furnish Approx. 1584 kg/3-phase Approx. 1500 kg/3-phase At the detail design stage 12.5 kA Re-strike Free

37 38

Bidder to furnish 12.5kA : Re-strike Free : 3 / 5 ms (approx) : Bidder to furnish : Bidder to furnish : Bidder to furnish : : Bidder to furnish

39 40 41 42 43

Close : 5 ms Open: 3.3 ms At the detail design stage At the detail design stage N/A N/A

44

B) Disconnectors/Grounding Switches B-I Manufacturer's name 1 Type & designation 2 Rated voltage 3

: :

As per vendor list Bidder to furnish

Hyundai 300DSM

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No.

Description of Technical Particulars i) Rated ii)Max. permissible 1.2/50 microsecond lightning impulse withstand voltage - Between line terminals and ground - Between terminals with disconnecting switch in open position Dry one minute power freq withstand voltage - Between line terminals and ground - Between terminals with disconnecting switch in open position Dry one minute power frequency withstand voltage i) Between line terminals and ground ii) Between terminals with disconnecting switch in open position : :

Requirement 220 kV 245 kV

Vendors Data 220 kV 245 kV

: : : :

1050kV(peak) 1200 kV

1050 kV (peak) 1200 kV

460kV (peak) 530kV kV (rms)

460 kV(peak) 530 kV

460 kV 530 kV 50 Hz 2000 A 2000 A 2000 A 100 kA 40 kA Bidder to furnish kA (peak) 40 40 100 kA *Bidder to furnish *Bidder to furnish 1 Amp As per IEC

460 kV 530 kV 50 Hz 3150 A 3150 A 3150 A 125 kA 50 kA 1600A (100times) 50 kA 50 kA 125 kA N/A N/A 0.5 280kV

7 8

9 10 11 12

13 14 15 16 17 18

19

20

: Rated frequency : Rated normal current Generator Transformer module : Line module : Bus coupler module : Rated peak short circuit current : Fault making capacity (For quick acting grounding switch) : Interruption of loop current : Rated short time current i) 1 second : ii) 3 second : Rated peak withstand current : Rated inductive breaking current : TRV caused by breaking/making inductive current : Rated capacitive breaking current : TRV caused by breaking/making capacitive curr ent : Rated insulation level - 1 minute power frequency withstand voltage : - 1.2/50 microsecond lightning impulse withstand voltage : - 250/2,500 microsecond switching impulse withstand voltage : Maximum temperature rise above ambient at rated current - Contacts, : - Hottest part : Motor operating mechanism - current During Closing : - current During opening : - Closing time : - opening time : - Operating voltage and Range :

460kV (rms) 1050 kV (rms) Not applicable

460kV (rms) 1050 kV (rms) N/A

65 Deg. C 75 Deg. C 10Amps 10 Amps < 10 sec < 10 sec -15/+10% Un

65 75 1.8 A 1.8 A < 5 sec < 5 sec 220V 80-110%

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0 Sr. No. 21 Description of Technical Particulars Design data - Type of contacts - Contact area - Contact pressure - Surface treatment and thickness of surface coating/silver electrolytic plating - Overtravel Distance after making of contacts - Distance Between the contacts in the fully open position - current density at the Minimum Cross section of switch blade 22 23 24 25 26 27 - Speed of Break Partial discharge level at 1.2 Un / 3 Corona extinction voltage Radio interference level at 266 kV (rms) Total operating time of disconnector along with its operating mechanism Total operating time of disconnector after the command is given Auxiliary switches - No. of No and NC contacts - Rated voltage - Rated current - Test voltage No. of operations the switch can withstand without any need for inspection Type of mounting No. of poles per phase Safety factor taken into account while Type and material used for arcing contacts, if provided designing the disconnector. Weight of 3 pole isolating switch - with earthing blades - without earthing blades Type of interlock between main isolator and earthing switch Details of the type test reports enclosed and the standards as per which these tests have been carried out Rated maximum time duration of short circuit Rated mechanical terminal load. Rated supply voltage of operating devices and auxiliary circuits. Rated pressure of SF6 gas Minimum distance between poles with regard to insulation and forces caused by shortcircuit currents. Tests to be conducted by the manufacturer at works i) Type tests : : : : : :

