Вы находитесь на странице: 1из 2

Product data sheet

Characteristics

32733

circuit breaker Vigicompact NS400N STR23SE - 400A - 3 poles 3d - 300..30000mA

Main
Device short name Circuit breaker name Circuit breaker application Poles description Protected poles description Network type Network frequency [In] rated current [Ui] rated insulation voltage [Uimp] rated impulse withstand voltage [Ue] rated operational voltage Circuit breaker rating code Breaking capacity Compact NS400N Vigicompact NS400N Distribution 3P 3t AC 50/60 Hz 320 A 65 C 400 A 40 C
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

750 V IEC 60947-2 AC 50/60 Hz 8 kV IEC 60947-2 440 V IEC 60947-2 AC 50/60 Hz N 22 kA Icu IEC 60947-2 525 V AC 50/60 Hz 30 kA Icu IEC 60947-2 500 V AC 50/60 Hz 42 kA Icu IEC 60947-2 440 V AC 50/60 Hz 42 kA NEMA AB1 HIC 480 V AC 50/60 Hz 50 kA Icu IEC 60947-2 380/415 V AC 50/60 Hz 85 kA Icu IEC 60947-2 220/240 V AC 50/60 Hz 85 kA NEMA AB1 HIC 240 V AC 50/60 Hz 22 kA IEC 60947-2 525 V AC 50/60 Hz 30 kA IEC 60947-2 500 V AC 50/60 Hz 42 kA IEC 60947-2 440 V AC 50/60 Hz 50 kA IEC 60947-2 380/415 V AC 50/60 Hz 85 kA IEC 60947-2 220/240 V AC 50/60 Hz Yes IEC 60947-2 Category A STR23SE Electronic Earth-leakage protection Instantaneous short-circuit protection Overload protection (long time) Short time short-circuit protection MB 3 IEC 60947

[Ics] rated service breaking capacity

Suitability for isolation Utilisation category Trip unit name Trip unit technology Protection type

Earth-leakage add-on module name Pollution degree

Complementary
Control type Mounting mode Mounting support Upside connection Downside connection Circuit breaker CT rating Mechanical durability Electrical durability Connection pitch
Jan 24, 2011

Toggle Fixed Backplate Front Front 400 A 15000 cycles 6000 cycles IEC 60947-2 440 V In AC 50/60 Hz 12000 cycles IEC 60947-2 440 V In/2 AC 50/60 Hz 45 mm

Local signalling Long time pick-up adjstment type Ir Long time pick-up adjustment range Long time delay adjustment type [Tr] long-time delay adjustment

Positive contact indication Adjustable 48 settings 0.4...1 x In Fixed 5...75 s 6 x Ir 32...5 s 7.2 x Ir 90...180 s 1.5 x Ir Adjustable 8 settings 2...10 x Ir Fixed 004...006 s Fixed 11 x In Class A With Adjustable 03 A 1A 3A 10 A 30 A Adjustable 0 ms 60 ms 150 ms 310 ms LED 355 mm 140 mm 110 mm

Short-time pick-up adjustment type Isd [Isd] short-time pick-up adjustment range Short-time delay adjustment type [Tsd] short-time delay adjustment range Instantaneous pick-up adjustment type Ii Instantaneous pick-up adjustment range Earth-leakage protection class Earth-leakage protection Residual earth-leakage sensitity adjustment type [In] residual earth-leakage sensitive adjustment

Residual earth-leakage time delay adjustment type [t] residual earth-leakage time delay adjustment

Display type Height Width Depth

Environment
Standards Product certifications IEC 60947-2 ASEFA ASTA KEMA LCIE IP40 IEC 60529 IK07 EN 50102 -25...70 C -50...85 C 0911 Compliant

IP degree of protection IK degree of protection Ambient air temperature for operation Ambient air temperature for storage RoHS EUR conformity date RoHS EUR status