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT Requirement Multi / Tulip fingers Bidder to furnish Bidder to furnish 5-30 m Bidder to furnish 120-150 mm 2 A/mm2 Vendors Data Tulip 3632mm2 0.87kgf/mm 20-50 m 4mm 101mm 2 A/mm2 0.2m/s < 5 pico-coulombs 156kVrms 1000 microvolt <5s <5s

: : : : : :

Bidder to furnish < 5 pico-coulombs Bidder to furnish *Bidder to furnish 10 sec 10 sec

: : : : : 6 NO + 6 NC 220 V DC 10A make and 0.7A beak Bidder to furnish 1000/2000 Vertical / horizontal 1 As per IEC Bidder to furnish Bidder to furnish : : Electrical : As per IEC : : : : : As per IEC 150 kg N/A Electrical 6 NO + 6 NC 220 V DC 10 A 2kV(1min) 1000/2000 3 phase gang operation 1 As per IEC Cu

28 29 30 31 32 33

: : : :

34

35 36 37 38 39

1 to 3 secs *Bidder to furnish 220V DC 7.5 bar(max) during detail engg

3 At the detail design stage 220 V dc 5.5 Bar rel (max) Single phase in one enclosure

40 41

: As per IEC : Yes (with extra cost)

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0 Sr. No. 42 B- II 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 B- III 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT Requirement Vendors Data Yes Yes Hyundai 300 EAP 245 kV 125 kA (peak) N/A N/A N/A N/A Electric 5.2 A <5s 5.2 A <5s 220 V dc 5 kV Tulip 48 mm 130 mm 6t x 40mm 0.2 mm/s < 5 pico-coulomb 156 kV (rms) 1000 microvolt As per IEC

Description of Technical Particulars ii) Routine tests Tests to be conducted at site Safety Grounding Switches Manufacturer's name Type / designation Maximum permissible operating voltage Maximum make and carry current for one sec. Rated inductive breaking current TRV caused by breakin g/making inductive current Rated capacitive breaking current TRV caused by breakin g/making capacitive curr ent Details of motor operating mechanism providedcurrent Closing Closing time Opening current Opening time Operating voltage range & rated voltage Ground connection insulation Type of contacts Over travel distance Distance of fully open contacts Size of the removable link Speed of make Partial discharge level at 1.2 Un / 3 Corona extinction voltage Radio interference level at 266 kV (rms) Details of type test reports enclosed and the standards as per which these tests have been carried out No. of NO and NC contacts, its rated voltage and current 10A make and 0.7A break Speed Fault Making Grounding Switch High Manufacturer's name Type/ designation Maximum permissible operating voltage Maximum make and carry current for 1 sec. Rated inductive breaking current TRV caused by breakin g/making inductive current Rated capacitive breaking current TRV caused by breakin g/making capacitive Motor operating mechanism Making current Induced current switching capability Closing current Closing time Opening current Opening time : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : :

Acc. To Bid As per vendor list Bidder to furnish 245 kV 100 kA (peak) Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish Electric < 10 A < 10 secs < 10 A < 10 secs 220 V DC 5 kV Multi finger / Tulip Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish < 5 pico-coulomb 156 kV (rms) As per Standard As per IEC

6 NO + 6 NC/4 NO + 4 NC As per vendor list Bidder to furnish 245 kV 100 kA (peak) 80 A 2 kV 3A 12 kV electric 100kA peak Bidder to furnish 10A 10S 10A 10S

6 NO + 6 NC/4 NO + 4 NC Hyundai 300EYP 245 kV 125 kA(peak) 80 A 2 kV 3A 12 kV Motor spring 100 kA peak Capacitive: 80A at 2kV Inductive: 3A at 12kV 4.7 A <5s 5.6 A <5s

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 C)

Description of Technical Particulars Operating voltage range, rated voltage Design data Ground connection insulation Type of contacts Over travel distance Distance of fully open contacts Size of the removable link Speed of make Partial discharge level at 1.2 Un/ 3 Corona extinction voltage Radio interference level at 266 kV Has equipment been type tested and to which standards ? No.of NO and NC contacts, its rated voltage and current Total operating time of switch along with its operating mechanism Total operating time of switch after the command is given. CURRENT TRANSFORMERS (Particulars for all groups of CT's to be indicated either here or on separate sheet) Name of manufacturer Type Manufacturer's type / designation Rated voltage Normal continuous rating Normal ratio of transformation Rated primary current Rated secondary current Technical Particulars for CT Numbers of cores. Rated output (VA) Class of Accuracy Accuracy Limit factor Current error at rated primary current (%) Phase displacement at rated primary current (minutes) Composite error at rated primary accuracy limit current Knee point voltage (volts) Secondary Limiting Voltage Secondary Winding Resistance (ohm) Magnetizing Current (mA) at Knee point voltage Instrument Security Factor One second over current factor & corresponding value of current. Rated dynamic current (peak value) in amps. : : : : : : : : : : : : : :

Requirement 220 V DC During detail engg 5 - 10 kV Multi Finger / Tulip Bidder to furnish 80-100 mm Bidder to furnish Bidder to furnish 5 pico-coulomb Bidder to furnish *Bidder to furnish Yes / As applicable 6 NO + 6 NC/4 NO + 4 NC < 10 s < 10 s :

Vendors Data 220 V dc 10 kV Tulip 6.2 mm 100 mm 6t x 40mm 2.3 mm/s 5 pico-coulomb 156 kV (rms) 1000 microvolt Yes 6 NO + 6 NC/4 NO + 4 NC <5s <5s

1 2 3 4 5 6 7 8 Sr. No.

: : : : : : : :

As per vendor list Bidder to furnish Bidder to furnish 245 kV Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish Core I / II / III / IV / V / VI As per the specification requirement

Hyundai Bushing 300SR-CT 245 kV 1.2 Refer to SLD

1 2 3 4 5 6 7 8 9 10 11 12 13

: : : : : : : : : : : : :

Bidder Bidder Bidder Bidder 40kA 100kA

to to to to

furnish furnish furnish furnish 50 kA 125 kA

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 14 15 16 17 18 19 20 21 22 23 24 25

Description of Technical Particulars Rated continuous thermal current temperature rise over ambient. One minute power frequency dry withstand test voltage One minute power frequency wet withstand test voltage 1.2/50 microsecond lightning impulse withstand test voltage One minute power frequency withstand test voltage on secondaries Partial discharge level at 1.2 Un/ 3 Radio Interference voltage at 266 kV (rms) Corona extinction voltage Total weight Magnetization curves of CT cores Mounting details Overall dimensions (drawings with literature to be enclosed) Tests proposed to be conducted by the manufacturer at works i) Type tests ii) Routine tests Tests proposed to be conducted at site. VOLTAGE TRANSFORMERS Name of manufacturer Type designation Rated primary voltage (kV) Rated secondary voltage (V) Rated output per phase (VA) Rated burden (VA) Rated frequency (Hz) Standard values of rated voltage factor Limits of temperature rise One-minute power frequency withstand voltage 1.2/50 microsecond lightning impulse withstand voltage Total weight and dimensions Limits of voltage error and phase displacement in % Error angle Voltage error Accuracy class at rated burden Voltage factor and rated time Details of the tests to be conducted by the manufacturer at works i) Type tests ii) Routine tests Tests to be conducted at site. :

Requirement As per standard 460 kV(rms) : during detail engg : 1050kV (peak) : 2kV (rms) : : : : : : : : As per standard : < 5 Pico-coulomb Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish

Vendors Data As per IEC 460 kV 460 kV 1050 kV 2 kV < 5 Pico-coulomb 1000 microvolt 156 kV (rms) Approx. 600kg/3-phase Refer to specification. Bushing type Approx. 630mm(L)x 630mm(W)x 650mm(H)

26

27 D) 1 2 3 4 5 6 7 8 9 10 11 12 13

: : : : : : : : : : : : : : : : : :

Acc. To bid As per vendor list Bidder to furnish Wdg - I / II / III 220/3 kV 110/3 V - 110/3 V - 110/3 V As per the specification requirement 50 Bidder to furnish Bidder to furnish 460 kV(rms) 1050kV(peak) During detail engg

Yes(with extra cost) Yes Yes Nissin Inductive 220/3 kV 110/3 V - 110/3 V - 110/3 V Refer to SLD Refer to SLD 50 1.2(cont.)/1.5(30s) As per IEC 460 kV(rms) 1050kV(peak) Approx. 800kg/3phase

As per IEC

0.2/3P Refer to SLD Refer to SLD Refer to no.8

14

As per IEC : : : Yes Yes Yes

15

As per IEC

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 16 E) 1 2 3 4 5 6 7 8 9 10 11

Description of Technical Particulars Detailed drawing with literature to be enclosed with bid SF6 GAS Breaker Bus Bar Name of manufacturer Electrical properties(please give details) Compatibility with material used in switchgear Impurities in percentage(please mention details of impurities) Size of the cylinder in which gas is proposed to be supplied Condensation temperature Physical properties(please give details) Certification that gas meets the requirement of all the properties Tests to be conducted by the manufacturer at works Tests proposed to be conducted at site to detect and limit the moisture content in gas compartments Other details : - Normal pressure - Maximum pressure - Normal Operating density - Maximum gas density - Minimum pressure To maintain dielectric insulation for 245kV - Maximum leakage rate per year at Normal pressure in percentage - Maximum Permissible moisture content by weight - Permissible variation in ambient temperature - Details of gas filters - Effective life of filters - Test pressure for gas system - Constituents of gas in percent of ' weight' and volume of SF6, air, CH4, H2 : : : : :

Requirement As per IEC

Vendors Data Submitted after award

As per vendor list Bidder to furnish Yes Bidder to furnish Bidder to furnish

Ashai or Solvey As per IEC As per IEC As per IEC 600 kg/bottle As per IEC As per IEC As per IEC60376 No No

: : : :

Bidder to furnish As per IEC As per IEC As per IEC

: Bidder to furnish : : : : : : : 0.5 % per year : Bidder to furnish : : : : : : : : : : : Bidder Bidder Bidder Bidder As per to furnish to furnish to furnish to furnish IEC -5 dew point 5mm Absorbent 30 years CB: 6.5 / Others:4.5 As per IEC60376 0.5 % per year

Bidder to furnish Bar Bar Kg/m3 bar

CB: 7 / Others:5 CB: 7.5 / Others:5.5 CB: 52.51 / Others: 38.3 CB: 8 / Others: 6 CB: 6.5 / Others:4.5

12

13

14)

Alarm levels - First Alarm level for circuit breakers - Second Alarm level for circuit breakers - First Alarm level for all other components - Second Alarm level for all other components Gas Monitoring Devices Details of the sketches enclosed showing the type and location of gas density, gas pressure, gas moisture content and other fault monitoring devices to be supplied. Pressure Relief Devices - Rupturing pressure -Time to rupture -Details of the sketches enclosed showing the location and quantity of pressure relief devices used

Bidder to furnish 6.5 bar 6.2 bar 4.7 bar 4.5 bar Please refer to gas scheme drawing

Bidder to furnish

: : : : Bidder to furnish CB: 15 bar / other: 10 bar Approx. 60ms Please refer to gas scheme drawing

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. F) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 G)

Description of Technical Particulars SURGE ARRESTORS Manufacturer Type designation Class of arrestor Rated Voltage of Arrestor Rated Frequency Maximum continuous operating voltage(MCOV) Nominal discharge current Maximum discharge current (8/20 microsecond wave) Long duration discharge class Maximum 0.5 microsecond discharge voltage Residual voltage at 10kA (8/20 microsecond current wave) Residual voltage at 20kA, 8/20 microsecond current wave Maximum switching surge sparkover voltage Partial discharge level at 1.1 Un/ 3 Corona extinction voltage Radio interference level at 266 kV (rms) High current short duration test value Short circuit capability & class of pressure relief device Line discharge class Protective level provided by surge arrestor Energy level Details of the type test reports enclosed and the standards as per these tests have been carried out Details of Surge counter & milliammeter Detailed drawing with literature to be enclosed with bid SUPPORT & BARRIER INSULATORS (Details for each type of insulator used to be indicated separatel y) Manufacturer Type of insulators used One-minute power frequency dry withstand test voltage Dry flashover value Wet flashover value 1.2/50 microsecond lightning impulse withstand test voltage Creepage distance Puncture value of insulator in SF6 gas Weight of insulators in the SF6 GIS enclosure. Detailed drawing with literature to be enclosed with bid GAS PROCESSING UNIT Name of the manufacturer Capacity : : : : : : : : : : :

Requirement As per vendor list Bidder to furnish Bidder to furnish 179 kV 50 Hz 156 kV 10 kA 20 kA 3 Bidder to furnish Bidder to furnish Bidder to furnish : : : : : : : : : : Bidder to furnish < 5 pico-coulomb Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish 3 Bidder to furnish 8 kJ/kV As per IEC

Vendors Data Toshiba RVLUF-198KY 3 198kV 50Hz 160kV 10kA 20 kA 3 500kV at 10kA (Front time 1us) 463kV 495kV N/A < 5 pico-coulomb N/A N/A 100kA (4/10us) 50kA 0.1s 3 N/A 8kJ/kV at 2shot IEC60099-4

: : :

Bidder to furnish Bidder to furnish Support & Barrier

Refer to drawing No. M6747780 Data Refer to Memorandum N/A

1 2 3 4 5 6 7 8 9 10 H) 1 2

: : : : : : : : : :

As per vendor list Bidder to furnish 460 kV > 460 kV(rms) *Bidder to furnish 1050kV(peak) Bidder to furnish 1050kV Bidder to furnish Bidder to furnish

Hyundai 460 kV > 460 kV(rms) N/A 1050 kV Approx. 150mm 1050kV 30 kg Please refer to attached drawing for insulation spacer DILO Refer to catalogue

: :

Bidder to furnish Bidder to furnish

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 3 4 5 6 I) 1 2 3 4 5 J) 1 2 3 K)

Description of Technical Particulars Dimensions of unit Weight of the unit Purity of gas obtainable Description of plant & its various components to be attached PARTIAL DISCHARGE MONITORING SYSTEM Name of the manufacturer No of couplers Capacity Type of sensors Details of Spectrum Analyser GROUNDING CONNECTION Type of conductor Arrangement for connecting conductor to ground Type of painting, if any required to be carried out at end points of ground riser : : : :

Requirement Bidder Bidder As per Bidder to furnish to furnish IEC 60480 to furnish

Vendors Data Refer to catalogue Refer to catalogue Refer to catalogue Refer to catalogue

: : : : : : :

Bidder Bidder Bidder Bidder Bidder

to furnish to furnish to furnish to furnish to furnish

Hyundai 45 Above -20dBm@5pC UHF sensor 6 CH, 500~1500MHZ Copper Refer to attached Earthing drawing N/A

Bidder to furnish Bidder to furnish Bidder to furnish

: Bidder to furnish Bidder to furnish 102 158 191 65 104 100 100 Bidder to furnish Kg/cm Kg/cm Bidder to Kg/cm Kg Bidder Bidder Bidder sq. sq. furnish sq to furnish to furnish to furnish 2.5 4.1 5.2 4.0 Hot dip galvanized Hyundai

L)

M) 1 2

DESIGN CLEARANCE Minimum insulating clearances at nominal rated SF6 gas pressure and rated voltage/BIL voltage for the following : a) Main bus to ground : b) Circuit breaker -Contact To ground : - Across the contacts : c) Isolator switches - Contact to ground : - Across the contacts : d) Safety grounding switches - Contact To ground : - Across the contacts : STEEL SUPPORT STRUCTURES a)Structural steel - Minimum guaranteed yield point : - Ultimate tensile strength : b)Bolts and nuts - Minimum tensile strength of bolts : - Proof load on nuts : c)Type of galvanization : d)Manufacturer : WEIGHTS & DIMENSIONS Shipping weight of heaviest package : Dimensions of largest package :

(6.4 x 2.8 x 4.5) ( L x B x H) meter in including trailer height Bidder to furnish

4.8 x 2.4 x 2.4

3 4

Shipping weight of all special lifting devices wrenches and tools etc. Shipping weight of SF6 gas treatment unit

: :

Please refer to attached Installation equipment list Please refer to catalogue

Bidder to furnish

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 5

Description of Technical Particulars Weight of each type of switchgear bay module - Transmission line feeder - Generator transformer incoming feeder - bus coupler bay module Untanking height, (i.e. height under hook required) Shipping weight of SF6 gas cylinders required for first filling and testing Approximate shipping dimensions of all gas cylinders Clearance required between max hook reach & highest point of equipment Details of lifting & handling tackles supplied for loading, unloading consignments Total tonnage to be shipped. TOLERANCES Tolerance (vertical & horizontal) and at interface of SF6 to Transformer oil bushing Tolerance (vertical & horizontal) and at interface of SF6 to GIS bus Reactor bushing OTHER INFORMATIVE DETAILS Offered system is of proven design & type tested : Type test report submitted GIS testing clearance diagram Bay control ler Model, technical details & catalogue Bay control ler communication protocol Recommendation for Optimization of the GIS layout Confirmation on Insulation Co-ordination study Per set price of offered LA (optional) Per meter price of GIB (optional) Civil work guide Rental charges for testing & commissioning tools & tackles for the GIS Recommended capacity of the GIS hall crane Gas compartment diagram for the offered GIS Complete layout of the offered GIS w.r.t. Project Power House Layout Reference List of supply Dynamic Load for the complete GIS for determination of the floor thickness Time schedule for supply, Tentative erection, commissioning & testing of the offered GIS On Line PD monitoring system (optional) Off Line PD monitoring system (optional) Offer for the Mandatory spares No Deviation against the specification : : :

Requirement Bidder to furnish

Vendors Data Approx. 10,000 kg Approx. 8,000 kg Approx. 5,000 kg Please refer to section drawing Approx. 900 kg 1.4m(L)x1.4m(W)x 2.6m(H)/4 bottle Refer to section drawing At the detail design stage Approx. 137,000kg Within 2mm

6 7 8 9 10 11 N) 1 2 O) 1 2 3 4 5 6 7 8 9 10

Bidder to furnish : Bidder to furnish : Bidder to furnish : Bidder to furnish : Bidder to furnish : : Bidder to furnish Bidder to furnish :

N/A : Yes : : : : : : : : : Bidder to furnish Bidder to furnish Bidder to furnish IEC 101/103 Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish Bidder to furnish : : : 5T/10T Bidder to furnish Bidder to furnish : : : Bidder to furnish : : : : : Bidder Bidder Bidder Bidder to furnish to furnish to furnish to furnish Yes Yes Yes Yes Bidder to furnish Bidder to furnish 3 ton Refer to gas scheme drawing F10054-02 Yes
Horizontal: 1400kgf/1-phase Vertical: 900kgf/1-phase

Yes Yes N/A HHI will provide mounting Space only As per IEC Yes Yes Refer to price breakdown Refer to price breakdown Refer to installation manual Refer to price breakdown

11 12 13 14 15 16 17 18 19 20 21

Yes

DATA SHEET - 245KV GIS DOC. NO. SK-GS-03-1169, R0

3 X 37 MW SAWRA KUDDU HYDRO ELECTRIC PROJECT

Sr. No. 22 23 24 25 26 27 28 29 30 31 32 33 34 35

Description of Technical Particulars GIS Surge Impedance GIS Surge/propagation Velocity Disconnector (Open) Capacitance Disconnector (Close) Capacitance Disconnector Surge Impedance Disconnector Propagation Velocity Voltage Transformer Capacitance Circuit Breakers (Open) Capacitance Circuit Breakers (Close) Capacitance Circuit Breakers Surge Impedance Circuit Breakers Propagation Velocity Surge Arrestor Surge Impedance Surge Arrestor Propagation Velocity Surge Arrestor Discharge Voltages Switching surges at1kA/2kA/3kA/5kA/10kA/20kA & 40kA : : : : : : : : : : : : : :

Requirement Bidder to furnish Bidder to furnish Bidder to furnish Bidder Bidder Bidder Bidder Bidder Bidder Bidder Bidder Bidder Bidder Bidder to furnish to furnish to furnish to furnish to furnish to furnish to furnish to furnish to furnish to furnish to furnish

Vendors Data 59.9 ohm 2.723 x 108 m/s 30pF(either end to ground) 30pF(between contacts) 44.3pF/m 82.9 ohm 2.724 x 108 m/s 100pF 90pF(either end to ground) 50pF(between contacts) 56.9pF/m 65.6 ohm 2.724 x 108 m/s 10 Ohm to 1 k Ohm 200 m / s 1kA : 393kV 2kA :403kV 3kA :N/A 5kA: :N/A 10kA: :N/A 20kA: :N/A 40kA: :N/A 227 217

36 37

Surge Arrestor TOV 1 Sec Surge Arrestor TOV 10 Sec

: :

Bidder to furnish Bidder to furnish